0% found this document useful (0 votes)
63 views1 page

Ctratio R1 3/24/2018 12:59 No N/A Ac 800A 200.0A 1.0A 50.0Hz 200.0A Yes No No

The document reports the results of a CTRatio test performed on March 24, 2018 at 12:59. The test measured a primary current of 199.96A and secondary current of 1.00115A, yielding a ratio of 200.0A:1.0014A or 0.14%. The test found the polarity to be OK and was performed automatically without a current clamp at an AC range of 800A, 50Hz frequency, and with nominal primary and secondary currents of 200A and 1A respectively.

Uploaded by

ganeshapec8
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
63 views1 page

Ctratio R1 3/24/2018 12:59 No N/A Ac 800A 200.0A 1.0A 50.0Hz 200.0A Yes No No

The document reports the results of a CTRatio test performed on March 24, 2018 at 12:59. The test measured a primary current of 199.96A and secondary current of 1.00115A, yielding a ratio of 200.0A:1.0014A or 0.14%. The test found the polarity to be OK and was performed automatically without a current clamp at an AC range of 800A, 50Hz frequency, and with nominal primary and secondary currents of 200A and 1A respectively.

Uploaded by

ganeshapec8
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

CTRatio: CTRatio R1

Date/Time: 3/24/2018 12:59


Overload: NO
Assessment: n/a
Range: AC 800A
Nominal values:
I prim.: 200.0A
I sec.: 1.0A
Frequency: 50.0Hz
I test: 200.0A
Automatic: YES
I sec. Manual NO
I sec. measured with current clamp NO
Results:
I prim.: 199.96A I prim Phase: 0.0°
I sec.: 1.00115A I sec Phase: 0.0°
Ratio: 200.0A: 1.0014A 0.14%
Polarity: OK
measured with Burden: NO