0% found this document useful (0 votes)
130 views2 pages

1core630 PDF

This document provides technical specifications for an 11kV single core cross-linked polyethylene insulated cable. The cable has a copper conductor with a cross-sectional area of 630 mm2, an XLPE insulation layer, an aluminum wire armor, and an outer PE sheath. Key specifications include the cable's operating voltage of 11kV, maximum conductor temperature of 90°C when buried, and maximum current carrying capacity of 707 amps when laid in the ground.

Uploaded by

anon_519673613
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
130 views2 pages

1core630 PDF

This document provides technical specifications for an 11kV single core cross-linked polyethylene insulated cable. The cable has a copper conductor with a cross-sectional area of 630 mm2, an XLPE insulation layer, an aluminum wire armor, and an outer PE sheath. Key specifications include the cable's operating voltage of 11kV, maximum conductor temperature of 90°C when buried, and maximum current carrying capacity of 707 amps when laid in the ground.

Uploaded by

anon_519673613
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

OLYMPIC CABLE COMPANY SDN. BHD.

11KV SINGLE CORE CROSS-LINKED POLYETHYLENE (XLPE) INSULATED, PVC INNER SHEATHED, ALUMINIUM WIRE ARMOURED, PE OVERSHEATHED CABLE

TECHNICAL DATA
2
REF DESCRIPTION UNIT 630 mm x 1C
1 Reference standard IEC 60502-2:1998
2 Voltage (Uo / U) kV 6.35 / 11
3 Number of cores 1
4 Conductor
- Material Plain Annealed Copper wires
- Cross sectional area mm2 630
- Number of strands Nos. Min. 53
- Conductor shape Compacted circular
- Conductor's outermost lay direction Right-handed ( Z)
5 Conductor Screen
-Material Semi-conducting compound
6 Insulation
- Material Cross-linked Polyethylene
- Nominal thickness mm 3.4
7 Insulation Screen
-Material Semi-conducting compound
-Method of application Extrusion
-Diameter over insulation screen (Approx.) mm 37.70
8 Metallic Screen
-Material Copper Tape
-Nominal thickness mm 0.08
9 Inner sheatlh
- Material Black PE
- Nominal thickness mm 1.4
- Overall diameter over inner shealth mm 40.66
10 Armouring
- Material Hard Drawn Round Aluminium Wire
- No of wire (approx.) / size Nos/mm 52 2.52
- Diameter over armouring mm 45.70
11 Outer Sheath
- Material Black PE
- Nominal thickness mm 2.6
- Overall diameter over outer shealth (approx.) mm 51.60
12 Completed Cable
- Approx. overall diameter mm 51.60
- Approx. weight per kilometer kg 7819
- Approx. cable length per drum m 1000 ± 2.5%
13 Condition Upon Which Current Carrying
Capacities are Based
- Soil thermal resistivity K-m/w 1.2
o
- Ground temperature C 25
o
- Ambient air temperature C 40
- Burial depth mm 800
- Type of earth bonding-Trefoil Bonding at both ends
- Load factor % 100
- Number of circuit 1

Page 1 of 2
OLYMPIC CABLE COMPANY SDN. BHD.

11KV SINGLE CORE CROSS-LINKED POLYETHYLENE (XLPE) INSULATED, PVC INNER SHEATHED, ALUMINIUM WIRE ARMOURED, PVC OVERSHEATHED CABLE

TECHNICAL DATA
2
REF DESCRIPTION UNIT 630 mm x 1C
14 Minimum Radius of Bend
- Laid direct in ground mm 619
- Laid in duct mm 619
- Laid in air mm 619
15 Minimum interal diameter of duct mm 82
o
16 Maximum DC Resistance of Conductor at 20 C ohm/km 0.0283
17 Maximum Conductor Temperature
0
- Laid direct in ground C 90
0
- Drawn into duct C 90
0
- Laid in air C 90
18 Maximum Current Carrying Capacity Based
on condition Specified (See Ref : 16)
- Laid in ground Amp 707
- Drawn into duct Amp 661
- Laid in air Amp 955
19 Conductor Short Time Current Rating
0
-Initial temperature C 90
0
-Maximum conductor short time temperature C 250
Short circuit current rating:-
-For 1 second kA 90.06
-For 3 second kA 51.99
20 Copper Tape Earth Fault Current Rating
0
- Initial temperature C 80
0
- Maximum conductor fault teperature C 200
- Short circuit current rating:-
- For 1 second kA 0.92
- For 3 second kA 0.53
21 Maximum Volt Drop at Maximum Conductor
Temperature
- For 1 - phase circuits mV/A.m -
- For 3 - phase circuits mV/A.m 0.18

Page 2 of 2