Wednesday, June 27, 2018
LD20P - Cell data sheet
Classification
Wiring principle Normal
Brand Alcad
Cell type LD20P
Cell P/N 892710812
Capacity at 5 hours rate 20 Ah
IEC Designation KL20P
According to IEC 60623
Physical data
Overall height 176 mm
Cell height
Width 122 mm Weight per cell 1.1 Kg
Length 35 mm Block length - 2 cells -
Block length - 3 cells - Block length - 4 cells -
Block length - 5 cells - Block length - 6 cells -
Block length - 7 cells - Block length - 8 cells -
Block length - 9 cells - Block length - 10 cells -
Construction
Container material Polypropylene No. of terminals/polarity 1
Separator type Grid Terminal material Steel
Connection torque 11.0 +/- 1.1 Nm Vent type
Terminal size M6
Handle No
Plates
Positive Negative
Type of plates Pocket Type of plates Pocket
Electrolyte
Electrolyte type: Renewal E13 Max/Min 25 mm
Electrolyte type: Initial E22 Vent oil quantity 15 cm3
Electrolyte per cell: Liquid 0.2 liters
Connection
Cable area 10 mm²
ALCAD confidential and proprietary. The data herein given are for information purposes only and are not binding on ALCAD. They may be
modified without prior notice. Please contact an ALCAD representative in order to obtain confirmation of the above data.
Visit our website at www.alcad.com
(377207) Version: 2.3, Last updated on 05/2018 P 1/3
Wednesday, June 27, 2018
LD20P - Cell data sheet
Charging
Float voltage 1.42 V/Cell High rate voltage (min) 1.47 V/Cell
Single-level voltage 1.43 V/Cell
Resistance/Short circuit
Internal resistance 7.20 mOhm Short circuit current 155 A
Performance data
Current discharge
After prolonged float charge of fully charged cells. Available amperes at +20°C +/- 5°C (+68°F +/- 9°F)
V/Cell 10h 8h 5h 3h 2h 1.5h 1h 30m 20m 15m 10m 5m 1m 30s 5s 1s
1 2.03 2.52 4.00 6.41 8.56 10.0 12.2 15.3 16.7 17.8 19.4 21.9 25.3 27.2 32.1 36.0
1.05 2.00 2.49 3.91 5.67 7.48 8.93 10.7 13.1 14.3 14.9 15.9 17.2 20.2 21.7 25.7 28.5
1.1 1.97 2.36 3.47 5.10 6.72 7.97 9.47 11.0 11.6 11.9 12.4 13.2 15.5 16.9 20.0 22.5
1.14 1.88 2.20 2.89 3.97 4.93 5.71 6.59 7.73 8.28 8.45 8.90 10.1 12.0 13.1 15.8 17.4
Power discharge
Available power (W), after prolonged float charged of fully charged cells at +20°C +/- 5°C (+68°F +/- 9°F)
V/Cell 10h 8h 5h 3h 2h 1.5h 1h 30m 20m 15m 10m 5m 1m 30s 5s 1s
1 2.35 2.88 4.47 6.85 8.96 10.4 12.4 15.4 16.8 17.8 19.5 21.9 25.3 27.2 32.1 36.0
1.05 2.33 2.87 4.45 6.24 8.10 9.6 11.4 13.9 15.1 15.7 16.7 18.0 21.2 22.8 27.0 30.0
1.1 2.30 2.75 4.01 5.77 7.54 8.89 10.5 12.2 12.8 13.1 13.6 14.5 17.0 18.6 22.0 24.8
1.14 2.21 2.58 3.37 4.59 5.68 6.56 7.54 8.83 9.45 9.6 10.2 11.5 13.7 14.9 18.0 19.9
ALCAD confidential and proprietary. The data herein given are for information purposes only and are not binding on ALCAD. They may be
modified without prior notice. Please contact an ALCAD representative in order to obtain confirmation of the above data.
Visit our website at www.alcad.com
(377207) Version: 2.3, Last updated on 05/2018 P 2/3
Wednesday, June 27, 2018
LD20P - Cell data sheet
Kt Factor
Current discharge
After prolonged float charge of fully charged cells. Kt factor at +20°C +/- 5°C (+68°F +/- 9°F)
V/Cell 10h 8h 5h 3h 2h 1.5h 1h 30m 20m 15m 10m 5m 1m 30s 5s 1s
1 9.9 7.93 5.00 3.12 2.34 1.99 1.64 1.31 1.20 1.13 1.03 0.91 0.79 0.73 0.62 0.56
1.05 10.0 8.02 5.11 3.53 2.67 2.24 1.87 1.53 1.40 1.34 1.26 1.17 0.99 0.92 0.78 0.70
1.1 10.1 8.47 5.76 3.92 2.97 2.51 2.11 1.82 1.72 1.68 1.62 1.52 1.29 1.19 1.00 0.89
1.14 10.6 9.08 6.93 5.04 4.05 3.50 3.04 2.59 2.42 2.37 2.25 1.99 1.66 1.53 1.27 1.15
Power discharge
Kt factor power, after prolonged float charged of fully charged cells at +20°C +/- 5°C (+68°F +/- 9°F)
V/Cell 10h 8h 5h 3h 2h 1.5h 1h 30m 20m 15m 10m 5m 1m 30s 5s 1s
1 8.51 6.94 4.47 2.92 2.23 1.92 1.61 1.30 1.19 1.12 1.03 0.91 0.79 0.73 0.62 0.56
1.05 8.59 6.96 4.50 3.20 2.47 2.08 1.76 1.44 1.33 1.28 1.20 1.11 0.94 0.88 0.74 0.67
1.1 8.68 7.28 4.99 3.46 2.65 2.25 1.90 1.65 1.56 1.53 1.47 1.38 1.17 1.08 0.91 0.81
1.14 9.05 7.75 5.93 4.36 3.52 3.05 2.65 2.27 2.12 2.08 1.97 1.74 1.46 1.34 1.11 1.01
ALCAD confidential and proprietary. The data herein given are for information purposes only and are not binding on ALCAD. They may be
modified without prior notice. Please contact an ALCAD representative in order to obtain confirmation of the above data.
Visit our website at www.alcad.com
(377207) Version: 2.3, Last updated on 05/2018 P 3/3