H V A C S Y S T E M S M O N I T O R I N G
Intelligent Low-Flow
Duct Smoke Detectors
Intelligent Models Available DH200PL DH200RPL
DH200PL (non-relay)
DH200RPL (with relay)
Product Overview
Air velocity rating from 100 to 4000 feet
per minute (0.5 to 20.32 m/sec.)
Patented telescopic sampling tube
Easily accessible code wheels The System Sensor Innovair™ DH200 Low-Flow Series photoelectric air duct smoke
detectors are capable of sensing smoke in air velocities from 100 to 4,000 feet per min-
Outside mounting tabs
ute (0.5 to 20.32 m/sec).
Easy and quick mounting to round
or rectangular ducts from 1′–12′
This Innovair features low-flow technology that enables duct smoke detection through-
(0.3–3.7 meters) wide
out a broad range of airflow environments. Many difficult to solve HVAC applications
Easy to clean occur in low airflow duct applications where reliable smoke detection is critical. Innovair
UL recognized field-replaceable low-flow technology can detect smoke at air speed velocities of 100 feet per minute or
power and sensor boards greater, while continuing the same reliable performance to 4,000 feet per minute.
Transparent cover for convenient
visual inspection The DH200 Series Detector samples air currents passing through a duct and gives
UL 268A listed dependable performance for shutdown of fans, blowers, and air conditioning systems,
3-year warranty preventing the spread of toxic smoke and fire gases through the protected area.
DH200PL (non-relay) These intelligent sensors communicate and are continuously monitored through the com-
munication line. Detector sensitivity changes caused by dirt, temperature, or humidity
Has outputs for remote LED display,
remote test are reported to the panel, allowing compensation algorithms to maintain the sensor’s set
sensitivity. An advance indication at the panel specifies the sensor address, allowing for
Incorporates zener diodes to conserve
selected maintenance to be performed as needed.
power for communications to other
devices
Remote alarm annunciation can be accomplished by using the RA400Z Remote
Requires com line power only
Annunciator or the RTS451 or RTS451KEY Remote Test Station. Both these devices
allow testing of the detector from a remote location.
DH200RPL (with relay)
Powered outputs for remote LED, and The Innovair family is designed for simplified installation and easy maintenance. The
remote test and sounder modular construction allows for easy cleaning and uncomplicated field replacement of
Two form “C” auxiliary contacts the UL recognized power and sensor boards.
Can be configured as a relay version or
jumpered to mimic a non-relay version WARNING: Duct smoke detectors have specific limitations.
Patented cover tamper trouble signal DUCT SMOKE DETECTORS ARE:
Requires both com line power and one of NOT a substitute for an open area smoke detector,
the following; 24VAC/DC or NOT a substitute for early warning detection, and
120/220VAC for operation NOT a replacement for a building’s regular fire detection system.
Refer to NFPA 72 and 90A for additional duct smoke detector application information.
APPROVED
S911 3013287 2125
342-02-E CS308 3240-1209:155
Architect/Engineer Specifications
The duct smoke detector shall be a System tor shall be an intelligent photoelectronic shall be included to reduce dust and resi-
Sensor Model DH200PL or DH200RPL detector. It shall be capable of local testing due effects, thereby reducing maintenance
Intelligent Low-Flow Duct Smoke Detector via magnetic switch or remote testing from and servicing. Sampling tubes shall be eas-
to be used with compatible control pan- the RTS451 or RTS451KEY Remote Test ily installed after the housing is mounted
els. The duct smoke detector shall be UL Station. The duct smoke detector housing to the duct by passing through the duct
listed per UL 268A, Standard for Smoke shall incorporate an airtight smoke cham- housing. Terminal connections shall be of
Detectors for Duct Applications, specifi- ber in compliance with UL 268A. The the strip and clamp method suitable for
cally for use in air handling systems. The housing shall be capable of mounting to 12-18 AWG wiring.
detector shall operate in air velocities from either rectangular or round ducts without
100 to 4000 feet per minute. The detec- adapter brackets. An integral filter system
DH200PL Specifications
Voltage Range Accessory Current Loads
15 to 32 VDC
Device Standby Alarm
Standby Current
RA400Z 0 mA 10 mA Max.
300µA @ 24 VDC (one communica-
tion ever y 5 seconds with LED blink RTS451/RTS451KEY 0 mA 7.5 mA Max.
enabled)
Wiring diagram for DH200PL Duct Smoke Detector using a UL listed control panel
COM (+)
COM (+)
COM (-)
COM (-)
+
COMMON
COMMON
RA400Z
RTS451
COM(+)
RA400Z
RTS451
COM(+)
COM(-)
COM(-)
TEST
TEST
KEY
KEY
COMMUNICATION
LINE
–
UL LISTED CONTROL 1ST DETECTOR 2ND DETECTOR
PANEL IN LOOP IN LOOP
Wiring diagram for DH200PL Duct Smoke Detector with optional RA400Z
(Must break tab on back of RA400Z when used with DH200PL.)
COMMON
RA400Z
COMMON
RA400Z
RTS451
COM(+)
COM(-)
TEST
KEY
+
DH200PL RA400Z
Wiring diagram for DH200PL Duct Smoke Detector with RTS451/RTS451KEY
COMMON
RA400Z
RTS451
COM(+)
COM(-)
TEST
KEY
COMMON
RA400Z
RTS451
COM(+)
COM(-)
TEST
KEY
COMMON TEST
4 5 6
FOR RTS451, TERMINAL 3 IS NOT USED.
FIELD INSTALLED (RTS451 DOES NOT HAVE A TERMINAL 6.)
JUMPER
FOR RTS451KEY, TERMINALS 3 AND 6
ARE NOT USED.
1 2 3
LED RESET
DH200PL RTS451/RTS451KEY
DH200RPL Specifications
Current Requirements (using no accessories)
Power supply voltage 20-30 VDC 24 VAC, 50-60HZ 120VAC, 50-60Hz 220/240 VAC, 50-60Hz
Max. standby current 26 mA 65 mA RMS 44 mA RMS 25 mA RMS
Max. alarm current 87 mA 182 mA RMS 52 mA RMS 30 mA RMS
Alarm response time 3 to 10 sec. 3 to 10 sec. 3 to 10 sec. 3 to 10 sec.
Power up time 2 sec. 2 sec. 2 sec. 2 sec.
Contact Ratings Accessory Current Loads at 24 VDC
Alarm auxiliar y contacts* (DPDT) Device Standby Alarm
10 A @ 30 VDC
PA400 0 mA 15 mA Max.
10 A @ 277 VAC (0.75 power factor)
240 VA @ 249 VAC (0.4 power factor) RA400Z 0 mA 12 mA Max.
1
⁄8 HP @ 120 VAC
RTS451/RTS451KEY 0 mA 10 mA Max.
1
⁄4 HP @ 240 VAC
Supervisory contact (SPST)
2.0 A @ 30 VDC (resistive)
*Minimum switching current for auxiliar y contact
must be 100 mA DC minimum @ 5 VDC.
Wiring diagram for DH200RPL Duct Smoke Detector using a UL listed control panel
NOTE: Jumper J1 shunt must be installed for 2-W applications. J1 shunt must be removed for power PCB super vision.
COM (-)
COM (+)
COM (+)
COM (-)
+ 1 2 1 2
NOTE: External power of 24V AC/DC or
COMMUNICATION
120/220 VAC must be connected in
LINE order to power all remote horn or
strobe accessories.
–
UL LISTED CONTROL
PANEL
J1 JUMPER 1ST DETECTOR J1 JUMPER 2ND DETECTOR
IN LOOP IN LOOP
Wiring diagram for DH200RPL Duct Smoke
Wiring diagram for DH200RPL Duct Smoke Detector with optional RA400Z Detector with RTS451/RTS451KEY
RTS 451/RTS451KEY
RA400Z
5 7
1
ALARM SIGNAL
DO NOT BREAK TAB ON RA400Z 3
NOT USED
5 6
ALARM SIGNAL NOT USED
7 2
AUX. POWER (—) CIRCUIT
REFERENCE
4 4
5 = Alarm Signal TEST +
7 = Aux. Power (—) TEST
3 5 SWITCH
TEST —
Wiring diagram for DH200RPL Duct Smoke Detector with optional PA400
PA400 FOR RTS451, TERMINAL 3 IS NOT
5 7
USED. (RTS451 DOES NOT HAVE
A TERMINAL 6.) FOR RTS451KEY,
TERMINALS 3 AND 6 ARE NOT USED.
5 = Alarm Signal
7 = Aux. Power (—)
Innovair™ 200 Series Low-Flow Specifications
Operating Temperature Range Duct Air velocity Width
32° to 131°F (0° to 55°C) 100 – 4000 ft./min. (0.5 – 20.32 m/s) 51⁄ 2″ (14 cm)
Operating Humidity Range Shipping Weight Depth
10% to 93% relative humidity DH200PL: 3.35lbs. (1.5 kg) 23⁄ 4″ (7 cm)
(non-condensing) DH200RPL: 3.90lbs. (1.8 kg)
Storage Temperature Range Length
–22º to +158ºF (–30º to +70º C) 143⁄ 4″ (37 cm)
Ordering Information
Par t No. Description Accessories Description
DH200PL Innovair™ intelligent low-flow photoelectric non- RTS451 Remote test station (see below)
relay duct smoke detector
RTS451KEY Remote test station w/key (see below)
DH200RPL Innovair™ intelligent low-flow photoelectric with
RA400Z Remote LED (see below)
relay duct smoke detector
PA400 Mini-Aler t™ Sounder (see below)
ST-1.5 Metal sampling tube duct widths 1′–2′
F36-09-11 Replacement filters
ST-3 Metal sampling tube duct widths 2′–4′
M02-04-00 Test magnet
ST-5 Metal sampling tube duct widths 4′–8′
P48-21-00 End cap for metal sampling tube
ST-10 Metal sampling tube duct widths 8′–12′
P48-61-00 End cap for plastic sampling tube
A5053 Replacement photoelectric sensor board
S08-39-01 Replacement photo insect screen
A5060 Replacement power board for DH200RPL (w/relay)
T80-71-00 Replacement plastic sampling tube
A5067 Replacement power board for DH200PL (w/o relay)
ALARM ALARM
ON
RESET TEST
RESET
RTS451 RTS451KEY RA400Z PA400
Remote Test Station Remote Test Station with Remote Mini-Aler t™ Sounder
(UL S2522) key (UL S2522) Annunciator (UL S3593)
(UL S2522) Device cannot be wired
directly to DH200PL
(non-relay).
System Sensor Sales and Service
System Sensor Headquarters System Sensor Canada System Sensor in China System Sensor – Far East System Sensor – India
3825 Ohio Avenue Ph: 905.812.0767 Ph: 86.29.524.6253 Ph: 85.22.191.9003 Ph: 91.124.237.1770 x.2700
St. Charles, IL 60174 Fx: 905.812.0771 Fx: 86.29.524.6259 Fx: 85.22.736.6580 Fx: 91.124.237.3118
Ph: 800/SENSOR2 System Sensor Europe System Sensor in Singapore System Sensor – Australia
Fx: 630/377-6495 Ph: 44.1403.891920 Ph: 65.6273.2230 Ph: 613.54.281.142
Documents-on-Demand Fx: 44.1403.891921 Fx: 65.6273.2610 Fx: 613.54.281.172
800/736-7672 x3
www.systemsensor.com
© 2003 System Sensor. The company reserves the right to change product specifications without notice. A05-0353-000•7/03•#1012