FieldServer Protocol Driver Sheet
Edwards Systems
                                          Technology- QuickStart
       FS-8700-93                                                                        Version: 1.05 / Rev. 2
1     DESCRIPTION                                           restarted to clear all point status, and then re-
                                                            annunciate any active devices after the FieldServer
The QuickStart Serial driver allows the FieldServer to      has been started. This should only be undertaken by
record data from Edwards System Technology QS1-             qualified technicians.
2/4-8 and QSC Fire Panels over the RS-232 printer
port. The FieldServer acts as a Passive Client              Should the panel be soft restarted unexpectedly, the
receiving messages and updating its internal data           FieldServer will recognize the "restart" command and
arrays which records the status of devices connected        clear all internal data arrays. There will be no need
to the QuickStart fire alarm control panel. The             for FieldServer restart; however, for a hard restart,
QuickStart panels currently do not support duplexed         the FieldServer data arrays should be manually
communications; therefore, this driver has only been        cleared by changing a bit in the CLEAR_FLAG data
designed to listen for messages passively and not to        array through RUINET, then soft restarting the panel
respond or to generate polls.                               again to ensure that status of all points is re-
                                                            annunciated and recorded by the FieldServer.
The main purpose of this driver is to record the status
of Fire Alarm System points in bit oriented data            1.2      Device States
arrays. It is limited by the information that the
QuickStart control panels broadcasts in the form of         Each addressable device (real or pseudo) can have
text messages through its RS-232 printer port.              multiple states: alarm supervisory, monitor, other
                                                            (security), and troubles.     These states are not
The types of EST messages supported by this driver          exclusive; therefore, a single addressable point may
are listed later in this fact sheet and in the              occupy multiple states at the same time.
FieldServer Driver Manual. Device status to the data
array mapping is also provided. Since there are a           Although there may be several trouble states for each
variety of optional cards that can be selected for each     device, there can only be a single alarm, supervisory,
QuickStart installation, each FieldServer application       monitor and other (security) state per address.
must be specifically configured before use.                 Therefore any restoring messages for these four
FieldServer data storage arrays for panel status will       states indicate that the device is clear of any active
be allocated according to the number and type of            problems for these types of conditions.
cards implemented. Message information will also be         However, there may be several trouble states for a
stored according to card and panel addressing.              single addressable port. These trouble states will be
This driver is connection oriented; therefore, only one     recorded in a separate trouble array of 2 byte
EST Panel may be connected to any single RS-232             elements. Each array element will correspond to a
FieldServer port.                                           device address and each bit within the element will
                                                            correspond to a trouble type. The mapping of
The driver currently accommodates European and              message trouble types to element bit configuration is
American English Conventional/Intelligent panels            given below. For modeling simplicity and flexibility, it
using the American English protocol with provisions         is assumed that all addressable points (real or
for using the British English protocol at a later date.     pseudo) can exist in all states.
1.1   FieldServer Synchronization                           2     FORMAL DRIVER TYPE
To synchronize the FieldServer's data arrays with the       Serial
QuickStart control panel's status, the panel must
                                                            Passive Client
have no active or disabled points on FieldServer
startup. Alternatively, a panel can be hard/soft
                                                                                                          Page 1 of 3
                                               www.sierramonitor.com
                                   FieldServer Protocol Driver Sheet
                                           Edwards Systems
                                         Technology- QuickStart
       FS-8700-93                                                                              Version: 1.05 / Rev. 2
                                                              Event Description Text Strings        State   Comments
3     COMPATIBILITY MATRIX                                                                                  -OPERATOR
                                                              ACTIVATE
                                                                                                            COMMAND- clears
                                                              RESTART
                                                                                                            all the Data Arrays
                                 Compatible with
 FieldServer Model                                            QUIESCENT           QUIE RST                  Not Implemented
                                 this driver                  ALARM ACTIVE        ALARM RST         A
 FS-x30                          Yes                          PULL STATION        PULL STA RST      A
                                                              HEAT ALARM          HEAT ALM RS       A
 SlotServer                      Yes                          WATERFLOW           WATERFLOW RS      A
 ProtoNode                       Yes                          STAGE ONE                             A
                                                              SUPERVISORY         SUP RST           S
 QuickServer FS-QS-10xx          No                           TAMPER              TAMPER RST        S
 QuickServer FS-QS-12xx          Yes                          SECURITY            SECURITY RST      O
 ProtoCessor FPC-ED2             No                           FIREPHONE           PHONE RST         M
                                                              MONITOR             MONITOR RST       M
 ProtoCessor FPC-ED4             Yes                          LATCH SUPV          LAT SUPV RST      S
                                                              LATCH TAMPER        LAT TAMP RST      S
                                                              UNKNOWN             UNKNOWN RST       O
4     CONNECTION INFORMATION                                  ALARM VERIFY        ALM VFY RST       M
                                                              PREALARM            PREALARM RST      M
                                                              TROUBLE OPEN        TBL OPEN RST      T
 Connection type:        RS-232 (Simplex)                     TROUBLE SHRT        TBL SHRT RST      T
 Baud Rates:             9600 (Vendor Limitation)             LCL TROUBLE         LCL TRBL RST      T
 Data Bits:              8 (Vendor Limitation)                MAINT ALERT         MAT ALERT RS      M
                                                              DIRTY HEAD          DTY HEAD RST      T
 Stop Bits:              1 (Vendor Limitation)                COMMN FAULT         COMM FLT RST      T
 Parity:                 None (Vendor Limitation)             GROUND FAULT        GND FLT RST       T
 Multidrop Capability:   No                                   INTERNAL TBL        INTR TRBL RS      T
                                                              BAD TYPE            BAD TYPE RST      T
                                                              BAD PRSONATY        BAD PRSTY RS      T
                                                              UNEPECT DEV         UNEC DEV RST      T
5     DEVICES TESTED                                          TROUBLE             TROUBLE RST       T
                                                              RELAY CONFIR        RLY CFRM RST      M
                                  Tested                      LCL MONITOR         LCL MNTR RST      M
 Device                                                       SWITCH              SWITCH RST        M
                                  (FACTORY, SITE)             TEST                TEST RST          T
 Edwards Systems                                              DEV COMPATBL        DEV COMP RST      T
 Technology- European and                                     AND GROUP           AND GRP RST       A
                                                              MATRIX GROUP        MATRIX G RST      A
 American QS1-2/QS4-8                    SITE                 SERVICE GRP         SERVICE G RS      T
 Addressable Panels, and the                                  TIME CONTROL        TIME CNTL RS      M
 QSC Conventional Panel                                       ACK                 ACK RST           M
                                                              DISABLED            DISABLED RST      T
                                                              DISAB SOUND         DISSOUND RST      T
                                                              OBJECT RUN          OBJETRUN RST      M
6     COMMUNICATIONS FUNCTIONS -                              ZONE ALARM          ZONE ALM RST      A
                                                              ZONE SUPER          ZONE SUP RST      S
      SUPPORTED FUNCTIONS AT A                                ZONE MONITOR        ZONE MON RST      M
                                                              OUTPUT GROUP        OUTPUT G RST      M
      GLANCE:                                                 AUDIBLE             AUDIBLE RST       M
                                                              VISUAL              VISUAL RST        M
                                                              SUPER OUTPUT        SUPER OUT RT      M
6.1    Message Types supported                                NONSUPER OUT        NONSUP OUT R      M
                                                              COMM ALM OUT        COMMALOUTRST      M
The primary purpose of this driver is to record the           LED OUTPUT          LEDOUTPU RST      M
status of devices connected to the QuickStart Fire
Control Panel by interpreting the text messages sent
to its printer port. Not all messages are interpreted,
as many messages and reports do not directly affect
device status. The following set of events and
messages are recognized and recorded I the data
arrays.
                                                                                                                  Page 2 of 3
                                                www.sierramonitor.com
                                         FieldServer Protocol Driver Sheet
                                                    Edwards Systems
                                                  Technology- QuickStart
       FS-8700-93                                                                                                                Version: 1.05 / Rev. 2
6.2    FieldServer            Limitations                      and
       Exclusions
     Only one QuickStart panel may be connected to
      any given RS-232 port at once.
     QuickStart and FieldServer synchronization
      requires some manual steps. This is described
      in the section of this fact sheet called
      “FieldServer Synchronization”.
     This driver cannot poll for data, thus if a
      message sent by the panel is lost or corrupted
      the status reported by the FieldServer will not
      correctly reflect the status of the panel until the
      panel is synchronized again or until the
      FieldServer receives a new message reporting
      the status of the lost message’s point.
     Because of the message structure for the
      QuickStart protocol, it was intended to be the
      only protocol assigned to any single port.
                                                                                                                                                 Page 3 of 3
                                                                 Sierra Monitor Corporation
                                                      1991 Tarob Court, Milpitas, California 95305 USA
                             O. +1 408 262-6611   TF: +1 800 72 SIERRA (74377) F. +1 408 262-9042        www.sierramonitor.com