BID DOCUMENTS
SECTION VI - TECHNICAL SPECIFICATIONS
PART II - TECHNICAL DATA SHEETS
SECTION VI – TECHNICAL SPECIFICATIONS
PART VI – TECHNICAL DATA SHEETS
III – ELECTRICAL WORKS
A. POWER CIRCUIT BREAKER
Name of Bidder: __________________________
Signature of Bidder: __________________________
NPC’s
ITEM DESCRIPTION UNIT SAMPLE DATA
REQUIREMENT
Circuit Breaker
1. Manufacturer By Contractor
2. Place of Manufacturer By Contractor
3. Nominal System Voltage, kV kV 138
4. No. of interrupter units per pole *1
5. No. of Phase 3
6. Rated Insulation Level
a. Lightning Impulse
kV 650
Withstand Voltage (BIL), kV
b. Power Frequency
kV 275
Withstand Voltage
7. Frequency Hz 60
8. Rated Continuous Current A * 4000
9. Rated Operating Sequence Cycles 0-3 min CO-3 min - CO
Rated short-time withstand
10. kA * 40
current (1s-3s), up to
Rated short-circuit breaking
11. kA * 40
current, up to
Vacuum or Gas
12. Type of Breaker
Insulated
Spring-Charged
13. Operating Mechanism
motor operated
14. Mechanism Voltage VDC 125
15. Trip and Closing Ckt. Voltage VDC 125
16. Temperature Range °C * -55 up to +55
17. Rated Break Time * 3 cycles
NATIONAL POWER CORPORATION VI-IIIG-1/2
BID DOCUMENTS
SECTION VI - TECHNICAL SPECIFICATIONS
PART II - TECHNICAL DATA SHEETS
Disconnect Switch
1. Manufacturer By Contractor
2. Place of Manufacturer By Contractor
3. Nominal System Voltage kV 138
4. Rated Current A * 4000
Short Circuit withstand
5. kA * 50
Current/3s
6. Rated Peak withstand Current kA * 125
Manual &
7. Operation Mechanism
Motorized
8. Rated Voltage of Motor VDC 125
9. Control Loop Voltage VDC 125
International Protection
10. IP65
marking
Notes * The Contractor shall determine the required rating but shall not be lower than the rating
indicated above.
** Contractor shall place in the filled-in data “submitted” or “will submit”, “will perform” or had
been performed” as appropriate
Name of Bidder: __________________________
Signature of Bidder: __________________________
NATIONAL POWER CORPORATION VI-IIIG-2/2