Spec - 1250 KVA (Oil Type)

This document is a specification sheet for a 1,250 kVA, 3-phase transformer with a primary voltage of 20 kV and secondary voltage of 400 volts. It lists the ratings, standards, accessories, and electrical performance requirements for the transformer. These include an insulation class of 24 kV, basic impulse level of 125 kV, temperature rise not exceeding 65°C, and accessories such as HV/LV bushings, oil filter valve, nameplate, and more. The transformer will be designed, manufactured and tested according to IEC 60076, SPLN 50/97, and SLI 1985 standards.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
592 views1 page

Spec - 1250 KVA (Oil Type)

This document is a specification sheet for a 1,250 kVA, 3-phase transformer with a primary voltage of 20 kV and secondary voltage of 400 volts. It lists the ratings, standards, accessories, and electrical performance requirements for the transformer. These include an insulation class of 24 kV, basic impulse level of 125 kV, temperature rise not exceeding 65°C, and accessories such as HV/LV bushings, oil filter valve, nameplate, and more. The transformer will be designed, manufactured and tested according to IEC 60076, SPLN 50/97, and SLI 1985 standards.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

PT. TRAFOINDO PRIMA PERKASA Spec. No. PT.

TRAFOINDO PRIMA PERKASA


Kantor : Jl. Hayam Wuruk 4 FX Jakarta 10120 Phone : 3451384,3850703,3861865 ; Fac. : 3850702,3861869
Pabrik : Jl. Siliwangi (Pasar Kemis), Desa Gembor, Kecamatan Jatiuwung, Tangerang 7. APPROXIMATE WEIGHT AND DIMENSION WITHOUT PACKING : to be informed later on
e-mail : trafo@trafoindonesia.com ; http : //www.trafoindonesia.com 7-1 The outline drawing of the transformer will be submited to customer
SPECIFICATION FOR TRANSFORMER
8. ACCESSORIES : The transformer will be furnished with all necessary accessories as follow :
To. Date 31 AUGUST 2018
Spec No. GENERAL ACCESSORIES SPECIAL ACCESSORIES
- HV Porcelain Bushing on Cover √ Plug in Bushing 50 mm2 c/w straight connector on cover
1. TYPE KNAN : Oil immersed self cooled / in / out door use / step-up / step-down / hermetically sealed √ LV Porcelain Bushing on Cover
distribution transformer - Oil Level Indicator w/o Contact √ Integrated Safety Device c/w Contact
- Thermometer w/o Contact - Magnetic Oil Level Gauge c/w Alarm Contact
2. SERVICE CONDITION : The transformer will be installed at the altitudes below 1.000 meters and the maximum √ Manual Off-Load Tap Changer - Dial Thermometer c/w Alarm & Trip Contact
o
ambient temperature does not exceed 40 C √ Name Plate - Buchholz Relay c/w Alarm & Trip Contact
√ Earth Terminal - Conservator c/w Sampling Valve
3. STANDARD : The transformer is designed, manufactured and tested in accordance with : √ Radiator - Breather c/w Silicagel
IEC 600-76 / SPLN 50 / 97 / SLI 1985 √ Drain Valve - Air-filled LV Junction Box
- Sampling Valve - HV/LV Cable Box
4. RATING √ Lifting lug - N2 Filling Valve
4-1 Number of Phase : 3 phase 4-2 Frequency : 50 Hz - Jacking Lug - Pressure Vacuum Gauge c/w Bleeder
4-3 Primary Voltage : 20 kV 4-4 Secondary Voltage : 400 Volt √ Roller - Pressure Relief Valve w/o Contact
Winding Connection : DELTA Winding Connection : WYE - Square Hole - Pressure Relief Device c/w Alarm Contact
4-5 Rated Capacity (total) : 1,250 kVA - Skid Base (Pad Mounted) - Radiator Fans
Incase of double primary voltage, Capacity will be : - Hanger ( Pole Mounted ) - Radiator Valves
at : - kV Rated Capacity : - kVA √ Oil Filter Valve - Terminal Control Box
at : - kV Rated Capacity : - kVA - Voltage Change Over Board - Neutral CT
Incase of double secondary voltage, Capacity will be : - Thermometer Pocket
at : - V Rated Capacity : - kVA - Winding Thermometer c/w Alarm & Trip Contact
at : - V Rated Capacity : - kVA - CT for Winding Thermometer
4-6 Additional Taps on High Voltage : +/- 2.5 % & +/- 5 % ( 5 Taps ) - Sudden Pressure Rise Relay + Seal in Relay c/w Alarm & Trip Contact
9. ADDITIONAL INFO : - Ladder
5. POLARITY AND PHASOR RELATIONSHIP : The transformer will be subtractive polarity for single phase and
phasor relationship for three will be Dyn-5 DESCRIPTION

6. ELECTRIC PERFORMANCE :
Primary Voltage Secondary Voltage
6-1 Insulation Class : 24 kV 1.1 kV
6-2 Basic Impulse Level : 125 kV - kV
6-3 Applied Voltage Test During 1 Minute : 50 kV 3 kV
6-4 Induced Voltage Test : Apply 2 times of the rate voltage at 350 cycles per second for 18 second
o
6-5 Temperature Rise : The coil temperature rise measured by resistance method will not exceed 65 C
o
and the oil temperature rise will not exceed 60 C
6-6 Losses at Rated Voltage 20 / 0.4 kV
No Load Losses : 2,000 Watt Note : - FR-3 Fluid
Load Losses ( at 75 °C ) : 15,000 Watt
Total Losses : 17,000 Watt
6-7 Efficiency at % Rated Capacity : 100 75 50 25 %
at P.F. = 1,0 : 98.66 98.90 99.09 99.07 %
6-8 Exciting Current / Off load Current at Nominal Voltage : 2.00 % Date of Approval :
6-9 Percent Impedance : 5.50 % PROPOSER :
6 - 10 Voltage Regulation at P.F. = 1,0 : 1.34 %
Voltage Regulation at P.F. = 0.8 : 4.24 % hp

P180949 - Af

You might also like