LECTURE #14
AC Voltage Controllers
The main purpose of AC voltage controller or AC regulator is to regulate the AC output
voltage apply to the load. Some of the applications of such AC voltage control are as
follows:
   a) Control of heating in industrial heating loads.
   b) Control of illumination in a lighting control system
   c) Control of the RMS magnitude of the voltage in a transformer tap changing
       system
   d) Speed control of industrial AC drive.
14.1 Circuit topology
                                                                Triac based circuit.
       Inverse parallel connection
                          IGBT based circuit with PWM control
Two types of control are normally used:
       (i)    Phase Control
       (ii)   Integral Cycle Control (On-Off Control)
14.2 Phase control
(1) Single phase bidirectional controllers with resistive loads
                               π+α
During the positive half-cycle of input voltage the power flow is controlled by varying the
delay angle of thyristor T1; and thyristor T2 controls the power flow during the negative
half-cycle of input voltage.
The load rms value
                            ˆ sin ωt , and the delay angles of thyristor T1 is α and T2 is
The input voltage, vs (t) = Vs
π+α
The rms output voltage,
              1                              
                  π              2π
                 ∫ ( v s ) dθ + ∫ ( v s ) dθ 
                           2              2
        Vo =                                                                                         (1)
             2π  α             π+α           
                       π                    π
                 2               1           2
        Vo =       ∫
                2π α
                     ( vs ) dθ = ∫ Vˆ s sin θ dθ
                           2
                                 πα
                                                (       )
               V̂s         1      sin 2α                                                          (2)
        Vo =                π−α +        
                 2         π         2 
NB:
  •     Varying the delay angle                 α   from 0 to   π   can vary the RMS output voltage from
        Vs to 0.
As the output voltage is periodical but non-sinusoidal, it consists of the fundamental as
well as higher harmonic components. The DC component is zero because of the
symmetry of the positive and negative waveform. Employing the Fourier analysis the
load voltage can be written as:
                           ∞
        vload (t ) =   ∑ a
                       n =1
                               n   cos nω t + bn sin nωt 
where
                                  2 ⋅π
                             1  ⌠                                               2
                                                                                  T
                                         vs ( t) ⋅cos ( n⋅ωt) d( ωt)
                                                                                T ∫0
                 an            ⋅                                      ⇔ a1 =        vs cos ( nωt )dt
                             π ⌡0
                                  2 ⋅π
                             1  ⌠                                                 T
                               ⋅        vs ( t) ⋅sin( n⋅ωt) d( ωt)             2
                                                                                T ∫0
                 bn                                                    ⇔ b1 =        vs sin ( nωt )dt
                             π ⌡0
             ˆ sin ωt
and vs (t) = V                             For intervals ( α, π ) and ( π + α, 2π )
              s
In the case of an induction motor load, the fundamental component VLoad _1 is of
interest
                     T
               2
               T ∫0
       a1 =         vs cos (1ωt )dt
             2  ˆ                              ˆ sin ωt cos (1ωt )dωt 
                 π                           2π
       a1 =     ∫ Vs sin ωt cos (1ωt )dωt + ∫ V s
            2π  α                          π+α                         
                ˆ π
               4V                       
                    ∫ sin ωt cos ωtdωt 
                 s
       a1 =
               2π  α                   
            ˆ π 1
           2V                                        
       a1 = s  ∫ ( sin(ωt − ωt) + sin(ωt + ωt) )dωt 
            π α 2                                   
            V̂s                           
                  π
       a1 =      ∫ ( sin 0 + sin 2ωt )dωt 
             π α                          
               V̂s   1                 π
       a1 =
                π     2 ( − cos 2ωt ) α 
               V̂s  cos 2α − 1 
        a1 =
                π      2      
                     T
           2
and    b1 = ∫ vs sin (1ωt )dt
           T0
               V̂s                sin 2α 
        b1 =              π − α + 2 
                π
 vload_1 can now be written as
            vload_1( t)   a1 ⋅cos ( ωt) + b1 ⋅sin( ωt)
            vload_1( t)                             (
                          Vload_1_mag⋅sin ωt + φ load_1                 )
where                                                                           a1 
            Vload_1_mag
                                   2
                              a1 + b1
                                            2                φ load_1       atan   
                                                                                b1 
                                   ⋅ a1 + b1 
                               1         2    2
             Vload_1_rms
                                 2
The power factor, assuming input power = output power
                                           Real_Power
             Power_Factor
                               Apparent_Input_Power
                                                2
Where                        Vload_rms
             Real_Power
                                       R
                               Vˆ   Vload _ rms 
             Apparent_Input =  s                
                               2      R       
                                   Vload _ rms          Vload _ rms
               Power_Factor =                       =
Therefore                               Vˆs           Vrms _ input
                                            
                                        2 
Example: (Rashid page 508)
A single-phase full-wave AC voltage controller has a resistive load R = 10 Ω and the
input voltage is Vs = 120 V, 50 Hz. The delay angles of thyristors T1 and T2 are equal: α1
= α2 = π/2. Determine (a) the RMS output voltage Vo (b) the input PF (c) the average
current of thyristors IA and (d) the RMS current of thyristors IR
(2) Single phase bidirectional controllers with resistive and inductive loads
  Phase control [Rashid –pg509][Lander-pg253]
              α ⇒ T1            β   π + α ⇒ T2
Analysis
REFER: (Rashid page 509)
Assume THY1 is fired during the positive half cycle and carries the load current. Due to
the inductance in the circuit, the current of THY1 will not fall to zero at ωt = π , when the
input voltage starts to be negative. THY1 continues to conduct until its current iTHY1 falls
to zero at ωt = β (extinction angle).
With inductive loads, the continuation of conduction beyond the voltage zero means that
there is no control below a certain firing angle delay. Firing control is only possible after
cessation of current (i.e current goes to zero).
When the thyristor THY1 conducts, the voltage equation becomes
                            di1
   V̂s sin ωt = Ri1 + L
                            dt
The above equation has a solution in the form of:
          V̂s
   i1 =       sin(ωt − φ) + A1e− (R / L)t
           Z
where load impedance Z = R 2 + (ωL) 2 and load angle φ = tan −1 (ωL / R)
when ωt = α, i1 = 0 then
             V̂s             R(α)
   A1 = −        sin(α − φ)e L ω
              Z
therefore
          V̂s 
                sin(ωt − φ) − sin(α − φ)e L ω 
                                          R ( α −t )
   i1 =
           Z                                        
The current i1 falls to zero at angle ωt = β (extinction angle). Thus
                                R ( α −t )
                                L ω
 sin(β − φ) − sin(α − φ)e                    =0
β can be found using iterative method (make initial guess of β, find β such as the left-
hand-side equation equals=0)
The rms output voltage
             1  ˆ                              
                  β              π+β
                            2               2
       Vo =
            2π  α
                                  (
                ∫ Vs sin θ dθ + ∫ V      )    (
                                     ˆ sin θ dθ 
                                      s                  )                                              (3)
                                 π+α            
                          β
                     2          2
       Vo =            ∫
                    2π α
                         Vs   (
                         ˆ sin θ dθ    )
                  V̂s         1        sin 2α sin 2β                                                   (4)
       Vo =                    β − α +       −       
                    2         π           2      2 
NOTES:
1) For inductive load, continuous gate pulse is required (i.e. duration of pulse=                    π −α   )
  for the converter to work properly.
                                                                   ; θ = θ = tan −1 
                                                 α       θ ≤α ≤π                         ωL 
2) Control range of the delay angle                  :                                   = load angle
                                                                                     R 
3) If α ≤ θ and continuous gate pulse, load current would not change with α , T1 turn-
  on at ωt = θ and T2 turn-on at ωt = π + θ . Hence, continuous and sinusoidal
  current will be obtained and the output voltage follows the input.
       α
                      ωL 
           θ = tan −1     = load angle
                      R 
14.3 INTEGRAL CYCLE
The thyristor switch connects the AC supply to load for a time tn. The on-time N usually
consists of an integral number of cycles. The thyristors are turned on at the zero-
crossing of AC input voltage.
Analysis
  (i) Harmonic and sub harmonic properties
             a0 = 0
                                 N
                        2π
                                 T
                    1
             an =
                    π    ∫   0
                                     Vˆs sin(ω t ) cos( nω t ) d (ωt )
                         VˆsT                                N
             an =            2           2
                                             (1 − cos(2nπ      ))
                    π (T − n )                               T
                             N
                        2π
                             T
                    1
             bn =
                    π    ∫
                         0
                                     Vˆs sin(ωt )sin(nωt )d (ωt )
                         VˆsT                              N
             bn =            2           2
                                             ( − sin(2nπ     ))
                    π (T − n )                             T
The magnitude of nth harmonic is found to be
                                     2         2
             c n = a n + bn
                        2Vˆs T                     N
              cn =        2         2
                                        (sin( nπ     ))
                     π (T − n )                    T
The rms load voltage is given as
                                     N 2π ˆ        2
              Vrms _ load =            ∫
                                    2πT 0
                                             (
                                          Vs sin ωt dωt   )
                              Vˆs       N
              Vrms _ load =
                                2       T
The average power is given as
                      Vˆs 2 N
              Power =
                      2R T
                                                                                 Vˆs       N
                                                               Vload _ rms         2       T       N
                                        Power_Factor =                       =                 =
The power factor is                                               Vˆs             Vˆ             T
                                                                                       s
                                                                      
                                                                  2                2
Comparison between integral-cycle and phase angle controlled
            PHASE ANGLE                                                      INTEGRAL CYCLE
1. Could be used to control light                             1. Unsuitable for light control i.e. light
                                                                dimmer due to present of sub-
                                                                harmonic components
2. Could be used for motor control.                           2. Unsuitable for motor control. Motor
                                                                will cogging
3. Could be used to control heater.                           3. Suitable for loads with a large
                                                                thermal time period such as electric
                                                                furnace
4. Generate radio frequency                                   4. No radio frequency interference
  interference
5. Effect of voltage dip (ripple voltage)   6. Significant effect due to voltage dips
  is less. Voltage dip is due to initial      because of sub-harmonic
  large starting current                      component.
14.4 Cycloconverter
Applicable for low speed and very large horsepower synchronous and induction motors.
The firing angles in each phase are cyclically controlled to yield a low-frequency
sinusoidal output. The output voltage is derived directly from the line-frequency input
without an intermediate dc link.