A dvanced G E reen nergy &C ontrol
Over and Under protection relay
M A N U A L
OUV Series
April 2018
02/26230107 : ! س- ا زھ ا د دة – ا ھرة- ز – ش ل ن ر ح8
8z Block –Belal ben Rabah St. – AlnozhaAlgadeda – Cairo – Egypt – Tel/Fax: 02-26230107
02
Website: www.agec-eg.com
www.agec E-mail: design@agec-eg.com
eg.com
Page 1 of 18
Index
Content Page
1. Safety cautions 3
2. Features 3
3. Device identification 4
3.1 Front 4
3.2 Back 5
4. Operation procedures 7
4.1 Start up 7
4.2 Settings 7
4.3 Faults 14
5. Technical Specifications 17
5.1 Electrical Specifications 17
5.2 Mechanical Specifications 17
5.3 Mechanical Protection 17
5.4 Electrical protection 17
6. Panel Cutout 18
7. Ordering information 18
Page 2 of 18
*For your safety, please read the following before using.
1. Safety Cautions
Warning
1. It must be mounted on Panel.
May
ay give an electric shock.
2. Do not connect terminals while power is on.
May
ay give an electric shock.
3. Do not disassemble and and modify this unit. If it is necessary please
contact us.
May
ay give an electric shock / cause fire.
4. Please check the terminals
terminal numbers before connecting power lines.
May cause fire.
5. While cleaning the unit, do not use water or an oil-based
oil based detergent.
May
ay cause an electric shock / fire and so the unit will be damaged.
6. check the polarity before connecting terminals.
terminals
May cause fire.
2. Features:
1- Measure and display the real value of the input 3 phase AC voltage (L-N).
(L
2- Measure and display the real value of the output DC voltage.
3- AC over (ANSI 59) and under voltage (ANSI 27) limits protection can be
adjusted via display.
4- DC over (ANSI 59) and under voltage (ANSI 27) limits protection can be
adjusted via display.
5- Indicate the fault in LCD.
6- All settings stored in EEPROM.
7- Numerical LCD (16 * 2). 2)
8- Parameters adjust via keypad.
keypad
9- Change over Form C relay for each protection function.
10- One Normally open relay Form A for common alarm.
11- Five programmable relays.
12- Five indication Leds for each relay.
13- Auto / Manual resetset option.
Page 3 of 18
3. Device identification
3.1. Front
1
2 DC = 126V (Normal) 3
4 222V 220V 221V
5 6
7 8
10 14
11 12 13
1 Numerical (16*2) LCD display shows measurements, settings and faults.
2 DC voltage measurement.
3 Normal operation for the relay.
4 AC 3 phase voltage measurement.
5 Up arrow key (increase parameter value in edition mode).
6 Down arrow key (decrease parameter value in edition mode).
7 Menu/ESC key (enter and exit in edition mode)
8 Enter/RESET key(store parameter value and enter in edition mode,reset.in protection mode).
9 Healthy Led.
10 Programmable relay 1 indication Led.
11 Programmable relay 2 indication Led.
12 Programmable relay 3 indication Led.
13 Programmable relay 4 indication Led.
14 Programmable relay 5 indication Led
Page 4 of 18
3.2. Back
8 7 6 5 4 3 2 1
NC COM NO - + NC COM NO
Aux Supply
R5 50-270 VDC/VAC
R4
BAT
AC 3Ph (380VAC) 110 / 220 VDC
E N L1 L2 L3 - +
R3 R2 R1.Gen
COM NO NC NO COM NC NO COM
24 23 22 21 20 19 18 17
16 15 14 13 12 11 10 9
1 Normally Open of internal relay (250VAC – 2 A) for programmable relay 4.
2 Common of internal relay (250VAC – 2 A) for programmable relay 4.
3 Normally Close of internal relay (250VAC – 2 A) for programmable relay 4.
4 Positive or Line of the aux. supply.
5 Negative or neutral of the aux. supply.
6 Normally Open of internal relay (250VAC – 2 A) for programmable relay 5.
7 Common of internal relay (250VAC – 2 A) for programmable relay 5.
8 Normally Close of internal relay (250VAC – 2 A) for programmable relay 5.
9 Common of internal relay (250VAC – 2 A) for general relay 1.
10 Normally Open of internal relay (250VAC – 2 A) for general relay 1.
11 Normally close of internal relay (250VAC – 2 A) for programmable relay 2.
12 Common of internal relay (250VAC – 2 A) for programmable relay 2.
13 Normally Open of internal relay (250VAC – 2 A) for programmable relay 2.
14 Normally close of internal relay (250VAC – 2 A) for programmable relay 3.
15 Normally Open of internal relay (250VAC – 2 A) for programmable relay 3.
16 Common of internal relay (250VAC – 2 A) for programmable relay 3.
17 Positive of the DC output & batteries.
18 Negative of the DC output & batteries.
19 Not connected.
20 Phase 3 of the 3 phase AC voltage of the device.
21 Phase 2 of the 3 phase AC voltage of the device.
22 Phase 1 of the 3 phase AC voltage of the device.
23 Neutral of the 3 phase AC voltage of the device.
22
24 Earth of the device & Station.
Page 5 of 18
• General relay can be changed between NO / NC using internal
jumper in the device
• Default of the relay is NO
Figure 1 Figure 2
Figure 3 Figure 4
• Long press on the lock key as shown in Fig.1
• Pull up the relay while holding the lock from the housing as showm
in Fig.2
• In Fig.3 jumper of the general relay is marked by an elipce.
• In Fig.4 Zoomed in view of the jumper.
Page 6 of 18
4. Operations Procedures:
Procedures
4.1 Start up :
First when connect power to
t the device the LCD will show the following:
AGEC
TEL: 02-26230107
Then shown the for example:
example
DC = 125 V (Normal)
222V 215V 219V
4.2 Settings :
To adjust
st the protection parameters we go to “edition
edition mode”
mode by
pressing MENU/ESC key for 3 sec until the screen shows
show :
->AC Settings
DC Settings
Using and keys you can select between different parameters like
DC settings and Reset settings.
To set AC settings Press then appear
->AC ovr active
AC ovr value
To activate AC over press Enter/Reset in the previous
ious screen.
Then appear
->AC ovr Enable
AC ovr Disable*
Press Enter/Reset to activate AC over , your selection will be
marked by (*)
->AC ovr Enable*
AC ovr Disable
Page 7 of 18
To set the other values of AC over press Menu/ESC in the
previous screen then appear
AC ovr active
->AC ovr value
To set AC over Value press Enter/Reset then
AC ovr value
AC ovr=250 V
To increase the
e AC over value press up arrow key
To decrease the AC over value press down arrow key
To store settings press ENTER/Reset key the display will show
AC ovr value
Save ok
Then appear
AC ovr value
->AC ovr hys
Press Enter/Reset to set AC over hysteresis value
AC ovr hys
AC ovr hys.=5 V
To increase the AC over hys value press up arrow key
To decrease the AC over hys value press down arrow key
To store settings press ENTER/Reset key the display will
show
AC ovr hys
Save ok
Then appear
AC ovr hys
->AC ovr delay
Page 8 of 18
Press Enter/Reset to set AC over delay value
AC ovr delay
AC ovr del.= 6 S
To increase the AC over delay value press up arrow key
To decrease the AC over delay value press down arrow key
To store settings press ENTER/Reset key the display will show:
show
AC ovr delay
Save ok
Then appear
AC ovr delay
->AC ovr relay
Press Enter/Reset to set AC over relay
AC ovr relay
AC ovr rel->1
To scroll between the AC over relays press up arrow key &
To select the desired press ENTER/Reset key the display will
show:
AC ovr relay
AC ovr rel->1*
Your selection will be marked by (*)
Press down arrow key until shows:
AC ovr relay
AC ovr rel->save
Press Enter/Reset to save
AC ovr relay
Save ok
Page 9 of 18
Then appear
AC over relay
-
->AC undr active
Press down 5 times then appear
AC undr relay
->Escape
Press Menu/Escape to get back to main screen in Edition Mode.
-
->AC settings
DC settings
Press Menu/Escape again to get back to Main screen
DC = 125 V (Normal)
222V 215V 219V
*Do the previous steps for all parameters
Page 10 of 18
To set AC under options :
Long press for
DC = 125 V (Normal) ->AC
>AC settings
222V 215V 219V 3 sec DC settings
AC over relay ->AC
>AC over active
5 Times
->AC under active AC over value
->AC undr enable AC un enabled
Then
AC undr disable* Save ok
Use & to AC undr value AC undr active
set value then to AC undr = 180 V ->AC
>AC undr value
save
AC undr value AC undr value
Then
Save ok ->AC
>AC undr hys
AC undr hys Use & to AC undr hys
Save ok set value then to AC undr hys.5 V
save
Then
AC undr hys AC undr delay Use & to
-> AC undr delay AC undr del.=5 S set value then to
save
AC undr delay AC undr delay
Then
->AC undr relay Save ok
To next Page
Page 11 of 18
From previous page
Use & to
AC undr relay scroll between relays , press AC undr relay
AC undr relay->1
>1 to save AC undr relay->1*
relay
Your selection is marked by
(*)
AC undr relay AC undr relay Press without
hold until screen
Save ok AC undr relay->save shows
Then
AC undr relay ->AC settings Press without
hold until screen
->Escape DC settings
shows
DC = 125 V (Normal) Reset Settings
222V 215V 219V ->Escape
>Escape
Do the previous steps for all parameters
For DC input value selection:
selection
Long press for
DC = 125 V (Normal) ->AC
>AC settings
222V 215V 219V 3 sec DC settings
->DC i/p select AC settings 1 Time
DC over active -> DC settings
->DC I/P=110 V * Use & to DC I/P=110 V
DC I/P=220 V select then to Save ok
save
To next page
Page 12 of 18
From previous page
AC settings ->DC
>DC over active
-> DC settings DC over value
DC = 125 V (Normal)
222V 215V 219V
* Your selection will be marked by (*)
*For Reset settings options:
Long press for
DC = 125 V (Normal) ->AC settings
222V 215V 219V 3 sec DC settings
2 Times
->Manual reset * DC settings
Auto reset ->Reset
>Reset settings
Use & to Auto reset
Then
select then to Enable ok
save
DC = 125 V (Normal) Reset settings
222V 215V 219V ->Escape
Your selection will be marked by (*).
Page 13 of 18
Parameters list:
Parameter ANSI Default Min Max Unit
DC Range 110 110 220 -
AC over voltage active
activ - Enable - - -
AC over voltage value (U>) 59 250 130 320 V
AC over hysteresis 5 0 30 V
AC over delay 5 0 30 sec
AC over relay - R1&R2 - - -
AC under voltage active - Enable - - -
AC under voltage value (U<) 27 180 110 270 V
AC under hysteresis
teresis 5 0 30 V
AC under delay 5 0 30 sec
AC under relay - R1&R3 - - -
DC over voltage active - Enable - - -
DC over voltage value (U>) 59 142 66 153 V
DC over hysteresis
teresis 5 0 30 V
DC over delay 5 0 30 sec
DC over relay - R1&R4 - - -
DC under voltage active - Enable - -
DC under voltage value (U<) 27 76 55 132 V
DC under hysteresis
teresis 5 0 30 V
DC under delay 5 0 30 sec
DC under relay - R1&R5 - - -
Reset settings - Manual - - -
4.3Faults :
When any fault occurs:
The LCD will show the fault.
fault
The Aux relay for the function will be active (NO & COM closed).
The fault red led related to the relay will be on.
In case of faults in Auto reset mode the related relay for each
protection function will reset automatically only if the reason of fault
disappeared like over , under voltage ……etc.
In case of faults in manual mode resetting the related relay for
each protection
ion function is done by pressing ENTER/RESET
ENTER/
key
Page 14 of 18
In case of AC faults, the LCD will show any of the following:
AC is over AC is under
AC input=260 V AC input=110 V
• In case of AC Over the general and the related relay will be
activated.
• In case of AC Under the general and the related relay will be
activated.
• If the AC value returned back to the user’s set value the LCD will show
Any of the following:
AC is normal <O> AC is normal <U>
Delay time= 4 S Delay time= 4 S
• In case of returning from the user’s over set value AC is normal will be
quoted by <O>.
• In case of returning from the user’s under set value AC is normal will
be quoted by <U>.
• After delay time is up screen goes back to main screen.
Page 15 of 18
In case of DC fault, the LCD will show any of the following:
DC is Over DC is under
DC input= 202 V DC input= 42 V
• In case of DC Over the general and the related relay will be
activated.
• In case of DC Under the general and the related relay will be
activated.
• If the DC
C value returned back to the user’s set value the LCD will
show
Any of the following:
DC is normal <O> DC is normal <U>
Delay time= 4 S Delay time= 4 S
• In case of returning from the user’s over set value DC
C is normal will be
quoted by <O>.
• In case of returning from the user’s under set value DC
D is normal will
be quoted by <U>.
• After delay time is up screen goes back to main screen.
If manual reset mode is enabled the fault will be locked even if the
fault reason disappeared until pressing to reset the related
relay of the fault.
If manual reset mode is enabled the fault can be cleared by
pressing ENTER/RESET key even if the fault reason is not
disappeared.
If Auto reset mode is enabled the fault will disappear automatically
if the fault reason disappeared.
Page 16 of 18
5. Technical Specifications:
5.1 Electrical Specifications:
Inputs:
Aux Power supply :50 to 270 VDC / VAC
DC Voltage range : 110 VDC or 220 VDC
AC Voltage range :380 VAC/3Ø
Frequency range : 50 Hz
Range of protection
Over Voltage – U>(ANSI 59) 0.6 Un to 1.4 Un.
Reset factor 1.15 Un.
Under Voltage– U< (ANSI 27) 0.5 Un to 1.2 Un.
Reset factor 0.9 Un.
Outputs:
Aux relay: 4 Free contact (NO,COM & NC) 2A @ 250VAC
Alarm: 1 Free contact (NO) or (NC) 2A @ 250VAC
5.2 Mechanical Specifications:
Dimension :96 mm * 96 mm * 112 mm.
Panel cutout :92 mm * 92 mm ± 1.
5.3 Protection Specifications
Temperature :-5oC to +60oC
Enclosure IP : IP 45
The enclosure is isolated according to standard EN 60439-1
specification.
The enclosure is protected against external mechanical shocks.
5.4 Electrical Protection:
Over and under AC input voltage which can be adjusted.
Over and under DC output voltage which can be adjusted.
Page 17 of 18
6. Panel Cutout 92±1
92±1
(Unit: mm)
7. Ordering information
OUV – XXXXX-X-X
OUV Over / Under Voltage protection relay Sires.
0 AC Over protection deactivated.
1 AC Over protection activated.
0 AC Under protection deactivated.
1 AC Under protection activated.
0 DC Over protection deactivated.
Functions
1 DC Over protection activated.
0 DC Under protection deactivated.
1 DC Under protection activated.
0 Earth Leakage protection deactivated.
1 Earth Leakage protection activated.
Outputs 1 1 Form C relay + Serina 12 V.
2 4 Form C relay + 1 Form A relay
DC range A 110 DC voltage.
B 220 DC voltage.
C 110 and 220 DC voltage.
Page 18 of 18