RESD Series Electronic Thermostat User Manual
RESD series thermostat adopts a button-hidden fashion appearance design. It
is used to control temperature for light industry, commercial and residential
environments. Models are available for heating, cooling and ventilating control. The
application is for the control of Fan Coil heating/cooling equipment.
      RESD series thermostats are microprocessor controlled and have a big LCD
display, which displays the current working state (cooling, heating, ventilating), fan
speed, ambient temperature, setting temperature etc. pushbutton includes turn on/off
(     ), mode (    ), clock (  ), fan speed (      ) and temperature adjustment (   ).
MODEL DENOMINATIONS
 RESD -
      HC2: Control Motorized Valve and 3-speed fan. When the temperature reaches the set-point, it will close the
            Motorized Valve and Fan both.
      HC4: Control 4 pipe fan coil units, Control two Motorized Valves and 3-speed fan. When the temperature reaches the
            set-point, it will close the Motorized Valve and Fan both.
BASIC FEATURES                                                 STATUS DISPLAY
     Room temperature setting                                     Working Status: Cool       , Heat       , Ventilation
     Manual or Auto 3-speed changeover                            Fan Speeds: Low         , Medium        , High    and Auto
     Defrost (low temperature protection)                         Room temperature display
     Clock, Timer,7 days programmable (-T74)                      Temperature setting display
     Blue backlight                                               FCU valve
     Auto Restart ( Option )                                      Clock week display
     Keypad Lock ( Option )
SPECIFICATIONS
     Sensing element:          NTC                                Rated Power: < 1 W
     Accuracy: Temperature ± 1°C Time ± 1 min/month               Wirings: Screw-in terminals, each terminal capable of
                                                                                                        2                   2
     Set-point range:          5 to 35°C                                      accepting 2 × 1.5 mm or 1 x 2.5 mm wires
     Display range:            0 to 55°C                          Housing: PC + ABS Flame Retardant
     Operation environment: T min 0°C T max 45°C)                 Dimensions: 86 × 86 × 13 mm ( W × H × D )
     Power supply:             85 to 260V~, 50/60Hz               Hole pitch: 60 mm ( Standard )
     Switch current rating: Resistive: 2 A, Inductive: 1 A        Protection Class: IP30
     Switching action          Type 1B                            Display: LCD
     Control pollution         degree 2
     Rated impulse V           2.5kV
     Ball Hardness             75°C
     Power reserve             24 hrs minimum
     Setting accuracy       ±0.5°C     ±1 minute
                                                           Page 1 of 4
WIRING DIAGRAMS
      RESD-HC2                              85to 260V~ 50/60Hz         RESD-HC4                              85to 260V~ 50/60Hz
                                                   N   L                                                            N   L
                         N                                                              N
                                                                                        V2            Heating
                         V1              Value                                          V1                Cooling
                         L                                                              L
                         Hi                                                             Hi
                         Med                                                            Med
                                      Fan                                                              Fan
                         Low                                                            Low
OPERATION
     On/Off: Press “     ” to turn on, press “   ” again to turn off thermostat and its output.
     Setting temperature: press “” to reduce temperature, press “” to raise temperature (0.5°C changed each press)
set point only valid in current period of time; Clock adjustment, turn on/off or 7 days programming modification, it will
perform new settings.
    Note: When 4 periods function On, press "” or ” ” to adjust current set-point, "Override" will show on LCD, it
denote the thermostat will run as per current setting instead of 4 periods setting.
     Mode Selection: Press “ ” to select cooling “ ”, heating “ ” or ventilation “            ” modes, the related icon will flash,
and it will be confirmed automatically after 6 seconds.
     Fan speed select: Press “      ” to select “    (Hi),      (Med),     (Low),     (Auto)”.
    In mode “       (Auto)”, the fan-speed will changed automatically. When: LOW-speed When the difference between
room-temperature and setting-temperature exceed 1°C , Auto MED-speed When exceed °CAuto HI-speed When e xceed 3°C.
CLOCK CALIBRATION
     Clock setting: Press “” till to display “hh:mm” and “hh” flash, press “” or “” to adjust hour, press “”, “mm” flash,
press “” or “” to adjust minute; Press “”, “week” flash, press “” or “” to adjust Mon to Sun.
TIMER ON AND TIMER OFF
     Timer on: Press “”, till to display “” and “ON” and all flash, and also “hh” flash, press “” or “” to adjust hour.
Press “”, “mm” flash, press “” or “” to adjust minute.
     Timer off: Press “”, till to display “” and “OFF” and all flash, and also “hh” flash, press “” or “” to adjust hour.
Press “”, “mm” flash, press “” or “” to adjust minute.
     Canceling timer on: Press “”, till to display “” and “ON” and all flash, and also “hh” flash, press “” or “” to
adjust hour to “--:--”. Press “”, “mm” flash, press “” or “” to adjust minute to “--:--”.
     Canceling timer off: Press “”, till to display “” and “OFF” and all flash, and also “hh” flash, press “” or “” to
adjust hour to “--:--”. Press “”, “mm” flash, press “” or “” to adjust minute to “--:--”.
                                                              Page 2 of 4
7 DAYS PROGRAMMING ( -T74 )
     7 days four events programming: four events each day (1, 2, 3, 4), there is starting time and programming temp for
each event. (chart.1)
    Please make good plan of starting time and temp. Before 7 days programming according below:
     Press “” for 3 seconds, until “PROG.”, “1” and “Mon” display, set 4 events programming of Mon according Chart 1
and below steps.
    “hh” flash in “hh:mm”, set hours with “” and “”; Press “”, “mm” flash in “hh:mm”, press “” and “”to set minutes.
    Press “”, programming temp. flash, press “” or “” to set programming temp.
    Press “”, set 2 - 4 events of Mon. by repeating steps above.
                                                                          Chart
       Week                      1                            2                           3                      4
                        Staring T / temp.℃        Staring T / temp. ℃         Staring T / temp. ℃      Staring T / temp. ℃
        Mon.              7:00       25℃             8:00         25℃             18:00       25℃        21:00       25℃
        Tue.              7:00       25℃             8:00         25℃             18:00       25℃        21:00       25℃
        Wed.              7:00       25℃             8:00         25℃             18:00       25℃        21:00       25℃
        Thu.              7:00       25℃             8:00         25℃             18:00       25℃        21:00       25℃
        Fri.              7:00       25℃             8:00         25℃             18:00       25℃        21:00       25℃
        Sat.              7:00       25℃             8:00         25℃             18:00       25℃        21:00       25℃
        Sun.              7:00       25℃             8:00         25℃             18:00       25℃        21:00       25℃
    Repeat above setting steps for “Tue Wed Thu Fri Sat Sun”.
KEYPAD LOCK ( Option )
     With thermostat standby for 30 seconds, the function will enable automatically. The " " will be displayed on the
LCD and keypads are locked for fear anyone operated.
     To disable the function: Press “     ” button for 5 seconds till " " disappeared on the LCD, the function will be disable.
AUTO RESTART ( Option )
     When the thermostat is at ON status for 6 seconds, if power cut, it will return back to running automatically with the
status how it is one minute ago after power coming back.
     When the thermostat is at OFF status for 6 seconds, if power cut, it will keep OFF status after power coming back.
DEFROST (Low temperature protection)
     Description: when the thermostat turns off and the room temperature is lower than 5 , it will be turned on
automatically in heating mode with “     ” showing, thermostat will be in heat mode and fan runs in high speed. The
thermostat will turn off when temperature is higher than 7 .
     Set low temperature protection: Turn off the thermostat, press “ ” and hold for 3 seconds, it will display “ON” or
“OF”, Press “” or “” key to adjust. “OF” indicates invalid low temperature protection, “ON“ indicates valid low
temperature protection function. The default is “OF”.
ALARM
    Trouble appears for sensor, fan and valve will be turned off by thermostat, as indicating “ ”
and “E1” or “E2”.
    E1: alarming for short circuit of sensor.E2: alarming for open circuit of sensor.
    “HI” indicated when temp. Is more than 55 . “LO” indicated if temp. Is lower than 0 .
                                                            Page 3 of 4
INSTALLATION
                                        1. Open the clip
           2. Wiring             3. Fix thermostat with two bolts   4. Lock surface and finished
Attention:
A standard electrical box is required: Wiring work should be done according to wiring diagram.
           Water, mud etc. impurity should be kept outside of thermostat or damage will occur