Blum 2017
Blum 2017
H I G H L I G H T S G R A P H I C A L A B S T R A C T
a r t i c l e i n f o a b s t r a c t
Article history:                                            On-site sewage treatment facilities (OSSFs), which are used to reduce nutrient emissions in rural areas,
Received 13 July 2016                                       were screened for anthropogenic compounds with two-dimensional gas chromatography–mass spectrometry
Received in revised form 16 September 2016                  (GC × GC–MS). The detected compounds were prioritized based on their persistence, bioaccumulation,
Accepted 16 September 2016
                                                            ecotoxicity, removal efficiency, and concentrations. This comprehensive prioritization strategy, which was
Available online xxxx
                                                            used for the first time on OSSF samples, ranked galaxolide, α-tocopheryl acetate, octocrylene, 2,4,7,9-
Editor: D. Barcelo                                          tetramethyl-5-decyn-4,7-diol, several chlorinated organophosphorus flame retardants and linear alkyl benzenes
                                                            as the most relevant compounds being emitted from OSSFs. Twenty-six target analytes were then selected for
Keywords:                                                   further removal efficiency analysis, including compounds from the priority list along with substances from the
Two-dimensional gas chromatography–mass                     same chemical classes, and a few reference compounds. We found significantly better removal of two polar con-
spectrometry                                                taminants 2,4,7,9-tetramethyl-5-decyn-4,7-diol (p = 0.0003) and tris(2-butoxyethyl) phosphate (p = 0.005) in
Non-target analysis                                         soil beds, a common type of OSSF in Sweden, compared with conventional sewage treatment plants. We also re-
Ranking                                                     port median removal efficiencies in OSSFs for compounds not studied in this context before, viz. α-tocopheryl
Decentralized sewage treatment
                                                            acetate (96%), benzophenone (83%), 2-(methylthio)benzothiazole (64%), 2,4,7,9-tetramethyl-5-decyn-4,7-
Removal efficiencies
                                                            diol (33%), and a range of organophosphorus flame retardants (19% to 98%). The environmental load
Organic micropollutants
                                                            of the top prioritized compounds in soil bed effluents were in the thousands of nanogram per liter range,
    ⁎ Corresponding author.
      E-mail address: kristin.blum@umu.se (K.M. Blum).
http://dx.doi.org/10.1016/j.scitotenv.2016.09.135
0048-9697/© 2016 The Authors. Published by Elsevier B.V. This is an open access article under the CC BY-NC-ND license (http://creativecommons.org/licenses/by-nc-nd/4.0/).
266                                            K.M. Blum et al. / Science of the Total Environment 575 (2017) 265–275
                                                viz. 2,4,7,9-tetramethyl-5-decyn-4,7-diol (3000 ng L−1), galaxolide (1400 ng L−1), octocrylene (1200 ng L−1),
                                                and α-tocopheryl acetate (660 ng L−1).
                                                   © 2016 The Authors. Published by Elsevier B.V. This is an open access article under the CC BY-NC-ND license
                                                                                                          (http://creativecommons.org/licenses/by-nc-nd/4.0/).
1. Introduction                                                                      et al., 2010; Wilcox et al., 2009). Removal efficiencies were mainly in-
                                                                                     vestigated in lab-scale (Leal et al., 2010; Teerlink et al., 2012) or field-
    Wastewater is commonly treated in sewage treatment plants (STPs)                 scale experimental facilities (Conn et al., 2010b; Du et al., 2014; Garcia
to reduce the nutrient load into the environment. Whereas centralized                et al., 2013) and rarely at real household or community OSSFs (Conn
STPs are only economically sustainable if the population is dense and                et al., 2010a, 2006; Wilcox et al., 2009). Furthermore, studies examining
large enough, smaller decentralized on-site sewage treatment facilities              the fate of OSSF contaminants in soil are sparse (Carrara et al., 2008;
(OSSFs) provide a larger economic benefit for smaller communities                     Conn et al., 2010b).
and single households in rural areas (Corcoran et al., 2010). In the                     Prioritization strategies based on non-targeted data to identify envi-
United States and Sweden, around 20% (Olshammar et al., 2015; U.S.                   ronmentally relevant contaminants have previously focused on criteria
EPA, 2008) of all households are connected to OSSFs. Sweden has                      such as ecotoxicity (Bastos and Haglund, 2012), exposure (Rager et al.,
753,000 OSSFs (Olshammar et al., 2015), of which infiltration systems                 2016; Singer et al., 2016) or bioactivity (Rager et al., 2016). Other
dominate (25%), followed by septic tanks without further treatment                   prioritization/ranking strategies have focused on selected groups
(22%), soil beds (SBs) (16%), grey water separation (17%), and aerobic               of water contaminants, such as active pharmaceutical ingredients.
treatment systems (ATSs) (2%) (Olshammar et al., 2015). Septic tanks                 These approaches prioritized based on ecotoxicity data (Sanderson
consist of a container that retains wastewater and allows for sedimenta-             et al., 2004), biodegradation, bioaccumulation and ecotoxicity data
tion to occur. Solids and digested organic matter settle to the bottom,              (Wennmalm and Gunnarsson, 2005), or prescription dispensation, en-
whereas floatable solids rise to the top and are discharged with the ef-              vironmental concentrations, half-lives, octanol-water partition coeffi-
fluent from the tank (U.S. EPA, 2000a). These treatment systems are                   cients, and ecotoxicity data (Cooper et al., 2008). Attempts have also
nowadays restricted in Sweden unless they are combined with addi-                    been made to start with large inventories of industrial chemicals or
tional treatment techniques. In soil infiltration systems, the septic tank            pharmaceuticals and use prioritization schemes to identify potentially
effluent is infiltrated into the ground at the treatment site to further re-           persistent and bioaccumulating substances (Andersson et al., 2011;
move nutrients (macropollutants). SBs are similar to infiltration sys-                Howard and Muir, 2011).
tems and consist of layers of soil, gravel, and sand that are surrounded                 In our study we applied a two-stage strategy (Fig. 1), to increase the
by a less permeable material to prevent uncontrolled infiltration (U.S.               knowledge of micropollutants emitted from OSSFs into the environ-
EPA, 2000b). ATSs exist as continuous or batch-flow systems and are                   ment (Stage I) and to evaluate the treatment efficiency of OSSFs
commonly called package treatment plants. By actively aerating the                   (Stage II). In Stage I, we aimed to identify and prioritize environmentally
waste water, they promote biological activity and enhance degradation                relevant organic contaminants emitted from OSSFs by using a two di-
processes (U.S. EPA, 2000c, 2000d).                                                  mensional gas chromatography–mass spectrometry (GC × GC–MS)
    Like STPs, OSSFs are primarily designed to remove macropollutants                based non-target methodology. The use of GC enabled us to identify
and pathogens rather than micropollutants (Petrovic, 2003), but few                  persistent and bioaccumulating non-polar compounds, which would
studies have focused on the occurrence of organic micropollutants in                 be difficult to detect using screening methodologies based on liquid
OSSF effluents. Most of these studies have focused on selected target                 chromatography (LC). Additionally, the use of GC× GC allowed better
analytes, including fragrances like tonalide (AHTN) (Leal et al., 2010)              separation of the analytes from interferences in complex samples with-
and galaxolide (HHCB), the biocide triclosan (TCS) (Conn et al., 2010a,              out extensive sample preparation. The resulting compounds were prior-
2010b, 2006), the UV filters 2-phenyl-5-benzimidazolesulfonic acid                    itized based on removal efficiencies and effluent concentrations along
(Leal et al., 2010) and octocrylene (OC) (Leal et al., 2010), nonylphenols           with environmental hazard criteria such as persistence, bioaccumula-
(Conn et al., 2010a, 2010b; Stanford and Weinberg, 2010), bisphenol A                tion potential, and toxicity (PBT), and environmentally relevant target
(BPA) (Conn et al., 2010a), and steroid estrogens (Leal et al., 2010;                analytes were selected. To widen the physicochemical property domain
Stanford and Weinberg, 2010). Such targeted approaches can oversee                   these target analytes were supplemented with analogues of the same
a large number of potentially relevant compounds. Non-targeted ap-                   classes of compounds and a few commonly used reference compounds.
proaches can be used to generate more comprehensive information                      This facilitated the evaluation of relative removal efficiencies between
about contaminants present in a wastewater sample. We have only                      different contaminants and different treatment technologies, specifical-
identified one study where non-targeted screening was used to find                     ly between SBs and STPs, and the quantification of environmental loads
contaminants in grey water extracts by gas chromatography–mass                       in Stage II (Fig. 1).
spectrometry (GC–MS) (Eriksson et al., 2003). However, this study did                    To the best of our knowledge, our study is the first to use a compre-
not include any environmental relevance prioritization for the 190 ten-              hensive non-targeted approach based on GC×GC–MS, combined with a
tatively identified components. In addition to concerns for emissions to
surface waters, micropollutants that most likely originated from OSSFs
have been detected in nearby ground water or drinking water wells,
e.g. the pesticide diethyltoluamide (DEET) (Del Rosario et al., 2014),
the pharmaceuticals ibuprofen (Carrara et al., 2008; Del Rosario et al.,
2014) and sulfamethoxazole (Godfrey et al., 2007), the plasticizer
tris(2-butoxyethyl)phosphate (TBEP) (Phillips et al., 2015), organo-
phosphorus flame retardants (OPs) (Schaider et al., 2016), per- and
polyfluoroalkyl substances, and steroid hormones (Swartz et al., 2006).
    Previous studies have reported similar removal efficiencies for ATSs
and STPs (Du et al., 2014; Garcia et al., 2013; Wilcox et al., 2009) and
worse removal efficiencies in anaerobic septic tanks compared to aero-                Fig. 1. Design of the study using comprehensive gas chromatography–mass spectrometry
bic systems (Conn et al., 2006; Du et al., 2014; Garcia et al., 2013; Leal           (GC×GC–MS).
                                               K.M. Blum et al. / Science of the Total Environment 575 (2017) 265–275                                         267
PBT based prioritization strategy, to identify organic micropollutants in            kept at 80 °C for 1 min, raised at a rate of 4 °C min− 1 to 300 °C, and
OSSF effluents. Our study is also the first to compare OSSFs and STPs                  held isothermal for 3 min. The secondary oven and the modulator
using multivariate analysis and to report removal efficiencies and efflu-              were operated with a +15 °C and +55 °C offset, respectively, to the pri-
ent concentrations for OSSFs for a number of emerging micropollutants.               mary oven. The modulation period was 3 s with a 0.6 s hot pulse time
                                                                                     and a 0.9 s cooling time. The transfer line temperature was set to
2. Experimental                                                                      325 °C, and the ion source temperature was set to 250 °C. Electron ion-
                                                                                     ization at 70 eV was used, and mass spectra were recorded from 45 to
   The study was divided into two stages (Fig. 1). The analytical proce-             750 m/z with a 260 s acquisition delay and an acquisition rate of 200 Hz.
dures used throughout Stage I are summarized in Fig. 2, whilst a more                    The data acquisition and processing was performed as described in
detailed description is given in Sections 2.1 and 2.2.                               Fig. 2 using the ChromaTOF-GC Software (v4.50.8.0, Leco®). The data
                                                                                     processing included baseline correction, picking of peaks with a
2.1. Non-target screening: identification of environmentally relevant con-            signal-to-noise ratio (S/N) ≥ 100, n-alkane retention index calculation,
taminants discharged from on-site sewage treatment facilities (Stage I)              area/height calculation based on the total ion chromatogram, and an
                                                                                     NIST-MS library search (covering EI MS spectra for ~240,000 chemicals)
2.1.1. Sampling design and sample collection                                         with a minimum similarity criterion of 65%. The resulting peaks were
    Based on the shares of OSSF installations in Sweden (Olshammar                   aligned using the Java application GUINEU (Castillo et al., 2011) based
et al., 2015), we selected SBs, ATSs, and grey water separation as repre-            on retention indices and spectra, and peak areas were normalized to
sentative OSSF treatment systems. Soil infiltration systems were not in-              chrysene-d12. The peaks were then filtered based on 13% detection fre-
cluded because they do not have a defined outlet and it is generally not              quency (minimum 8 out of 63 samples, including blanks, quality assur-
possible to sample effluents in those facilities. Septic tank influents were           ance standards, and technical replicates) and blank levels (normalized
not sampled due to sample heterogeneity problems.                                    peak area of a sample at least 10-fold higher than that of the blank). Fi-
    The first sampling campaign was conducted in October and Novem-                   nally, the spectra of the remaining peaks were searched again against
ber 2013. Influent and effluent wastewater was grab sampled at 13 dif-                 the NIST-MS library and manually investigated to ensure that peaks
ferent OSSFs in Sweden, including six SBs (1 to 40 population                        that were misassigned by the library were corrected or excluded. Only
equivalents (PE)), four ATSs (5 to 21 PE), and three grey water separa-              tentatively identified compounds of most likely anthropogenic origin
tion systems (2 to 10 PE). Influent samples were taken after the last                 were considered for the next step, therefore long-chain fatty acids and
chamber of the septic tank to obtain a relatively homogenous sample                  their esters, which often originate from excreta (Paxéus, 1996), were
of the influent. In addition, samples from conventional activated sludge              excluded (Fig. 2).
based treatment plants were taken – three medium-sized STPs (135 PE
to 2500 PE) and one sample from a large STP (440,000 PE) (Supplemen-                 2.1.4. Prioritization of chemicals
tal Table S1).                                                                           The approximately 300 tentatively identified compounds (Supple-
                                                                                     mental Table S2) were further characterized and filtered to isolate the
2.1.2. Liquid-liquid and Soxhlet extraction                                          most environmentally relevant OSSF-specific compounds (Fig. 2). The
    Wastewater samples were filtered through 12 μm cellulose nitrate                  compounds had to be persistent, bioaccumulative, or toxic (PBT) and
membrane filters (GE Healthcare Life Sciences, Buckinghamshire, UK),                  had to be used or produced in significant quantities. Apart from occur-
and the filters were wrapped in aluminum foil and stored at − 20 °C                   rence in effluent samples, the prioritized compounds fulfilled at least
until sample preparation. To avoid issues of poor representativity due               one of the following PBT cut-off values: i) a half-life in water ≥
to small facility sizes (1 to 40 people connected), we pooled samples                60 days, ii) a bioconcentration factor (BCF) ≥ 1000, iii) a ratio of predict-
from similar treatment types resulting in five samples i.e. influent/                  ed environmental concentration to predicted no effect concentration
effluent from SB, ATS and grey water influent. An IS (113 ng chrysene-                 (PEC/PNEC) ≥ 0.01, or iv) listed as European or Swedish industrial
d12) and 25 mL saturated sodium chloride solution were added to                      chemicals with an acute (LC50/EC50) or chronic (ChV) ecotoxicity end-
each 500 mL composite water sample. The samples were subsequently                    point ≤1.0 mg L−1 or ≤0.1 mg L−1, respectively. These thresholds are
extracted with 100 mL, 50 mL, and 50 mL dichloromethane. The com-                    similar to criteria suggested by REACH and the U.S. EPA for the identifi-
bined extracts were filtered through 10 g sodium sulfate, rinsed with di-             cation of PBT chemicals (EPI Suite™ Appendix B, 2004) (Annex XIII,
chloromethane, and evaporated to 1 mL. The filters were extracted 16 h                REACH).
by Soxhlet extraction with 250 mL toluene, IS (113 ng chrysene-d12)                      Aquatic ecotoxicity (LC50, EC50, and ChV), half-lives in water,
was added, and the volume was reduced to 1 mL. The corresponding ex-                 and BCFs were estimated for each identified compound using the
tracts were combined and analyzed in triplicate with comprehensive                   ECOSAR, BIOWIN3, and BAFBCF modules in the EPI Suite™ toolbox
two-dimensional gas chromatography and time-of-flight mass spec-                      (www.epa.gov, 2008). The PEC was calculated by using the maximum
trometry (GC×GC–ToFMS).                                                              concentration found in either ATS or SB effluent and multiplying this
                                                                                     value by an uncertainty factor of 10 (due to the semi-quantitative anal-
2.1.3. Comprehensive gas chromatography time-of flight mass spectrometry              ysis) and dividing it by a dilution factor of 1000 as recommended for
    The samples were analyzed with a Pegasus 4D mass spectrometer                    local surface water scenarios (Lijzen and Rikken, 2004). The corre-
(Leco Corp., St. Joseph, MI, USA), equipped with an Agilent Technologies             sponding PNEC was calculated using the lowest ecotoxicity value from
6890 gas chromatograph (Palo Alto, CA, USA), a secondary oven, and a                 the ECOSAR model divided by an uncertainty factor of 10 as recom-
dual stage cryogenic (liquid nitrogen) modulator. A BPX50 column                     mended for long-term data from at least three species representing
(29.5 m, 0.25 mm ID, 0.25 μm film thickness, SGE) was used for first-                  three tropic levels (Echa, 2008). The used industrial chemicals invento-
dimension separation, and a VF-1ms column (1.2 m, 0.15 mm ID,                        ries were the European low and high production volume chemicals
0.15 μm film thickness, Agilent Technologies) was used for the                        (Rännar and Andersson, 2010), the EINECS database (Stenberg et al.,
second-dimension separation. The polar-nonpolar column combination                   2009), and a database of chemicals used in large amounts in Sweden
was chosen because it was suspected that the STP samples might con-                  compiled by the Swedish Chemicals Agency (Fischer, 2011).
tain high levels of petroleum hydrocarbons from storm water runoff.                      The resulting compounds were manually checked for possible bio-
Helium was used as the carrier gas at 1.0 mL min−1. The extracts were                genic or anthropogenic origin and only anthropogenic compounds
injected with a 1 μL pulsed splitless injection. The inlet was purged at             were considered for the next step. To improve the semi-quantitative
20 mL min−1 for 1 min, the inlet pulse was 40 psi for 1.5 min, and the               data and to detect low-abundance compounds, the GC × GC–MS data
inlet temperature was 280 °C. The primary oven temperature was                       files were reprocessed with Chroma-ToF using a specific quantification
268   K.M. Blum et al. / Science of the Total Environment 575 (2017) 265–275
                                            mass for each compound and a S/N cut-off of 10 (Fig. 2). The compounds
                                            were also semi-quantified using chrysene-d12. The lower S/N limit and
                                            the integration based on extracted ion chromatograms resulted in
                                            some previously undetected compounds appearing in the blanks. For
                                            those compounds, we calculated MLOQs corresponding to 10 times
                                            the maximum concentration found in one blank (Supplemental
                                            Table S3). If a compound did not appear in any sample at a concentra-
                                            tion higher than the MLOQ, it was excluded.
                                                To rank the compounds that passed the filtering process by environ-
                                            mental relevance, a scoring system was developed (Table 1) and applied
                                            to the dataset. Scores were given from 1 to 5 in five categories (removal
                                            efficiency, half-life, BCF, PEC/PNEC, and maximum concentration in SB
                                            or ATS effluent), and a total score was obtained based on the sum of
                                            the single scores. The lowest score represents the most problematic
                                            chemical.
Table 1
Scoring system for the 46 identified compounds.
Score 1 2 3 4 5
  Removal efficiency                     Removal b75%                Removal b75%                 Removal N75%                Present in effluent, but not       100% removalb
                                        in SB and ATS               in SB or ATS                 in SB and ATSa              in influent in SB or ATS
  Half-life (days)                      180                         60                           37.5                        15                                b15
  BCF                                   N10,000                     N1000                        N100                        N10                               b10
  PEC/PNEC                              N1                          N0.1                         N0.01                       N0.001                            b0.001
                                                                                                                                                               Missing value
  Maximum effluent                       N1000                       N500                         N100                        N50                               b50
   concentrationc (ng L−1)
BCF = bioconcentration factor, PEC/PNEC = predicted environmental concentration/predicted no effect concentration, SB = soil bed, ATS = aerobic treatment system.
 a
    = or present in effluent, but not in influent in ATS and SB.
 b
    = or below limit of quantification in effluent, but present in influent.
 c
    = maximum concentration in SB or ATS effluent.
all samples were loaded. The analytes were eluted from the cartridges                         was 115 s at a flow rate of 25 mL min−1. Helium was used as the carrier
with 8 mL dichloromethane/acetonitrile (80:20, v/v) followed by                               gas at 1.0 mL min−1. The primary oven temperature was kept at 90 °C
10 mL dichloromethane.                                                                        for 2 min, raised at 10 °C min− 1 to 335 °C, and held isothermal for
    Filters with suspended solids were lyophilized for 45 h, soaked in                        2 min. The secondary oven and the modulator were operated at a +
10 mL dichloromethane/acetonitrile (80:20, v/v), and 30 μL IS mixture                         10 °C (up to 335 °C) and +15 °C offset, respectively. The modulation pe-
(Supplemental Table S6) was added. Filters were sonicated for 30 min,                         riod changed over the run, modulating at 1.7 s from start to 780 s, at
the extract was decanted, and 10 mL fresh solvent mixture was added.                          2.0 s from 780 s to 1374 s, and at 2.5 s from 1374 s to the end (Supple-
This sonication process was repeated twice and the third sonication                           mental Table S7) to obtain a sufficient number of modulations across a
step was performed only with dichloromethane.                                                 first dimension GC peak. The transfer line temperature was set to
    The combined extracts of SPE eluate, flask rinse SPE eluate, and filter                     335 °C and the ion source temperature was set to 300 °C. Electron ioni-
extract were filtered through 10 g sodium sulfate. The solvent was ex-                         zation was performed at 70 eV, and mass spectra were recorded at
changed to toluene, reduced to 500 μL, and 10 μL 13C6-labeled PCB-97                          200 Hz from 38 to 480 m/z after a 360 s acquisition delay.
and PCB-188 recovery standard in toluene (Supplemental Table S6)                                  Samples were analyzed in batches (effluent recovery tests, influent
was added for IS recovery calculations.                                                       recovery tests, effluent samples, influent samples, and blanks), and
                                                                                              each batch contained a calibration with seven calibration solutions
2.2.3. Comprehensive gas chromatography high-resolution time-of-flight                         resulting in at least three useful data points for each analyte. The instru-
mass spectrometry                                                                             ment was tuned in between each set.
    Stage II samples were analyzed with a Pegasus 4D HRT mass                                     The ChromaTOF-HRT software (V.1.90, Leco Corp., St. Joseph, MI,
spectrometer (Leco Corp., St. Joseph, MI, USA) equipped with an Agilent                       USA) was used for data processing. The raw data files were mass cali-
7890 gas chromatograph (Palo Alto, CA, USA). A conventional nonpolar-                         brated to perfluorotributylamine mass ions, and characteristic target
polar column combination was used because Stage I samples did not                             analyte ions were searched within a given retention time window and
contain any elevated levels of aliphatic hydrocarbons. The primary col-                       with a 0.005 Da mass tolerance.
umn was a Rtx-5MS (30.0 m, 0.25 mm ID, 0.125 μm film thickness) from
Restek (Bellefonte, PA, USA). The secondary column, a Restek Rxi-17Sil                        2.2.4. Quality assurance and control
MS (2.0 m, 0.25 mm ID, 0.125 μm film thickness) of which 0.6 m were                                The 26 target analytes were quantified using the ions listed in the
placed inside the secondary oven, was connected to an uncoated apolar                         Supplemental Table S9. In addition, five 1-substituted linear alkyl
deactivated silica column (1.0 m, 0.25 mm) from Sigma-Aldrich                                 benzenes (LABs) are listed which were used for method development
(Steinheim, Germany) situated in the transfer line. A pulsed splitless in-                    1-phenyldecane (1-C10-LAB), 1-phenylundecane (1-C11-LAB), 1-
jection with 50 psi inlet pulse pressure and 3 mL min−1 septum purge                          phenyldodecane (1-C12-LAB), 1-phenyltridecane (1-C13-LAB), and 1-
flow was used. The inlet pulse lasted 120 s, and the inlet purge time                          phenyltetradecane (1-C14-LAB). The target analytes were quantified
                                                                                              using the isotope dilution technique with carefully matched labeled IS.
Table 2
                                                                                              Structurally identical deuterated or 13C-labeled standards were used
                                                                                              for 2,4,7,9-tetramethyl-5-decyn-4,7-diol (TMDD), tributylphosphate
  Name Type Built, modified           Households/Population         Treatment steps            (TBP), tris(2-chloro-ethyl)phosphate (TCEP), tris(1-chloro-2-
                                     equivalents
                                                                                              propyl)phosphate (TCIPP), tris(1,3-dichloro-2-propyl)phosphate
  SB1     SB     2006                9/−                           S, SB                      (TDCPP), triphenylphosphate (TPP), benzophenone (BP), OC, hexachlo-
  SB2     SB     1993                28/−                          S, SB
                                                                                              robenzene (HCB), n-butylbenzenesulfonamide (n-BBSA), TCS,
  SB3     SB     2010                4/−                           S, SB
  SB4     SB     1992                37/−                          S, SB                      thiabendazole (TBZ), BPA, α-tocopheryl acetate (α-TPA), AHTN, and
  SB5     SB     2012                13/−                          S, SB                      musk xylene, and labeled compounds with similar structural
  STP1    STP    1971, 1996          −/1200                        M, C, S, A, S, (C),        features, physicochemical properties, and extraction efficiencies were
                                                                   (D)                        used for LABs, 2-(methylthio)benzothiazole (MTBT), TBEP, tris(2-
  STP2    STP    1934, 1939, 1970    −/110,000                     1) M, C, S, A, S, C,
                                                                                              ethylhexyl)phosphate (TEHP), 2-ethylhexyldiphenylphosphate
                                                                   (D)
                                                                   2) M, C, S, BB, S,         (EHDPP), tricresylphosphate (TCP), 4-octyl phenol (4-OP), HHCB, and
                                                                   C, (D)                     musk ketone.
  STP3    STP    1972, 2015          −/100,000                     M, C, S, A, S, (D)             Before and after the sampling, Milli-Q water was pumped through
  STP4    STP    1940/50, 1960,      −/150,000                     M, C, S, A, S, C,
                                                                                              each sampler to account for background levels (Blank 1 to Blank 6 in
                 1990                                              (D)
  STP5    STP    1941, 1971, 2011,   −/780,000                     M, C, S, A, S, C, SF       Supplemental Table S10). In addition, a field blank and a laboratory
                 2015                                                                         blank were processed with Milli-Q water (Blank F1 and Blank L1 in Sup-
S = sedimentation, M = mechanical treatment, C = chemical treatment, A = active
                                                                                              plemental Table S10). Instrumental limit of detection and quantification
sludge, BB = bio bed, D = disinfection, SF = polishing sand filter, optional treatment         (LOD and LOQ) were determined by extrapolation to S/N 3 and S/N 10,
steps are in brackets, 1) = line 1, 2) = line 2.                                              respectively. For compounds appearing in the blank, the MLOQ was
270                                             K.M. Blum et al. / Science of the Total Environment 575 (2017) 265–275
calculated by multiplying the maximum concentration determined in                     were filtered for occurrence in our effluent samples, and then further fil-
the blanks by 10. Recovery tests were performed for the SPE method                    tered for PBT properties, production volume or emission potential ac-
using triplicate influent and effluent samples spiked with native                       cording to Section 2.1.4 and Fig. 2. The compounds that passed these
analytes and the 1-subsituted LABs (Supplemental Table S11). Three                    filters were manually checked for anthropogenic origin which resulted
non-spiked influent samples, one non-spiked effluent sample, and one                    in 63 remaining compounds (Supplemental Table S2).
Milli-Q blank were analyzed in each effluent and influent batch.                            The 63 compounds were re-processed using a compound specific
    The target analysis method developed for Stage II was evaluated                   quantification ion, and were semi-quantified using chrysene-d12,
based on linearity, LOD, LOQ, recoveries, and precision. Good linearities             which resulted in a lower percentage of non-detects, but also in
were obtained for both SPE recovery tests and for samples with regres-                the elimination of 17 compounds due to elevated blank levels
sion coefficients (R2) ≥ 0.99. Instrumental LOQs ranged from 3.3 pg μL−1               (Section 2.1.4, Supplemental Table S3). Although these background
for TBP to 49 pg μL−1 for TCP, and MLOQs ranged from 23 ng L−1 for TBP                compounds potentially have environmental relevance, they are likely
to 1300 ng L−1 for BPA. Native analyte SPE recovery experiments result-               not of OSSF origin and thus not in the scope of this study.
ed in excellent median relative recoveries of 95% and 94% in effluent and                  The final set of anthropogenic contaminants of potential environmen-
influent, respectively. The recovery tests were performed in triplicates,              tal concern consisted of 46 compounds (Fig. 2, Supplemental Table S2)
and standard errors ranged from 0.2% for 4-OP and 1-C10-LAB to 13%                    and included pharmaceuticals, like the pain reliever acetylsalicylic acid,
for HHCB in influent and up to 28% for BP in effluent (Supplemental                     the stimulant caffeine, the antiepileptic carbamazepine, the anticonvul-
Table S12).                                                                           sant ethosuximide, and the antidepressant mirtazapine; the OPs TDCPP,
    The median absolute IS recoveries in the influent, effluent, and blank              TCEP, TCIPP, tris(3-chloropropyl)phosphate (TCPP), TBEP, TBP and TPP;
samples were 189%, 115%, and 92%, respectively. Only TBZ-13C6 and                     rubber and plastic additives like MTBT and n-BBSA; personal care prod-
nonylbenzene-d24 had recoveries ≤ 50% (Supplemental Tables S13–                       uct ingredients like α-TPA; the UV stabilizers octyl salicylate (OS),
S15). The high apparent recoveries in the influent might be due to ma-                 oxybenzone, and OC; LABs like 5-phenylundecane (5-C11-LAB), 4-
trix shielding of active sites in the GC liner resulting in enhanced analyte          phenylundecane (4-C11-LAB), 4-phenyldodecane (4-C12-LAB) and 6-
transfer to the column (Rahman and El-Aty, 2013). However, with the                   phenyldodecane (6-C12-LAB), which are impurities in linear alkyl
extensive use of labeled standards and careful matching of native                     sulfonates containing detergents; surface-active compounds like TMDD
analytes and IS, matrix enhancement should not significantly affect                    and N,N,N′,N′-tetraacetylethylenediamine; flavor and fragrances like α-
the final results.                                                                     cumyl alcohol and HHCB; and pesticides like 2,3-dichlorobenzonitrile
                                                                                      and DEET.
2.2.5. Removal efficiency calculations and statistical analysis                            By scoring the 46 contaminants based on their removal efficiency,
    Sample concentrations below LOQ, LOD, and MLOQ were substituted                   half-life, BCF, PEC/PNEC, and maximum concentration found in either
with LOQ/2, LOD/2, and MLOQ/2, respectively, for removal efficiency                    ATSs or SBs (Table 1, Fig. 2), the potential environmental relevance of
calculations. The percentage removal efficiency was calculated                         the identified compounds could be estimated. Theoretically the scores
as 1 minus the concentration in effluent divided by the concentration                  can range from 5 to 25, with the most relevant compounds scoring
in influent, times 100. In case of a negative removal efficiency,                       the lowest (Fig. 3). Individual scores for the 46 compounds are given
the value was set to 0%. Negative removal efficiencies have often                      in Supplemental Table S18. HHCB scored the lowest with a total score
been reported and have been attributed to the fluid dynamics of the                    of 8, followed by α-TPA, OC, TMDD, 4-C12-LAB, TCPP, TDCPP, 6-C12-
system (e.g. not taking hydraulic retention times into account),                      LAB, TCEP, OS, caffeine, 5-C11-LAB, and 4-C11-LAB. HHCB scored low
deconjugation of metabolites, and desorption from return activated                    due to its high concentration in OSSFs in combination with the risk of
sludge in the secondary treatment process (Blair et al., 2015; Verlicchi              causing adverse effects in the environment and its overall low scores
et al., 2012). Analytical bias also cannot be ruled out, because dense                in all categories. α-TPA was highly ranked because of a long half-life
samples such as influent are generally more difficult to extract than                   and high risk for causing adverse effects in the environment, whereas
lean samples such as effluent.                                                         OC was ranked high due to its bioconcentration potential, low removal
    Principal component analysis (PCA) was performed with SIMCA                       efficiency, and high PEC/PNEC. TMDD was poorly removed and was
(v.13.0.3, Umetrics, Umeå, Sweden) to study variations in compound-                   present in high abundance, 4-C12-LAB had a high PEC/PNEC and BCF,
specific removal efficiency for the different treatment plants and tech-                and TCPP showed low removal efficiency and high persistence and
niques. Compounds were excluded from data analysis if ≥ 50% of the                    abundance.
data was missing. Removal efficiencies were mean centered and scaled                       Eriksson et al. (2003) identified compounds using non-target
to unit variance prior to PCA.                                                        screening of grey water that were also highly ranked in our study,
    The removal efficiencies and influent and effluent concentrations                    such as α-TPA, TCEP, TPP, geranyl acetone and caffeine. Octocrylene
were also analyzed for significant differences between SBs and STPs                    and galaxolide have been detected in grey water (Leal et al., 2010),
with the Wilcoxon's sum rank test (Wilcoxon, 1945), and the correla-                  and Conn et al. (2010a, 2010b) targeted for TCEP, TCIPP and TDCPP in
tion between the logarithm of the octanol–water partition coefficient                  OSSF influent and effluent without success. Rager et al. (2016) used LC
(log KOW) and removal efficiencies was tested with Spearman's rank                     coupled to high-resolution MS to screen for and prioritize contaminants
correlation.                                                                          based on detection frequency, bioactivity, exposure and abundance in
                                                                                      household dust. Similar to our study, they found TCPP, TCIPP, 4-C12-
3. Results and discussion                                                             LAB, and DEET among the top-ranked (n = 25) contaminants. Consider-
                                                                                      ing that various screening and ranking approaches for different kinds of
3.1. Non-target screening: identification of environmentally relevant con-             environmental matrices picked up compounds identical to some of our
taminants discharged from on-site sewage treatment facilities (Stage I)               priority compounds, our strategy appears to be successful in the identi-
                                                                                      fication of environmentally relevant compounds.
    The peak extraction and alignment of all peaks found in all samples                   Ultimately, the derived scores were used to select chemicals of high
resulted in a total of ≥ 200,000 features as can be seen from the                     environmental concern to include in Stage II. Low score (top ranked)
workflow schematics (Fig. 2). After detection frequency and blank filtra-               chemicals were complemented with structurally related compounds
tion, manual inspection to exclude features with a poor spectral library              belonging to same compound classes and some commonly used refer-
match, and exclusion of compounds because they had long alkyl chains                  ence compounds to reach a total of 26 target analytes (Table 3, Fig. 2).
indicating biogenic origin, approximately 300 compounds remained                      This extension was done to expand the physicochemical domain
(Supplemental Table S2). These tentatively identified compounds                        of the studied chemicals and to facilitate the understanding of
                                                         K.M. Blum et al. / Science of the Total Environment 575 (2017) 265–275                                       271
fundamental removal and degradation processes in OSSFs. The selection                          removed in SBs compared to STPs (Wilcoxon's sum rank test, α =
criteria for the final list of compounds to include in Stage II are given in                    0.01). The median removal efficiencies of TMDD in SBs and STPs were
Table 3.                                                                                       33% and 0%, respectively, whereas the median removal efficiencies of
                                                                                               TBEP were 80% and 68%, respectively (Table 4).
3.2. Evaluation of soil beds and large-scale sewage treatment facilities                           PCA was used to analyze and visualize differences in removal pattern
(Stage II)                                                                                     between the two types of sewage treatment. The score plot in Fig. 6A
                                                                                               shows a weak separation of SBs and STPs along PC2 (with SB4 as an out-
3.2.1. Removal pattern                                                                         lier). As already seen in Fig. 5, STPs seem to be more diverse in their re-
    Volatilization, sorption to solids followed by sedimentation, and bio-                     moval behavior than SBs. However, SB3 also appears to be quite
degradation are reported to be the major removal pathways of contam-                           different from the rest of the SBs. It was the smallest of the studied
inants in wastewater treatment (Conn et al., 2006; Simonich et al.,                            SBs with 4 households connected and also had the lowest median re-
2002). The sorption potential of an organic compound can often be re-                          moval efficiency (60%). The plants STP1, STP3, and SB3 differed from
lated to its hydrophobicity using the log KOW (Fernandez et al., 2014).                        the other plants along PC1 and showed deviating removal efficiencies
Since the hydrophobicity of a chemical influences its affinity to organic                        for specific chemicals. TCEP, TCIPP and TBZ showed a better removal
matter, and thus its removal efficiency in treatment plants, the calculat-                      and HHCB, MTBT and BP a worse removal in these plants as compared
ed overall median removal efficiencies of each compound (df = 100%)                             to the majority of plants (SB1, SB2, SB4, SB5, STP2, STP4, STP5)
were correlated to the log KOW (Fig. 4). SB, STP, and overall median                           (Fig. 6B, Supplemental Table S19). The main drivers for the separation
removal efficiencies were significantly correlated (Spearman rank                                of SBs and STPs along PC2 were the better removal of HHCB, AHTN,
correlation, α = 0.01) to the log KOW with a correlation of 85% (p =                           TBEP, TBP, and TMDD and the worse removal of OC and EHDPP in
0.00003), 82% (p = 0.0001), and 85% (p = 0.00003), respectively. OC,                           most SBs (Fig. 6B, Supplemental Table S19). The cluster of compounds
EHDPP, α-TPA, TCS, TEHP, and HHCB had the highest overall median re-                           in region 1 (EHDPP, OC, TCS, TPP, and 6-C12-LAB) are very hydrophobic
moval efficiency (≥90%) and were also the most hydrophobic chemicals                            (log KOW 4.6 to 8.0), whereas the compounds in region 2 (TBEP, MTBT,
investigated (log KOW 4.8 to 12), whereas TDCPP, TMDD, TCIPP, and                              TMDD, TCIPP, TDCPP, and TBZ) are in comparison rather hydrophilic
TCEP were removed with reduced efficiency between 22% and 44%                                   (log KOW 2.5 to 3.8) (Fig. 6B). Consequently, many compounds that
and are less hydrophobic (log KOW 1.4 to 3.7). AHTN, BP, TPP, TBP,                             were better removed in SBs are relatively hydrophilic. SBs contain vari-
TBEP, and MTBT were removed with efficiencies between 64% and                                   ous layers of gravel and sand and have a high solid-to-water ratio, which
87%, and their log KOW is between 3.2 and 5.7. Sorption is crucial during                      could increase sorption of compounds with moderate hydrophobicity
sedimentation and soil filtration, which explains the higher removal ef-                        and polar or polarizable functional groups, that might interact with sim-
ficiency of hydrophobic compounds. Volatility did not explain any vari-                         ilar functional groups in the SB material. Although SBs should be aerated
ation in removal efficiency in our study. Furthermore, it was hard to                           to promote aerobic biodegradation, anaerobic sections can occur if the
explain the low removal of TMDD and chlorinated OPs (TCEP 22%,                                 SBs do not work properly. In combination with longer residence times
TCIPP 26%, and TDCPP 44%) solely by lipophilicity. TMDD, TCIPP and                             in SBs, anaerobic sections promote reductive dehalogenation of chlori-
TDCPP have a much lower removal than other target compounds with                               nated OPs such as TDCPP, TCIPP, and TCEP (Rittmann et al., 1994),
similar log KOW (Fig. 4). Instead, their high water solubility (TMDD 2 g                       whereas the biodegradation in active sludge treatment in STPs is exclu-
L−1,TCIPP 2 g L−1 and TDCPP 0.1 g L−1) and resistance to biological deg-                       sively aerobic.
radation (TCIPP 21% and TDCPP 0% degraded; 28 days OECD degrada-                                   Because internal LAB isomers (i.e. phenyl substitution is near the
tion test) may partly explain their low removal (World Health                                  center of the alkyl chain) are more susceptible to biodegradation than
Organization, 1998).                                                                           external LAB isomers (i.e. phenyl substitution is near the end of the
    The compounds with the lowest overall median removal efficiency                             alkyl chain) (Eganhouse et al., 1983), the ratio between, for example,
(≤80%) and highest occurrence (df = 100%) are presented in a boxplot                           (6-C12-LAB + 5-C12-LAB) and (4-C12-LAB + 3-C12-LAB + 2-C12-
(Fig. 5). The removal efficiency in STPs (n = 5) varied to a greater                            LAB) (the internal/external ratio) was previously used to assess biodeg-
extent compared to SBs (n = 5), and the largest variation was                                  radation in the aquatic environment (Takada and Ishiwatari, 1990) and
observed for MTBT with a removal of 0% in STP3 and 94% in STP2.                                STP treatment efficiencies (Hartmann et al., 2000). Influent has internal/
TMDD (p = 0.0003) and TBEP (p = 0.005) were significantly better                                external ratios around 1, whereas effluent usually has ratios around 3 or
                                                                                               larger (Isobe et al., 2004). We only had analytical standards available for
                                                                                               6-C12-LAB and 3-C12-LAB, thus we used the ratio between those two
                                                                                               isomers to evaluate the treatment efficiency. In SB3, the ratio between
                                                                                               6-C12-LAB and 3-C12-LAB was 1.5, which indicates overall low microbi-
                                                                                               ological activity and agrees with the results from the PCA removal effi-
                                                                                               ciency analysis.
                                                                                                   Few studies have reported the removal efficiencies in OSSFs of sim-
                                                                                               ilar target analytes. The removal of TCS in OSSFs was reported to be 47 ±
                                                                                               18% (Conn et al., 2006), 39% (Conn et al., 2006), 75 ± 23% (Conn et al.,
                                                                                               2006), 98% (Leal et al., 2010), and ≥90% (Conn et al., 2010b) in septic
                                                                                               tanks, wetlands, biofiltration systems, ATSs, and SBs, respectively. ATS
                                                                                               lab-scale experiments showed an average removal efficiency of AHTN,
                                                                                               HHCB, and OC of 32%, 80%, and 91%, respectively (Leal et al., 2010).
                                                                                               Our median removal efficiency was 91% for TCS and 87%, 95%, and 98%
                                                                                               for AHTN, HHCB, and OC, respectively, which is at the upper end of
                                                                                               the results of the cited studies (Table 4). We are aware of only two stud-
                                                                                               ies (Du et al., 2014; Garcia et al., 2013) that have compared OSSF and
                                                                                               STP treatment efficiency by treating STP influent using different OSSF
                                                                                               technologies (ATS and septic systems). The routine water quality
Fig. 3. The top ranked compounds with the lowest total score and their scoring in removal
efficiency, half-life for aquatic biodegradation, bioconcentration factor (BCF), PEC/PNEC
                                                                                               parameters (Garcia et al., 2013) and contaminant concentrations
(predicted environmental concentration/predicted no effect concentration), and                 (Du et al., 2014; Garcia et al., 2013) did not significantly deviate be-
maximum concentration found in samples. Compound abbreviations are given in Table 3.           tween STPs and OSSFs (α = 0.05), but the effluent toxicity was highest
272                                                       K.M. Blum et al. / Science of the Total Environment 575 (2017) 265–275
Table 3
The 26 selected target analytes for Stage II along with compounds classes, abbreviations, corresponding ranks, total score and selection criteria. Reference compounds are marked in italic.
  Biocides                    Hexachlorobenzene                             HCB                n.d.           n.d.              Classical persistent organic pollutant, which was previously
                                                                                                                                detected in STP effluents (Robles-Molina et al., 2013)
                              Thiabendazole                                 TBZ                n.d.           n.d.              As example for a more polar biocide
                              Triclosan                                     TCS                n.d.           n.d.              Classical biocide, previously studied in OSSFs (Conn et al.,
                                                                                                                                2010a, 2010b, 2006; Leal et al., 2010)
  Food additive               α-Tocopheryl acetate                          α-TPA              2              12                Top 5 ranking
  Fragrances                  Galaxolide                                    HHCB               1              8                 Overall top ranked
                              Musk ketone                                                      n.d.           n.d.              Common nitro-aromatic musk found in STP effluents
                                                                                                                                (Heberer, 2002)
                              Musk xylene                                                      n.d.           n.d.              Common nitro-aromatic musk found in STP effluents
                                                                                                                                (Heberer, 2002)
                              Tonalide                                      AHTN               n.d.           n.d.              Commonly found polycyclic musk to complement HHCB
                                                                                                                                (Heberer, 2002)
  Linear alkyl benzenes       3-Phenyldodecane                              3-C12-LAB          n.d.           n.d.              External LAB isomer found in detergents as impurity, together
                                                                                                                                with the internal isomer 6-C12-LAB, it can be used to assess
                                                                                                                                biodegradation activity (Takada and Ishiwatari, 1990)
                              6-Phenyldodecane                              6-C12-LAB          5              15                Top 5 ranking
  Organophosphorus            2-Ethylhexyldiphenylphosphate                 EHDPP              n.d.           n.d.              Supplement for an aryl organophosphorus flame
    flame retardants                                                                                                             retardant (Marklund et al., 2005)
                              Tributylphosphate                             TBP                6              16                Top 10 ranking
                              Tricresylphosphate                            TCP                n.d.           n.d.              Supplement for an aryl organophosphorus flame retardant
                              Triphenylphosphate                            TPP                12             22                Moderate score, but typical aryl organophosphorus
                                                                                                                                flame retardant (Marklund et al., 2005)
                              Tris(1,3-dichloro-2-propyl)phosphate          TDCPP              5              15                Top 5 ranking
                              Tris(1-chloro-2-propyl)phosphate              TCIPP              12             22                Moderate score, but structurally very similar to
                                                                                                                                tris(3-chloropropyl)phosphate (TCPP) which scored in
                                                                                                                                the top 5
                              Tris(2-butoxyethyl)phosphate                  TBEP               7              17                Top 10 ranking
                              Tris(2-chloro-ethyl)phosphate                 TCEP               5              15                Top 5 ranking
                              Tris(2-ethylhexyl)phosphate                   TEHP               n.d.           n.d.              Identified during screening, supplement for alkyl
                                                                                                                                organophosphorus flame retardant (Marklund et al., 2005)
  Plasticizer                 n-Butylbenzenesulfonamide                     n-BBSA             14             24                Moderate score, but detected previously in STP
                                                                                                                                effluents (Huppert et al., 1998) and therefore included
                                                                                                                                as example of a plasticizer.
  Polymer impurity            Bisphenol A                                   BPA                n.d.           n.d.              Previously studied in OSSFs (Conn et al., 2010a; Leal
                                                                                                                                et al., 2010)
  Rubber additive             2-(Methylthio)benzothiazole                   MTBT               8              18                Top 10 ranking
  Surfactants                 2,4,7,9-Tetramethyl-5-decyn-4,7-diol          TMDD               4              14                Top 5 ranking
                              4-Octyl phenol                                4-OP               n.d.           n.d.              4-OP has been found in ground water effected by OSSFs and
                                                                                                                                studied in OSSFs (Conn et al., 2006; Phillips et al., 2015)
  UV stabilizers              Benzophenone                                  BP                 n.d.           n.d.              To supplement OC with another commonly detected UV
                                                                                                                                stabilizer (Kasprzyk-Hordern et al., 2009)
                              Octocrylene                                   OC                 3              13                Top 5 ranking
n.d. = rank/score not determined, since reference compound, STP = sewage treatment plant, OSSF = on-site sewage treatment facility, LAB = linear alkyl benzene.
                                                                                                 Fig. 5. Removal efficiencies in soil beds (SBs) and sewage treatment plants (STPs) for
                                                                                                 compounds with a median removal efficiency ≤80% and a detection frequency = 100%
                                                                                                 (detected in influent or in effluent of the same treatment plant). The boxes represent
                                                                                                 the 25th and 75th percentiles, the median is indicated as a horizontal line in the box,
Fig. 4. Overall median removal efficiencies in % versus the logarithm of the octanol–water        and the mean is presented as a cross. Error bars represent the minimum and maximum
partition coefficient (log KOW) for compounds with detection frequency = 100% (detected           removal efficiency measured in SB or STPs. Data points are indicated as dots. *
in influent or effluent of the same treatment plant); log KOW values were retrieved from           Significantly better removed by SB than STP (Wilcoxon's sum rank test, α = 0.01).
KOWWIN v.1.68 (www.epa.gov, 2008). Compound abbreviations are given in Table 3.                  Compound abbreviations are given in Table 3.
                                                          K.M. Blum et al. / Science of the Total Environment 575 (2017) 265–275                                                         273
Table 4                                                                                          HCB, α-TPA, 6-C12-LAB, 3-C12-LAB, TBP, TPP, TEHP, EHDPP, 4-OP, and
Median removal efficiencies in % for soil beds (SBs) and sewage treatment plants (STPs),          BP. 4-OP was identified in STP5 effluent only (10 ng L− 1), and HCB
and the probability (p-value) that the SB removal efficiency is worse than the STP removal
(Wilcoxon's sum rank test) for compounds with a detection frequency = 100% (detected
                                                                                                 was found in SB1 and STP2 effluent at around 5 ng L− 1. 3-C12-LAB
in influent or in effluent of the same treatment plant).                                           was only detected in SB3 effluent. BPA, n-BBSA, musk xylene, musk ke-
                                                                                                 tone, and TCP were not detected.
                                                Median removal
                                                                                                     To the best of our knowledge, only TCS, BPA, AHTN, HHCB, OC, and
                                                efficiency in %
                                                                                                 TBEP have been reported before in OSSF effluent (Conn et al., 2010a,
                                                SB             STP           p-value
                                                                                                 2010b, 2006; Leal et al., 2010; Phillips et al., 2015). These studies detect-
                                                n =5           n =5          (α = 0.01)          ed TCS at much higher concentrations and reported up to 57,000 ng L−1
  Tris(2-chloroethyl)phosphate                  19             24            0.7                 (Conn et al., 2010a) in septic tank effluent (Conn et al., 2010b, 2006),
  2,4,7,9-Tetramethyl-5-decyn-4,7-diol          33             0             0.0003              up to 230 ng L−1 (Conn et al., 2010b) in biofiltration effluent, and up
  Tris(1-chloro-2-propyl)phosphate              34             18            0.6                 to 350 ng L− 1 (Leal et al., 2010) in aerobically treated grey water.
  Tris(1,3-dichloro-2-propyl)phosphate          56             31            0.3
                                                                                                 AHTN, HHCB, and OC were detected at 1500 ng L−1, 2100 ng L−1, and
  2-(Methylthio)benzothiazole                   64             65            0.3
  Triphenylphosphate                            78             86            0.8                 3500 ng L− 1 (Leal et al., 2010), respectively, in aerobically treated
  Tris(2-butoxyethyl)phosphate                  80             68            0.005               grey water. The HHCB and OC concentrations agree well with the levels
  Benzophenone                                  83             80            0.4                 we detected. TBEP was found at concentrations N 20,000 ng L−1 below
  Tributylphosphate                             83             29            0.2                 leach beds of OSSFs in a commercial area (Phillips et al., 2015), which
  Tonalide                                      87             86            0.2
  Triclosan                                     91             96            1
                                                                                                 is N20 times higher than what we detected in SB effluent in a residential
  Tris(2-ethylhexyl)phosphate                   92             94            0.9                 setting. BPA was detected up to 13,000 ng L−1 in septic tank effluent
  Galaxolide                                    95             84            0.01                (Conn et al., 2010a), but was not detected above MLOQ (1300 ng L−1)
  α-Tocopheryl acetate                          96             99            1                   in our samples.
  2-Ethylhexyldiphenylphosphate                 98             99            0.9
  Octocrylene                                   98             99            0.9
                                                                                                 4. Conclusions
in one type of OSSF (Garcia et al., 2013). However, they did not examine                             For the first time, a GC × GC–MS based non-target screening was
SBs, so a direct comparison is not possible.                                                     used in combination with PBT prioritization to successfully identify en-
                                                                                                 vironmentally relevant compounds discharged from OSSFs. The rele-
3.2.2. Environmental load                                                                        vance of the selected priority pollutants was confirmed in Stage II,
    In 55% of the cases, the maximum concentration detected in SB                                where the top-ranked compounds were detected with high detection
effluent was higher than the concentration in the STP effluent, but no                             frequency and at high concentrations in SB effluent samples. The top-
significant differences were found with the Wilcoxon's sum rank test                              four compounds – HHCB, α-TPA, OC, and TMDD were detected at levels
(α = 0.01).                                                                                      up to 1400 ng L−1, 660 ng L−1, 1200 ng L−1, and 3000 ng L−1 in SB ef-
    The most frequently detected compounds were AHTN, TCIPP, TBEP,                               fluent, respectively. In addition, six contaminants (α-TPA, TMDD, BP,
TDCPP, TCEP, MTBT, and TMDD. Concentrations above 1000 ng L− 1                                   LABs, TBZ and MTBT) were found for the first time in OSSF effluents. Be-
were detected for TCIPP and TMDD in SB and STP effluent; for                                      cause OSSFs are diffuse sources of contamination, the high levels of con-
HHCB, TBEP, and α-TPA in STP effluent; and for OC in SB effluent                                   taminants in OSSF effluents will taint surface and ground waters,
(Table 5). TDCPP, TCEP, and MTBT were detected at levels higher than                             potentially impacting not only sensitive ecological systems (Brodin
100 ng L−1 in SB and STP effluent, and AHTN was found at a maximum                                et al., 2013), but also drinking water supplies (Godfrey et al., 2007;
concentration of 90 ng L− 1. Less frequently detected were TBZ, TCS,                             Swartz et al., 2006).
Fig. 6. Removal efficiencies of soil beds (SBs) and large sewage treatment plants (STPs) presented in a principle component analysis (PCA) with A) the score scatter plot and B) the loading
plot. The first and second principle component (PC) explain 34% and 21% of the variation, respectively. Compounds in region 1 and 2 have a log KOW of 4.6 to 8.0 and 2.5 to 3.8, respectively.
The more hydrophobic the compound, the darker its dot. Compound abbreviations are given in Table 3.
274                                                    K.M. Blum et al. / Science of the Total Environment 575 (2017) 265–275
Table 5
Detected compounds in soil bed (SB) or sewage treatment plant (STP) effluent and their respective maximum and median concentration and detection frequency (df).
    The comparison of removal efficiencies in STPs and SBs showed that                        References
TMDD and TBEP were significantly better removed in SBs than in STPs,
and that STPs differed more between plants in their removal efficiencies                      Andersson, P.L., Fick, J., Stefan, R., 2011. A multivariate chemical similarity approach to search
                                                                                                  for drugs of potential environmental concern. J. Chem. Inf. Model. 51, 1788–1794.
than SBs, a non-intuitive observation that calls for further research. Inde-
                                                                                             Bastos, P.M., Haglund, P., 2012. The use of comprehensive two-dimensional gas chroma-
pendent of treatment type, the more hydrophilic compounds like chlori-                            tography and structure–activity modeling for screening and preliminary risk assess-
nated OPs were more poorly removed than highly hydrophobic                                        ment of organic contaminants in soil, sediment, and surface water. J. Soils
                                                                                                  Sediments 12, 1079–1088. http://dx.doi.org/10.1007/s11368-012-0533-x.
compounds like α-TPA and OC. This insufficient removal implies that
                                                                                             Blair, B., Nikolaus, A., Hedman, C., Klaper, R., Grundl, T., 2015. Evaluating the degradation,
existing OSSF and STP treatment technologies need to be upgraded to                               sorption, and negative mass balances of pharmaceuticals and personal care products
improve the removal of hydrophilic pollutants by e.g. ozone or activated                          during wastewater treatment. Chemosphere 134, 395–401. http://dx.doi.org/10.
carbon treatment (Luo et al., 2014). However, such treatment technolo-                            1016/j.chemosphere.2015.04.078.
                                                                                             Brodin, T., Fick, J., Jonsson, M., Klaminder, J., 2013. Dilute concentrations of a
gies are currently expensive or difficult to use in OSSFs, which calls for                         psychiatric drug alter behavior of fish from natural populations. Science 339,
more research on the development of advanced removal technologies.                                814–815. http://dx.doi.org/10.1126/science.1226850.
    Because we found that compounds with low removal efficiencies are                         Carrara, C., Ptacek, C.J., Robertson, W.D., Blowes, D.W., Moncur, M.C., Sverko, E., Backus, S.,
                                                                                                  2008. Fate of pharmaceutical and trace organic compounds in three septic system
generally more hydrophilic, and because this study focused on com-                                plumes, Ontario, Canada. Environ. Sci. Technol. 42, 2805–2811.
pounds detectable by GC×GC–MS, we suggest further studies on OSSF                            Castillo, S., Mattila, I., Miettinen, J., Orešič, M., Hyötyläinen, T., 2011. Data analysis tool for
effluents also including LC-MS based techniques. The complementary                                 comprehensive two-dimensional gas chromatography/time-of-flight mass spectrom-
                                                                                                  etry. Anal. Chem. 83, 3058–3067. http://dx.doi.org/10.1021/ac103308x.
use of these techniques is likely to efficiently capture both persistent                      Conn, K.E., Barber, L.B., Brown, G.K., Siegrist, R.L., 2006. Occurrence and fate of organic
and bioaccumulating chemicals (mainly by GC–MS) and acutely toxic                                 contaminants during onsite wastewater treatment. Environ. Sci. Technol. 40,
chemicals (mainly by LC-MS). Additionally, our study was limited to rel-                          7358–7366. http://dx.doi.org/10.1021/es0605117.
                                                                                             Conn, K.E., Lowe, K.S., Drewes, E., Hoppe-jones, C., Tucholke, M.B., 2010a. Occurrence of
atively well-functioning SBs, thus best-case scenarios for a typical treat-
                                                                                                  pharmaceuticals and consumer product chemicals in raw wastewater and septic
ment technique in Sweden. Future studies are encouraged to also                                   tank effluent from single-family homes. Environ. Eng. Sci. 27. http://dx.doi.org/10.
include poor functioning plants, and preferably also cover other types                            1089/ees.2009.0364.
                                                                                             Conn, K.E., Siegrist, R.O.L.S., Barber, L.B., Meyer, M.T., 2010b. Fate of trace organic com-
of existing OSSFs.
                                                                                                  pounds during vadose zone soil treatment in an onsite wastewater system. Environ.
                                                                                                  Toxicol. Chem. 29, 285–293. http://dx.doi.org/10.1002/etc.40.
Acknowledgements                                                                             Cooper, E.R., Siewicki, T.C., Phillips, K., 2008. Preliminary risk assessment database and
                                                                                                  risk ranking of pharmaceuticals in the environment. Sci. Total Environ. 398, 26–33.
                                                                                                  http://dx.doi.org/10.1016/j.scitotenv.2008.02.061.
    This work was supported by the Swedish Research Council Formas                           Corcoran, E., Nellemann, C., Baker, E., Bos, R., Osborn, D., Savelli, H., 2010. Sick Water? The
through the project RedMic (216-2012-2101). We would like to thank                                Central Role of Wastewater Management in Sustainable Development. UNEP and UN-
Berndt Björlenius, Linnéa Tjernström, and Wen Zhang from the Royal                                Habitat http://dx.doi.org/10.1007/s10230-011-0140-x.
                                                                                             Del Rosario, K.L., Mitra, S., Humphrey, C.P., O'Driscoll, M.A., 2014. Detection of pharmaceu-
Institute of Technology for providing some of the wastewater samples.                             ticals and other personal care products in groundwater beneath and adjacent to
Thanks to João Figueira and Elin Näsström from Umeå University for                                onsite wastewater treatment systems in a coastal plain shallow aquifer. Sci. Total En-
data processing support and thanks to Mátyás Ripszám from Umeå Uni-                               viron. 487, 216–223. http://dx.doi.org/10.1016/j.scitotenv.2014.03.135.
                                                                                             Du, B., Price, A.E., Scott, W.C., Kristofco, L.A., Ramirez, A.J., Chambliss, C.K., Yelderman, J.C.,
versity for technical support.                                                                    Brooks, B.W., 2014. Comparison of contaminants of emerging concern removal, dis-
                                                                                                  charge, and water quality hazards among centralized and on-site wastewater treat-
Appendix A. Supplementary data                                                                    ment system effluents receiving common wastewater influent. Sci. Total Environ.
                                                                                                  466-467, 976–984. http://dx.doi.org/10.1016/j.scitotenv.2013.07.126.
                                                                                             Echa, 2008. Guidance on Information Requirements and Chemical Safety Assessment.
   Supplementary data to this article can be found online at http://dx.                           Chapter R.10: Characterisation of Dose [concentration]-response for Environment.
doi.org/10.1016/j.scitotenv.2016.09.135.                                                          Eur. Chem. Agency, pp. 1–65.
                                                                K.M. Blum et al. / Science of the Total Environment 575 (2017) 265–275                                                               275
Eganhouse, R.P., Blumfleld, D.L., Kaplan, I.R., 1983. Long-chain alkylbenzenes as molecular             Rahman, M.M., Abd El-Aty, A.M., Shim, J.H., 2013. Matrix enhancement effect: a blessing
     tracers of domestic wastes in the marine environment. Environ. Sci. Technol. 17,                       or a curse for gas chromatography? — a review. Anal. Chim. Acta 801, 14–21.
     523–530.                                                                                               http://dx.doi.org/10.1016/j.aca.2013.09.005.
EPI Suite™ Appendix B, 2004. Interpretive Guidance Document for Sustainable Futures                    Rännar, S., Andersson, P.L., 2010. A novel approach using hierarchical clustering to select
     Summary Assessment Updated September 2004.                                                             industrial chemicals for environmental impact assessment. J. Chem. Inf. Model. 50,
Eriksson, E., Auffarth, K., Eilersen, A., Henze, M., Ledin, A., 2003. Household chemicals and               30–36.
     personal care products as sources for xenobiotic organic compounds in grey waste-                 Rittmann, B.E., Wrenn, B.A., Valocchi, A.J., Ray, C., Raskin, L., 1994. IN SITU BIOREMEDIA-
     water. Water SA 29, 135–146.                                                                           TION. 2nd edition. NOYES PUBLICATION, Park Ridge, New Jersey.
Fernandez, R., Mcdonald, J.A., Khan, S.J., Le-clech, P., 2014. Removal of pharmaceuticals              Robles-Molina, J., Gilbert-López, B., García-Reyes, J.F., Molina-Díaz, A., 2013. Gas chroma-
     and endocrine disrupting chemicals by a submerged membrane photocatalysis reac-                        tography triple quadrupole mass spectrometry method for monitoring multiclass or-
     tor (MPR ). Sep. Purif. Technol. 127, 131–139. http://dx.doi.org/10.1016/j.seppur.                     ganic pollutants in Spanish sewage treatment plants effluents. Talanta 111, 196–205.
     2014.02.031.                                                                                           http://dx.doi.org/10.1016/j.talanta.2013.03.006.
Fischer, S., 2011. Exposure index table on product register data for year 2011.                        Sanderson, H., Johnson, D.J., Reitsma, T., Brain, R.A., Wilson, C.J., Solomon, K.R., 2004. Rank-
Garcia, S.N., Clubbs, R.L., Stanley, J.K., Scheffe, B., Yelderman, J.C., Brooks, B.W., 2013. Com-           ing and prioritization of environmental risks of pharmaceuticals in surface waters.
     parative analysis of effluent water quality from a municipal treatment plant and two                    Regul. Toxicol. Pharmacol. 39, 158–183. http://dx.doi.org/10.1016/j.yrtph.2003.12.
     on-site wastewater treatment systems. Chemosphere 92, 38–44. http://dx.doi.org/10.                     006.
     1016/j.chemosphere.2013.03.007.                                                                   Schaider, L.A., Ackerman, J.M., Rudel, R.A., 2016. Science of the total environment septic
Godfrey, E., Woessner, W.W., Benotti, M.J., 2007. Pharmaceuticals in on-site sewage efflu-                   systems as sources of organic wastewater compounds in domestic drinking water
     ent and ground water, Western Montana. Ground Water 45, 263–271. http://dx.doi.                        wells in a shallow sand and gravel aquifer. Sci. Total Environ. 547, 470–481. http://
     org/10.1111/j.1745-6584.2006.00288.x.                                                                  dx.doi.org/10.1016/j.scitotenv.2015.12.081.
Hartmann, P.C., Quinn, J.G., King, J.W., Tsutsumi, S., Takada, H., 2000. Intercalibration of           Simonich, S.L., Federle, T.O.M.W., Eckhoff, W.S., Rottiers, A., Webb, S., Sabaliunas, D., Wolf,
     LABs in marine sediment SRM1941a and their application as a molecular marker in                        W.D.E., 2002. Removal of fragrance materials during U.S. and European wastewater
     Narragansett Bay sediments. Environ. Sci. Technol. 34, 900–906.                                        treatment. Environ. Sci. Technol. 36, 2839–2847.
Heberer, T., 2002. Occurrence, fate, and assessment of polycyclic musk residues in the                 Singer, H.P., Wössner, A.E., McArdell, C.S., Fenner, K., 2016. Rapid screening for exposure
     aquatic environment of urban areas – a review. 30, 227–243.                                            to “non-target” pharmaceuticals from wastewater effluents by combining HRMS-
Howard, P.H., Muir, D.C.G., 2011. Identifying new persistent and bioaccumulative organics                   based suspect screening and exposure modeling. Environ. Sci. Technol. http://dx.
     among chemicals in commerce II: pharmaceuticals. Environ. Sci. Technol. 45,                            doi.org/10.1021/acs.est.5b03332.
     6938–6946. http://dx.doi.org/10.1021/es201196x.                                                   Stanford, B.D., Weinberg, H.S., 2010. Evaluation of on-site wastewater treatment technol-
Huppert, N., Würtele, M., Hahn, H.H., 1998. Determination of the plasticizer N-                             ogy to remove estrogens, nonylphenols, and estrogenic activity from wastewater. En-
     butylbenzenesulfonamide and the pharmaceutical ibuprofen in wastewater                                 viron. Sci. Technol. 44, 2994–3001. http://dx.doi.org/10.1021/es903422b.
     using solid phase microextraction (SPME). Fresenius J. Anal. Chem. 362, 529–536.                  Stenberg, M., Linusson, A., Tysklind, M., Andersson, P.L., 2009. A multivariate chemical
     http://dx.doi.org/10.1007/s002160051119.                                                               map of industrial chemicals–assessment of various protocols for identification of
Isobe, K.O., Zakaria, M.P., Chiem, N.H., Minh, L.Y., Prudente, M., Boonyatumanond, R., Saha,                chemicals of potential concern. Chemosphere 76, 878–884. http://dx.doi.org/10.
     M., Sarkar, S., Takada, H., 2004. Distribution of linear alkylbenzenes (LABs) in riverine              1016/j.chemosphere.2009.05.011.
     and coastal environments in South and Southeast Asia. Water Res. 38, 2448–2458.                   Swartz, C.H., Reddy, S., Benotti, M.J., Yin, H., Barber, L.B., Brownawell, B.J., Rudel, R.a., 2006.
     http://dx.doi.org/10.1016/j.watres.2004.02.009.                                                        Steroid estrogens, nonylphenol ethoxylate metabolites, and other wastewater con-
Kasprzyk-Hordern, B., Dinsdale, R.M., Guwy, A.J., 2009. The removal of pharmaceuticals,                     taminants in groundwater affected by a residential septic system on Cape Cod, MA.
     personal care products, endocrine disruptors and illicit drugs during wastewater                       Environ. Sci. Technol. 40, 4894–4902. http://dx.doi.org/10.1021/es052595+.
     treatment and its impact on the quality of receiving waters. Water Res. 43,                       Takada, H., Ishiwatari, R., 1990. Biodegradation experiments of linear alkylbenzenes
     363–380. http://dx.doi.org/10.1016/j.watres.2008.10.047.                                               (LABs): isomeric composition of C,2 LABs as an indicator of the degree of LAB degra-
Leal, L.H., Vieno, N., Temmink, H., Zeeman, G., Buisman, C.J.N., 2010. Occurrence of xeno-                  dation in the aquatic environment. Environ. Sci. Technol. 24, 86–91.
     biotics in gray water and removal in three biological treatment systems. Environ. Sci.            Teerlink, J., Martínez-Hernández, V., Higgins, C.P., Drewes, J.E., 2012. Removal of trace or-
     Technol. 44, 6835–6842. http://dx.doi.org/10.1021/es101509e.                                           ganic chemicals in onsite wastewater soil treatment units: a laboratory experiment.
Lijzen, J.P.A., Rikken, M.G.J., 2004. RIVM report no. 601900005/2004 EUSES 2.0, European                    Water Res. 46, 5174–5184. http://dx.doi.org/10.1016/j.watres.2012.06.024.
     Union System for the evaluation of substances.                                                    U.S. EPA, 2000a. Decentralized Systems Technology Fact Sheet Septic System Tank. United
Luo, Y., Guo, W., Ngo, H.H., Nghiem, L.D., Hai, F.I., Zhang, J., Liang, S., Wang, X.C., 2014. A             States Environmental Protection Agency Office of Water Washington, D.C. EPA.
     review on the occurrence of micropollutants in the aquatic environment and their                  U.S. EPA, 2000b. Decentralized Systems Technology Fact Sheet Septic Tank - Soil Absorp-
     fate and removal during wastewater treatment. Sci. Total Environ. 473-474,                             tion Systems. United States Environmental Protection Agency Office of Water
     619–641. http://dx.doi.org/10.1016/j.scitotenv.2013.12.065.                                            Washington, D.C. EPA.
Marklund, A., Andersson, B., Haglund, P., 2005. Organophosphorus flame retardants and                   U.S. EPA, 2000c. Wastewater Technology Fact Sheet Package Plants. United States Envi-
     plasticizers in Swedish sewage treatment plants. Environ. Sci. Technol. 39,                            ronmental Protection Agency EPA 832-F-99-062.
     7423–7429.                                                                                        U.S. EPA, 2000d. Decentralized Systems Technology Fact Sheet Aerobic Treatment. United
Olshammar, M., Sidvall, A., Svanström, S., Ek, M., Rosenquist, L., Ejhed, H., 2015. SMED rap-               States Environmental Protection Agency.
     port 2015: Uppdatering av kunskapsläget och statistik för små avloppsanläggningar.                U.S. EPA, 2008. Septic Systems Fact Sheet.
Paxéus, N., 1996. Organic pollutants in the effluents of large wastewater treatment                     Verlicchi, P., Al Aukidy, M., Zambello, E., 2012. Occurrence of pharmaceutical compounds
     plants in Sweden. Water Res. 30, 1115–1122. http://dx.doi.org/10.1016/0043-                            in urban wastewater: removal, mass load and environmental risk after a secondary
     1354(95)00278-2.                                                                                       treatment—a review. Sci. Total Environ. 429, 123–155. http://dx.doi.org/10.1016/j.
Petrovic, M., 2003. Analysis and removal of emerging contaminants in wastewater and                         scitotenv.2012.04.028.
     drinking water. TrAC Trends Anal. Chem. 22, 685–696. http://dx.doi.org/10.1016/                   Wennmalm, A., Gunnarsson, B.P., 2005. Public health care management of water pollution
     S0165-9936(03)01105-1.                                                                                 with pharmaceuticals: environmental classification and analysis of pharmaceutical
Phillips, P.J., Schubert, C., Argue, D., Fisher, I., Furlong, E.T., Foreman, W., Gray, J., Chalmers,        residues in sewage water. Drug Inf. J. 39, 291–297.
     A., 2015. Concentrations of hormones, pharmaceuticals and other micropollutants in                Wilcox, J.D., Bahr, J.M., Hedman, C.J., Hemming, J.D.C., Barman, M.A.E., Bradbury, K.R.,
     groundwater affected by septic systems in New England and New York. Sci. Total En-                     2009. Removal of organic wastewater contaminants in septic systems using advanced
     viron. 512-513, 43–54. http://dx.doi.org/10.1016/j.scitotenv.2014.12.067.                              treatment technologies. J. Environ. Qual. 38, 149–156. http://dx.doi.org/10.2134/
Rager, J.E., Strynar, M.J., Liang, S., McMahen, R.L., Richard, A.M., Grulke, C.M., Wambaugh,                jeq2007.0365.
     J.F., Isaacs, K.K., Judson, R., Williams, A.J., Sobus, J.R., 2016. Linking high resolution        Wilcoxon, F., 1945. Individual comparisons by ranking methods. Biom. Bull. 1, 80–83.
     mass spectrometry data with exposure and toxicity forecasts to advance high-                      World Health Organization, 1998. Environmental Health Criteria 209 - Flame Retardants:
     throughput environmental monitoring. Environ. Int. 88, 269–280. http://dx.doi.org/                     Tris(chloropropyl) Phosphate and Tris(2-chloroethyl) Phosphate (Geneva).
     10.1016/j.envint.2015.12.008.                                                                     www.epa.gov, 2008. EPIWEB 4.1.