CALCULATION SHEET
#REF!
                                                                                                                             FOAM DEMAND CALCULATION
JOB NO.          :    STC-0781
FIRE ZONE        :    11
LOCATION         :    Condensate Storage Tank Area
                                                                                                               PREP'D               :       CM
PROJECT          :    GG Field Development                                                                     CHK'D                :       AGK/JH
                                                                                                               APP'D                :       CK
CLIENT           :    PHE ONWJ                                                                                 REV                  :       2
DATE             :    7-May-14
                                                     CONDENSATE STORAGE TANK (BANG-T-050A/B)
                                                                          10.06 m
                                                                                                                                                 9.14 m
Type of Foam Chamber                                                                   :   Type II, Fixed Discharge Outlet
Tank diameter                                                                          :                 10.06 m
Tank height                                                                            :                  9.14 m
Roof                                                                                   :   Fixed Roof (Cone)
Primary Fire Protection (Foam Chamber)
Annular Ring Area (Total Surface Area)                                                 :                79.49 m2
Foam Application Rate                                                                  :                  4.1 L/min.m2         NFPA 11 Table 5.2.5.2.2
Foam Solution Discharge Rate (Annular Ring Area x Application Rate)                    :               325.89 L/min
Foam Concentration Type                                                                :                  3% AFFF
Foam Application Duration                                                              :                   55 min              NFPA 11 Table 5.2.5.2.2
Number of foam pourer required                                                         :                    1                  NFPA 11 Table 5.2.5.2.1
Foam Concentrate Quantity with 20% additional margin (Primary)                         :                 645 ≈ 650 litres      For 1 Tank
Fire Water Application Rate (20% Hydraulic Contingency)                                :                 379 L/min
                                                                                       :                 100 USGPM             For 1 Tank
Supplementary Protection (Foam Hose Stream)
Area to be protected by foam hose stream is small spill fire around condensate tanks.
mobile foam equipment will be connected to water hydrant.
Foam Solution Discharge Rate                                                          :                     50 gpm             NFPA 11 Section 5.9.2.3
Foam Concentration type                                                               :                    3% AFFF                                               2
Foam Application Duration                                                                                   10 min             NFPA 11 Table 5.9.2.4
Number of Hose Streams                                                                :                      1                 NFPA 11 Table 5.9.2.2
Foam Concentrate Quantity with 20% additional margin (Total)                          :                     18 gallon
                                                                                      :                     68 ≈ 70 litres
Diked Areas - Outdoor (Fire Water-Foam Monitor)
Area to be protected by fire water-foam monitor is dike area of condensate storage tanks in case of pool fire.
Portable foam container will be connected to fire water monitor.
Dike area                                                                             :                     484 m2            For 1 Dike Area
Tank Area (Total Surface Area)                                                        :                    79.5 m2
Area to be protected                                                                  :                     405 m2
Foam monitor application rate                                                         :                     6.5 L/min.m2      NFPA 11 Table 5.7.3.2
Foam Solution Discharge Rate (Area to be protected x Application Rate)                :                   2629 L/min
Foam Concentration Type                                                               :                     3% AFFF
Foam Application Duration                                                             :                      30 min           NFPA 11 Table 5.7.3.2
Foam Concentrate Quantity with 20% additional margin (Total)                          :                   2840 ≈ 3000 litres
Since OPF Balongan will activate two (2) fire water-foam monitor as together in case of pool fire at dike area, hence foam concentrate quantity of 3000 litres
will be divided for two (2) monitor which each monitor will be 1500 litres
                                                                                   CALCULATION SHEET
                                        #REF!
                                                                                   FOAM MAKER SYSTEM
JOB NO.      :   STC-0781
FIRE ZONE    :   11
LOCATION     :   Condensate Storage Tanks Area
                                                                         PREP'D      :   CM
PROJECT      :   GG Field Development                                    CHK'D       :   AGK/JH
                                                                         APP'D       :   CK
CLIENT       :   PHE ONWJ                                                REV         :   2
DATE         :   7-May-14
                                          DIAPHRAGM (BLADDER) PROPORTIONING TANK
                                                         CALCULATION SHEET
                                       #REF!
                                                         FOAM MAKER SYSTEM
JOB NO.     :   STC-0781
FIRE ZONE   :   11
LOCATION    :   Condensate Storage Tanks Area
                                                PREP'D     :   CM
PROJECT     :   GG Field Development            CHK'D      :   AGK/JH
                                                APP'D      :   CK
CLIENT      :   PHE ONWJ                        REV        :   2
DATE        :   7-May-14