Objectives
The Objective of this course is to give
Field Teams a ‘hands on’ experience of
solving engineering problems.
Power routes for BTS Site
63A
E.L.C.B
D 10A, 2P
Mains ATS I In/Out door Lights
(WAPDA 03 Φ)
S
Generator T 10A, 2P Tower Lights
(03 Φ)
R
I 10A, 2P Emergency Lights
B
RF Antenna
U M/W
10A, 2P Fire Device Antenna
T
I 16A, 2P E.L.C.B. 25A Sockets
O
N BTS Cabinet
Microwave
32A, 2P ACs IDU
P
A 10A/32A
Spares
2P (each)
N DC Supply
E 32A, 4P
-54V
Rectifier
L
LVD
(AC Supply)
Battery
(D.P) Backup
CONTENTS
………… Introduction
………… Equipment Description
………… Installation and Wiring
………… Maintenance and Component Replacement
………… Handling
ATS
Generator Load
(Standby Source)
WAPDA
(Normal Source)
AUTOMATIC TRANSFER SWITCH
ATS
Cable Glands
Ducting for Power Cables
ATS Components 0
3 1
Fuses
ATS Selection Switch
Electromechanically Relay Timer Delay Relays
Magnetic Contactors
3 Phase Monitor (UVR)
Indicators Circuit Breakers
Auxiliary Contact Block
Interlock Unit
Front Mount
Magnetic Contactor Coil
Contacts Status
ATS Selection Switch Position Mains control (Φ)
Gen set control(Φ)
Gen Auto Start
Input (1) Output (A1)
OFF Input (2) Output (B2)
Input (3) Output (C3)
Input (1) Output (A1)
1 Input (2) Output (B2)
(Mains) Input (3) Output (C3)
Input (1) Output (A1)
2 Input (2) Output (B2)
(Auto) Input (3) Output (C3)
Input (1) Output (A1)
3 Input (2) Output (B2)
(Gen) Input (3) Output (C3)
ATS Selection Switch Position:
Four positions;
0 = OFF
1 = Normal Source
2 = Auto Function
3 = Emergency Source
Power Source Availability:
Provides LEDs to indicate if a power source is available. LEDs
may be Red, Yellow & Blue for 03 phases.
(a) Normal Source (WAPDA) – Available
(b) Emergency Source (Generator) – Available
Load Transferred Availability:
Two LEDs for Normal & Emergency Source.
POWER CABLES BEFORE & AFTER PM
Before PM After PM
Wapda phase (In)
Gen phase (In)
N (0) N (00)
Coil Coil
NC
v
NC
Wapda Gen
Magnetic Magnetic
Contactor Contactor
Interlock (Mechanical & Electrical)
MCB Order Information
S25 1S C10
Type Rated Current
Pole
17.5 mm 4 Pole
Catalog number explanation
A9-30-10-84
Frame size Coil voltage
(see coil voltage selection chart)
Power pole
30 = 3 NO
Auxiliary contacts
40 = 4 NO
22 = 2 NO & 2 NC 10 = 1 NO & 0 NC
01 = 0 NO & 1 NC
11 = 1 NO & 1 NC
00 = No auxiliary provided
Coil voltage selection chart
Hz 12 24 48 110 120 125 208 220 240 277 380 415 440 480 500 600
50 81 83 84 84 34 36 80 42 86 86 51 53 55
60 81 83 84 80 85 86 55
SINGLE GENSET ATS
DUAL GENSETS ATS
Thank You
20