Cable
Classification
• Operating voltage
•Operating frequency
• Conductor type
• Insulation level
• Core number
• Neutral and Earthing cable
• Derating factors
• Cross section area (mm2)
Operating
Voltage
• The higherthe operating voltage,
the more insulation required,
also lower crossectional area
required due to the presence of
lower current.
4.
🔍 Summary Table— Voltage Class Overview
Classification
Nominal System
Voltage Range
Typical Rating
(U₀/U)
Example
Applications
Low Voltage (LV) Up to 1 kV
0.3/0.5, 0.45/0.75,
0.6/1 kV
Building wiring,
domestic
distribution
Medium Voltage
(MV)
3.3 kV – 33 kV 3.6/6 to 18/30 kV
Industrial feeders,
substations
High Voltage (HV) 66 kV – 220 kV (+)
64/110 to 127/220
kV
Transmission
networks
Conductor Types
• Aluminum(Al) and Copper (Cu).
• According to the International Annealed Copper Standard (IACS), although aluminum only has 61% of
the conductivity of copper it is only 30% of the weight, and therefore significantly cheaper.
• All medium voltage cables are made from Al because of two reasons:- Low current and Underground
cable cost, except cables used to fed motors load.
• Low voltage cables are preferred from Cu in the electrical distribution network.
• The voltage drop (mV/A.m) for aluminium cables is higher than the equivalent copper cable.
8.
Conductor Types
• Aluminumcables appear cheaper, but this doesn’t take into consideration the extra cost and effort
involved in installing less pliable aluminum cables. Therefore, copper cables are still primarily used for the
low voltage network, except in situations where overhead cables are installed, and weight is a factor.
• Aluminum cable requires a larger cross-sectional area to match the conductivity of the equivalent copper
cable. An aluminum cable needs a 56% larger cross-sectional area to achieve the same conductive
capability as a copper cable.
• If run underground, the size and number of conduits would need to increase to match the increased
aluminum cable cross-sectional area. If run above ground, the width of cable tray would need to increase
to accommodate larger and additional aluminum cables.
• Installation of aluminum cables are more difficult due to the flexibility and size.
Conductor Types
Key Insight💡
• Larger cross-sections reduce resistance and improve current
capacity.
•Copper cables carry more current and handle higher short-
circuit stress than Aluminum.
Armouring Types
Type Advantages
S.T.A(Steel Tape Armoured) S.T.A withstands mechanical stress
more than SWA, that’s why it is used
in underground cables.
S.W.A (Steel Wire Armoured) S.W.A more flexible than S.T.A, It
withstands high pull loads.
Number of
Cores
Number ofCores Application
Single Core Cable If CSA of each phase greater than 300mm2, used in riser of residential
buildings, and as an earthing cable.
Two Core Cable Used in low voltage single phase system, where only a phase and a neutral
are needed, there is no earthing system [ L& N only ].
Three Core Cable Same application of two core but an additional core for earthing [L, N and
E], also used in the medium voltage cable where only 3 phases are needed
[R, S, and T].
Four Core Cable Used in the low voltage system where three phases are needed in addition
to the neutral [R, S, T and N].
18.
Cable Formation
Cable FormationApplication
Trefoil Formation • Same distance apart between which means the magnetic field and circulating
currents are equivalent for each cable phase.
• Trefoil phase formation is more commonly used for Low and Medium Voltage
applications up to 132kV due to ease of installation and the reduction in space the
formation has.
⚠️Heat Dissipation Limitation
Because the cables are touching each other, the heat dissipation is restricted.
This leads to higher cable temperature and therefore a lower current-carrying
capacity compared to flat or spaced formations.
19.
Cable Formation
Cable FormationApplication
Flat Formation What is Flat Formation?
Flat formation is an arrangement where three single-core cables (phases R, Y, and B)
are laid side-by-side in a straight line with equal spacing between them.
📏 Purpose:
To provide better air circulation and heat dissipation, especially for high-current
installations.
Common in Medium and High Voltage (MV & HV) systems.
Used where space is available — such as in trenches, ducts, or outdoor installations.
Ideal for long horizontal runs (substations, feeders, transmission corridors).
Since the cables are not symmetrically spaced, the magnetic field around each phase
is unequal.
20.
Derating factor
• Deratingfactors or correction factors are the factors which makes a cable current carrying capacity less than
the designed value. For example, ambient air temperature, soil temperature and laying method of the cable.
• If a cable has derating factor of 0.8, this means that the cable can only provide 80% of it’s rated current
capacity, so we need to select a higher current capacity cable to compensate for this drop.
• Let’s say we have a cable with a current capacity of 100 Amps and the load is 100 Amps, this cable will not
be
able to satisfy load requirement due to derating factor, it will give only 80 Amps.
• If we select a higher current cable of value = I/derating factor = 100/0.8 = 125 Amps and install this cable in the
same conditions. This cable will provide 125*0.8 = 100 Amps, which is the required current.
22.
Key Observations fromthe table
Parameter Explanation
Number of Circuits More circuits laid together cause greater mutual
heating → lower derating factor.
Formation Type
Flat formation provides slightly better cooling
than trefoil → higher derating factors.
Spacing (L)
Increasing spacing between circuits (e.g., from
touching → 0.15 m → 0.30 m) improves heat
dissipation → higher derating factors.
23.
Typical Applications byNumber of Circuits
Typical Applications by Number of Circuits
3️
3️
⃣
No. of Circuits
How It’s
Configured
Where It’s Used Comment
1 Circuit
One set of
cables from
source to load
Apartment
risers, DB
feeders
Typical small LV system
2 Circuits
(Parallel)
Two identical
sets of cables in
parallel
Transformer →
Main DB
For medium loads or
reduced voltage drop
3–4 Circuits
(Parallel)
Three or four
identical runs
Factory feeders,
large
commercial
mains
For high currents or long
distances
5–6 Circuits
(Parallel)
Five or six
identical cable
sets
Substation
outputs,
industrial
distribution
For high-capacity systems
or redundancy
24.
Selection of Neutraland
Earthing Cable Cross
Section Areas
By eng. Ahmed Mahdy/ Khadija Academy
25.
Neutral
Conductor Cross
Section Area
•If the C.S.A of the phase conductor less than 35 𝑚𝑚2, then the neutral C.S.A will be the same as the
C.S.A of any of the three phases.
• If the C.S.A of the phase conductor greater than 35 𝑚𝑚2, then the neutral C.S.A will be half the
C.S.A of any of the three phases.
26.
Example
Phase Conductor Size(mm²) Neutral Conductor Size (mm²) Rule Applied
10 mm² 10 mm² Equal (≤35 mm²)
25 mm² 25 mm² Equal (≤35 mm²)
35 mm² 35 mm² Equal (≤35 mm²)
50 mm² 25 mm² May be reduced (>35 mm²)
95 mm² 50 mm² May be reduced (>35 mm²)
Example Table
4️
⃣
27.
Earthing
Conductor Cross
Section Area
•If the C.S.A of the phase conductor less than 16 𝑚𝑚2, then the earthing C.S.A will be the same as
the
C.S.A of any of the three phases
• If the C.S.A of the phase conductor 25 𝑚𝑚2 or 35 𝑚𝑚2 then the earthing C.S.A will be 16 𝑚𝑚2
• If the C.S.A of the phase conductor greater than 35 𝑚𝑚2, then the earthing C.S.A will be half the
C.S.A of any of the three phases
28.
Single or
Multi Core
Cable
Powercables can be designed as:
•Single-core cable → each phase (R, Y, B) has its own insulated
conductor
•Multi-core cable → all three phases and neutral (and sometimes
earth) are contained in one outer sheath
•Left diagram:
Multi-core cable —
all phases (R, C, T /
N / E) under one
sheath; compact,
used for LV feeders.
•Right diagram:
Single-core cables
— individual phase,
neutral, and earth
laid side by side or
in trefoil; used for
larger cross-
sections or high
current.
29.
Cable Design –How To Select
Cable Cross-Sectional Area?
By eng. Ahmed Mahdy/ Khadija Academy
30.
Find Rated
Current ofThe
Load and The CB
Rating
• I rated
=
40∗74
6
3∗380∗0
.8
=
56.6 𝐴
• I CB = I rated * 1.25 = 56.6 *1.25 =
70.75 A.
• I Cable
=
I
CB
Derating
factor
31.
Derating Factors
- Catalog
•Assume using PVC cable, the air
temperature in the installation area is
50 °C, derating factor
= 0.82.
• The cable rating = 70.75
=86.28 A.
0.82
• Cable selected is (4x25)+16
mm2