Power-Angle Relationship
Fig. 13.3 Power-angle relationship
Both transmission circuits in-service: Curve 1
operate at point "a" (Pe = Pm)
One circuit out-of-service: Curve 2
lower Pmax operate at point "b" higher reactance higher to transmit same power
Effects of Disturbance
The oscillation of is superimposed on the synchronous speed 0 ( = d dt ) << Speed deviation
r 0
the generator speed is practically equal to 0, and the per unit (pu) air-gap torque may be considered to be equal to the pu air-gap power torque and power are used interchangeably when referring to the swing equation.
Equation of Motion or Swing Equation
2 H
where: Pm Pmax H t = = = = =
d 2 dt 2
= P
max
sin
mechanical power input (pu) maximum electrical power output (pm) inertia constant (MW-sec/MVA) rotor angle (elec. radians) time (secs)
Response to a Short Circuit Fault
Illustrate the equal area criterion using the following system:
Examine the impact on stability of different fault clearing times
Stable Case
Response to a fault cleared in tcl seconds - stable case
Stable Case
Pre-disturbance:
both circuits I/S : Pe = Pm, = 0 operating point a
cont'd
Fault On:
operating point moves from a to b inertia prevents from changing instantaneously Pm > Pe
rotor accelerates to operating point c
Post Fault:
faulted circuit is tripped, operating point shifts to d
rotor decelerates rotor speed > increases
Pe > Pm
0
operating point moves from d to e such that A1 = A2 at e, speed = 0, and = m Pe > Pm
rotor decelerates; speed below
decreases and operating point retraces e to d with no damping, rotor continues to oscillate
Unstable Case
Response to a fault cleared in tc2 seconds - unstable case