(c) Pilot Relaying Schemes
Use communication channels (pilots) between the terminals of the line that they protect Determine whether the fault is internal or external to the protected line, and this information is transmitted For an internal fault, circuit breakers at all terminals of the protected line are tripped; for an external fault the tripping is blocked Communication medium may be pilot wire (metallic wires), power-line carrier, microwave, or fibre optic
Permissive Overreaching Scheme:
Fig. 13.30 Permissive overreaching relay
Each terminal station of the line has: Underreaching zone 1 phase and ground directional distance relays covering about 75-80% of the line
trip local breakers instantaneously
Overreaching zone 2 phase and ground directional distance relays covering about 120% of the impedance of the protected line.
send permissive signal to remote end trip local breakers if permissive signal received from remote end if apparent Z remains inside relay characteristic for fixed time (typically 0.4
Fig. 13.31 Relay characteristic at station A
Fig. 13.31 Fault locations F1, F2 and F3
Fault Clearing Times
Composed of relay time and breaker operating time
EHV relays: 1-2 cycles Circuit breakers: 2-4 cycles
Breaker failure backup protection provided for each breaker on all critical circuits
if a breaker fails to operate at a local
Local (Bus A) breakers 1 and 2
Remote (Bus B) breakers 3 and 4
Primary relay time (Fault detection) Auxiliary relay(s) time Communication time Breaker trip module Breaker clearing time Total Time
25 ms 3 ms 3 ms 33 ms (2 cycles) 64 ms
25 ms 9 ms 17 ms (microwave) 3 ms 50 ms (3 cycles) 104 ms
Fault cleared from bus A in 64 milliseconds Fault cleared from bus B in 104 milliseconds
Notes: (i) For purposes of illustration, 2 cycle breakers have been assumed at A and 3 cycle breakers at B (ii) Communication time depends on channel medium used. With power line carrier, the time may be longer
Fig. 13.34 Typical fault clearing times for a normally cleared fault
Breaker 4 assumed to be stuck Breakers 1, 2, 3, 4, and 5 assumed to be 2 cycle air-blast breakers (33 ms) Breakers 6 and 7 assumed to be 3 cycle oil breakers (50 ms)
Local Breaker 5 Primary relay time (at bus B) Auxiliary relay(s) time Communication channel time Breaker failure timer setting Breaker tripping module time Breaker time 25 ms 3 ms 3 ms 33 ms Remote breakers 6 and 7 25 ms 9 ms 17 ms 3 ms 50 ms Local backup breaker 3 25 ms 6 ms 90 ms 3 ms 33 ms Remote backup breakers 1 and 2 25 ms 12 ms 17 ms 90 ms 3 ms 33 ms
Total time Fault cleared from bus C in 104 milliseconds Fault cleared from bus B in 157 milliseconds Fault cleared from bus A in 180 milliseconds
64 ms
104 ms
157 ms
180 ms
Notes: Breaker failure timer setting has been assumed to be 90 ms for the 2 cycle breaker 4. This could vary from one application to another. For a 3 cycle oil breaker a typical value is 150 ms
Fig. 13.34 Typical fault clearing times for a stuck breaker fault