0 ratings0% found this document useful (0 votes) 7K views23 pagesMacClean NF2001
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content,
claim it here.
Available Formats
Download as PDF or read online on Scribd
INSTALLATION
AND OPERATING
INSTRUCTIONS
NF SERIES
CHEM-FREE™ IRON REMOVAL SYSTEMS
MODELS:
NFO750 NFO750M
NFO751 NFO751M_
NF 1000 NF 1000M
NF1001 NF1001M
NF2000 NF2000M
NF2001 NF2001M
NF3001 NF3001M
TESTED AND LISTED UNDER NSF
‘STANDARD 42 FORIRONREDUGTION
NF3001 IS PRESENTLY NOT LISTED
AND CURRENTLY NOT AVAILABLE,
Morutacored and sols under US Patent No 3.649532
Chemical Engineering Corporation
12628 U.S. 33 North, Churubusco, IN 46723
IN107G (0-945)TABLE OF CONTENTS
DESCRIPTION
GENERAL INFORMATION
BEFORE INSTALLATION
SECTION
INSTALLATION
PLUMBING SYSTEM CLEAN-UP.
BACKWASHING INSTRUCTIONS:
TROUBLESHOOTING
SPECIFICATIONS & OPERATING DATA
Copyright © 1993 by Chemical Engineering Corporation. All rights reserved. Not to be reprinted in any form without writen permission.
SECTION I: GENERAL INFORMATION
Congratulations on your purchase of a Chem-Free™ Iron
Removal System! The Chem-Free fiter removes dissolved,
precipitated and bacterial iron from your water supply.
Contrary to conventional methods, your Chem-Free filter
requires NO chemicals (either added to the water supply or
the filter). The unique process is patented and requires
ONLY periodic backwashing for a few minutes to flush out
entrapped iron that has accumulated in the filter tank.
‘When properly installed, the Chem-Free Iron Removal Sys:
tem will provide many years of trouble-free service. Read
this manual all the way through first, and then follow the
installation steps in the proper sequence.
DESCRIPTION AND OPERATION OF THE SYSTEM:
‘The Chem-Free filter consists of two major components
which are’
1) AHYDRO-CHARGER™, located between the well head
and the pressure tank, adds a small amount of airto the
iron-laden water whenever the well pump runs.
2) Abackwashing type fitter containing aspecial media that
‘causes the iron in the “Hydro-Charged’ water to precipi-
tate throughout the fiter bed (rather than on the surface
as in chemical oxidizing fiers.) This process produces
aniron removal capacity of from 30,000 to 50,000 parts
per milion (ppm) compared to 6,000 to 8,000 ppm for
4
chemical oxidation processes. The media DOES NOT
require a chemical regenerant (such as potassium
permanganate) for oxygen enrichment, salt, chlorine or
any other chemicals.
Your Chem-Free fiter automatically adjusts the pH to neutral
or higher on acid water WITHOUT an acid neutralizer (a
required piece of equipment with chemical oxidation fiters
whenever the pH is less than 6.7). The ability to raise pH
when itis below neutral (7 or less) greatly enhances the
Chem-Free fite’s ability to remove iron efficiently,
NOTE: Replenishment of the component of the filter media
that adjusts pH, "MpH Adder™", may be required periodi-
cally, the frequency of which is dependent on the raw water
pH, the manganese (Mn) concentration in the water (it any)
and the water consumption rate.
Periodic backwashing of the filter bed flushes the precipi
talediron to the drain and readies the filter for use again. The
duration of the backwash procedure is approximately 30
minutes. The frequency of backwashing depends on iron
concentration and water usage, and ranges from daily to
once every 6 days. The volume of water consumed during
the entire backwashing procedure is approximately 100
gallons (models NF 1000 and NF 1001).INSPECTING AND HANDLING YOUR WATER SOFTENER:
Inspect the equipment for shipping damage. If damaged,
notify the transportation company and request a damage
inspection.
Handle the equipment with care, Damage can result if
dropped or i set on sharp, uneven projections on the floor.
Do not turn the filter unit’ upside down.
MAKE SURE YOUR WATER HAS BEEN THOROUGHLY
‘TESTED:
An analysis of your water should be made prior to the
selection of your water conditioning equipment, Your
Chem-Free dealer will generally perform this service for
you, and may send a sample to the factory for analysis
and recommendations. Enter your analysis below for a
permanent record.
NOTE: Hydrogen sulfide (H,S) must be tested for at the
well site, For accuracy, the sample must be drawn with
the pump RUNNING, and the test be completed within
ONE minute atter the sample is drawn.
ANALYSIS OF YOUR WATER.
Hardness pg
Iron (Fe) ppm
‘Manganese (Mn) ppm
pH
Tannins (Humic Acid) ppm
Hydrogen sulfide (H,S) ppm
Other
Other
The following description of the water constituents listed
above on the selection of the appropriate Chem-Free
‘model, and their effect on its operation will help to highiight
their significance:
IRON (Fe)
lron concentrations as low as 0.3 ppm (0.1 ppm under
‘some conditions) will cause staining. The iron concentra-
tion, together with the flow rate demand and the consump-
tion rate of the water determines the basic size filter
system. The higher these factors are, the larger the
required system. The Chem-Free filter system is capable
f filtering out the three main types of iron found in water
supplies: Soluble iron (also known as “clear water” or
ferrous iron), precipitated iron (also known as “red water”
or ferric iron) and bacterial iron (also known as iron
bacteria). There is no apparent upper limit of iron concen-
tration for the Chem-Free filter, but special care must be
taken when selecting a filter model if your water has a
combination of high iron, very low pH and/or manganese
levels above 0.2 ppm.
SECTION 2: BEFORE INSTALLATION)
The Chem-Free fiter is not bactericidal, Le. it does not
remove or kil “bacterial iron’. It removes the iron upon
which the bacteria may live or which it deposits in your
plumbing fixtures, thus eliminating its effects.
MANGANESE (Min)
‘The presence of manganese can be bothersome, even
for a Chem-Free iron filter (and it is devastating for
chemical oxidizing systems). As little as 0.05 ppm of
manganese can produce a brownish or black stain. The
ability of the Chem-Free filter to remove manganese
depends on its concentration and the pH of the water.
Although not specifically designed for the removal of
manganese, the oxidation of manganese is very similar to
that of iron. ‘ts oxidation is more pH dependent than that
of iron, therefore, a pH of 8.2 or higher must be obtained.
When this pH level is achieved, the precipitation of man-
ganese may more readily occur. To accomplish this,
‘models are available where the media contains additional
quantities of MpH Adder, the pH raising component
(model designations with "M” suffix). In any application
involving manganese, a larger model fiter is generally
recommended (but only if the pumping rate is sutficient to
backwash the larger size.)
Ht, however, the manganese concentration is low (0.1 ppm
of less) and the pH is 6.5 or higher, a Chem-Free filter
containing standard Chem-Free filter media will generally
perform satisfactorily, although backwashing should be
performed at more frequent intervals. Under more severe
conditions where the pH is very low andlor the manga-
nese concentration is high, an acid neutralizer or chemical
feed pump injecting soda ash installed ahead of the
Chem-Free filter will maintain the required 8.2 pH level
longer than the Chem-Free fier will between replenish-
ment with MpH Adder
pH
‘The pH of water measures its acidity. Water with a pH of
less than 7.0 is acidic, above 7.0 itis alkaline, and a pH of
7.0 is neutral. The lower the pH value the greater the
acidity, and the higher the pH value the more alkaline.
Acidic water (pH less than 7.0) is corrosive to pipes,
appliances, etc. A pH of 7.0 or higher facilitates iron
removal - which is why the Chem-Free fier is designed to
increase the pH when itis less than 7.0.
The pH increasing component of Chem-Free media is
‘sacrificial’. that is, it slowly dissolves during the process
or increasing pH. The rate this occurs is proportional to
the degree of the pH increase and the water consumption
rate (.2., the greater the pH increase and water consump-
tion, the ‘greater the sacrificial rate). Thus, when the pH
is increased to 8.2 or more, as is necessary when manga-
nese is present, the sacrificial rate is even greater. Under
the most severe conditions, the MpH component of the
media may have to be replenished two to four times per
year. On the other hand, if the raw water pH is 7.0 or
above and no manganese is present, the sacrificial rate is
very slight (see NOTE, Sec. 1)‘TANNINS (Humic Acid)
Tannins (a humic acid), which may be present in some
water supplies, are the result of various forms of decaying
vegetation (the test for tannins can be performed by your
dealer). Tannins can cause problems in the operation of
the Chem-Free fitter by forming a sticky coating on the
media, thus rendering it incapable of fitering the iron.
Generally with tannin concentrations of 0.5 ppm or less,
more frequent backwashing will prevent the sticky coating
from forming. It does appear, however, that the level of
tannin concentration affects the operation of the Chem-
Free fiter differently in different geographical areas (in
some areas the Chem-Free filter wll perform satisfactorily
when tannin concentration is considerably greater than
0.5 ppm). tis therefore recommended that if the tannin
concentration is 0.5 ppm or more, contact your dealer
BEFORE installing the system.
HYDROGEN SULAIDE (H,S)
Hydrogen sulfide (often referred to as “sulfur’), is easily
detectable by its objectionable “rotten egg” odor. Sulfur
ccorrodes iron, brass, copper and silver. While the Chem-
Free iron fiter is not intended to be used as a sulfur fitter,
itis capable of removing sulfur in concentrations of up to
20r 3 ppm, and sometimes as high as 5 ppm. Whenever
hydrogen sulfide is present, backwashing must be per-
formed at more frequent ‘intervals, and the pumping
system MUST include a standard air-to-water pressure
tank with an air-relief valve.
CHECK YOUR WATER PRESSURE AND PUMPING RATE:
‘Twowater system conditions must be checked carefully to
avoid unsatisfactory operation or equipment damage:
1) MINIMUM water pressure required at the filter tank
inlet is 20 psi. IF PRESSURE IS OVER 100 PSI, A
PRESSURE REDUCING VALVE MUST BE IN-
‘STALLED IN THE WATER SUPPLY LINE AHEAD OF
THE HYDRO-CHARGER.
NOTE: \f you have a municipal or a community water
supply and daytime water pressure is 85 psi or more,
nighttime pressure may exceed 100 psi. Call you local
water department or plant operator to obtain pressure
readings. If you have a private well, the gauge on the
pressure tank will indicate the high and low system
pressure. Record your water pressure data below:
WATER PRESSURE
Low psi High psi
2) The pumping rate of your well pump must be sufficient
for satistactory operation of the HYDRO-CHARGER
and to BACKWASH the filter. For models NF1001 and
NF1001M the REQUIRED rate is 5 gpm (refer to
SPECIFICATIONS AND OPERATING DATA for the
backwash requirement for other models). To measure
the pumping rate of your pump, follow these instruc-
tions:
22
‘a, Make certain no water is being drawn. Open spigot
nearest pressure tank. When pump starts, close
spigot and measure time (in seconds) to refill pres-
sure tank (when pump shuts off). This figure
represents CYCLE TIME.
b. With the pressure tank full, draw water into a
container of known volume, measure the number of
gallons drawn until the pump starts again. This is
DRAW-DOWN. Divide this figure by CYCLE TIME
and multiply the result by 60 to arrive at the PUMP-
ING RATE in gallons per minute (gpm). To aid in
your calculation, insert the data in the following
formula:
DRAW-DOWN + CYCLE TIME__x
° (gals.) (secs.)
= PUMPING RATE __
(gpm)
EXAMPLE: CYCLE TIME is 65 secs.; DRAW-
DOWN is 6 gals; then, PUMPING RATE equals:
6 gal. + 65 secs. x 60 = 5.5 gpm
NOTE: The addition of tne HYDRO-CHARGER to
the pumping system or plumbing and other water
treatment devices (such as an acid neutralizer) may
reduce the flow rate at the filter drain to an inad-
equate level to properly backwash the filter. f you
are uncertain whether your flow rate is adequate,
contact your dealer BEFORE installing your Chem:
Free filter, so that corrective action, it required, may
be taken.
LOCATE WATER CONDITIONING EQUIPMENT CAREFULLY:
1) Locate as close as possible to water supply source.
2) Locate as close as possible to a tloor or laundry tub
drain.
3) Locate in correct relationship to other water condition
ing equipment (see Figs. 1, 2 or 3 in Sec. 3).
4) Filters and softeners should be located in the supply
line BEFORE the water heater. Temperatures above
100° F (38° C) damage filters and softeners and will
void the factory warranty.
Do NOT install a filter or softener in a location where
freezing temperatures occur. Freezing may cause
permanent damage to this type equipment and will
also void the factory warranty.
5)
6) Allow sufficient space around the unit for easy servic-
ing.
7) If your water source is a community water supply, a
public water supply, OR you wish to bypass water
Used for a geothermal heat pump, lawn sprinkling, out:buildings or other high demand applications, refer to
Figs. 2 or 3 for additional equipment required. Also,
reler to the SPECIAL INSTRUCTIONS following Step.
11 of Sec. 3, INSTALLATION.
‘THE IMPORTANCE OF YOUR PRESSURE TANK:
The pressure tank found on private well systems becomes
an integral part of the Chem-Free filter system by provid-
ing necessary mixing and "residence time” to the "Hydro-
Charged” water. While the Chem-Free iron filter system
will perform satisfactorily with either a captive-air (blad-
der’) type pressure tank or a standard air-lo-water type
with an air volume control (air-relief valve), the bladder
type requires more careful adjustment of the HYDRO-
CHARGER to prevent gases from collecting in the pres-
sure tank and the head area of the filter tank,
A PROPERLY SIZED PRESSURE TANK OF EITHER
STYLE WILL REQUIRE A MINIMUM PUMP CYCLE OF
60 SECONDS TO REFILL FROM THE WELL PUMP ON-
TO-OFF PRESSURE SETTINGS. IF CYCLE TIME OF
PUMP IS LESS THAN 60 SECONDS, PRESSURE TANK
IS TOO SMALL CAUSING EXCESSIVE WEAR ON THE
PUMP AND PROBABLE FAILURE OF THE FILTER
SYSTEM.
Under more severe operating conditions (low pH, high
iron, manganese and small concentrations of sulfur), a
standard air-to-water type pressure tank with an air-relief
valve MUST be used (if bladder type tank is already in
place - do not remove it - install the air-to-water pressure
tank between the HYDRO-CHARGER and the bladder
type tank)
NOTE: \ your pressure tank (or any part of your water
system) is not functioning properly, corrective action MUST
be taken BEFORE installation of your Chem-Free Iron
Filter.
23
FACTS TO REMEMBER WHILE PLANNING YOUR IN-
STALLATION:
1) Allinstallation procedures MUST conform to local and
state plumbing codes.
2) Allwater MUST pass through the HYDRO-CHARGER
ASSEMBLY, pressure tank and the Chem-Free filter,
OR refer to the special instructions for a splt-stream
installation in Sec. 4. (System may maltunction if this
instruction is ignored.)
3) If lawn sprinkling, a swimming pool, geothermal heat-
ing/cooling or water for other devices/activities are to
be treated by the Chem-Free filter, a larger model fter
MUST be selected to accommodate the higher de-
mands of these terms. ‘The pumping rate of the well
pump must be sulficient to accommodate these iterns
plus the backwashing requirement of the fiter. Con-
sult your dealer for alternative instructions if the pump-
ing rate is insufficient
4) Remember that the fter INLET is attached to the pipe
that supplies water (i.e., runs to the pump), and the
OUTLET is the line that runs toward the hot water
heater
Before commencing the installation itis advisable to
study the existing piping system and to determine the
size, number and type of fittings required. Typical
system schematics shown in these instructions (Figs.
1, 2 or 8) will be of assistance
5)
NOTE: \ the plumbing system is used as the ground
leg of the electric supply, continuity should be main-
tained by installing ground straps around any noncon-
ductive plastic piping used in installation.
6) IMPORTANT: Aiways use tefion tape on threaded
plastic fittings. NEVER use pipe dope, as it will
deteriorate the plastic fitings.SECTION 3: INSTALLATION)
PROPER INSTALLATION SEQUENCE OF WATER CONDITIONING EQUIPMENT IS VERY IMPORTANT.
REFER TO THE DIAGRAM FOLLOWING FOR YOUR PARTICULAR WATER SUPPLY.
|RON FREE WATER ——
RON REE —— an neuer
SOT wate wae
Jo puve.
caneoueR.
Pressure
Pressure saree.
ave
aan
hee
Ly aT i
ae
SOFTENER RON
ALTER FroRo-CHARGER
FIGURE 1, STANDARD INSTALLATION
IRON FREE WATER ——
ON pace —— 1 waa fo
See ae a SoannaeRs
10 wah BELA
wey 4
outer 7p pune
cerrati,
5 5
so.a190 Pama
wae Heo
sezoNoany Pawar Sit
| aemaure oatasone
sane “ae ‘ive
ine
| & \ Ww ah
1 torte
seconoany
SOMENER RON re troe-cnances
rare ‘wes
FIGURE 2. SPLIT-STREAM INSTALLATION
on FRE WaTER ———
water FoR
eon pace —— wn hides
SENTE —_—_ of oTnen.
te ve Euan
ere
int
LJ ew
Water
pacssune
Somme ROW Sere trono-cunosn
rureR
FIGURE 3. PUBLIC WATER SUPPLY INSTALLATION
34WOTE: Have you read Section 4, PLUMBING SYSTEM
CLEANUP, for instructions on some procedures that MAY
need to be performed first?
Step 1. (a) if MEDIA is already in the MEDIA TANK,
proceed to Step 2. If MEDIA is shipped
separately, add media thru filport adaptor
using funnel (Figure 4). Fillport cap can be
removed by removing quick release clip.
NEVER ADD MEDIA ABOVE LINE INDI-
CATED ON SIDE OF TANK. You may have
received more media than required for the
initial fill, ave extra media for future repienish
ment
(b) Reinstall filport cap. Make sure cap is fully
inserted before reinstalling clip.
(o) I BYPASS VALVE/YOKE ASSEMBLY is not
factory pre-installed, attach using clips and
screws as shown in Figure 5.
FUNNEL
LLPORT
‘BODY
FIGURE 4. FILLING TANK MEDIA
32
Step 2.
Step 3.
ovruer
KNOB
Shut off all water at_main supply. On a
PRIVATE WELL SYSTEM, turn off power to
pump and drain pressure tank. Make certain
pressure is relieved from complete system by
‘opening nearest faucet to drain system. SHUT.
OFF FUEL SUPPLY TO WATER HEATER.
Cut _main supply line as required to fit HY-
DRO-CHARGER in plumbing between well
pump and pressure tank (HYDRO-CHARGER
‘may be installed in a vertical or horizontal
position). Position HYDRO-CHARGER so
that WATER FLOW ADJUSTING SCREW is
accessible for adjustment by screwdriver.
Allow at least 6 to 8 in. of straight run of 1 in.
pipe on both INLET and OUTLET side of
HYDRO-CHARGER. Install unions at end of
straight runs to facilitate HYDRO-CHARGER.
removal and inspection. Be certain direction
‘of FLOW ARROW on HYDRO-CHARGER
label points TOWARD pressure tank, and
pressure control switch is located on pressure
tank side of the HYDRO-CHARGER as in
Figures 1, 2 or 3 (rapid cycling of pump may
‘occur if pressure switch is located on well
side). If a check valve is located bet-
= BrPASS VALE
__ INLET ouTLET INLET
Nos KNOB nos
SERVICE Bypass
POSrTION POSITION
FIGURE 5. INLET/OUTLET CONNECTIONS:Step 4.
Step 5.
Step 6.
ween HYDRO-CHARGER and pressure tank,
it will prevent HYDRO-CHARGER from per:
forming properly. Relocate to well side of
HYDRO-CHARGER.
NOTES:
1. If heat is applied near HYDRO-CHARGER,
remove rubber check valve to prevent damag.
ing it. On badly scaled, older pumping sys-
tems, it may be advantageous to install a
“WYE" strainer to prevent plugging of HY-
DRO-CHARGER nozzle with scale. WYE
strainer must precede union on inlet side of
HYDRO-CHARGER
It existing water system includes a captive-
air type pressure tank and it is desirable to
install an additional air-to-water type with air
release (NOT as a split-stream type installa-
tion), install air-to-water tank between hydro-
charger and existing captive-air tank.
IMPORTANT: Betore proceeding, with HY-
DRO-CHARGER installed, re-verily adequate
pumping rate following the procedure de-
scribed in Section 2. And after verification of
adequate flow, depressurize system as de-
scribed previously
Cut main supply line as required to fit plumb-
ing to INLET and OUTLET of BYPASS VALVE
ASSEMBLY.
Solder or solvent weld plumbing. DO NOT
apply heat to any fiting connected to BYPASS.
or CONTROL VALVE, as damage may result
to internal parts or connecting adapters. MAKE.
CERTAIN WATER FLOW ENTERS
THROUGH INLET AND DISCHARGES
THROUGH OUTLET.
NOTE: \t installation is to be SPLIT-
STREAMED prior to MEDIA TANK (Figure 2)
or is a PUBLIC WATER SUPPLY type instal-
lation (Figure 3) refer to special instructions
following Step 11
‘Attach ORAIN LINE to DRAIN LINE FITTING.
To prevent back pressure from reducing flow
rate below minimum required for backwash,
DRAIN LINE MUST be sized according to run
length and relative height. Be careful not to
bend flexible drain tubing sharply enough to
cause “kinking” (ifkinking occurs DRAIN LINE.
MUST be replaced!) Typical examples of
MINIMUM DRAIN LINE diameters are:
1) 1/2 in. 1D up to 15 ft. when discharge is
lower than inlet,
2) 5/8 in. ID up to 15 ft. when discharge is
slightly higher than inlet.
3) 9/4 in. 1D when drain is 25 ft. away and/
or drain is installed overhead.
Some areas prohibit the use of flexible drain
33
Step 7.
Step 8.
lines. Check with local code officials prior to
installation.
Position DRAIN LINE over drain and secure
firmly. To prevent back-siphoning of sewer
water, provide an air-gap of at least 2 in. or 2
pipe diameters between end of drain hose
and drain (Figure 6). Do not raise DRAIN
LINE more than 10 ft. above floor.
SBE'SE Jn oo
BE
ow
oT.
FIGURE 6. DRAIN
Make certain BYPASS VALVE INLET and
OUTLET KNOBS are in "BYPASS" position.
Turn on power to well pump or open main
supply vaive completely. Manually stage con:
trol to BACKWASH POSTION by turning
“MANUAL REGERNERATION KNOB’, p. 5:
3, clockwise to "BACKWASH" position. Open
BYPASS VALVE INLET KNOB approximately
1/4 of the way to full open (SERVICE POSI-
TION) allowing the unit to fill slowly. This will
purge any entrapped air in the bed. Once
water is flowing to drain, open both the
BYPASS VALVE INLET and OUTLET KNOBS:
completely.
(a)
(b) Check for leaks. Leave unit in BACKWASH
for at least 10 minutes or until drain line water
runs clear, whichever is longer. This proce-
dure will "reclassify" media that may have
been disturbed during shipping and handling,
Alter this preliminary backwash, stage CON-
TROL VALVE to service position and plug
timer into a 110/120V, 60 Hz non-switched
power source. Manually initiate a complete
“regeneration” process, allowing the unit to
automatically proceed through a backwash
and rapid rinse, see "HOW TO MANUALLY
BACKWASH YOUR FILTER AT ANY TIME”,
P53.
Step 9. Set HYDRO-CHARGER by following these steps:
(a)
(o)
(c)
Open nearest faucet until pump starts, then
close faucet.
Place a finger lightly over SUCTION PORT
(See Figure 7). A slight suction should be
detected for approximately ONE-THIRD of
Pumping cycle TIME (do not confuse with
one-third of PRESSURE RANGE).
|f suction duration is too short, increase by
turning WATER FLOW ADJUSTING SCREW
(Figure 7) CLOCKWISE. To decrease dura-
tion, turn COUNTER-CLOCKWISE(6) Repeat Steps (a) through (c) until proper
setting is obtained,
NOTE: When the duration of the suction is
too long, cold water may have a “milky” ap-
pearance caused by excess air in the system.
Correct this condition by reducing the duration
of suction. This condition is commonly asso-
ciated with bladder-type pressure tanks, In
extreme cases where elimination of excess air
prevents system from performing satisfacto-
fly, it may be necessary to install a standard
air-to-water type pressure tank with an air-
relief vaive (See SECTION 2: THE IMPOR.
TANCE OF YOUR PRESSURE TANK.)
WATER FLOW
ADJUSTING SCREW.
WATER
FLOW,
WATER
FLOW,
im
Z SUCTION PORT.
FIGURE 7. HYDRO-CHARGER
Set Time-Of-Day (See HOW TO SET TIME
CONTROL, Page 5-3) and set BACKWASH
frequency (See SECTION 5: BACKWASHING
INSTRUCTIONS). Installation is now com-
plete.
Step 11.
NOTE: Due to the nature of the Chem-Free
media on start-up it sometimes requires 2 or
3 days for the Chem-Free fiter to completely
remove the iron. Do not become alarmed if
this occurs. During the initial backwashings, a
small amount of fine white media may be
‘observed in drain water. This is normal and
beneficial for the efficient operation of your
filter system.
SPECIAL INSTRUCTIONS FOR SPLIT-STREAM AND
PUBLIC WATER SUPPLY TYPE INSTALLATIONS:
For SPLIT-STREAM type installations, a secondary PRES.
SURE TANK must be installed as in Figure 2. On PUBLIC.
WATER SUPPLY type insiallations, a PRESSURE TANK
must be installed as in Figure 3. It is recommended in
both applications to use a standard air-to-water type
pressure tank with a deep-well air volume control (air
release valve). The pressure tank should be of same
capacity as would normally be installed it water system
were a standard private well type. Also note both applica
tions require a NORMALLY-CLOSED SOLENOID VALVE.
Follow standard installation procedures above with follow-
ing additions and modifications.
34
1) Install PRESSURE TANK (SECONDARY PRESSURE
TANK in Fig. 2) as indicated by appropriate diagram.
2)_ Install NORMALLY-CLOSED SOLENOID VALVE, 110/
120V, 60Hz atter water meter and AFTER a line split
for untreated water (if there is one)
3) On both types installation, install HYDRO-CHARGER.
between PRESSURE TANK (SECONDARY PRES-
SURE TANK on SPLIT-STREAM type installations)
and NORMALLY-CLOSED SOLENOID VALVE.
4) Install PRESSURE SWITCH after HYDRO-CHARGER
‘and wire itto SOLENOID VALVE (SECONDARY PRES-
‘SURE SWITCH on SPLIT-STREAM). Set HIGH pres-
sureon PRESSURE SWITCH (which controls opening
and closing of SOLENOID VALVE) 2 to 3 psi LOWER,
than LOW pressure on PRIMARY PRESSURE
SWITCH.
EXAMPLE: \i PRIMARY PRESSURE SWITCH is set
at 40/60 psi, set SECONDARY PRESSURE SWITCH
20/38 psi.
For PUBLIC WATER SUPPLY type installations, con-
tact your local water department or plant operator and
ask what the normal LOW system pressure is. Set
HIGH pressure on PRESSURE SWITCH 2 to 3 psi
LOWER than this figure.
NOTE: Failure to set PRESSURE SWITCH as de-
scribed above will NOT allow proper closing of SOLE-
NOID VALVE during periods of low system pressure.
Improper function of SOLENOID VALVE will cause
total failure of system
‘SPECIAL SERVICE INSTRUCTIONS:
Under normal circumstances removal of valve should
never be required. However, if it must be removed, it can
be done by disassembling the quick release clamp, by
removing latch. Pressure should be relieved before
attempting any disassembly. Upon reassembly, all o-
rings should be lubricated with silicone grease. Reas-
semble clamp as. shown in Figure 8. MAKE SURE
ARROWS ON LATCH SIDE OF CLAMP ARE ALIGNED.
i
FIGURE 8.SECTION 4: PLUMBING SYSTEM CLEAN-UP|
‘THE FOLLOWING PROCEDURES ARE GUIDELINES ONLY BUT HAVE PROVEN SUCCESSFUL IN MOST INSTANCES,
UNDER NO CIRCUMSTANCES SHOULD ANY PROCEDURE OUTLINED BELOW BE FOLLOWED IF CONTRARY TO THE
APPLIANCE MANUFACTURERS INSTRUCTIONS. SHOULD THERE BE ANY QUESTIONS CONCERNING THE ADVISABIL-
ITY OF PERFORMING A PROCEDURE, IT IS STRONGLY RECOMMENDED THE MANUFACTURERS AUTHORIZED
SERVICE OUTLET BE CONSULTED PRIOR TO PERFORMING THE PROCEDURE.
The plumbing system and water using appliances that
have been exposed, even for a short time, to iron-fouled
water need to be cleaned of the precipitated iron that has
collected in them or iron “bleed” (staining) will continue to
be a problem.
Depending on the amount of iron in the water and the
length of time the water system has been exposed to iron
fouling, select from the following procedures those that
apply to the type system and appliances that need cleaned
to assure iron-free water at the points of use.
‘SOFTENER,
It is not uncommon that the softener was installed in an
effort to remove ferrous ("clear water’) iron from the water
supply. Typically, a softener will remove some ferrous iron
until the resin bed becomes fouled to the extent that it will
lose both hardness removal capacity and the limited
capacity for iron removal. This is the condition to expect
the softener to be in when planning a system clean-up.
Prior to closing main supply valve or turning power off to
a private well system and preparatory to instaling the
Chem-Free fiter system, do the following:
1) Disconnect brine draw line from brine cabinet and
place the loose end into a five gallon plastic pail filed
with a solution of hot water and 10 ozs. of resin mineral
cleaner (IRON-X™)
2) Manually advance control timer to BRINE DRAW
position (refer to instructions provided with your soft-
ener), and allow all hot mineral cleaner solution to be
drawn into mineral bed. Then IMMEDIATELY:
3) Close main water supply valve or turn power off to
pump and proceed with fiter installation. During time
Fequired to instal fiter system, iron-fouled softener
resin will be chemically cleaned
4) Alter fiter installation is completed and final adjust-
ments made with water turned on and brine tube
reconnected, manually reposition timer on softener to
BACKWASH position. Allow timer to perform an
automatic, complete backwash and regeneration cycle,
During backwashing of softener, all iron cleaned from
the resin will be washed down drain. It is advisable
atter chemically cleaning softener to regenerate sys
tem twice to fully restore capacity lost due to iron
fouling,
44
HOTWATERHEATER
If the hot water heater has been exposed to both iron and
hardness for a long period of time, replacement of the
heater tank may be the only practical solution to prevent
continued staining originating from this source. After
completing the installation of the Chem-Free filter system,
clean the hot water heater by following these instructions:
1) Shut off fuel supply to hot water heater and close
heater inlet water valve.
2) Drain hot water tank completely. Open inlet water
valve allowing heater tank to be refiled with iron-free
water. Continue flushing until water runs clear to
drain.
3) after approximately 30 minutes flushing, water does
NOT clear, terminate flushing operation. Refll hot
water heater with water and pour approximately 1/2
gallon of household bleach into top of heater tank
Allow bleach solution to stand in tank for 20 to 30
minutes. Flush tank again until water is clear at drain.
Turn fuel supply on.
NOTE: |i water does not clear in approximately 10
minutes, water heater probably should be replaced.
DISHWASHER
Consult owner's handbook and follow manufacturers in-
structions,
TOILET FLUSH TANKS,
Prior to commencing installation of the Chem-Free filter
system, pour 4 to 6 ounces of resin mineral cleaner
(IRON-X) or inhibited muriatic acid into flush tanks and
bowls and let stand. When installation is completed, flush
toilets several times with iron-free water. If iron deposits
or stains remain, repeat procedure until clear.SECTION 5:_BACKWASHING INSTRUCTIONS]
Periodic BACKWASHING of the Chem-Free filter bed is
required to flush out the entrapped iron that has accumu-
lated. This procedure is performed automatically at 1:00
a.m. for a period of approximately 30 minutes, and wil not
interfere with a softener regeneration which is usually set
for 2:00 am.
‘TOSET BACKWASH FREQUENCY FOR NORMAL HOUSE-
HOLD APPLICATIONS:
To determine and set BACKWASHING FREQUENCY,
follow these instructions:
1) Select BACKWASHING FREQUENCY SCHEDULE
corresponding to your model
2) Locate box intersected by number of persons in your
family and iron concentration of water (if iron concen-
tration is between two numbers in SCHEDULE, use
higher number).
3) Number in box represents number of times per 6 days
timer should be set. Refer to HOW TO SET TIME.
CONTROL to set timer.
EXAMPLE: You have model NF1001, 4 in family and
8 ppm iron. Refer to SCHEDULE for model NF1001
and locate box intersected by 4 in family and 8 ppm
iron. ‘The figure “1” in box indicates a BACKWASH
frequency of one time per 6 days (ita "2" or °3" were
in box, frequencies of twice or three times per six days
respectively would be indicated.)
NOTE: The BACKWASHING FREQUENCY SCHED-
ULES are based on average water consumption rates,
and are merely guides. They are not intended to be
Used if water used by outside spigots, a swimming
pool, geothermal heat pump, or other high water
usage devices or activities are to be treated by your,
Chem-Free filter. If your application includes any of
these, and you have already determined your model
Chem-Free filter is capable of handling the flow rates
involved, refer to the next paragraph for instructions on
setting BACKWASH FREQUENCY.
54
‘TO SET BACKWASH FREQUENCY COMMERCIAL MOD-
ELS AND NON-STANDARD HOUSEHOLD APPLICATIONS:
It your filter is to be used for a commercial application or
for reasons covered above the BACKWASHING FRE-
QUENCY SCHEDULE is not applicable, determine the
backwashing frequency as follows:
1) Estimate DAILY IRON REMOVAL by multiplying iron
concentration by estimated daily water consumption
(use 60 gals. per person per day for normal household
applications)
Estimated Daily
Water Usage x Iron Concentration
was) ‘bem
= Daily ron Removal
(ppm)
2) Calculate BACKWASH FREQUENCY by inserting
DAILY IRON REMOVAL trom above into the following
formula (refer to specifications for IRON REMOVAL,
CAPACITY of your model):
Iron Removal Daily
Capacity Of + tron
Your Mode! Removal
(pom) (ppm-gals)
= Backwash Frequency
(Gays)
The resulting number of days between backwashings
should be converted to the nearest MORE FRE-
QUENT obtainable timer setting (.e., a calculated
ftequency of 3.7 days should be converted to a 3 day
interval, and a 9.2 frequency to a 6 day interval). Itis
‘not possible, however, to set the timer less frequently
than once every 6 days.
It your water contains high iron concentration, manga-
nese, tannins or hydrogen sulfide it may be advisable
to increase the backwash frequency up to daly, if
necessary. It should be noted, however, that increas-
ing the frequency or duration of backwashing WILL
NOT overcome an insufficient pumping rate.BACKWASHING FREQUENCY SCHEDULES
MODELS: NFO750, NFO751, NFO750M, NFO7SiM
3 jo 3 ole ©
Pi
: e 3 o g ef 7
Baie gz | <|8 °| =| ala] z)
= zie & ie
z|e Bl eis Els | z\s als |
2 gles Zl= z “i
i 3 5 5 -
Slo gle? glele o |ole SK 2
5 3| 2 a] & 8 :
° =| |e z| |e © 2 als oI
Z| 3 -
< ° g = «| 2 «| o
g a] [z e-Fe
g : =
o > * & o of & e |
g ge) Bl al= ‘ 7
ae a = z a
Bet 2 im g| {2 of = g ale w
zt ae & 8
glee? &| |» of EB] fe -|- a
a eee ae a
als 2 gle 2
olesé Slalsect t} 0 2
gle & Sli*s e
3 gli
52MANUAL REGENERATION
KNOB
RED TIME-SET
BUTTON
TIME OF DAY
ARROW
HOW TO SET THE TIME OF DAY:
(1) Press and hold the red button in to disengage the drive
gear.
(2) Tum the large gear untithe actual time ofday is opposite
the time of day pointer
(3) Release the red button to again engage the drive gear.
HOW TO SET THE SKIPPER WHEEL:
I you are setting the TIME CONTROL after MIDNIGHT but
before NOON (i.e. A.M), the red pointer on the SKIPPER,
WHEEL MUST be between two numbers as shown. If you
are setting the TIME CONTROL after NOON but betore
MIDNIGHT (i.e. P.M.) the red pointer MUST be COVERING
one of the numbers. Setting the SKIPPER WHEEL in this
manner will provide a 1:00 A.M. backwashing time.
CAUTION: If directions above on HOW TO SET THE
‘SKIPPER WHEEL are not followed, BACKWASHING will
not take place at the appropriate time of day.
HOW TO SET DAYS ON WHICH FILTER IS TO BACK-
WASH:
Set the days that backwash is to occur by sliding tabs on the
skipper weel outward to expose trip fingers, Each tab is one
53
‘12 HOUR GEAR
SKIPPER WHEEL
(SHOWS EVERY DAY
REGENERATION)
RED POINTER,
Extend or retract fingers to obtain the desired
backwashing schedule. Typically, these units are
backwashed every third day.; Consult your dealer for
‘specific recommendations for your water.
HOW TO MANUALLY BACKWASH YOUR FILTER AT
ANY TIME,
ay.
‘Tum the manual backwash knob clockwise until the knob
engages the program wheal. This slight movement of the
knob will start the backwash program,
‘The backwash knob will make one revolution in approxi-
mately 1 1/2 hours and stop in the position shown in the
drawing. Even though it takes 1 1/2 hours for the knob to
complete one revolution, the backwash cycle of your unit is
approximately 30 minutes in duration.
NOTE: Should it become necessary to change the
TIME-OF-DAY which backwash is to start, the time on
12 HOUR GEAR must be altered. For example, if 2:00
‘a.m. regeneration time is desired instead of 1:00 a.m.,
set the 12 HOUR GEAR one hour earlier than actual
time.SECTION 6: TROUBLESHOOTING)
A. Water clear when
drawn, turns red
Upon standing (Stain
producing)
B. Water red when
‘drawn trom tap
C. Excessive pressure
loss through fiter
D. “Milky” or “bubbly
water (Appears to
contain small
bubbles)
”
2)
3)
4)
5)
6)
7
8)
v
2)
3)
4)
5)
2)
3)
4)
5)
Insufficient airdraw by Hydro-Charger.
Bypass open or leaking.
Fiter bed overloaded with precipitated
iron due to backwash, or failure to back-
‘wash due to malfunction of control timer
‘or unplugged control valve power cord
Presence of manganese or tannins.
Flow rate excessive for model
Check-valve located between Hydto:
Charger and pressure tank,
Pumping cycle too short, limiting rasi-
dence time in pressure tank (may be
water -logged}
pH of treated water too low (should be
7.0 or higher, with manganese, pH must
be 82)
Fiter bed overloaded with precipitated
iron due to insufficient backwash flow
rate.
Fiter bed overloaded with precipitated
iron due to insufficient backwash, or
failure to backwash due to malfunction
‘of control timer or unplugged contro!
valve power cord.
Hydro-Charger drawing too much air,
causing early precipitation of iron
Hydro-Charger installed to far rom pres-
‘sure tank or pressure tank installed too
far from fiter tank causing iron to precipi
tate before tank filter.
Solenoid valve (Spit-Steam or Public
‘Water Supply type installation) malfunc-
tion or inadequate supply system pres:
surelow rate.
Fiter bed overloaded with precipitated
‘Control nlevoutletvaive(s) not fully open.
‘Sand, sit or mud collecting in fter bed.
Filter bed not property “classified”
“Comenting” or “channeling” of filter
media,
Excess Hydro-Charger air-draw.
Excess gases in water (carbon dioxide,
hydrogen sulide, methane)
»
2)
3)
4)
5)
6)
n
8)
1)
2)
3)
4)
5)
(Check Hydro-Charger adjustment. I unable to adjust
for long enough draw, check pumping rate
Close bypass valve andlor repair as necessary.
Upon correction of problem (increase backwash fre-
‘quency if problem determined to be insufficient fre-
quency), manually backwash until backwash water
starts to clear (in more severe iron-fouling cases, fter
bed may need chemical cleaning - contact dealer
Recheck water analysis.
Reread SEC. 2: FACTS TO REMEMBER WHILE
PLANNING YOUR INSTALLATION.
Relocate check-valve.
Correct condition.
Replenish MpH component in media (contact dealer).
a, Recheck well pumping rate and repair or replace as
required
b. Check for obstructions or kink in drain tine
€e. Check for improper drain line flow controller (see
specs). Upon correction of this problem, if manu-
ally backwashing does not clear bed of iron, fiter
bbed may need chemical cleaning - contact dealer.
Upon correction of problem (increase backwash fre
‘quency it problem determined to be insufficient tre-
quency), manually backwash until backwash water
stars to clear (in more severe iron-fouling cases. fiter
‘bed may need chemical cleaning - contact dealer.
Reduce Hydro-Charger air-draw.
Relocate closer to fier.
Repair or replace as necessary.
Refer to Section B above,
Fully open iniovoutlet valves.
‘Check well for these conditions,
Manually backwash to reciassity.
rod (sti) fiter bed to breakup hardened layer. In-
crease backwash frequency lo prevent occurrence,
Check adjustment for duration of draw in excess of
one-third pumping cycle (see Sec. 3, Step 10).
May require draining of water system or installation of
air-reliet control on pressure tank. A PT-Plus pressure
tank may be installed in conjunction with a pre-existing
bladder tank.SECTION 7: SPECIFICATIONS AND OPERATING DATA
ITEM
Filter Media Volume (cu t.) (Note 1)
Gravel Underbed (bs)
Nominal Capacity ppm-gal
‘Operating Flow Rates, gpm: (Note 2)
‘Continuous (No duration mit)
‘Service (Intermittent)
Peak (10 minutes max. duration)
Pressure Loss @ Flow Rates, psi
Continuous
Service
Poak
Backwash Flow Rate (gpm): (Note 3)
Service Pipe Size (in. (Note 4)
‘Tank Diameter x Height (n.)
‘Minimum Space Required (in.)
wath
Depth (wiBypass)
Height
‘Approx. Shipping Weight (bs.)
‘Maximum operating temperature 100° F (38°C); Electrical requirements 110/120V, 60H; Operating pressure 20- 100 psi
TES:
(1) Replenishment of pH adjusting component of me-
dia may be required periodically, the frequency of
which is dependent on raw water pH, manganese
concentration and water consumption rate. Con-
sult dealer for more information.
2
For satistactory performance, indicated durations
should not be exceeded. Flow rates specified are
adequate for normal residential applications. Do
ot use Service or Peak flow rates when sizing
commercial applications or if treated water is 10
supply a geothermal heat pump, swimming pool,
etc. (contact dealer before selecting equipment).
Service flow rates have been tested against NSF
Standard 42 and have a rated pressure drop of
less than 10 psi.
7A
(3) For system to operate properly, pumping rate of
well pump MUST be sufficient to backwash unit at
rate specified,
(4) Service Pipe size is 3/4” on models not shown
above: NF0750, NFO750M, NF1000, NF1000M,
NF2000M.COMPONENT PARTS LIST
te esc were se _M so
ae rer ee ve ae
7 | es yi a Tre et Fate rae rae reste
a [ome ons one oan
[oar Aorta) Fees FaOH
3 __ [tan Care rose ose
[Fon ay nT i) Fesor
Oo ze ooze
1 [oveenae oe om orca
3 | Froese 38768 Fra Fear
Te ay. at aug 5 Fase
one T = 7158
| pasoac or = me
Dew ts ie areas wre or
Fei
acres waa uc wei32) Me)
iis sere Su ae io
[eee case eases cs 655 Te
[ie Tm To Tosa Tie
[nn om) oo oa aoe
72 | inon cage Cnson He hoo Heo re
or vem e102 wae ve102
[woe re09 He ree revo
2 Jones ree ree ree renee
2 _ [Beas Scew ves veo Co vais
2 [soew rare cy ra rete rei08
Tet Rr 987 "een ean Teo Tee
NOTE: When ordering components, always specty mode! number. Components for models ending with "0" (., NF1000) andlor with
*Y" sulfx (i., NFO7SOY) are same as equivalent model above
26
ee
20
72“N" SERIES BACKWASH CONTROL PARTS LIST
ONLY THOSE PARTS CIRCLED IN DRAWING AND/OR LISTED BELOW ARE STOCK ITEMS
‘ALL OTHERS ARE SPECIAL ORDER, NON-RETURNABLE
‘a | 603si-8w Power Head Assy, Complete, UCover, (Inc. Ret, Items 2.27)
eB | isesix ‘Skipper Whee! Assy. (Ine. Ret. tems 4-9)
c | s235x 12-Hour Gear Assy, (ie. Ref, ems 10-15)
oD | iassax Control Valve Body Assy. (inc. Ret toms 30-36 E & G)Spec. Model Number
| coroz-se Piston Assembly
| ors Seel Kit (ne. Ret. ems 32 & 33)
G | 60sae-x Drain Line Fiow Contol Assy Incl, Ret tems 37-48)
| 10080: ‘Adapter Couping Assy. (In Ret. items 45-48)
5) | 600%9/18706x | 1" Bypass Vaive Assy (Inet Rl. Items 45 8 47-51)
60089/18706.02x| 3/4" Bypass Valve Assy. Inc Rel. ems 4 & 47-51)(Optonal)
1 | zzcorx Valve Cover, Specity Model No
za | 19170 Motor, +10v 60H2
oa | 11386 Motor Mtg. & Ground Serew
27 | asim Main Dive Gear
23 | 13547 Strain Rolf = Flat Cord
23 | ree Power Cord, 110V/60 Hz
a5 | 13308 Distributor Tube O-Ring-1"
3s | 12281 Tank O-Ring
37 | 13903 Injector Cover O-Ring
33 | 13301 Injector O-Ring
30 | 13163 InjectovDrain Housing
ao | 13166 injector Cover
a1 | 43315, Injector Mtg. Serew
2 Drain Line Flow Control Buton
12092 5.0 GPM (1000 & 1001)
12408 7.0 GPM (2000 & 2001)
a | 3173 Drain Line Flow Control Burton Retainer
4s | 12308 Drain Line Fting
a5 | 13305, Couping O-Ring
43 | 13700 Adaptor Couping
a7 | 13255 Adapter Cip
ae | isats Screw: Adapter Coupling
4a | 18660 Orrng
50 | 18861 ving (ORG-218)
51 | 18706 Adapter Yoke, 1"
18706-02 Adapter Yoke, 342 NPT (Optional
74Chem-!
™ Filter System
Five Year Limited Warranty
GENERAL CONDITIONS
Damage to any part of this water conditioner because
of misuse, misapplication, neglect, alteration, acci-
ent, installation or operation contrary to our printed
instructions, or damage caused by freezing, flood, fre
or Act of God, is not covered by this warranty. In all
such cases, regular parts and service charges will
apply.
We assume no warranty ability in connection with this
water conditioner other than specified herein. This
warranty isin ieu ofall other warranties, expressed or
implied, including warranties of fitness for a particular
purpose. We do not authorize any person or repre-
sentative to assume for us any other obligations onthe
sale ofthis water conditioner.
‘Should a defect or malfunction occur, contact your
dealer. If you are unable o contact your dealer, return
the part, treight prepaid, directly to the factory (ad
dress below). Enclose with the part a full description
of the problem, with your name, full address, date
purchased, model and serial number and selling
dealer's name and address. We will repair or replace
the part and return it to you at no cost if our repair
department determines it to be defective under the
terms of this warranty.
This water conditioner is manufactured by:
Chemical Engineering Corporation
12628 U.S. 33 North, Churubusco, IN 46723
WARRANTY POLICY
Chemical Engineering Corporation, Churubusco, In-
diana warrants this water conditioner as stated herein:
From the date of installation, we will repair or replace
any par, within the warranty period described below,
which we find defective because of faulty materials or
workmanship or corrosion. You pay only freight o our
factory and local labor charges.
© One year on entire unit.
* Three years on complete control valve.
'* Five years on control valve excluding internal and
electrical pars.
Five years on mineral tank excluding mineral.
FILL IN THE FOLLOWING AND.
KEEP FOR YOUR RECORDS
owADDENDUM FOR GRAINGER
STOCK NOs. 3P976, 5P; 71, 3P972
THE ACCOMPANYING INSTRUCTION MANUAL SHOWS A FILLPORT ADAPTOR
NOT SHIPPED ON THE STOCK NOs. LISTED ABOVE, CONSEQUENTLY, THE
FOLLOWING STEPS SHOULD READ AS FOLLOWS:
Ti
Step 1 (a)
(b)
(c)
(a)
(e)
(f)
(9)
SECTION 71 & 3P972)
If MEDIA is already in MEDIA TANK, proceed to Step 2. If MEDIA
is shipped separately, remove CONTROL VALVE by disassembling
quick release CLAMP (see Fig. 8, P.3-4 - 3P976 & 5P235,
P.3-1 - 3P971 & 3P972).
Remove center DISTRIBUTOR tube and pour GRAVEL out of
MEDIA TANK into a bucket.
Place DISTRIBUTOR back into MEDIA TANK making sure it rests
on the bottom center of TANK.
Lubricate inside of bell end of CENTERING TOOL, provided, with
silicone grease and place over end of DISTRIBUTOR.
Add GRAVEL removed in (b), back to MEDIA TANK while holding
down on CENTERING TOOL.
Add MEDIA to MEDIA TANK while holding down on CENTERING
TOOL and holding DISTRIBUTOR in center of TANK. NEVER
ADD MEDIA ABOVE LINE INDICATED ON SIDE OF TANK. You
may have received more MEDIA than required for the initial fill,
save extra MEDIA for future replenishments.
Reattach CONTROL VALVE making sure DISTRIBUTOR goes into
tube adaptor protruding from bottom of VALVE.NT & NF START-UP
BACKWASHING
INSTRUCTIONS
FOR PRE-WASHED CATALYST MEDIA
Ongoing product testing Indicates the Catalyst Media can support higher backwash rates
without danger of loss of media, therefore the drain line flow control button is now being
omitted from all Catalyst Filters. Chem-Free Filters still have drain line flow control buttons.
Failure to perform following procedure may result in loss of media upon Initial backwash:
1) Install unit per installation instructions.
2) With unit bypass valve in *bypass" position, manually index control valve to "backwash" postion.
(Refer to instruction manual.)
3) Open bypass valve approximately 1/2 open. This will allow unit to fill slowly from the bottom up,
thus eliminating air entrapment which can occur if unit is filled with water from the top.
4) Once a steady flow of water is going to drain, completely open bypass valve to "service" position.
5) Allow unit to continue to "backwash" to drain for approximately 15 minutes. Advance control valve
to "rapid rinse" position to compact the bed for service.
6) You may wish to manually initiate an automatic regeneration and allow unit to cycle through the
steps of "backwash" and “rapid rinse" to verify proper operation of system and further clean the
bed.
7) During this initial regeneration you should observe the flow to drain to make sure well and well
pump are capable of maintaining a steady flow rate. Ifthe pump or well recovery is not adequate,
i.e., system pressure continuously decreases, the fiter will not properly clean Itself of fitered
material and will eventually fail.
NOTE: When installing a Catalyst Filter do not install drain line overhead or use flexible vinyl
tubing, either will result in failure of the system. :‘eBid BEG
owen
Auedwiog
ey Mold
Jequinn
Jequiny
lees 1ePoW
“eo1yJ0 sno Bunoeluoo uayM elqeteAe oq Pinoys e1ojo104) Pue YOU UE Jo GOUENSs} e10}9q peysenbed 2 IM
Jequinu [EYES BULL “e}EId4OEq AAIEA OU 10 J8AOD @AIEA JO.]UOD OU JOUYO 0} PareUpe S1 eyeId BIE EY “(Mojeq eunBy
898) Jequinu jepow yun ey) 0} xeU eyeId BIEP oY) UO peyeoo| JqWiNU jeUEs YUN BUY epnjou! FSM pue seuN}oeNuEW
‘aut Aq panssi (YOu) UoHeZUOUINY SpooD UINJeY B Aq paIueduioooe oq JETT uowenyene AjUeLeM 40} suMeIO AUY
SWIVTDXLINVUUVM
IMPORTANT
READ THIS BEFORE INSTALLATION
AND
YOU COULD SAVE YOURSELF
MONEY AND AGGRAVATION.1. Use of any lubricant, other than a silicone paste (not spray) material, as manufactured by Dow Coming, will damage
the control valve body, intemal parts and timer gears and will void warranty. Spray lubricants, such as WD40, or
silicone sprays which may contain petroleum components, and other lubricants like Vasoline, Crisco and most oils
will soften and deteriorate any plastic parts they may contact.
2. Media lodged in control valve due to improper start-up upon installation, after adding replenishment media’ or
rebedding is not covered under warranty. Media can be flushed into the valve when air passes through the bed
while the filter is being backwashed.
PROPER START-UP:
‘A. With unit bypass valve in "Bypass" position (Fig. A),
‘manually index control valve to "Backwash" position.
(Refer to instruction manual).
OUTLET
INLET
FIG.A
BYPASS.
POSITION
If Media Being Used is Activated Carbon or Filter
‘AG: Once a steady flow of water is going to drain,
place both the Inlet and Outlet Knobs of the bypass
valve in "Bypass" position (Fig. C1) and allow media
to soak for atleast 2 hours. After the soaking period,
slowly open Inlet Knob to *Service" position and allow
water to flow to drain until water runs clear. Advance
control vaive to "Rapid Rinse" and then to “Service".
OUTLET INLET
t {
FIG. C1
IHF127B(7-163)
B. With Outlet Knob closed, (in *Bypass" position) open
Inlet Knob of bypass valve approximately 1/4 open
(Fig. B). This wil allow unit to fill slowly from the
bottom up, thus eliminating air entrapment which can
occur if unt is filed with water from the top. (ie, while
control vaive is in "Service" position).
OUTLET INLET
Hae set
FIG.B
1/4 OPEN
If Media is Chem-Free, Greensand or Neutralizer:
When filter tank is completely filled with water as
indicated by a steady flow of water to drain, open both
Inlet and Outlet Knobs of bypass valve to "Service"
position (Fig. C2) and allow water to flow until drain
water runs clear. Advance control valve to "Rapid
Rinse" and then to "Service".
a si eg
FIG. c2
‘SERVICE
POSITION T