An Introduction For Users and Manufacturers: Field Communication Protocol
An Introduction For Users and Manufacturers: Field Communication Protocol
                                      HART
                                      FIELD COMMUNICATION PROTOCOL
             HART
                                 ®
                          HART
                                              ®
                                       HART
                                                           ®
                                                              HART
                                                              FIELD COMMUNICATION PROTOCOL
WHY COMMUNICATION ?
       '4-20 mA' is a tried, tested and widely-     management and utilization of 'smart'
       used standard, so why do we need to          instrument networks.
       update it? Because only a limited
       amount of information (the measured          HART permits two-way
       variable) is sent by a 4-20 mA signal.       communications, so instrument
                                                    parameters can be interrogated and
       'Smart' field devices using the HART         even adjusted from anywhere on the
       (Highway Addressable Remote                  cable.
       Transducer) protocol enhance
       operations because digital data is           HART also has an all-digital mode
       transmitted along with the 4-20 mA           that allows many instruments to be
       signal - without interfering with it! This   connected to a single cable, cutting
       has two important benefits: firstly,         installation costs dramatically yet
       existing cabling and current control         retaining all HART advantages.
       strategies remain secure; secondly,
       the additional data - typically tag          The HART protocol is supported by
       numbers, measured variables, range           major instrument suppliers and the
       and span data, product information           HART Communication Foundation, so
       and diagnostics - can be used during         interoperability is assured, along with
       installation, calibration, maintenance       easy integration with higher level host
       and operations to cut costs                  systems and equipment.
       substantially and improve the
                                                                                              1
                       ®
    HART
    FIELD COMMUNICATION PROTOCOL
METHOD OF OPERATION
         Production
         management level
                                      4-20 mA                        management system       4-20 mA                                         management                        4-20 mA                       management
                                                                                                                                             system                                                          system
                                              RB                                                     RB                                                           Controller             RB
                           #                                 #                     #                          #                              planning terminal                                     #
                                  #                                                      #
                                                                 #                                                #                                                                                    #
                           Gateway                     Bell 202-
                                                       Modem
                                                                                                                                  if applicable 4-20 mA
                                         #                                                                            #                                                            #
                                                  HART
                                              #                                                                                                                                        #
                                                  barrier/
                                                  isolator                                                                DX
                       auxiliary power
         Process management level
                                                                                                                      MUX
                                                                                                          non-                #         field
                                                                                                                                        multiplexer
                                                                                                          hazardous                                                                      4-20 mA
                                              4-20 mA                                               4-20 mA                       4-20 mA
# # #
                                             PD                                                    pH                          T                                               #
                                                       hand-held
         Field level                                    terminal
                                                  PD                                                    pH                          T
         Process
                                 HART field device
                                         a                                                     b                          c                                                    d
2
                                                                                                                                                ®
                                                                                                                          HART
                                                                                                                          FIELD COMMUNICATION PROTOCOL
Process
                                                                                                                                               Figure 3
                                                                                                            With multi-drop mode, installation costs are
                                                                                                     considerably reduced. As many as 15 field devices
                                                                                                      can be operated from one auxiliary power supply.
                                                                                                     Management systems and hand-held terminals can
MULTI-DROP                                                                                                                                     be used.
                                                                                                                                                                3
                       ®
    HART
    FIELD COMMUNICATION PROTOCOL
                                                               HART follows the basic Open                    Data transfer rate: 1200 bit/s
                                                               Systems Interconnection (OSI)                  Logic '0' frequency: 2200 Hz
                                                               reference model, developed by the              Logic '1' frequency: 1200 Hz
                                                               International Organization for
                                                               Standardization (ISO) [3]. The OSI             The vast majority of existing wiring is
                                                               model provides the structure and               used for this type of digital
                                                               elements of a communication system.            communication. For short distances,
                                                               The HART protocol uses a reduced               unshielded, 0.2 mm2 two-wire lines
                                                               OSI model, implementing only layers            are suitable. For longer distances (up
                                                               1, 2 and 7 (see Figure 4).                     to 1500m), single, shielded bundles of
                                                                                                              0.2 mm2 twisted pairs can be used.
                                                                                                              Beyond this, distances up to 3000m
                                                                                                              can be covered using single,
                                                                                                              shielded, twisted 0.5 mm2 pairs.
4
                                                                                                                             ®
                                                                                                       HART
                                                                                                       FIELD COMMUNICATION PROTOCOL
Universal commands
   understood by all field devices.      Examples of all three command
                                         sets can usually be found in a field
Common practice commands                 device, including all universal
  provide functions which can be         commands, some common-
  carried out by many, though not        practice commands and any
  all, field devices. Together, these    necessary device-specific
  commands comprise a library of         commands.
  the most common field device
  functions.
Device-specific commands
   provide functions which are
   restricted to an individual device,
   permitting special features to be
   incorporated that are accessible
   by all users.
                                                                                                                                               5
                       ®
    HART
    FIELD COMMUNICATION PROTOCOL
                           OPERATING CONDITIONS
                                             The HART standard [4] requires level      frequencies in both directions (see
                                             3 resistance to interference in the       Figure 2). As can be seen in Figure 3,
                                             lines in accordance with                  in multi-drop mode it is also possible
                                             IEC 801-3 and -4. This satisfies the      to interconnect field devices in
                                             general requirement for noise             accordance with DIN VDE 0165.
                                             resistance.
HART AT A GLANCE
     ● Simultaneous analog and digital        ● Multi-drop connection is permitted.    four of which are transmitted on
     communication. The analog signal         Several 'smart' devices can be           demand. Thus, devices with several
     contains the process information; the    connected to a single twisted pair of    measurement functions (e.g. Coriolis
     digital is used for two-way              wires, reducing wiring costs.            mass flow meters) can transmit
     communication of both process and                                                 several variables in each message.
     device information.                      ●  Can be used with leased telephone
                                              lines, so multi-drop connections can
     ● Accepts other analog units. With       cover great distances using
     simultaneous analog and digital          inexpensive interface technology.
     communication, you can also use
     analog indicators, recorders and         ● Provides an open message
     controllers while communicating with     structure. This enables new HART
     'smart' field devices.                   devices with new features to be
                                              added, thereby retaining compatibility
     ● A process management system and        with existing units.
     a hand-held terminal can both
     communicate simultaneously, as           ● The protocol allows up to 256
     shown in Figure 2.                       variables in each field device, any
6
                                                                                                                               ®
                                                                                                            HART
                                                                                                            FIELD COMMUNICATION PROTOCOL
                                                                             TECHNICAL DATA
DATA TRANSMISSION                           HARDWARE
                                            RECOMMENDATIONS:
Type of data transmission:
Frequency shift keying (FSK) in             Type of connection and length                         For an in-depth examination of
accordance with Bell 202, relating to       limitations:                                          whether a particular hook-up will
the transfer rate and the frequency for                                                           work, refer to the specification for the
bit information '0' and '1'.                    Distance         Line type        min. conduct.
                                                   (m)                                 area       Physical layer in the HART document
                                                                                   AWG/(mm2)      [4].
Transfer rate:                                  ≤ 1.500        multiple 2-wire,      24/0.2
1200 bit/s                                                    twisted, common
                                                                  shielding
'0' bit information frequency:
2200 Hz                                         > 1.500         single 2-wire,       20/0.5
                                                ≤ 3.000       twisted, shielded
Link layer:
                                                          l   = 1.633 [m]
recognizes: all groups of up to three       Then as is:
corrupt bits and practically all longer     In intrinsically safe applications, there
and multiple groups.                        may be further restrictions.
Application layer:
Communication status transmitted in
a response message.
                                                                                                                                             7
                      ®®
    HART
    FIELD
    FIELD COMMUNICATION
          COMMUNICATION PROTOCOL
                        PROTOCOL
                                          [2] Appendix to Bell System Technical Reference      [4] HART Smart Communications Protocol
                                          PUB 41004, "Data Communications Using                Specification, Rev. 5.1.4, January 1991.
                                          Voiceband Private Line Channels", October 1973.
8
HART
                    ®
             HART
                                 ®
                          HART
                                              ®
                                       HART
                                                           ®
                      ABB                                          Masoneilan
     Adaptive Instruments Corporation                    Measurement Technology Ltd
                 Allen-Bradley                              Meridian Instruments B.V.
               Analog Devices                             MESCO Engineering GmbH
       Anderson Instrument Co., Inc.                            Micro Motion, Inc.
      Apparatebau Hundsbach GmbH                                  Milltronics Ltd.
    Applied System Technologies, Inc.                   Moore Industries-International Inc.
           Arcom Control Systems                               Moore Products Co.
          Bailey - Fischer & Porter                        MTS Systems Corporation
              Beamex Oy, Ab                                     Neles-Jamesbury
                  BESTA AG                                   Peek Measurement Ltd.
              Brooks Instrument                                  Pepperl + Fuchs
          BTG Källe Inventing AB                             Pondus Instruments AB
            Delta Controls Limited                           Princo Instruments, Inc.
               Drägerwerk AG                                       Raytek, Inc.
    Drexelbrook Engineering Company                     Rittmeyer Ltd. Measuring Control
            Elcon Instruments sr.                           Robertshaw Tennessee
             EMCO Flowmeters                                Rosemount Analytical Inc.
          Endress + Hauser GmbH                                  Rosemount Inc.
            Endress + Hauser Ltd                       Rössel Messtechnik GmbH & Co.
          Fieldbus International AS                            Saab Tank Control
               Fisher Controls                                     Samson AG
      Fisher-Rosemount Systems Inc.                          Schlumberger Industries
                Flowdata, Inc.                                     Siemens AG
               Foxboro-Eckardt                           Smar International Corporation
             Fuji Electric Co., Ltd.                            SMC Corporation
          Harold Beck & Sons, Inc.                                Softing GmbH
           Hartmann & Braun AG                                Solartron Transducers
                   Helios AG                                        SOR, Inc.
      Hersey Measurement Company                         Southwest Research Institute
               Honeywell, Inc.                           Sparling Instruments Co., Inc.
 Honeywell Loveland Controls Company                         The Foxboro Company
         Instrumenfirman INOR AB                      Toshiba Corporation - Principle Office
         Johnson Yokogawa Corp                               Two Technologies, Inc.
             K-TEK Corporation                                Valmet Automation Inc.
                Kamstrup A/S                                   Valtek International
           Kay-Ray/Sensall, Inc.                              VEGA-Grieshaber KG
              KDG Mobrey Ltd.                                  Viatran Corporation
Knick Elektronische Meßgeräte GmbH & Co.                       W. C. Groenuijzen
     Krohne Mebtechnik GmbH & Co.                        Westlock Controls Corporation
              Leeds & Northrup                                 Whessoe Varec, Inc.
            MACTek Corporation                               Wireless Scientific, Inc.
           Magnetrol International                       Yamatake-Honeywell Co., Ltd.