                                                       The Caterpillar Electronic Modular Control Panel
                                                       (EMCP II+) places full-featured power metering,
                                                       protective relaying, simultaneous engine and
                                                       generator parameter viewing, and expanded AC
                                                       metering at your fingertips. Engine and generator
                                                       control, diagnostics, and operating information is
                                                       accessible via the control panel keypads or a
                                                       remote, personal computer. The advanced
                                                       microprocessor-based EMCP II+ combined with
                                                       the Caterpillar Customer Communication Module
                                                       (CCM) and Relay Driver Module (RDM) give you
                                                       the flexibility to remotely manage the specific
                                                       needs of your total system.
FEATURES
UL 508A                                                ●   Load demand relay opens and closes based
● UL 508A Listed                                           on generator kW output, programmable to
                                                           activate at an adjustable setpoint.
RELIABLE, DURABLE, AND ACCURATE                        ●   Simultaneous viewing of engine and
● Environmentally sealed, die-cast aluminum                generator parameters with toggle between
  housing isolates and protects electrical                 auto parameter scrolling and individual
  components against failure caused by                     parameter display.
  moisture and dirt contamination.                     ●   Simultaneous viewing of all AC L-L voltages,
● Rigorous vibration testing ensures panel                 all AC L-N voltages, or all AC line currents.
  dependability.                                       ●   Expanded remote customer communication
● Maintains metering accuracy from –40° C                  module supported by an open RS-232C
  (–40° F) to 70° C (158° F)                               architecture — easily interfaces with existing
● Electrical noise immunity of 100 volts/meter             plant systems and equipment.
● True RMS sensing ensures AC metering
                                                       KEYPAD PROGRAMMABILITY
  accuracy is 0.5% for AC volts, amps, and
                                                       ● User-friendly, convenient, customer
  power parameters.
                                                         programmability directs the customer to
● The digital, 32 bit microprocessor-based
                                                         logical parameter groups — AC metering,
  system eliminates the need for a number of             protective relaying, engine monitoring —
  switches, meters, transducers, relays, and             for quick keypad access.
  sending units. That means less wiring and
                                                       ● Programmable, spare control relay with
  fewer opportunities for mechanical failures.
                                                         remote control capability provides additional
ADVANCED FEATURES THAT SUPPORT                           flexibility for customer control function.
YOUR BUSINESS NEEDS                                    ● 10 LED alarms, five programmable for
● Full-featured power metering, accessible with          customer inputs, provide more information
  one keypad touch, allows you to view                   at a glance.
  generator set kW, kVA, kVAR, kW hours, kVAR
  hours, percent rated power, and power factor.        REGULATORY APPROVALS
                                                       ● U.S. sourced control panels
● Customer programmable protective relaying,
  available as alarm and shutdown, protects              meet CSA requirements.
  against undervoltage, overvoltage,                   ● Larne sourced control panels
  underfrequency, overfrequency, overcurrent,            meet CE requirements.
  and reverse power.
LEHX9590-05
        W H E R E     T H E    W O R L D         T U R N S     F O R    P O W E R
C O N T R O L S
STANDARD/OPTIONAL FEATURES
                                 EMCP II+                                           PROTECTIVE RELAYING
                            STANDARD FEATURES                                       Setpoint programming
 Digital (LCD) Indication    AC voltage — 3 phase (L-L & L-N)
                                                                                    provides the flexibility to
                             AC amps (3 phase & total)                              custom configure protective
                             kW (total & per phase)                                 relays in a manner which
                             kVA (total)                                            best suits a customer’s
                             kVAR (total)                                           application. The customer
                             kWhr (total)
                             kVARhr (total)
                                                                                    determines the response
                             PF (average total & per phase)                         type and timing of
                             Percent of rated (total)                               protective relay functions:
                             Frequency                                              ● Alarm enable/disable
                             DC voltage
                             Coolant temperature                                    ● Alarm threshold level
                             Oil pressure                                           ● Alarm time delay
                             rpm                                                    ● Shutdown enable/disable
                             Hours run
                             System diagnostic                                      ● Shutdown threshold level
                             L/R exhaust manifold temperature (3500 only)           ● Shutdown time delay
                             Oil temperature (except 3300/3406)
                                                                                    Setpoints are factory set for
 Controls                    Auto start/stop
                               Purge cycle (gas packages only)
                                                                                    optimum performance and
                               Staged shutdown (gas packages only)                  generator protection.
                             Emergency stop                                         Setpoint values may be
                             Lamp test                                              viewed with the engine
                             Cycle crank                                            running or stopped.
                             Voltage control
                             Cooldown timer
                             Phase selector switch
                             Load demand relay
                             Spare relay — programmable
 Enclosure                   NEMA 12, IP44
                             Vandal door (Not available on 3406, 3456)
 Indicating Lights with      Low oil pressure
   Shutdown                  High coolant temperature
                             Overspeed
                             Overcrank
                             Emergency stop
                                High inlet air temp (gas TA engines only)
                                Detonation sensitive timing (gas LE engines only)
                             Fault shutdown
                             Fault alarms
                             3 spare lights/4 spare inputs,
                                customer programmable (shutdown
                                or alarm) to spare alarm or fault LEDs
 Protective Relaying         Programmable relays:
                               Over/undervoltage
                               Reverse power relay
                               Over/underfrequency
                               Overcurrent
                            OPTIONAL FEATURES
 Protective Devices          Low coolant level (standard on some packages)
 Miscellaneous Controls      Electronic governor:
                               Isochronous speed control
                               Load share
                             Alarm modules — local (with horn and silence switch)
                             Frequency control
                             Common alarm/shutdown volt free contact
                             Generator running volt free contact
                             Ether starting aid (not available on gas packages)
                             Remote annunciator modules
                             Computer communications data link
                             Panel lights
LEHX9590-05
                                                             2
C O N T R O L S
EXPANDED SYSTEM FLEXIBILITY
ALARMS AND ANNUNCIATORS                              The combined power of the EMCP II+ and CCM
EMCP II+ control panel includes two slots for        now enable you to control the packaged
optional alarm or synchronizing modules. Each        generator set and ancillary equipment. Text
alarm module contains a block of eight LEDs.         editable software enables you to control the
Customers select from the following:                 EMCP II+ spare relay and the Relay Driver
● NFPA99/110 alarm modules                           Module (RDM).
● Custom alarm module                                RELAY DRIVER MODULE (RDM)
● Manual synchronizing module                        The Caterpillar RDM expands the number of
                                                     relays available to the customer. One RDM
                                                     contains nine relay outputs which can be
                                                     directly connected to ancillary equipment such
                                                     as lamps, fuel tank controls, or other devices
                                                     such as louvers. The RDM requires the use of
                                                     the CCM.
CUSTOMER INTERFACE MODULE
The Customer Interface Module (CIM) is a relay
board that provides nine contacts for custom
remote annunciation.
                                                     SYSTEM SOFTWARE
REMOTE COMMUNICATION                                 CCM PC is a user-friendly, IBM compatible,
The Caterpillar Customer Communication               windows-based program.
Module (CCM) provides a means to remotely
monitor and control single or multiple               CCM PC interfaces with the CCM and EMCP II+.
packaged generator sets at a common site.            Remote control ability, parameter status
By accessing the CCM from a personal computer        display, diagnostic viewing/clearing options,
or other RS-232C device, each unit can be            and parameter logging are among its standard
remotely started and stopped, and all engine         tools. An on-line help system provides fingertip
and generator parameters can be monitored            access to software questions and instructions.
on a “real time” basis. Published, open              Integrated file management facility allows you
architecture enables you to connect the CCM          to copy, move, delete, view, print, and rename
to an existing plant information system.             documents and files from within CCM PC
                                                     without the use of DOS file names or the
                                                     Windows File Manager.
                                                     CCM PC, used in conjunction with relay driver
                                                     module, enables you to individually label and
                                                     control each RDM relay.
LEHX9590-05
                                                 3
C O N T R O L S
EMCP II + SPECIFICATIONS
EMI Immunity
  IEC 801-2, IEC 801-3, IEC 801-4, EN 5082-2
Enclosure
  NEMA 12, IP44
Humidity
  0 to 100% relative humidity
Impervious to:
  salt spray, fuel, oil and oil additives, coolant,
  spray cleaners, chlorinated solvents, hydrogen sulfide
  and methane gas, and dust
Input and output protection
  all inputs and outputs are protected against short circuits to (+/-) battery
Input voltage range (24 VDC nominal)
  14 to 45 VDC
Power requirements
  10 watts (with generator set in standby mode — no alarms)
Reverse polarity protected
Shock, withstands 20 g
Temperature range
  Operating: –40° C to 70° C (–40° F to 158° F)
  Storage: –55° C to 85° C (–67° F to 185° F)
Vibration
  withstands 2.0 g @ 18 to 500 Hz
EMCP II+ SYSTEM HIERARCHY DRAWING
               Serial Data Link
 RDM
                                                  EMCP II+
           Serial Data Link                                                                               CCM
  Remote         CIM     Alarm                                                         Cat Data Link
Annunciator              Module                                                                                     PC or other
     (maximum of 3 modules)                                                                                          RS-232C
                                                                                                                      device
                                                                                                  www.CAT-ElectricPower.com
                                                                                                             © 2003 Caterpillar
                                                                                                            All rights reserved.
U.S./European sourced                                                                                         Printed in U.S.A.
LEHX9590-05 (7-03)                                           Materials and specifications are subject to change without notice.