Flare Sizing Calculation Sheet

This document provides calculations for sizing a flare stack for a natural gas facility. It includes input data on vapor flow rates, temperatures, and wind velocities. The calculations determine the inside diameter of 0.19m, flame length of 21.61m, and required flare stack height of 21.26m to ensure safe dispersion of gases. A diagram references the dimensional requirements including the horizontal and vertical distance of the flame center from the top of the stack. The results are then compared to another software program showing good agreement between the calculated parameters.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
897 views8 pages

Flare Sizing Calculation Sheet

This document provides calculations for sizing a flare stack for a natural gas facility. It includes input data on vapor flow rates, temperatures, and wind velocities. The calculations determine the inside diameter of 0.19m, flame length of 21.61m, and required flare stack height of 21.26m to ensure safe dispersion of gases. A diagram references the dimensional requirements including the horizontal and vertical distance of the flame center from the top of the stack. The results are then compared to another software program showing good agreement between the calculated parameters.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 8

CALCULATION SHEET Date

FLARE SIZING Rev.


CNG LAMPUNG Page
Input Data
Vapor flow rate, Qm lb/h 17017.66
kg/h 7709
Relative molecular mass, MW 24.79
Flowing Temperature, T R 497.83
Heat Combustion, Hc BTU/lb 18917.008
MJ/kg 44.05
Specific heat ratio, K (Cp/Cv) 1.234
Flowing pressure at flare tip, P psia 14.69
kPa 101.3
Wind Velocity, Uµ m/s 28
ft/s 91.87
Compressibility Factor, Z 0.991

Calculation for Flare Diameter


Mach No., Ma 0.2
Inside Diameter, d ft 0.630
in 7.560
m 0.192
Calculated Mach No. 0.2
Calculation of Flame Length
Heat Liberated, Q Btu/hr 3.22E+08
Length of flame, L Use figure 6 in API 521 ft 70.86
m 21.6123
Calculation of Flame Distortion caused by Wind Velocity
Vapour flow rate, qvap ft3/s 69.21
Flare Tip velocity, Uj ft/s 222.01
uµ/uj 0.41
Use figure 7 in API 521 0.20
Use figure 7 in API 521 0.95
ft 14.18
∑▒ 〖∆� / ft 67.32
�〗
∑▒ 〖∆� /
�〗
Calculation
∑▒∆� of Required Flare Stack Height
Fraction
∑▒∆� of Heat Radiated, F 0.3
Max. Allowable Radiation, K Use Table 12 in API 521 BTU/h.ft2
500
kW/m2 1.58
Fraction of the radiated heat transmitted through the atm, t 1
Distance from flame center to grade-level boundary, D ft 123.98
Radius Distance Max., r ft 131
Radius from flare center, r' ft 97.34
Flame heigth, h' ft 76.79
Flare Stack Height, h ft 69.70
m 21.26
Flame Center
Horizontal Distance of flame center from the top of flare stack, xc ft 33.66
m 10.26
Vertical Distance of flame center from the top of flare stack, yc ft 7.09
m 2.16
Dimensional Reference for Sizing Flare Stack
∑▒∆�
67.32 ft

L 70.86 ft
Wind direction

91.87 ft
∑▒∆�
14.18 ft
yc
7.09 ft

xc
33.66 ft
d

0.63 ft D
h 69.7 ft h' 76.79 ft 123.98 ft

r'
97.34 ft

r
131 ft
Perbandingan Hasil Validasi Template Flare Sizing

Parameter Unit PLNE Template


Mach No., Ma 0.2
Inside Diameter, d m 0.19
Heat Liberated, Q 321923214.6 BTU/hr
Length of flame, L m 21.61
∑▒∆�
m 4.32
∑▒∆�
m 20.53
Distance from flame center to grade-level boundary, D m 37.81
Radius Distance Max., r m 39.96
Flame heigth, h' m 23.42
Flare Stack Height, h m 21.26
Horizontal Distance of flame center from the top of flare stack, xc m 10.26
Vertical Distance of flame center from the top of flare stack, yc m 2.16
ng

PGTB Result
0.2
0.19
9430000 kW
25
4.75
23.63
37.8
40
25.13
22.754
11.81
2.38
Vapour Mass Rate lb/hr
Liquid Mass Rate lb/hr
Vapour Density rv lb/ft3
Vapour Viscosity cP
Liquid Density rl lb/ft3
Diameter Particles D m
ft
Vapor Flow Rate ft3/s
Liquid Flow Rate ft3/s
Gravitational Acc g ft/s2

C(Re)2
C Refer to Fig 12 API 521

Operating Pressure P psi


Operating Temperature T F
R
Drain Volume US gal
ft3
Liquid Holdup AL1 /L
Take Min
Holding and Surge Volume AL2 /L
Cross-sectional area remaining for vapour Av
AV = AT - (AL1 + AL2)
Total drum diameter ht
169000
31000
0.18
0.01
31
600.00
0.0019686
260.80
0.28
32.2

4.02E+04
0.67

2
300
759.67
500
66.8
66.8
30.0
500
Mach No. Condition
0.2 Continues
0.5 Emergency/Peak
0.7 Maximum