Tank Pressure & Vacuum Protection
Design Sheet
Stored Material Crude Oil Tank T - 400
Flash Point F o
350 (Estim.) MAWP in WC
Boiling Point F o
360 (Estim.) Max Vacuum oz/in2
Latent Heat Vap. Btu/lb 144 (Hexane) Diameter ft
Molecular Wt. 274 Max fill Height ft
Max fill Volume gal
Inflows, SCFH Wetted Area ft2
Normal Operation 12,861
Relief Scenario 20,578 Fire Therm. Conductivity BTU/hr-ft2
Required Capacity SCFH
Outflows, SCFH 40,104
Blow Through From Upstream SCFH
Breathing, Note 1 From Hose SCFH
Out SCFH 6,295 Relief, Hose +unload SCFH
In SCFH 10,491
Vent Valve set at 4 in WC Consider this when using emission vapor control system
Required SCFH NA Normal max inflow + out breathing + Blowoff (normal unloading)
selected SCFH NA With vent system Pressure Drop of 9 in WC
Fail Open SCFH 0 Consider this only if the tank vents to a vacuum source or header
Blanket Gas Valve set at 2" WC
Required SCFH 50,595 sum of outflows + in Breathing + fail open vent valve
Selected SCFH 75,893 Fisher Model ___ Regulator with ___" trim.
Valve Fail Open SCFH 0 This flowrate assumes the valve's Cv determines the capacity
Pressure Relief Cases
Inflow SCFH 102,766 Relief Inflow + Out Breathing + Blanket Gas Valve + Relief Blowoff
Fire SCFH 877,654 Fire + Blanket Gas valve
Outflow SCFH 50,595 sum of outflows + in Breathing + fail-open vent valve + Steam Failure
Conservation Vent
Pressure side set at 5 in WC, Rated at 20 in WC
Required SCFH 0 zero (if have Vent Valve and Emergency vent) or worst case
Selected Size SCFH 44,000 each from catalog; total number 1 Total
Vacuum Side set at 0.5 oz/in Vacuum, rated at
2
2 1/2 oz/in 2
Required SCFH 50,595 Outflow Case
Selected Capacity SCFH 15,000 each from catalog; total number 1 Total
Emergency Relief, Note 2
Set at 10 in WC, Rated at 20 in WC
Required SCFH 833,654 zero (if Con vent has capacity) or Worst case - Con Vent
Selected Size SCFH 680,000 each from catalog; total number 1 Total
Selected Equipment: Tag Manufacturer Model Size, in
Blanket Gas Regulator PCV 400B Fisher 1190 2
Conservation Vent PVSV 400
Emergency Vent
Notes:
1) For Tanks larger than 840,000 gal (20,000 Bbls), refer to API-2000 for breathing requirements.
2) Fire hatch is not required if: cone roof tank has a weak roof seam, or Conservation Vent has capacity.
T - 400
55.4
0.5
50.0
30.0
440,620
4,712.4
4,582 21,591,212
801,761
547,330
MSW Memo:
79612.46
mal unloading)
urce or header
ve
he capacity
+ Relief Blowoff
ve + Steam Failure
worst case
44,000
15,000
n Vent
680,000
Cv
2400
ts.
capacity.