DKG-116 User Manual                                                     V-03 (30.03.
2011)
                                           DKG-116 MANUAL AND
                                           REMOTE START UNIT
             DESCRIPTION                                  MEASUREMENTS
The DKG-116 is a low cost                      Generator Volts: L1-N, L2-N, L3-N
gasoline/diesel genset control unit            Generator Volts: L1-L2, L2-L3, L3-L1
designed to start and stop a genset both       Generator Frequency
manually and remotely.                         Battery Voltage
The manual control is made using RUN
and STOP pushbuttons on the front
                                                                OPTIONS
panel. The remote control is made via
                                               Auxiliary output (negative pulling).
REMOTE START input signal.
                                               Magnetic pickup input.
When RUN button is pressed or a Remote
Start signal arrives, the engine will be                      FEATURES
cranked up to 3 times. When it runs, the
crank relay will be immediately deactivated    Both Manual and remote control
and after Holdoff timer delay, fault           Generator protection
checking will be enabled. When the engine
is running, if a fault condition is detected   Built in alarms and warnings
then the engine is shutdown immediately        Remote Start operation available
and the unit indicates the source of the       True RMS measurements
failure through related alarm led.
                                               Tamper-proof engine hours display
If the Remote Start signal disappears or       Field adjustable parameters
the STOP button is pressed or the genset
will immediately stop.                         High current Fuel and Crank outputs
                                               Optional auxiliary output
The MENU button selects display
parameter scroll and allows program            Optional magnetic pickup input
mode entry and lamp test functions.            Digital inputs: 4
The total engine run hours is kept in a        Survives cranking dropouts
tamper-proof non-erasable memory which         Sealed front panel
is not affected by power failures.
                                               Standard panel dimensions: 96x48mm
                                               Plug-in connection system
DKG-116 User Manual                                                            V-03 (30.03.2011)
      PRECAUTIONS FOR INSTALLATION AND SAFE USE
               Failure to follow below instructions will result in death or
               serious injury.
     Circuit breakers must be connected serially to BAT+, PHASE-L1, PHASE-L2 and PHASE-
      L3 terminals, in close proximity of the unit.
     Fuses must be of fast type with a maximum rating of 6A.
     Disconnect all power before working on equipment .
     When the genset is running, do not touch terminals.
     Do not try to clean the device with solvent or the like. Only clean with a dump cloth.
     Verify correct terminal connections when wiring.
     Electrical equipment should be serviced only by competent service personnel. No
      responsibility is assured by the manufacturer or any of its subsidiaries for any
      consequences arising out of the use of this material.
     Only for front panel mounting.
                           CONNECTION DIAGRAM
DKG-116 User Manual                                                                    V-03 (30.03.2011)
                                           PROGRAMMING
                  Both ‘High Temperature’ and ‘Emergency Stop’ inputs must be connected
                  to ‘Battery negative’ prior to enter the programming mode.
The unit offers 12 programmable parameters listed below.
                                       FACTORY
NO SYMBOL RANGE                                                      DESCRIPTION
                                         SET
 1                    70-500 V         170 V           Low AC voltage shutdown limit
 2                    70-500 V         300V            High AC voltage shutdown limit
 3                    0-1000           50              MPU crank cut frequency divided by 4
 4                    0-1              0               Nominal frequency: 0=50Hz 1=60Hz
 5                    0-1              0               Oil input: 0=pressure switch 1=level switch
 6                    0-1              0               Fuel output type 0:Fuel 1:Stop
                      0-3              0               Relay 3 function
 7
                                                       0:Alarm 1:Choke 2:Stop 3:Preheat
 8                    0-15 sec         0               Choke timer in seconds
 9                     0-15 sec             10         Preheat timer in seconds
                     0-7              0               Connection topology:
                                                       0=1phase 1=2phases 2=3 phases 3=3 phases ,
                                                       center tapped delta (voltage checks on first 2
 10
                                                       phases only)
                                                       4..7= same as 0..3, but voltages are not
                                                       displayed
 11                       0-15 sec             5       Under/over voltage delay timer
 12                  -                -               Phase L1-N calibration value
 13                  -                -               Phase L2-N calibration value
 14                  -                -               Phase L3-N calibration value
The program mode is entered by long-pressing the MENU button. Each depression of the MENU
button will switch to the next parameter.
Another long press will enable the lamp test mode. Then any depression of MENU button will return
the display to normal mode.
If no key is pressed, then the unit will return to normal display mode with a delay.
                                     1- When genset is in off mode; press MENU button for 5 sec to
           MENU
                                        enter program mode and display the Low AC Voltage limit.
                                     2- Press RUN or STOP buttons until requested value is displayed.
     RUN          STOP
      N                              3- Press MENU button for saving the Low AC Voltage limit and
           MENU                         displaying the next program parameter.
                                     4- Press RUN or STOP buttons until requested value is displayed.
     RUN          STOP
      N
                                     5- Press MENU button for saving the parameter and displaying
           MENU                         the next parameter.
                                     6- Repeat steps 4 and 5 as required.
                                     7- Any time on settings, press MENU button for 3 sec. to exit from
   RUN            STOP
                                        program mode.
      N
DKG-116 User Manual                                                                 V-03 (30.03.2011)
   TECHNICAL SPECIFICATIONS                                 DIESEL ENGINE SELECTION
  Alternator voltage: 15 to 300 V-AC (Ph-N)
  Alternator frequency: 50 or 60 Hz nominal.                                   In order to control
  Measurement Accuracy: 0.5% + 1 digit
                                                                               diesel engines,
                                                                               connect a conductive
  Overspeed: nominal frequency + 14%
                                                                               wire to between
           (+24% overshoot)
                                                                               terminals 1 and 3.
  Underspeed: 30 Hz
  Crank time: 10 sec.
  Crank rest: 10 sec.
  Crank attempts: 3                                         PANEL CUTOUT DIMENSIONS
  Stop timer: 10 sec.
  Holdoff timer: 10 sec.
                                                                                                    44mm
  DC Supply Range: 9.0 to 16.0 V-DC
  Cranking dropouts: survives 0 V for 100ms.
  Typical Standby Current: 12mA-DC (display off)
  Maximum Operating Current: 130 mA-DC
  Fuel and Crank outputs: 10A @ 12V-DC
  Auxiliary Output: 1A @ 12V-DC (negative pulling
  protected semiconductor output)
                                                                            92mm
  Magnetic pickup Input: 1.5 to 30Vpp
  Operating temp.: -40°C (-40°F) to 80 °C (176°F).
  Maximum humidity: 95% non-condensing.                     PACKAGING INFORMATION
  Dimensions: 102 x 55 x 40 mm (WxHxD)
                                                          Pieces per Package: 24
  Packed weight: 140 g
                                                          Package Size: 280 x 170 x 215mm (LxWxH)
  Case Material: High Temp. ABS/PC (UL94-V0)
                                                          Package Weight: 3.6 kg
  IP Protection: IP65 (front panel), IP30 (rear)
  Conformity (EU directives)
          -2006/95/EC (low voltage)
          -2004/108/EC (EMC)
  Norms of reference:
          EN 61010 (safety requirements)
          EN 61326 (EMC requirements)
                                        DATAKOM Electronics Ltd.
  Tel: +90-216-466 84 60 Fax: +90-216-364 65 65 e-mail: datakom@datakom.com.tr http: www.datakom.com.tr