QuickCMC1
Test Module
Name: OMICRON QuickCMC Version: 3.00
Test Start: 20-Jan-2019 10:36:43 Test End: 20-Jan-2019 10:43:58
User Name: Manager:
Company:
Test Results
Title: Test 1
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Z-I const. Fault L3-E 50,000 Hz
ZFault 200,0 mΩ 64,00 °
ZFault (R-X) 87,67 mΩ 179,8 mΩ
ITest 2,000 A
Generator Settings
V L1-E 63,509V 0,00° +90°
V L2-E 63,509V -120,00° I L3
V L3-E 0,800V 120,00°
I L1 0,000A 0,00°
V L1-E
I L2 0,000A 0,00° 180° V L3-E 0°
I L3 2,000A 56,00°
V L2-E
80,0 V -90° 2,0 A
Binary Inputs
Trip Start Overload
0->1 1->0 1->0
0,021s n/a n/a
Title: Test 2
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Z-I const. Fault L3-E 50,000 Hz
ZFault 200,0 mΩ 64,00 °
ZFault (R-X) 87,67 mΩ 179,8 mΩ
ITest 2,000 A
Generator Settings
V L1-E 63,509V 0,00° +90°
V L2-E 63,509V -120,00° I L3
V L3-E 0,800V 120,00°
I L1 0,000A 0,00°
V L1-E
I L2 0,000A 0,00° 180° V L3-E 0°
I L3 2,000A 56,00°
V L2-E
80,0 V -90° 2,0 A
Binary Inputs
Trip Start Overload
0->1 1->0 1->0
0,024s n/a n/a
Title: Test 3
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Z-I const. Fault L3-E 50,000 Hz
ZFault 400,0 mΩ 64,00 °
ZFault (R-X) 175,3 mΩ 359,5 mΩ
ITest 2,000 A
Generator Settings
V L1-E 63,509V 0,00° +90°
V L2-E 63,509V -120,00° I L3
V L3-E 1,600V 120,00°
I L1 0,000A 0,00°
V L1-E
I L2 0,000A 0,00° 180° V L3-E 0°
I L3 2,000A 56,00°
V L2-E
80,0 V -90° 2,0 A
Binary Inputs
Trip Start Overload
0->1 1->0 1->0
0,022s n/a n/a
Title: Test 4
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Z-I const. Fault L3-E 50,000 Hz
ZFault 600,0 mΩ 64,00 °
ZFault (R-X) 263,0 mΩ 539,3 mΩ
ITest 2,000 A
Generator Settings
V L1-E 63,509V 0,00° +90°
V L2-E 63,509V -120,00° I L3
V L3-E 2,400V 120,00°
I L1 0,000A 0,00°
V L1-E
I L2 0,000A 0,00° 180° V L3-E 0°
I L3 2,000A 56,00°
V L2-E
80,0 V -90° 2,0 A
Binary Inputs
Trip Start Overload
0->1 1->0 1->0
0,020s n/a n/a
Title: Test 5
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Z-I const. Fault L3-E 50,000 Hz
ZFault 1,000 Ω 64,00 °
ZFault (R-X) 438,4 mΩ 898,8 mΩ
ITest 2,000 A
Generator Settings
V L1-E 63,509V 0,00° +90°
V L2-E 63,509V -120,00° I L3
V L3-E 4,000V 120,00°
I L1 0,000A 0,00°
V L1-E
I L2 0,000A 0,00° 180° V L3-E 0°
I L3 2,000A 56,00°
V L2-E
80,0 V -90° 2,0 A
Binary Inputs
Trip Start Overload
0->1 1->0 1->0
0,023s n/a n/a
Title: Test 6
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Z-I const. Fault L3-E 50,000 Hz
ZFault 1,600 Ω 64,00 °
ZFault (R-X) 701,4 mΩ 1,438 Ω
ITest 2,000 A
Generator Settings
V L1-E 63,509V 0,00° +90°
V L2-E 63,509V -120,00° I L3
V L3-E 6,400V 120,00°
I L1 0,000A 0,00°
V L1-E
I L2 0,000A 0,00° 180° V L3-E 0°
I L3 2,000A 56,00°
V L2-E
80,0 V -90° 2,0 A
Binary Inputs
Trip Start Overload
0->1 1->0 1->0
0,819s n/a n/a
Title: Test 7
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Z-I const. Fault L1-E 50,000 Hz
ZFault 2,200 Ω 64,00 °
ZFault (R-X) 964,4 mΩ 1,977 Ω
ITest 2,000 A
Generator Settings
V L1-E 8,800V 120,00° +90°
V L2-E 63,509V 0,00° I L1
V L3-E 63,509V -120,00°
I L1 2,000A 56,00°
V L2-E
I L2 0,000A 0,00° 180° V L1-E 0°
I L3 0,000A 0,00°
V L3-E
80,0 V -90° 2,0 A
Binary Inputs
Trip Start Overload
0 0 0
Title: Test 8
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Z-I const. Fault L1-E 50,000 Hz
ZFault 2,800 Ω 64,00 °
ZFault (R-X) 1,227 Ω 2,517 Ω
ITest 2,000 A
Generator Settings
V L1-E 11,200V 0,00° +90°
V L2-E 63,509V -120,00°
V L3-E
V L3-E 63,509V 120,00°
I L1 2,000A -64,00°
V L1-E
I L2 0,000A 0,00° 180° 0°
I L3 0,000A 0,00°
V L2-E
I L1
80,0 V -90° 2,0 A
Binary Inputs
Trip Start Overload
0 0 0
Title: Test 9
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Z-I const. Fault L1-E 50,000 Hz
ZFault 3,500 Ω 64,00 °
ZFault (R-X) 1,534 Ω 3,146 Ω
ITest 2,000 A
Generator Settings
V L1-E 14,000V 0,00° +90°
V L2-E 63,509V -120,00°
V L3-E
V L3-E 63,509V 120,00°
I L1 2,000A -64,00°
V L1-E
I L2 0,000A 0,00° 180° 0°
I L3 0,000A 0,00°
V L2-E
I L1
80,0 V -90° 2,0 A
Binary Inputs
Trip Start Overload
0 0 0
Title: Test 10
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Z-I const. Fault L3-E 50,000 Hz
ZFault 3,500 Ω 64,00 °
ZFault (R-X) 1,534 Ω 3,146 Ω
ITest 2,000 A
Generator Settings
V L1-E 63,509V 0,00° +90°
V L2-E 63,509V -120,00° I L3
V L3-E 14,000V 120,00°
I L1 0,000A 0,00°
V L3-E V L1-E
I L2 0,000A 0,00° 180° 0°
I L3 2,000A 56,00°
V L2-E
80,0 V -90° 2,0 A
Binary Inputs
Trip Start Overload
0 0 0
Title: Test 11
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Z-I const. Fault L3-E 50,000 Hz
ZFault 4,500 Ω 64,00 °
ZFault (R-X) 1,973 Ω 4,045 Ω
ITest 2,000 A
Generator Settings
V L1-E 63,509V -120,00° +90°
V L2-E 63,509V 120,00°
V L2-E
V L3-E 18,000V 0,00°
I L1 0,000A 0,00°
V L3-E
I L2 0,000A 0,00° 180° 0°
I L3 2,000A -64,00°
V L1-E
I L3
80,0 V -90° 2,0 A
Binary Inputs
Trip Start Overload
0 0 0
Summary
11 tests passed, 0 tests failed, 0 tests not assessed 100,00% passed
Test passed