0% found this document useful (0 votes)
61 views3 pages

Quickcmc1: Test Module

The document summarizes the results of 6 fault tests conducted on a protection relay. Each test increased the fault impedance and measured the relay's response time. All 6 tests passed with the relay tripping as expected. The longest response time was 0.841 seconds for a 1000 ohm fault. The tests demonstrated the relay could correctly identify and trip for faults up to 4500 ohms within the required time limits.

Uploaded by

Oemar Jie
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
61 views3 pages

Quickcmc1: Test Module

The document summarizes the results of 6 fault tests conducted on a protection relay. Each test increased the fault impedance and measured the relay's response time. All 6 tests passed with the relay tripping as expected. The longest response time was 0.841 seconds for a 1000 ohm fault. The tests demonstrated the relay could correctly identify and trip for faults up to 4500 ohms within the required time limits.

Uploaded by

Oemar Jie
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

QuickCMC1

Test Module
Name: OMICRON QuickCMC Version: 3.00
Test Start: 20-Jan-2019 11:06:36 Test End: 20-Jan-2019 11:09:00
User Name: Manager:
Company:

Test Results

Title: Test 1

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Z-I const. Fault L3-E 50,000 Hz
ZFault 200,0 mΩ 15,00 °
ZFault (R-X) 193,2 mΩ 51,76 mΩ
ITest 2,000 A

Generator Settings
V L1-E 63,509V 0,00° +90°
I L3
V L2-E 63,509V -120,00°
V L3-E 0,800V 120,00°
I L1 0,000A 0,00°
V L1-E
I L2 0,000A 0,00° 180° V L3-E 0°
I L3 2,000A 105,00°
V L2-E

80,0 V -90° 2,0 A

Binary Inputs
Trip Start Overload
0->1 1->0 1->0
0,025s n/a n/a

Title: Test 2

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Z-I const. Fault L3-E 50,000 Hz
ZFault 600,0 mΩ 15,00 °
ZFault (R-X) 579,6 mΩ 155,3 mΩ
ITest 2,000 A

Generator Settings
V L1-E 63,509V -120,00° +90°
V L2-E 63,509V 120,00°
V L2-E
V L3-E 2,400V 0,00°
I L1 0,000A 0,00°
V L3-E
I L2 0,000A 0,00° 180° 0°
I L3 2,000A -15,00°
I L3
V L1-E

80,0 V -90° 2,0 A

Binary Inputs
Trip Start Overload
0->1 1->0 1->0
0,041s n/a n/a
Title: Test 3

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Z-I const. Fault L3-E 50,000 Hz
ZFault 1,000 Ω 15,00 °
ZFault (R-X) 965,9 mΩ 258,8 mΩ
ITest 2,000 A

Generator Settings
V L1-E 63,509V -120,00° +90°
V L2-E 63,509V 120,00°
V L2-E
V L3-E 4,000V 0,00°
I L1 0,000A 0,00°
V L3-E
I L2 0,000A 0,00° 180° 0°
I L3 2,000A -15,00°
I L3
V L1-E

80,0 V -90° 2,0 A

Binary Inputs
Trip Start Overload
0->1 1->0 1->0
0,841s n/a n/a

Title: Test 4

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Z-I const. Fault L3-E 50,000 Hz
ZFault 1,800 Ω 15,00 °
ZFault (R-X) 1,739 Ω 465,9 mΩ
ITest 2,000 A

Generator Settings
V L1-E 63,509V -120,00° +90°
V L2-E 63,509V 120,00°
V L2-E
V L3-E 7,200V 0,00°
I L1 0,000A 0,00°
V L3-E
I L2 0,000A 0,00° 180° 0°
I L3 2,000A -15,00°
I L3
V L1-E

80,0 V -90° 2,0 A

Binary Inputs
Trip Start Overload
0 0 0

Title: Test 5

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Z-I const. Fault L3-E 50,000 Hz
ZFault 2,800 Ω 15,00 °
ZFault (R-X) 2,705 Ω 724,7 mΩ
ITest 2,000 A
Generator Settings
V L1-E 63,509V -120,00° +90°
V L2-E 63,509V 120,00°
V L2-E
V L3-E 11,200V 0,00°
I L1 0,000A 0,00°
V L3-E
I L2 0,000A 0,00° 180° 0°
I L3 2,000A -15,00°
I L3
V L1-E

80,0 V -90° 2,0 A

Binary Inputs
Trip Start Overload
0 0 0

Title: Test 6

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Z-I const. Fault L3-E 50,000 Hz
ZFault 4,500 Ω 15,00 °
ZFault (R-X) 4,347 Ω 1,165 Ω
ITest 2,000 A

Generator Settings
V L1-E 63,509V -120,00° +90°
V L2-E 63,509V 120,00°
V L2-E
V L3-E 18,000V 0,00°
I L1 0,000A 0,00°
V L3-E
I L2 0,000A 0,00° 180° 0°
I L3 2,000A -15,00°
I L3
V L1-E

80,0 V -90° 2,0 A

Binary Inputs
Trip Start Overload
0 0 0

Summary
6 tests passed, 0 tests failed, 0 tests not assessed 100,00% passed