BLDV400
BLDV400
                                                                                                                                                      20301837
IMPORTANT SAFETY INFORMATION                                                                      BLDV7 Series Gas Fireplace
INSTALLER                                                        OWNER
Please leave these instructions with the appliance.              Please retain these instructions for future reference.
           •	 Read this owner’s manual carefully and completely before trying to assemble, operate,
 WARNING
This fireplace is a vented product. This fireplace must be       4.	 Never install the fireplace
properly installed by a qualified service person. The glass          •	 in a recreational vehicle
door must be properly seated and sealed. If this unit is not
                                                                     •	 where curtains, furniture, clothing, or other flam-
properly installed by a qualified service person with glass
                                                                          mable objects are less than 42" from the front, top,
door properly seated and sealed, combustion leakage can
                                                                          or sides of the fireplace
occur.
                                                                     •	 in high traffic areas
CARBON MONOXIDE POISONING: Early signs of carbon
monoxide poisoning are similar to the flu with headaches,
                                                                     •	 in windy or drafty areas
dizziness and/or nausea. If you have these signs, the fire-      5.	 This fireplace reaches high temperatures. Keep children
place may not have been installed properly. Get fresh air            and adults away from hot surfaces to avoid burns or
at once! Have the fireplace inspected and serviced by a              clothing ignition. Fireplace will remain hot for a time after
qualified service person. Some people are more affected              shutdown. Allow surfaces to cool before touching.
by carbon monoxide than others. These include pregnant           6.	 Young children should be carefully supervised when
women, people with heart or lung disease or anemia,                  they are in the same room as the appliance. Toddlers,
those under the influence of alcohol, and those at high              young children and others may be susceptible to acci-
altitudes.                                                           dental contact burns. A physical barrier is recommended
Propane/LP gas and natural gas are both odorless. An                 if there are at risk individuals in the house. To restrict
odor-making agent is added to each of these gases. The               access to a fireplace or stove, install an adjustable
odor helps you detect a gas leak. However, the odor added            safety gate to keep toddlers, young children and other
to these gases can fade. Gas may be present even though              at risk individuals out of the room and away from hot
no odor exists.                                                      surfaces.
                                                                 7.	 Do not modify fireplace under any circumstances. Any
Make certain you read and understand all warnings. Keep
                                                                     parts removed for servicing must be replaced prior to
this manual for reference. It is your guide to safe and proper
                                                                     operating fireplace.
operation of this fireplace.
                                                                 8.	 Turn fireplace off and let cool before servicing, install-
1.	 This appliance is only for use with the type of gas              ing, or repairing. Only a qualified service person should
    indicated on the rating plate. This appliance is not             install, service, or repair the fireplace. Have burner
    convertible for use with other gases unless a certified          system inspected annually by a qualified service
    kit is used.                                                     person.
2.	 For propane/LP fireplace, do not place propane/LP            9.	 You must keep control compartments, burners, and
    supply tank(s) inside any structure. Locate propane/LP           circulating air passages clean. More frequent cleaning
    supply tank(s) outdoors. To prevent performance prob-            may be needed due to excessive lint and dust. Turn off
    lems, do not use propane/LP fuel tank of less than 100           the gas valve and pilot light before cleaning fireplace.
    lbs. capacity.
                                                                 10.	Have venting system inspected annually by a
3.	 If you smell gas
                                                                     qualified service person. If needed, have venting
       •	 shut off gas supply.                                       system cleaned or repaired. Refer to Cleaning and
       •	 do not try to light any appliance.                         Maintenance, Page 44.
       •	 do not touch any electrical switch; do not use any     11.	Keep the area around your fireplace clear of com-
            phone in your building .                                 bustible materials, gasoline, and other flammable
       •	 immediately call your gas supplier from a neighbor’s       vapor and liquids. Do not run fireplace where these
            phone. Follow the gas supplier’s instructions.           are used or stored. Do not place items such as
                                                                     clothing or decorations on or around fireplace.
                                                                                                          Continued on page 4
20301837                                                                                                                    
BLDV7 Series Gas Fireplace                     IMPORTANT SAFETY INFORMATION & Code approval
     service technician to inspect the appliance and replace               Never connect unit to private (non-utility)
     any part of the control system and any gas control which
                                                                           gas wells. This gas is commonly known
     as been submerged in water.
                                                                           as wellhead gas.
19.	 Do not operate fireplace if any log is broken.
20.	 Do not use a blower insert, heat exchanger insert, or
     any other accessory not approved for use with this
     fireplace.
21.	 Do not operate the fireplace with glass door removed,
     cracked, or broken.
Code Approval
Direct Vent type appliances draw all combustion air from
outside of the dwelling through the vent pipe.
These appliances have been tested by CSA and found to
comply with the established standards for DIRECT VENT
GAS FIREPLACE HEATERS in the USA and Canada as
follows:
      LISTED VENTED GAS FIREPLACE HEATER
                  TESTED TO:                                                         !   WARNING
    BLDV400/500: ANSI Z21.88-2009 / CSA 2.33-2009
     BLDV300: ANSI Z21.50b-2009 / CSA 2.22b-2009                                                   HOT GLASS WILL
                                                                                                    CAUSE BURNS.
                       STANDARDS
                                                                                                 DO NOT TOUCH GLASS
A manufactured home (USA only) or mobile home OEM                                                   UNTIL COOLED.
installation must conform with the Manufactured Home
Construction and Safety Standard, Title 24 CFR, Part                                            NEVER ALLOW CHILDREN
3280, or when such a standard is not applicable, the                                               TO TOUCH GLASS.
Standard for Manufactured Home Installations, ANSI/
NCSBCS A225.1, or Standard for Gas Equipped Recre-
ational Vehicles and Mobile Housing, CSA Z240.4.
                                                                                                               20301837
product features                                                                              BLDV7 Series Gas Fireplace
                 FP2073
                 BLDV controls
20301837                                                                                                                     
BLDV7 Series Gas Fireplace                                        pRE-INSTALLATION INFORMATION
                                                               D
                                   Rough
                                   Opening                           M          7" Dia.
                          V        Depth                                            4" Dia.
                                                                                N
                U                     S E
                                                                                                 1/2” or 5/8”
                                                                                                 (13 or 16 mm)
                                                     R - Rough Opening Width
       V
                                     Rough
                              T      Opening
                                     Height
                                                                                             C
                                             Q
                                                               B               F
                                                                                        G
                                                                                                                 L
    Figure 2 -                                                                      I
    Fireplace Specifications and                 O            H                O                             K
                                                                                             J
    Framing Dimensions                                        A
                                                                                        Gas Line
                                                                                        Access
                                                                                                                    20301837
pre-installation information                                                                     BLDV7 Series Gas Fireplace
              wherever cold air could enter the room, with noncombustible material.
              It is especially important to insulate the outside chase cavity between
              the studs and under the floor on which the appliance rests, if the floor
              is above ground level.
20301837                                                                                                                      
BLDV7 Series Gas Fireplace                                                        pRE-INSTALLATION INFORMATION
Fireplace Location
Plan for the installation of your appliance. This includes determining where the unit is to
be installed, the vent configuration to be used, framing and finishing details, and whether
any optional accessories (i.e. blower, wall switch, or remote control) are desired. Consult
your local building code agency to ensure compliance with local codes, including permits
and inspections.
The following factors should be taken into consideration:
•	 Clearance to side-wall, ceiling, woodwork, and windows. Minimum clearances to com-
     bustibles must be maintained.
•	   This fireplace may be installed along a wall, across a corner, or use an exterior chase.
     Refer to Figure 3 for suggested locations.
•	   Location should be out of high traffic areas and away from furniture and draperies due
     to heat from appliance.
•	   Never obstruct the front opening of the fireplace.
•	   Do not install in the vicinity where gasoline or other flammable liquids may be stored.
•	   Vent pipe routing. Refer to Venting section found in this manual for allowable venting
     configurations.
•	   These units can be installed in a bedroom. Refer to National Fuel Gas Code ANSI
     Z233.1/NFPA 54 — (current edition), the Uniform Mechanical Code — (current edition),
     and Local Building Codes for specific installation requirements.
•	   These units can be installed in a bathroom.
                                                                    A	   Flat on Wall
            E            A
                                                                    B	   Cross Corner
                                                  B                 C	   Island**
       Y
                                                                    D	   Room Divider*
                                           X                        E	   Flat on Wall Corner*
                             C
                                                                    F	   Chase Installation
                                                                    Y	   4" Minimum
            D
      Y                                          B
                                                               **	 Island (C) and room divider (D) installation is possible as long
                F                                                  as the horizontal portion of vent system (X) does not exceed
                                                                   20'.
                                                               *	   When you install your fireplace in (D) room divider or (E)
                                                                    flat on wall corner positions (Y), a minimum of 4" clearance
                                               LU584-1              must be maintained from perpendicular wall and front of
                                               Locating unit
                                                                    fireplace.
          Figure 3 -                           2/4/99 djt
          Possible Fireplace Locations
                                                                                                                           20301837
clearances                                                                                              BLDV7 Series Gas Fireplace
Clearances to combustibles
           top opening of fireplace. Mantel shelf shall not exceed 12" maximum depth
           at 13" minimum height from opening.
Wall
                                                                                                                   Combustible
                                                                                                                   Material Area
                                                                  FP2334a
71” Minimum                                                                                1”           156O”
   Ceiling
                                                              Side of Fire-                                     356O”
                                                                                                                        456O”
                                                              place Opening             256O”
                                                                                                                                45°
                                                                                           3”
                                        12” Max.                                                  5”
                                         Depth                    Top View
                                                                                                   6”
                                                                                   Figure 4a -
                                                      13” Min.                     Mantel Clearances
                                                   From Opening             FP2334a
                                                                            BLDV side leg clear
                     6”
                    Min.
FP2333
Figure 4 -
Clearances From The Mantel, Ceiling, and Side Wall
mantel clearances
                           FP2333
NOTE: The combustible        area above the facing must not protrude more than 3/4" from the
                          BLDV mantel clear
facing. If it does, it is considered a mantel and must meet the mantel requirements listed in
this manual.
20301837                                                                                                                              
BLDV7 Series Gas Fireplace                               SECURING FIREPLACE to floor or framing
The fireplace must be secured to the floor and/or to framing studs as shown in Figure 5. Use two
(2) wood screws or masonry/ concrete screws to secure fireplace to the floor. Use four (4) screws
to attach fireplace to framing. The side nailing flanges are 1/2" or 5/8" to accommodate different
wall thickness.
                                                     Drywall Support
                                                     Tabs
                                                     (Do not use for
                                                     framing or header)
                            Nailing Flange
Framing
Screw
Nailing Flange
  Figure 5 -                                                                                       Nailing
  Securing Fireplace to Floor                                                                      Flanges
  and Framing Studs
                                                                                       FP2335
                              Screws
Screw
10                                                                                                           20301837
VENTING INSTALLATION INFORMATION                                                                  BLDV7 Series Gas Fireplace
 WARNING
             Read all instructions completely and thoroughly before attempting installation. Failure
             to do so could result in serious injury, property damage or loss of life. Operation of
             improperly installed and maintained venting system could result in serious injury,
             property damage or loss of life.
             Failure to follow these instructions will                  (25 mm) per 24” (610 mm).
             void the warranty.                                    There must not be any obstruction such as bushes, gar-
                                                                   den sheds, fences, decks or utility buildings within 24”
                                                                   (610 mm) from the front of the termination hood.
                                                                   Do not locate termination hood where excessive snow or
            This fireplace must be vented to the                   ice build up may occur. Be sure to check vent termina-
WARNING
            outside. The venting system must NEVER                 tion area after snow falls, and clear to prevent accidental
            be attached to a chimney serving a                     blockage of venting system. When using snow blowers,
            separate solid fuel burning appliance.                 make sure snow is not directed towards vent termination
            Each gas appliance must use a separate                 area.
            vent system. Do not use common vent                    Location of Vent Termination
            systems.                                               It is imperative the vent termination be located observing
                                                                   the minimum clearances as shown on following page.
             Always maintain minimum clearances around vent systems. The minimum clearances to
             combustibles for horizontal vent pipe are 3" at the top* and 1" at the sides and bottom of the
 WARNING
             vent system until the pipe penetrates the nearest vertical wall (1" required). A 1" minimum
             clearance all around the pipe must be maintained at outside wall and on vertical runs. Do not
             pack the open air spaces with insulation or other materials. This could cause high temperatures
             and may present a fire hazard.
             * Unless the vertical run is 7Z\x feet or higher (top vent units only), the clearances for the
             horizontal run is 1" at the top.
20301837                                                                                                                      11
BLDV7 Series Gas Fireplace                                                                                          VENTING INSTALLATION INFORMATION
                                   D 
                                             E 
                                        V 
                                  L                              C                    B 
                                             B                 V          Fixed
                                                                                                              B         V 
                                                                         Closed
                                                                                      V                    Fixed
                                                                         Ope                    Operable
                                                                            rable                          Closed
                                                          F    V 
                                                                                                                        B 
                                                                    B                                 V             X                           M 
                                                                                           B                 J 
     Figure 6 -                               CFM145a                                                 A 
                                                                                                                                           I         V    K    X 
     Termination Locations
                                              V  VENT TERMINATION                 X  AIR SUPPLY INLET                    AREA WHERE TERMINAL IS NOT PERMITTED 
                                                                                                                          
 1 In accordance with the current CSA-B149 Installation Codes                                              NOTE: 1. Local codes or regulations may require different 		
 2 In accordance with the current ANSI Z223.1/NFPA 54 National Fuel                                        		 clearances.
 Gas Codes                                                                                                 	     2. The special venting system used on Direct Vent Fireplaces 	
 † A vent shall not terminate directly above a sidewalk or paved                                           		 are certified as part of the appliance, with clearances 	
 driveway which is located between two single family 		                                                    		 tested and approved by the listing agency.
 dwellings and serves both dwellings                                                                       	     3. MHSC assumes no responsibility for the improper 		
  only permitted if veranda, porch, deck or balcony is fully open on a                                    		 performance of the appliance when the venting system 	
 minimum 2 sides beneath the floor:                                                                        		 does not meet these requirements.
12                                                                                                                                                                  20301837
Venting INSTALLATION INFORMATION                                                                                   BLDV7 Series Gas Fireplace
        Termination Clearances
        Termination clearances for buildings with combustible and noncombustible exteriors.
        Inside Corner                            Outside Corner                          Alcove Applications*
                                                                                                                       D
                                                                                                              C                 C
                                                                          F=
                             G=                                           Combustible
                             Combustible                                   6" (152 mm)                                 V
                  G
                              6" (152 mm)                                 Noncombustible
                                                          V
                                                                           2" (51 mm)                                      E
                             Noncombustible                                                                        O
                      V       2" (51 mm)                          F
         Balcony -                           Balcony -
         with no side wall                   with perpendicular side wall
                                                                                                          E = Min. 6” (152 mm) for
                                                                                                          non-vinyl sidewalls
                                                                                                          Min. 12” (305 mm) for
                                                                                                          vinyl sidewalls
                                                                                                          O = 8’ (2.4 m) Min.
                            M                                 M                              	   No.
                                                                                             	 of Caps		 DMin.		 CMax.
                             V                                        V
                                                                                             	    1	    3’ (914 mm)	 2 x DActual
                                                                          P                  	    2	    6’ (1.8 m)	  1 x DActual
                                               Combustible &                                 	    3	    9’ (2.7 m)	  2/3 x DActual
             M=                                Noncombustible
             Combustible &
                                                                                             	    4	    12’ (3.7 m)	 1/2 x DActual
             Noncombustible                     M = 24" (610 mm)
                                                                                                 DMin. = # of Termination caps x 3
              12" (305 mm)                      P = 20” (508 mm)
                                                                                                 CMax. = (2 / # termination caps) x DActual       584-15
*NOTE: Termination in an alcove space (spaces open only on one side and with an overhang) is permitted with the dimensions specified for vinyl or
non-vinyl siding and soffits. 1. There must be a 3’ (914 mm) minimum between termination caps. 2. All mechanical air intakes within 10’ (1 m) of a
termination cap must be a minimum of 3’ (914 mm) below the termination cap. 3. All gravity air intakes within 3’ (914 mm) of a termination cap must
be a minimum of 1’ (305 mm) below the termination cap.      Figure 7 -
                                                              Termination Clearances
20301837                                                                                                                                             13
BLDV7 Series Gas Fireplace                                                Venting INSTALLATION INFORMATION
                                                                    How to Use the Vent Graph
T-Lock Pipes
                                                                    The Vent Graph should be read in conjunction with the
When using unitized T-Lock pipe it is not necessary to              following vent installation instructions to determine the re-
use sealant on the joints. The only areas of the venting            lationship between the vertical and horizontal dimensions
system that need to be sealed with high temperature sili-           of the vent system.
cone sealant are the sliding joints of any telescope vent
sections used in the system.                                        1. 	Determine the height of the center of the horizontal
                                                                        vent pipe exiting through the outer wall. Using this di-
To join T-Lock pipes together, simply align both inner and              mension on the Sidewall Vent Graph, Figure 10, locate
outer pipes with the next section. Align the internal beads             the point intersecting with the slanted graph line.
of the female end with the T-channels of the male end.
                                                                    2. 	From the point of this intersection, draw a vertical line
Figure 9
                                                                        to the bottom of the graph.
              Internal
              Beads                T-Channel                        3. 	Select the indicated dimension, and position the fire-
                                                                        place in accordance with same.
                                                                    EXAMPLE A:
                                                                    If the vertical dimension from the floor of the unit is 11’ (3.4
                                                                    m) the horizontal run to the face of the outer wall must not
                                                                    exceed 14’ (4.3 m).
                                                  Arrow
                                                  Indentations      EXAMPLE B:
                                                                    If the vertical dimension from the floor of the unit is 7’ (2.1
                                                                    m), the horizontal run to the face of the outer wall must not
                                                                    exceed 7’ (2.1 m).
                                                                    Refer to Page 18 for requirements for snorkels.
                                           FP2740
                                                                                 40
                                                                                 38
            Female End                 Male End
Figure 9 -                                                                       36
T-Lock Pipe Joints
                                                                                 34
                                                                                       2    4    6   8  10  12 14  16 18  20
                                                                               Horizontal dimension from the finished outside wall
                                    FP2741                                          to the center of the pipe on the fireplace
                                                                   Figure 10 -
                                    T-lock undo                    Rear Wall Venting Graph
14                                                                                        FP2337                          20301837
                                                                                          sidewall vent graph
VentING installation                                                                                    BLDV7 Series Gas Fireplace
          bottom until the flue penetrates the outside wall. A minimum 1" clearance
          all around the flue is acceptable at this point of penetration.
          If the vertical rise is 71/2 ft. or more, only a 1" clearance is needed on top
          of any horizontal run.
          Vertical sections of this vent system require a minimum of 1" clearance to
          combustibles on all sides of the pipe.
12”
  Figure 11 -
  Combustible
  Clearances for Vent
  Pipe
FP2338
                                                   FP2338
                                                   min. vent clear
20301837                                                                                                                       15
BLDV7 Series Gas Fireplace                                                                ventING installation
Vertical Sidewall Application                                   Example: According to the vent graph (Page 15) the
Minimum clearance between vent pipes and combus-                maximum horizontal vent length in a system with a 7Z\x’
tible materials is 3" (76 mm) on top, and 1" (25 mm) on         (2.3 m) rise is 20’ (6 m) and if a 90° elbow is required in
the bottom and sides unless otherwise noted. Refer              the horizontal vent it must be reduced to 17’ (5.2 m).
to Page 15                                                      In Figure 15, dimension A plus B must not be greater than
When vent termination exits through foundations less            17’ (5.2 m)
than 20” (508 mm) below siding outcrop, the vent pipe           •	 The maximum number of 45° elbows permitted per in-
must flush up with the siding.                                      stallation is six (6). These elbows can be installed in
                                                                    either the vertical or horizontal run.
It is best to locate the fireplace in such a way that mini-
                                                                •	 For each 45° elbow installed in the horizontal run, the
mizes the number of offsets and horizontal vent length.
                                                                    length of the horizontal run MUST be reduced by 18”
The horizontal vent run refers to the total length of vent          (457 mm). This does not apply if the 45° elbows are
pipe from the flue collar of the fireplace (or the top of the       installed on the vertical part of the vent system.
Transition Elbow) to the face of the outer wall.                •	 The maximum number of elbow degrees in a system is
Horizontal plane means no vertical rise exists on this por-         270°. Figure 15
tion of the vent assembly.                                      Example:	        Elbow 1	 =	 90°
•	 The maximum number of 90° elbows per side wall in-           	                Elbow 2	 =	 45°
   stallation is three (3). Figure 12                           	                Elbow 3	 =	 45°
•	 If the min. 12" rise with a 90° elbow is fitted directly     	                Elbow 4	 =	 90°
   on top of the first 12" section, the maximum horizontal      	Total angular variation	 =	 270°
   vent run before the termination or a vertical rise is 36”
   (914 mm). Figure 13                                                              90°
•	 If a 90° elbow is used in the horizontal vent run (level                                           B
                                                                          A
   height maintained) the horizontal vent length is re-
   duced by 36” (914 mm). Figures 13 & 14. This does
   not apply if the 90° elbows are used to increase or
   redirect a vertical rise. Figure 12
                                  3 x 90°
                                  Elbows
      Figure 12 -
      Maximum Three (3)                                                                        A + B = 17' (Max.)
      90° Elbows per Instal-
      lation                    12”                                                                 (5.2m)
                                Min.                                                 7'6"
                                                                                   (2.3m)
                                                                                              Figure 14 -
                                                                 FP1178                       Horizontal Run Reduction
                       FP1176
                                                     36" 
                                                  (914mm) 
                 36"                                Max.
              (914mm)                                                                     1                               1
                Max.
                                                                                          2                               2
                                                                1 + 2 + 3 + 4 = 270°
   12”                                                                                    3                               3
(305 mm)                                                                                  4
   Min.                                                                                                                   4
                                                                  Figure 15 -
                                                                                          12”
                                                                  Maximum Elbow
                                                                                          Min.
                                                                  Usage
                         FP1177
     Figure 13 -
     Maximum Horizontal Run with 12" Minimum Rise                                                           FP1180
16 20301837
                      Max 20"
ventING installation                                                                            BLDV7 Series Gas Fireplace
                       7Z\x”
                   (190 mm)                                                                                     X
                                                        FP2293
 Figure 16 -        Fireplace Hearth                               Figure 18 -
 Locate vent opening on wall                                       Horizontal Length
                                                                   Requirement
Step 2
Secure firestop to the inside frame, center in the 9B\," x                                                                        X
9B\," vent opening.
                     VO584-100
Step 3               Vent Opening
                     2/99 djt
Place fireplace into position. Measure the vertical height
(X) required from the base of the flue collars to the center
of the wall opening. Figure 17
Step 4                                                                                                           FP1182
                                                                       Attic Insulation
                                                                       Shield
                                                                       (7DV1AIS)
     1 + 2 + 3 + 4 = 270°
                         1
                                                                 1
                         2
                                                                 2    Upper Floor
                         3
     Figure 24 -                                                 3
     Maximum Elbow       4                                                                                            11”
                                                                 4                                                 (279 mm)
     Usage
                                                                       Ceiling Installation
                            12” Min.
                                                                                                                            FP1029
                                                                             Joist
                                                FP1179
                                                                                                                          Firestop
                                                                                                                          Spacer
20                                                                                                                          20301837
ventING installation                                                                                     BLDV7 Series Gas Fireplace
Horizontal Overhang
                                                                        2 ft. 
                                                                                        2 ft. Min.
                                                                        Min.
                                                                                         Lowest
                                                                                         Discharge
                                                                                         Opening
           	    Roof Pitch	H (feet)                      Termination
           	    Flat to 6/12	      1.0                   Vent
           	 Over 6/12 to 7/12	   1.25                                                                             12
           	 Over 7/12 to 8/12	    1.5                                                    H*                   X
           	 Over 8/12 to 9/12	    2.0
                                                    Storm Collar
           	 Over 9/12 to 10/12	   2.5                                                                                  FP1971
           	 Over 10/12 to 11/12	 3.25
                                                         Flashing
           	 Over 11/12 to 12/12	  4.0
                                                                                 FP1971
                                                                                 Min chimney clearance
                                                 3 #5 Sheet Metal
                                                 Screws per Joint
Sealant
Storm Collar
                                               TWL101a
                     Figure 29 -
                     Roof Flashing
                                                TWL101a
                                                Twist Lock Pipe
                                                2/8/99 djt
20301837                                                                                                                         21
BLDV7 Series Gas Fireplace                                                                fireplace installation
A qualified installer or service person must For propane/LP units, never connect fireplace
                                                               CAUTION
           connect appliance to gas supply. Follow                       directly to the propane/LP supply. This
           all local codes.                                              burner system requires an external regulator
                                                                         (not supplied). Install the external regulator
                                                                         between the burner system and propane/LP
                                                                         supply.
installation items needed
Before installing fireplace and burner system, make sure you have the items listed below.
•	 External regulator 	               •	 Piping (check local codes)	     •	 Sealant (resistant to propane/LP gas)
	 (supplied by installer)	            •	 Equipment shutoff valve*	       •	 Test gauge connection*	
•	 Sediment trap (recommended) 	 •	 Tee joint	                           •	 Pipe wrench
•	 approved flexible gas line with gas connector (if allowed by local codes — not provided)
*	 A CSA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge
connection. Purchase the CSA design-certified equipment shutoff valve from your dealer.
For propane/LP connections only, the installer must supply an external regulator. The external regulator will reduce
incoming gas pressure. You must reduce incoming gas pressure to between 11 and 13 inches of water. If you do not
reduce incoming gas pressure, burner system regulator damage could occur. Install external regulator with the vent
pointing down as shown in Figure 30. Pointing the vent down protects it from freezing rain or sleet.
                                           100 lb. (min)                 Use only new black iron or steel pipe. Internally
                 External                  Propane/LP                    tinned copper or copper tubing can be used
                 Regulator                 Supply Tank
                                                                         per National Fuel Code, Section 2.6.3, providing
                                                               CAUTION
Figure 30 -
External Regulator with Vent Pointing Down
(Propane/LP Only)
                   FP1977
                   external regulator
22                                                                                                               20301837
fireplace installation                                                                                    BLDV7 Series Gas Fireplace
                                                                      CAUTION
                                                                                upstream of the appliance. Union tee and
           piping may make the necessary gas
                                                                                plugged 1/8” NPT pressure tapping point
           connections to this appliance.
                                                                                should be installed upstream of the appliance.
                                                                                Figure 31
NOTE: The gas line connection may be made using 1/2" rigid tubing or an approved flex connector.
Since some municipalities have additional local codes it is always best to consult your local authorities
and the current edition of the National Fuel Gas Code ANSI.Z223.1, NFPA54. In Canada CSA-B149
(1 or 2) Installation Code.
                                                                     CAUTION
of the appliance. Union tee and plugged 1/8" NPT pres-
                                                                                Use pipe joint sealant that is resistant to liquid
sure tapping point should be installed upstream of the
appliance. Figure 31
                                                                                petroleum (LP) gas.
IMPORTANT: Install main gas valve (equipment shutoff
valve) in an accessible location. The main gas valve is for
turning on or shutting off the gas to the fireplace.
Check your building codes for any special requirements for locating equipment shutoff valve to
fireplaces.
Apply pipe joint sealant lightly to male threads. This will prevent excess sealant from going into pipe.
Excess sealant in pipe could result in clogged burner system valve.
We recommend that you install a sediment trap/drip leg in supply line as shown in Figure 31. Locate
sediment trap/drip leg where it is within reach for cleaning. Install in piping system between fuel
supply and burner system. Locate sediment trap/drip leg where trapped matter is not likely to freeze.
A sediment trap collects moisture and contaminants and keeps them from going into the burner
system gas controls. If sediment trap/drip leg is not installed or is installed wrong, burner system
may not run properly.
 Approved Flexible
 Gas Line
                                                                                                      Natural Gas
                                                                                                    From Gas Meter
                                                                                           (4.5" w.c. to 10.5" w.c. Pressure)
                                                                                                      Propane/LP
                                        Tee Joint                                              From External Regulator
           Sediment Trap/Drip Leg                                                           (11" w.c. to 13" w.c. Pressure)
                                      Pipe Nipple
                                                              3"
                                                                 M
                                             Cap                   ini
                                                                         mu
                                                                                m
                                    Figure 31 -
                                    Gas Connection
                                    FP1978
                                    gas connection
20301837                                                                                                                         23
BLDV7 Series Gas Fireplace
                       Millivolt - CHECK GAS PRESSURE and Electrical installation
Electrical Wiring
This fireplace will work without any electrical supply. Electricity is only needed to operate
blower.
NOTE: If installed in mobile home, fireplace must be bolted securely to floor.
           by a qualified, licensed electrician. Main power                  Label all wires before disconnecting when
                                                                             servicing controls. Wiring errors can cause
           must be off when connecting to main electrical
                                                                             improper and dangerous operation.
           power supply or performing service. All wiring
 WARNING
24                                                                                                                20301837
glass removal                                                                                      BLDV7 Series Gas Fireplace
Glass Frame
                  Figure 33 -
                  Removing Glass Frame
CAUTION
                                                                                    FP2339
                   !   WARNING                                                      glass frame
20301837                                                                                                                     25
BLDV7 Series Gas Fireplace                                            REMOTE WALL SWITCH & Blower INSTALLATION
                                                                                        WARNING
may be used with this appliance. Attach the wall switch in a
junction box at the desired location on the wall. Figure 34. Do                                   Do not connect wall switch to (110 V)
not extend beyond the wall switch wire length provided.                                           circuit.
NOTE: Extended lengths of wire may cause the fireplace
not to function properly. Longer length of wire is permitted
if the wire is made out of larger gauge (diameter) wire.
Always check with local code.
                                                                                                                 OPTIONAL REMOTE
                                                                                                                   WALL SWITCH
                                                                                                                            ON
                                                                       ON           RS
                                       PILOT        HI
                                                                                                                            OFF
                                 OFF
ON
                                                         LO   TH
                                                              TP
                                                              TH/TP
                                                                            OFF
      Figure 34 -
                                                                                                                 OPTIONAL REMOTE
      Wiring Diagram for Wall Switch                                                                             CONTROL RECEIVER
                                                                                                                            ON
OFF
26                                                                                                                                  20301837
OPTIONAL FAN/BLOWER SYSTEM                                                               BLDV7 Series Gas Fireplace
3.	  Remove logs.
4.	  Remove grate from engine by lifting up.
5.	  Remove hearth brick and wall brick panels.
6.	  Disconnect the gas line to the valve.
7.	  Remove screws securing engine base to firebox floor and lift engine up
     to remove.
8.	 Two (2) magnetic strips have been supplied to secure each blower
     to the firebox floor. Place on bottom of each blower before installing.                            Magnet
     Figure 36
9.	 The blowers are to be inserted flat through the engine cutout in the fire-             KT503
     box floor. Slide each blower over to the sidewall location. Figure 37
10.	 Turn blowers with discharge vent facing up. Slide the discharge vent so Figure 36 -
     that it is facing up. Slip discharge vent flange under the flange bracket Magnet Installation
     flush against the sidewall. Slide blower side tabs over into side flange.
     Figure 38. The blower is now locked in place.
11.	 Attach the speed control to the underside of the firebox us-                         KT503
     ing the supplied velcro, locating as far to the right or left as
     possible.                                                                            blower magnets
12.	 The thermal sensor clip is located beneath the firebox floor                         11/08
     near the center. Slide the thermal sensor into the clip until
     it snaps in place. Make sure the terminals on the thermal
     sensor are perpendicular to the clip. Figure 39
WARNING: It is important to arrange the blower wire har-
     ness so the wires can not come in contact with blower fan
     blades.
13.	 Connect wiring according to the wiring diagram Figure 40.
14.	 Replace engine in reverse order of removal.
15.	 Plug in the blower.
16.	 Re-install firebrick, grate, logs, and glass door in reverse
     order of removal.
17.	 To test blower operation, set the variable speed blower on
     the LOW setting. Turn the fireplace on high. The blower Engine
     should turn on within 10 minutes.                                Cutout
18.	 If the blower does not turn on, turn the fireplace off and
                                                                       Figure 37 -
     allow cooling. Unplug the blower. Using a jeweler’s style
                                                                       Insert Blowers through
     screwdriver, turn the white dial on the side of the variable
                                                                       Engine Cutout                         KT504
     speed control 1/8 turn counterclockwise. Figure 40. This
     will allow the blower motor to start at the low speed setting
     as the fireplace cycles on and off. Retest the blower.
Finishing
                                                                              KT504
1.	 Re-install the lower access panel.
                                                                              install blower
2.	 To use the blower, turn the knob on the speed control clockwise. The blower should be operating
                                                                              11/08
    at the highest speed. Continue to turn the knob until it reaches the desired speed.
20301837                                                                                                             27
BLDV7 Series Gas Fireplace                                                                OPTIONAL FAN/BLOWER SYSTEM
KT505
                                                        Figure 38 -
                                                        Blower Installation Position
NOTE: Some older units are not equipped with mounting brackets. Velcro and magnets
are used to mount blowers to sidewall and floor.
                                              KT505
                                              install blower
Clip
          thermal
          Sensor
          Figure 39 -                                                               Figure 40 -
          Thermal Sensor Installation                                               Location of White Dial on Speed Control
                                                   Variable                    Thermal
                                                  Fan Control      White
                                                                (Hi Temp)       Sensor
                                                    1      2
                                            OFF                ON
                                                                        (Hi Temp)
                                                                                                     Blower
                                                                         White
                                                                                                     Motor
                        110/115V AC                                                      Black
                         Blower Plug       Black
                                           White                                Blower
                                           Green                                Motor
                                                                                                 White
                                                    Figure 41 -
                                                    Blower Wiring Diagram
                                             SC blower
                                       is equipped  withwiring diagram
                                                          a three-prong  (grounding) plug for
                                             8/08
                                       your protection against shock hazard and should be
                                       plugged directly into a properly grounded three prong
                                       receptacle.
28                                                                                                                        20301837
OPERATING INSTRUCTIONS (Milli-volt)                                               BLDV7 Series Gas Fireplace
                             WARNING
                                       If you do not follow these instruction
                                       exactly, a fire or explosion may result
                                       causing property damage, personal injury
                                       or loss of life.
  A.	 This appliance is equipped with a pilot which must be lit with built-in piezo ignitor while
      following these instructions exactly.
  B.	 BEFORE OPERATING smell all around the appliance area for gas. Be sure to smell next
      to the floor because some gas is heavier than air and will settle on the floor.
  WHAT TO DO IF YOU SMELL GAS:
  	 •	 Turn off all gas to the appliance.
  	 •	 Open windows.
  	 •	 Do not attempt to light any appliance.
  	 •	 Do not touch any electric switch; do not use any phone in your building.
  	 •	 Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's
          instructions.
  	 •	 If you cannot reach your gas supplier, call the fire department.
  C. 	Use only your hand to push in, or turn the gas control knob. Never use tools. If the knob will
      not push in or turn by hand, don't try to repair it. Call a qualified service technician. Force
      or attempted repair may result in a fire or explosion.
  D. 	Do not use this appliance if any part of it has been under water. Immediately call a qualified
      service technician to inspect the appliance and to replace any part of the control system
      and any gas control that has been under water.
 initial lighting
 Purge air from the supply line as follows:                 Never use an open flame to
 	 •	 Open main shutoff valve.                              check for gas leak.
 	 •	 Unscrew main pressure test point.
 	 •	 Leave inlet test screw open until gas comes in.
 	 •	 When gas is flowing, tighten inlet screw immediately.
 leak testing
 1.	 Follow the pipe from the gas supply line connection to the gas valve. Check connection for
     leaks with soap and water mixture.
 2.	 Next check for gas leaks at the burner with soap and water mixture.
 3. 	 Check the pilot for gas leaks with soap and water mixture.
20301837                                                                                                 29
BLDV7 Series Gas Fireplace                                     OPERATING INSTRUCTIONS - Milli-volt
                                                                   WARNING
 You may check for gas leaks with the following methods                       If using a soap and water
 only:                                                                        solution to test for leaks,
                                                                              DO NOT spray solution onto
 	 •	 Soap and water solution
                                                                              control body.
 	 •	 An approved leak testing spray
 	 •	 Electronic sniffer
                                                                     NOTE: Remove any excessive pipe
                                                                     compound from the connections.
     danger
                                         Lighting pilot
              The control has an interlock device that does not allow the lighting of the fireplace
 WARNING
              up to the moment the safety device of the flame has not interrupted the gas flow.
              After that period of time (when the magnet is closed), it is possible to start the
              lighting operation.
              The gas control knob is designed to be operated by hand. DO NOT use any tools
              during this operation. Damaged knobs may result in serious injury.
                                                                                                      OF
      Release and check that pilot continues to
      burn.
                                                                                          PIL
                                                                             Figure 42 -               OT
  If the pilot does not stay lit, repeat steps 1 and 2.                      Pilot Position
                                                                                       FP1935
30                                                                                     control knob pilot 20301837
OPERATING INSTRUCTIONS - milli-volt                                               BLDV7 Series Gas Fireplace
                                       Lighting burner
 main burner switch
 The “ON/OFF/RS” switch for the main burner can be found
 behind door of the fireplace. This switch allows you to turn on
 and to turn off the main burner without using the gas valve knob.
                                                                                 ON
                                                                                       OFF
 Make sure the button is in the “ON” position to light the main
                                                                                      RS
 burner. Figure 43
                                                                                 Figure 43 -
 Lighting the burner                                                             On/Off/RS Switch
 Depress and turn the knob counterclockwise              to the “ON”
 position. Figure 44. It will take less than four (4) seconds for the
 burner to ignite.
ON
                                                                                              OFF
 Pilot position
                                                                                                  P
 Depress and turn knob to pilot position to keep burner off while
                                                                                           ILOT
                                                                                      PIL
 maintaining the pilot light. Figure 45                                                    OT
                                                                             Figure 44 -
                                                                             On Position
                                                                ON
                                                       PILOT 
                                                                               FP1937
                                                            
                                                           
                  Figure 45 -
                                                           F 
                  Pilot Position
                                                                OF
                                                                               control knob on
                                                    PIL
                                                                 OT
                                                          PI L O
                                                                T
                                                   OFF
ON
                                   Figure 46 -     PIL
                                   Off Position                 OT
20301837                                                                                                 31
BLDV7 SIGNATURE        COMMAND - CHECK GAS PRESSURE and Electrical installation
      Series Gas Fireplace
1.	 Check gas type. The gas supply must be the same as
    stated on the appliance’s rating decal. If the gas supply                                          Pressure Inlet
    is different from the fireplace, STOP! Do not install the
    appliance. Contact your dealer immediately.
2.	 To ease installation, a 24" (610 mm) flex line with manual
    shut-off valve has been provided with on this appliance.
    Install and attach 1/2" gas line onto shut-off valve.
3.	 After completing gas line connection, purge air from
    gas line and test all gas joints from the gas meter to
    the fireplace for leaks. Use a solution of 50/50 water
    and soap solution or a gas sniffer.
4. To check gas pressures at valve, turn captured screw
    counter clockwise 2 or 3 turns and then place tubing
    to pressure gauge over test point. Turn unit to high.
                                                                                                               Pilot Adjust-
    Figure 50. After taking pressure reading, be sure and                        Pressure Outlet               ment Screw
    turn captured screw clockwise firmly to reseal. Do not
    over torque. Check test points for gas leaks.                Figure 47 -
                                                                 Signature Command Valve
                                                                   WARNING
                                                                              Do not use open flame to check for gas
                                                                              leaks. FP1909a
                                                                                     signature command valve
                                                                                     alternate view
Electrical Wiring                                                                    8/08
General                                                                      Electrical connections should only
1.	 This fireplace is equipped with the Signature Control                    be performed by a qualified, licensed
    valve which operates on 6 volts. The 6 volt DC adapter                   electrician. Main power must be off when
    plugs into the fireplace junction box A/C power supply.                  connecting to main electrical power supply
    Four (4) “AA” batteries are used for back up during
                                                                  WARNING
    mounted thermostat and/or Signature Command wire-                        Label all wires before disconnecting when
    less controls.                                                           servicing controls. Wiring errors can cause
2.	 The command center control may be mounted on the                         improper and dangerous operation.
    wall with the use of the SCSWEK 15ft. wall mount exten-
    sion kit.
32                                                                                                                  20301837
SIGNATURE COMMAND - Electrical installation                                                   BLDV7 Series Gas Fireplace
                                                                      Figure 48 -
                                                                      Junction Box Wiring Diagram
                                                                               FP1912
COMMAND CENTER WALL INSTALLATION                                WALL SWITCH INSTALLATION
The command center may be mounted on the wall with
                                                                               Junction box wiring
                                                                The wall switch wire connection is located off the 2 ft. wire
the use of the SCSWEK Kit (15ft. cable, junction box, wall                     8/08
                                                                harness from the control box to the command center. Fig-
cover).                                                         ure 49. The connection is labeled “Wall Switch”. Unplug
Mount the junction box provided at the desired location         the male and female connectors and connect the two (2)
on the wall. Do not extend beyond the 15 ft. wire cable         low voltage wires provided. Run wire to desired location
provided. If a longer distance is required, the 15 ft. may be   on wall. Up to 50 ft. of 18 ga. wire may be used if neces-
extended up to 30 ft. maximum by using two (2) SCSWEK           sary. Attach wires to wall switch. Mount the wall switch in
cables plugged together.                                        to junction box and screw on cover.
Route the wire from junction box to lower control area at
bottom of fireplace. Unplug the 12" cable from the com-
                                                                WARNING
mand center. Attach the connector to the pins from wire                   Do not connect wall switch to 110 V
by pushing in to connector making sure to follow the color                circuit.
code on connector. Plug the 15 ft. extension cable into the
2 ft. cable. Remove command center from the fireplace
and plug the other end of the extension cable into the
command center. Snap on wall cover provided and screw
to junction box.
20301837                                                                                                                  33
BLDV7 Series Gas Fireplace                                                                                                     ELECTRICAL INSTALLATION
                                                                        Optional
           To Junction Box
                                                                       AC Module
           in Fireplace
                                                                                                                                                Pilot
                               Optional
                                 Light { White
                                          Black
                                                           Connector
             Optional       White
                                                            Plug in 
             Blower     {   Black
                                Optional { White
                                           Black
                                  Aux.
                                                   Green
                                                                         Connector Pin
                                                                        To Control Board
          Input 300 Watt Max. Each
          Optional A/C Module Replaces 6V Adapter
          When Used
                                                                                                                        RF Receiver
                                                                                                                        ON/OFF Button
                                                                         Control Board
                                              6V AC                                                                        Black / Thermopile
                                              Adapter                                                                      Red / Thermopile
                                                                               Conversion                                  Sensor
                                                                               NG/LP
Ignitor / Sparker
                                                                                                        Plug-in Connector
                                                                                                        Control Board to Command Center
                                                                                                               OFF/LO        LED
                                                                                                                                   ON/HI
              NOTE: Wall switch wires must be con-                                                                                    Master Switch
              nected together if a wall switch is not
              being used.
                                                                                           Plug-in Connector       Command Center
                                                                                           Stepper Motor to                                              Optional
                                                                       Ground              Control Board                                                Wall Switch
                                                                                     DC Power/Green
                                                                       Plug-in Connector
                                                                       Control Board to
                                                                       Solenoid
                                                                                                                             Gas Out
                                                           Gas In
Figure 49 -
                                                                                                                          Pilot Gas Tubing
Signature Command Wiring Diagram
                                                                                                Valve
34                                                                                                                                                            20301837
OPTIONAL FAN BLOWER SYSTEMS                                                                                                    BLDV7 Series Gas Fireplace
                                                                                         WARNING
WARNING
          appliance is equipped with a three-prong                                                 performed by a qualified licensed electrician.
          (grounding) plug for your protection against                                             Main power supply must be turned off before
          shock hazard and should be plugged directly                                              connecting the fan to the main electrical
          into a properly grounded three-prong                                                     power supply or performing service.
          receptacle.
                                   To Junction Box
                                   In Fireplace
                                                                                                                                       Optional AC
                                                          Optional                                                                     Module
                                                          Light      {   WHITE
                                                                         BLACK
                                                         WHITE
                                                 BLACK
                                                          Optional
                                                          AUX        {   BLACK
                                                                         WHITE
                                                                                 GREEN
               Blower (300w Max)
                                                                                                         Connector
                                                                                                         Pin To Contro l Box
Control Box
               Blower (300w Max)
                                          Figure 50 -
                                          BLOTSDVSC Blower Wiring Diagram
                                                                     FP2684
                                                                     BLOTSDVSC fan wiring
20301837                                                                                                                                              35
BLDV7 Series Gas Fireplace                                                OPTIONAL FAN BLOWER SYSTEMS
                                                                            120VAC
                                    Receptacle 
                                                             Junction 
                                                               Box
                                                                         BLACK
                                                                         GREEN
Speed Control
                   Figure 51 -
                   BLOTSDV Blower Wiring Diagram
                                                                                           FP2685
Before installing the blower, wire the receptacle into an
electrical circuit. This should be done before framing the
fireplace. Wire with minimum 60° C wire in accordance
with prevailing codes.               FP2685
                                    BLOTSDV blower wiring
36                                                                                                  20301837
OPERATING INSTRUCTIONS - SIGNATURE COMMAND                                    BLDV7 Series Gas Fireplace
                          WARNING
                                    exactly, a fire or explosion may result
                                    causing property damage, personal
                                    injury or loss of lie.
 A.	 This appliance is equipped with an ignition device which automatically lights the pilot. Refer
     to the instructions.
 B.	 BEFORE OPERATING smell all around the appliance area for gas. Be sure to smell next to
     the floor because some gas is heavier than air and will settle on the floor.
20301837                                                                                               37
BLDV7 Series Gas Fireplace                  OPERATING INSTRUCTIONS - SIGNATURE COMMAND
                             OPERATing INSTRUCTIONS
 1.	 STOP! Read the safety information above.
 2.	 This appliance is equipped with an ignition device which automatically lights the burner. Do not try
     to light the burner by hand.
 3.	 With five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell
     gas, STOP! Follow "B" in the safety information on page 38. If you do not smell gas, go to next step.
 4.	 Press the master switch to the "ON" (-) position. Within eight (8) seconds it will beep once. This
     indicates the system is ready.
 5.	 Press "ON " button. Sparker will spark and pilot flame will light.
 6.	 Once pilot flame is established, the main burner flame will light automatically.
 7.	 If the pilot will not stay lit after several tries, turn the master switch to "OFF" and call your service
     technician or gas supplier.
                             OFF                  Master
                                                  Switch
          OFF             ON
                                                           ON
Command Center
                    FP1913
                                                                                     FP1914
                    Switch box                                                       Pilot w sparker
                    8/08                                                             8/08
38                                                                                                     20301837
SIGNATURE COMMAND SYSTEM OPERATION INSTRUCTIONS                                         BLDV7 Series Gas Fireplace
FEATURES                                                                  RF Receiver          To Thermopile
                                                                          ON/OFF                 To Sensor
Command Center
                                                                                                          To Sparker
•	 Easy Access Function Operation and System Configuration
•	 Operation Confirmation/Fault Diagnostic Indications (LED/       NG/LP
   Buzzer)                                                         Conversion
•	 ON/OFF/HI/Med/Low Operation
•	 Optional Wall Mounting                                      Control Board                        To Command
Control Board                                                                                       Center
                                                                      6 V AC                     To Stepper Motor
•	 Electronic Ignition                                                Adapter
•	 Pilot Lockout safety feature                                                                To Valve
•	 Electric Power Regeneration from Thermopile to save bat-      Command
                                                                                OFF
   tery                                                                         LED
                                                                 Center
•	 6-hour Automatic Shut Down Option                                           ON
•	 Convenient NG/LP Gas Type Conversion                             Master Switch
•	 Standing Pilot/Intermittent pilot Conversion
•	 Previous settings Restoration Ability (Memory Off)
•	 Uninterrupted Operation During Power Outage (Automatic
   Battery Backup)
•	 ON/OFF RF Remote Receiver
•	 Optional Transmitter Learn Capability                                                Battery Door
AC Module Board (Optional, requires TSFSC Remote)                  Figure 52 -
•	 Easy Snap-on Design                                             Signature Command System Components
•	 Embedded Compact 120 VAC Adapter with Auto Battery
   Back up Feature
•	 Remote Controlled 3-step Blower, Lighting, and On/Off Auxiliary AC Outputs FP1917
Transmitter (Optional)                                                         Signature components
	                                                    TSFSC	      TSTSC	    TSMSC	
                                                                               8/08 RTSC	      RMSC
Three Flame Height Settings	                            X	          X	        X	         X	      X
Low battery Indication for Transmitter 	                X	          X	        X	         X	      X
Child Proof Lock-out	                                   X	          X	        X	         X	      X
LCD Backlight	                                          X	          X	        X	         X	      X
Security Codes 16	                                      X	          X	        X	         X	      X
Countdown 6 hr Timer	                                   X	          X	        X	         --	     --
Standard Thermostatic Control Mode	                     X	          X	        --	        X	      --
Smart Mode Thermostat (Auto Flame & Blower Modulation)	 X	          X	        --	        --	     --
Three Brightness Settings for Lights 	                  X	          --	       --	        --	     --
Three Speed Control for Blower	                         X	          --	       --	        --	     --
On/Off Auxiliary	                                       X	          --	       --	        --	     --
Programmable Timer to turn blower on and off	           X	          --	       --	        --	     --
BATTERY INSTALLATION
The Command Center uses four (4) "AA" batteries as back up for power outages. The system can operate for ap-
proximately six (6) months on battery power.
To Install Batteries (not included):
1.	 Press down the battery door tabs and pull out to remove battery door.
2.	 Install the batteries as indicated on Command Center.
3.	 Close battery door by snapping in place.
4.	 When the four (4) batteries are installed the system will operate without power.
5.	 The batteries should be replaced when the LED indicates low battery or at least once a year.
20301837                                                                                                            39
BLDV7 Series Gas Fireplace             SIGNATURE COMMAND SYSTEM OPERATION INSTRUCTIONS
SYSTEM CONFIGURATION/SETUP
All System configuration/setup is done on the Command Center.
NOTE: When using On/Off wall switch, the switch must be in the ON position to perform all configura-
tion set ups at the command center.
Intermittent/Standing Pilot Setup (Default intermittent)
1.	 Holding the ON button on the Command Center while turning on the master switch will toggle be-
    tween standing pilot and intermittent pilot.
2.	 After the above operation, one beep (for standing pilot) or two beeps (for intermittent pilot) will be
    given as confirmation.
Six-hour Safety Shutdown Option (Default ON)
1.	 The system comes preset from the factory with a six (6) hour shutdown from its last command of
    operation. This is done to prevent the fireplace from continuing to operate if unattended. You may
    disable this feature if you wish.
NOTE: By disabling this feature, your fireplace may continue to operate unattended.
2.	 When the master switch is in the ON position (“-”), pressing the ON button and the OFF button
    on the Command Center simultaneously will toggle between enabling and disabling the six-hour
    shutdown option.
3.	 After the above operation, one beep (for enabling the six-hour shutdown option) or two beeps (for
    disabling the six-hour shutdown option) will be given as confirmation.
Remote Transmitter Learn Function (Default OFF)
1.	 The RF receiver button located on the Control Board must be in the on position before the learn
    function can begin. Use paper clip to depress button. One beep for RF receiver ON or two beeps
    for RF receiver OFF will be given as confirmation. Refer to Figure 57 for location.
2.	 After the RF receiver is on, holding the OFF button on the Command Center while turning on the
    master switch will activate the learn function for the transmitter.
3.	 After the above operation, two beeps will be given and the green LED on the Command Center will
    flash for 10 seconds.
4.	 During the 10 seconds, press the OFF button on a transmitter to learn. Another two beeps will be
    given to confirm a successful learning. Refer to transmitter instructions for remote operations.
Shutting Off the Standing Pilot (Temporary Shut Off)
To shut off the standing pilot for service or summer shut down, press and hold the ON button on the
Command Center for 3 seconds when the master switch is in the ON position (“-”) and the main burner
is off.
Note: Pilot will resume the next time system is turned on.
Key Combinations for System Settings
NOTE: When On/Off wall switch is used, it must be in the On position to perform all system setups.
40                                                                                                                 20301837
SIGNATURE COMMAND SYSTEM OPERATION INSTRUCTIONS                                                    BLDV7 Series Gas Fireplace
FUNCTIONS/OPERATION
Turning on the fireplace
1.	 Turn on the master switch and wait for a beep.
2.	 Press the ON button on the Command Center or turn on wall switch. Pilot will light and burner will come on High
    setting or last memory setting (See Turning Off Fireplace below). For memory feature.
Pilot Safety Lockout Function
1.	 If the pilot doesn’t light after sparking for 30 seconds, pilot trial lockout happens. The LED on the Command Center
    flashes Green once every 2 seconds, until reset.
2.	 If the pilot flame is lost during normal operation, the system will try three (3) times to relight after three (3) failures,
    flame loss lockout happens. The LED on the Command Center flashes Red-Green once every 2 seconds, until
    reset.
3.	 Turning the master switch on the Command Center to the off position, then ON again will reset the system.
Flame Height Control
1.	 Press the ON button (on the Command Center) once to turn on the main burner with maximum flame height.
2.	 Press the OFF button to decrease flame height. The first two presses will decrease the flame height to medium and
    low.
3.	 The third press on OFF will turn off the main burner. In standing pilot configuration, the pilot will stay; in intermittent
    pilot configuration, the pilot will be shut off.
Turning the Fireplace Off
There are three ways to turn the fireplace off.
1.	 Flip the master switch to the off (“O”) position. (This will turn the entire system OFF.)
2.	 Press the OFF button to Medium, Low, then Off.
3.	 Hold the OFF button anytime for three seconds or by turning off the wall switch. These two commands of OFF are
    (Memory Off) the system will remember all last settings before turning off. The next time the fireplace is turned on,
    all settings will resume. To reset, change to the desired settings and shut off by using the Memory Off commands
    and the system will be reset to those new settings.
Command Center Operations:
The following functions are available on the Command Center.
	        Function	Operation
	 Power Up	          Flip the master switch to the ON ("_") position to power up the system
	 Fireplace ON	      Press the ON ▲ button on the Command Center or turn on wall switch to turn the fireplace on
	 Fireplace OFF	     Flip the master switch to the OFF ("o") position OR press the OFF ▼ button 3 			
		                   times OR for Memory Off, hold the OFF ▼ button 3 seconds, or turn off wall switch
	 Flame Height Up	   Press the ON ▲ button once to turn on the fireplace with maximum flame height
	 Flame Height Down	 Press the OFF ▼ button to lower the flame height to Medium and Low
burner. Replace logs and check flame again. Save left             Figure 53 -
over rock wool to refresh when cleaning later. Too much           Placement of Rock Wool on Burner
rock wool can disturb the flame and cause sooting on                                FP2340
the glass or logs.                                               WARNING            BDVL base
                                                                            Do not use the entire bag of rock wool
                                                                            to cover the burner. This could cause
                                                                            the flame to burn poorly and may lead to
lOG placement                                                               sooting.
1.	 Place the rear log (#1) in place by sliding it over the
    rear pins on the right and the left.
2.	 Place the right front log (#3) over the burner and grate
    by matching the hole on the bottom of the log with
    the pin on the burner. Also match the cut-out on the
    bottom of the log with the bars on the grate. Note:
    When this log is in place pull towards the front.
3.	 Place the left front log (#5) over the burner and grate
    by matching the holes on the bottom of the log with
    the pin on the burner. Also match the cut-out on the
    bottom of the log with bars on the grate. Note: When
    this log is in place the branch on this log will lay over
    the rear log on the left. Pull log forward.
4.	 Place the right upper log (#2) at an angle toward
    the burner by matching the rectangular notch on the
    bottom of this log with the rectangular protrusion on
    the right front log (#3). The burned side of this log will
    point toward the burner.
LG648
                                                                                 Figure 54 -
                                                                                 Rock wool placement
                                                                                        LG648
                                                                                        BLDV ember place
42                                                                                                                    20301837
final installation                                                                                BLDV7 Series Gas Fireplace
5.	 Place the left upper log (#6) at an angle by matching the rectangular notch on the bottom of this log
    with the rectangular protrusion on the side of the left front log (#5). The split end should point toward
    the front.
6.	 Place the small twig (#4) by having the small pointed end of the log toward the front of the fireplace
    and the fat end resting evenly with the pointed ends of the right and left front logs. Also, the notch
    on this log will match the middle tong on the grate.
                                              Rear Log #1                                     Right Front Log #3
LG530 LG531
LG533
                                                     LG533a
                                                                               Step 4 - Right Upper Log (#2)
                  Step 3 - Left Front Log (#5)
                                                              Small Twig #4
                                                                                      LG533
                                                                                      BLDV rt upper log
                        LG534                                                         8/08
                        Lt upper log
                        8/08
LG534
                                                     LG534
                                                     BLDV small twig
BLDV7 Series Gas Fireplace                                                   cleaning and maintenance
                                                                                                       Sensor
WARNING
                                                                     Figure 56 -
                                                                     Burner Flame Appearance
                                                                                                                       LG647
                                                                                     LG647
                                                                                     BLDV log flames
44                                                                                                                    20301837
cleaning and maintenance                                                                      BLDV7 Series Gas Fireplace
Vent SysteM
The fireplace and venting system should be inspected before initial use and at least annually by a
qualified field service person. Inspect the external vent cap on a regular basis to make sure that no
debris is interfering with the airflow. Inspect entire venting system to ensure proper function.
Glass Door
Thoroughly clean the inside of the glass door after using the fireplace for ten hours. Periodically clean
the glass door as necessary.
When cleaning the glass, remember:
•	 Do not remove the glass when hot. Allow glass to cool before removal.
•	 NEVER use abrasive materials.
•	 Keep children and pets a safe distance away.
•	 Never operate the fireplace without the glass door properly secured.
•	 Never operate the fireplace if the glass is broken.
•	 Replace any glass that is chipped, cracked, or broken. Replacement glass door assemblies MUST
   be supplied by the fireplace manufacturer – No substitute materials may be used.
•	 Handle glass door with care to avoid striking or scratching it on hard objects.
To clean glass door, follow “Glass Removal” procedure outlined in the Final Installation section. Film
deposit on the inside of the glass should be cleaned off using a nontoxic, non-corrosive, non-abrasive,
mild-cleaning solution. Simply apply an adequate amount to the glass and wipe off with a damp cloth.
After all maintenance has been completed, re-install glass door.
Logs
Leave logs installed in the fireplace for cleaning. Vacuum surface of the logs with a brush attach-
ment. If logs must be removed for cleaning, handle carefully by holding gently at each end. Gloves
are recommended to prevent skin irritation from ceramic fibers. If skin becomes irritated, wash gently
with soap and water. Vacuum surface of logs with brush attachment or brush logs with a soft bristle
brush (i.e. clean, dry paintbrush). To place logs back in the fireplace, see “Log Placement” found in
the Final Installation section.
NOTE: Do not use fluids to clean ceramic fiber logs.
Rock wool
Replace or add rock wool as required following installation instructions in the Final Installation sec-
tion of this manual.
20301837                                                                                                             45
BLDV7 Series Gas Fireplace                                                                   troubleshooting
2.	 Pilot will not stay lit A.	 Defective thermocouple       A.	 Check that thermocouple flame impinges on thermo-
    after carefully follow-                                      couple. Clean and/or adjust pilot for maximum flame
    ing lighting instruc-                                        impingement. Ensure that the thermocouple connec-
    tions.                                                       tion at the gas valve is fully inserted and tight.
                                                             	 Disconnect the thermocouple from the valve, place
                                                                 one millivolt lead wire on the tip of the thermocouple
                                                                 and the other meter lead wire on the thermocouple
                                                                 copper lead. Start the pilot and hold the valve knob in.
                                                                 If the millivolt reading is less than 15 mV, replace pilot
                                                                 assembly.
                            B.	 Defective valve              B.		If thermocouple is producing more than 15 mV, replace
                                                                 faulty valve.
3.	 Pilot burning, valve     A.	 Defective switch, wall      A.	 Check switch and wire for proper connection. Place
    knob turned to “ON”,         switch, remote control or       jumper wires across terminals of switch. If burner
    switch is turned to          wire                            comes on, replace defective switch.If the switch is OK,
    “ON” or “RS”, but                                            repeat the same procedure on remote control If burner
    burner will not ignite.	                                     comes on, replace remote control.
                                                             	 Place jumper wire across wire at gas valves (terminals
                                                                 marked TH and TP/TH). If burner comes on, wires are
                                                                 faulty or connections are bad. Replace wire.
                            B.	 Pilot flame too small        B.		If pilot flame is not close enough to the thermopile,
                                                                 adjust pilot flame.
                            C.	 Defective or malfunction-    C.		Check thermopile wire connections to make sure
                                ing thermopile                   all are tight and that the thermopile is fully inserted
                                                                 into pilot assembly. Check thermopile with a millivolt
                                                                 meter. Connect leads to TP and TP/TH terminals on
                                                                 the control valve. If meter reading is below 325 mV,
                            D.	 Defective valve                  replace pilot assembly.
                                                             D.		Turn valve knob to “On” and switch to “ON.” Take a
                                                                 reading at the thermopile leads (TP & TP/TH) on the
                                                                 valve. If the meter reads greater than 175 mV and the
                                                                 burner does not light, replace defective valve.
46                                                                                                              20301837
troubleshooting                                                                            BLDV7 Series Gas Fireplace
5.	 The pilot and main     A.	 Inner vent pipe leaking       A.	 Check for flue product leak. Replace defective pipe
    burner extinguish          exhaust gases back into           section.
    while in operation	        system	
                           B.	 Horizontal vent improperly
                               pitched	                      B.	 Check horizontal-venting piping is running upward 1/4"
                                                                 per foot. Do not run the pipe level or downward.
                           C.	 Improper vent cap installa-   C. Check for proper installation and freedom from debris
                               tion                              or blockage.
6.	 Glass Soots	           A.	Flame impingement on logs	 A. Install log set per the instructions
                                                         	 Inspect the injector and air intake area. Make sure
                                                            this area does not have any blockage from debris and
                                                            clean.
                                                         	 Check gas supply.
7.	 Flame burn blue        A.	Insufficient oxygen being      A.	Ensure that the vent cap is installed properly and free
    and lifts off burner      supplied	                         of debris. Ensure that the vent system joints are tight
    (ghosting)                                                  and have no leaks. Ensure that no debris has been
                                                                blocking the inner air intake at the bottom back of the
                                                                combustion chamber. Ensure that the glass is properly
                                                                secure and latch.
20301837                                                                                                               47
BLDV7 Series Gas Fireplace                                                                                             troubleshooting
                                                                                                                          Sparking is happening
                                No sparking on           C      Check pilot         Check                 Go through      elsewhere (under the
                                the pilot                       connections         grounding                 B           pilot), re-install/replace
                                                                                                                          the pilot
                                              FP1911
                                              troubleshoot sc
                                              8/08
48                                                                                                                                         20301837
REPLACEMENT PARTS                                                                BLDV7 Series Gas Fireplace
	FIREBOX COMPONENTS
	Ref.	   Description	Qty.	                                   BLDV300	        BLDV400	          BLDV500
	 1.	    Junction Box Assy (not shown)	            1	       26D2128K	        26D2128K	        26D2128K
	 2.	    Sheet Metal Base	                         1	
                                                 743000      20302194	        74D0514	         74D0515
	 3.	    Glass Frame Assy	                       BLDV 7 parts20301034	
                                                   1	                        74D0096K	        74D0211TK
	 4.	    Control Cover	                            1	        20302002	       74D0038K	         74D0119
		       Accessories / Field Installed Options
	 5.	    T-Stat Blower w/ Speed Control	           1	      BLOTBLDV	      BLOTBLDV	           BLOTBLDV
	 5.	    SCS Blower w/ Speed Control & Time Delay	 1	    BLOTBCDVSC	     BLOTBCDVSC	         BLOTBCDVSC
	 6.	    Decorative Mesh Glass Cover	              1	     BLDV300SD	      BLDV400SD 	         BLDV500SD
	 7.	    Firebrick Set - Cottage Clay	             1	    FBBLDV300CC	    FBBLDV400CC	        FBBLDV500CC
	 7.	    Firebrick Set - Cottage Red	              1	    FBBLDV300CR	    FBBLDV400CR	        FBBLDV500CR
	 7.	    Firebrick Set - Vintage Brown	            1	    FBBLDV300VB	    FBBLDV400VB	        FBBLDV500VB
20301837                                                                                                  49
BLDV7 Series Gas Fireplace                                         REPLACEMENT PARTS
7 9
                             10
                                                                  11,12,13,14
                                      743000
                                      BLDV millivolt parts
50                                                                                 20301837
REPLACEMENT PARTS                                                         BLDV7 Series Gas Fireplace
Accessories
	 11.	 Thermostatic Remote Control	   1	    RCST / RCT / RCSTEB / RCSITE / WWTD
	 12.	 Remote Control On/Off	         1	        RCB / RCBE / RCMT / WMTD
	 13.	 Wall Switch Kit	               1	                   MVWS	
	 14.	 Wall Thermostat Kit	           1	                     WT
	 15.	 Forged Andiron 8C\v	           1	                   FAI83/4
20301837                                                                                         51
BLDV7 Series Gas Fireplace                                                      REPLACEMENT PARTS
                             1
                                                      2
      3
                                                                                    5
               6
                                                                                        8
                                            7
12
                                                          13, 14, 15, 16, 17
                     9
                                                                               20
                                      743000
                                      BLDV SC parts
52                                                                                          20301837
REPLACEMENT PARTS                                                                            BLDV7 Series Gas Fireplace
NOTE: TSFSC must be used with SCS A/C Module to control lights,
blower and aux.
20301837                                                                                                               53
BLDV7 Series Gas Fireplace                                         REPLACEMENT PARTS
logs 	
                             5             1
                  6
                                                               2
54                                                                             20301837
VENTING COMPONENTS                                                                                        BLDV7 Series Gas Fireplace
VERTICAL VENTING
         3/10/10 T-lock
     2/25/99 djt
           BLDV7 Series Gas Fireplace
20301837                          57
Requirements for the Commonwealth of                               of eight (8) feet above grade directly in line with the exhaust
BLDV7 Series Gas Fireplace                                         vent terminal for the horizontally vented gas fueled heating
Massachusetts
                                                                   appliance or equipment. The sign shall read, in print size no
This product must be installed by a licensed plumber or            less than one-half (1/2) inch in size, “GAS VENT DIRECTLY
gas fitter when installed within the Commonwealth of               BELOW, KEEP CLEAR OF ALL OBSTRUCTIONS”.
Massachusetts.
                                                                   Inspection
Note Regarding Vented Products
                                                                   The state or local gas inspector of the side wall horizontally
Flex line installation must not exceed 36 inches and must          vented gas fueled equipment shall not approve the
have a T shutoff valve.                                            installation unless, upon inspection, the inspector observes
Any residence with a direct vent product must have a CO            carbon monoxide detectors and signage installed in
detector installed in the residence.                               accordance with the provisions of 248 CMR 5.08(2)(a)1
Installation of the fireplace or vented gas log in the State       through 4.
of Massachusetts requires the damper to be permanently             Exemptions
removed or welded in the fully open position.
                                                                   The following equipment is exempt from 248 CMR
In addition, neither a naturally vented gas log nor a vent-        5.08(2)(a)1 through 4:
free product may be installed in a bedroom or bathroom in
the State of Massachusetts.                                        •	 The equipment listed in Chapter 10 entitled “Equipment
                                                                        Not Required To Be Vented” in the most current edition
All gas fitting and installation of this heater shall only be
                                                                        of NFPA 54 as adopted by the Board; and
done by a licensed gas fitter or licensed plumber.
                                                                   •	   Product Approved side wall horizontally vented gas
For all side wall horizontally vented gas fueled equipment              fueled equipment installed in a room or structure
installed in every dwelling, building or structure used in              separate from the dwelling, building or structure used
whole or in part for residential purposes, including those              in whole or in part for residential purposes.
owned or operated by the Commonwealth and where the
side wall exhaust vent termination is less than seven (7) feet     MANUFACTURER REQUIREMENTS
above finished grade in the area of the venting, including but     Gas Equipment Venting System Provided
not limited to decks and porches, the following requirements
                                                                   When the manufacturer of Product Approved side wall
shall be satisfied:
                                                                   horizontally vented gas equipment provides a venting
Installation of Carbon Monoxide Detectors                          system design or venting system components with the
At the time of installation of the side wall horizontal vented     equipment, the instructions provided by the manufacturer
gas fueled equipment, the installing plumber or gas fitter         for installation of the equipment and the venting system
shall observe that a hard wired carbon monoxide detector           shall include:
with an alarm is installed on each additional level of the         •	 Detailed instructions for the installation of the venting
dwelling, building or structure served by the side wall               system design or the venting system components; and
horizontal vented gas fueled equipment. It shall be the
                                                                   •	 A complete parts list for the venting system design or
responsibility of the property owner to secure the services
                                                                      venting system.
of qualified licensed professionals for the installation of hard
wired carbon monoxide detectors.                                   Gas Equipment Venting System NOT Provided
In the event that the side wall horizontally vented gas fueled     When the manufacturer of a Product Approved side wall
equipment is installed in a crawl space or an attic, the hard      horizontally vented gas fueled equipment does not provide
wired carbon monoxide detector with alarm and battery              the parts for venting the flue gases, but identifies “special
back-up may be installed on the next adjacent floor level.         venting systems”, the following requirements shall be
                                                                   satisfied by the manufacturer:
In the event that the requirements of this subdivision can not
be met at the time of completion of installation, the owner        •	 The referenced “special venting system” instructions
shall have a period of thirty (30) days to comply with the            shall be included with the appliance or equipment
above requirements; provided, however, that during said               installation instructions; and
thirty (30) day period, a battery operated carbon monoxide         •	 The “special venting systems” shall be Product
detector with an alarm shall be installed.                            Approved by the Board, and the instructions for that
Approved Carbon Monoxide Detectors                                    system shall include a parts list and detailed installation
                                                                      instructions.
Each carbon monoxide detector as required in accordance
with the above provisions shall comply with NFPA 720 and           A copy of all installation instructions for all Product Approved
ANSI/UL 2034 listed and IAS certified.                             side wall horizontally vented gas fueled equipment, all
                                                                   venting instructions, all parts lists for venting instructions,
Signage                                                            and/or all venting design instructions shall remain with
A metal or plastic identification plate shall be permanently       the appliance or equipment at the completion of the
mounted to the exterior of the building at a minimum height        installation.
58                                                                                                                     20301837
              Limited lifetime warranty policy
                                         BLDV7 Series Gas Fireplace
Lifetime Warranty
The following components are warranted for life to the original owner, subject to proof of purchase: Firebox,
Combustion Chamber, Heat Exchanger, Grate and Stainless Steel Burners.
Five Year Warranty
The following components are warranted five (5) years to the original owner, subject of proof of purchase:
Ceramic Fiber Logs.
Basic Warranty
MHSC warrants the components and materials in your gas appliance to be free from manufacturing and
material defects for a period of two years from date of installation. After installation, if any of the components
manufactured by MHSC in the appliance are found to be defective in materials or workmanship, MHSC will,
at its option, replace or repair the defective components at no charge to the original owner. MHSC will also
pay for reasonable labor costs incurred in replacing or repairing such components for a period of two years
from date of installation. Any products presented for warranty repair must be accompanied by a dated proof
of purchase.
This Limited Lifetime Warranty will be void if the appliance in not installed by a qualified installer in accor-
dance with the installation instructions. The Limited Lifetime Warranty will also be void if the appliance is not
operated and maintained according to the operating instructions supplied with the appliance, and does not
extend to (1) firebox/burner assembly damage by accident, neglect, misuse, abuse, alterations, negligence
of others, including the installation thereof by unqualified installers, (2) the costs of removal, reinstallation or
transportation of defective parts on the appliance, or (3) incidental or consequential damage. All service work
must be performed by an authorized service representative.
This warranty is expressly in lieu of other warranties, express or implied, including the warranty of merchant-
ability of fitness for purpose and of all other obligations or liabilities. MHSC does not assume for it any other
obligations or liabilities in connection with sale or use of the appliance. It states that do not allow limitations on
how long an implied warranty lasts, or do not allow exclusion of indirect damage, those limitations of exclusions
may not apply to you. You may also have additional rights not covered in the Limited Lifetime Warranty.
MHSC reserves the right to investigate any and all the claims against the Limited Lifetime Warranty and decide
upon method of settlement.
IF WARRANTY SERVICE IS NEEDED...
1.	 Contact your supplier. Make sure you have your warranty, your sales receipt and the model/
    serial number of your MHSC product.
2.	 DO NOT ATTEMPT TO DO ANY SERVICE WORK YOURSELF.
20301837                                                                                                           59
               Based on CSA P.4.1-09
            Efficiency Ratings
	     Model	EnerGuide Ratings
		               Fireplace Efficiency (%)
	 BLDV300NSC7	              tbd
	 BLDV300PSC7	             64.2
	 BLDV400NV7	              63.8
	 BLDV400PV7	              60.2
	 BLDV400NSC7	
       Recherchez dans la  68.1
                              brochure
	 BLDV400PSC7	             62.8
     les caractéristique de rendement
	 BLDV500NV7	              61.1
        énergétique de foyer
	 BLDV500PV7	              64.9
                                au gaz
	 BLDV500NSC7	   Énerguide 64.1
             Selon CSA   P.4.1-09
            Based on CSA P.4.1-09
	 BLDV500PSC7	             67.9
                       MHSC
       149 Cleveland Drive • Paris, Kentucky 40361
                    www.mhsc.com