QCM-PPDM Portable partial discharge monitor for transformers and GIS QCM-PPDM Portable partial discharge monitor for

QCM-PPDM Portable partial discharge monitor for transformers and GIS


QCM-PPDM
TECHNICAL SPECIFICATIONS Portable partial discharge monitor for transformers and GIS
Power supply Voltage range 90 to 264 VAC, 47-63 Hz; 40 to 290 VDC universal supply
Supply current 110 mA @ 230 VAC
Power 70 W

MCU (Master
Control Unit)
Input 6 UHF channels
1 additional channel for noise antenna
Smart and easy CBM Handy system for precise assessment
Outputs Alarm indications on the screen: - PD fault alarm - PD alarm
- PD warning alarm - System status indicator
of partial discharge during testing,
UHF sensors
MMI

Mounting
LCD display with full touch interface

Internal or External
commissioning and periodic inspections
(optional) Output Communicates to portable Full characterization and localization of partial discharge faults to determine the severity of
l

Bandwidth Wideband 300 - 1500 MHz PD and help in scheduling maintenance


Sensitivity > 6 mm, < 5pC
Very rapid and easy deployment enables maximum time for condition assessment of assets
l
Remote SMARTSUB Operating system Windows XP / Windows 7 compatible
software
Max monitoring locations 100+ Robust and rugged design to maximize portable operation life and support inspections /
l

Memory 1GB, upgradable (if required) testing for extended period of time (24 hours up to 12 months)
Min size for installtion 20 MB
System alarms System fault, channel fault
Accurate fault detection improves reliability of HV testing ensuring safe and stable HV
l

apparatus installed in substations


PD alarms / PD warning Gradient, PD Trend

Performance Sample rate 15.4 KS/s per channel


Total of 107.5 KS/s for 7 channels (simultaneous sampling) Product Summary
Data storage 16 GB Description A self sufficient and portable PDM system
Clock 1.2 GHz for rapid monitoring and analysis of partial discharge in
Time synchronization Yes gas insulated switchgear (GIS) and power
Noise gating coincidence filters Yes transformers. The system is field operated, touch
Comms Ethernet ports - external RJ45 (10/100 Mbps) screen based and gives engineers the tools required
USB One port to facilitate firmware upgrade, configuration upgrade and manual for diagnosing partial discharge with limited or no
download of data access to the main PDM infrastructure.
l Allows the operator to have l Excellent interference immunity for
GPRS Optional
confidence in the reliability and PD measurement under difficult Application Used for low-cost, high performance
Environmental Ambient operating temperature -25ºC to +55ºC continued operation of the plant conditions periodic online and offline PD testing on HV insulating
Storage temperature -25ºC to +75ºC
l Extends residual life of aging plant l Usable for HV GIS commissioning system of GIS and power transformers in transmission
Humidity 5 - 95% non-condensing
and defers capital costs tests installations, power plants and large industrial
Enclosure rating NEMA IP66
consumers. The information gained from the system
Siesmic IEEE C37.98 (Seismic Testing of Relays) l Implementation of efficient, condition- l Retrofits to most major GIS and may be used for condition based maintenance
Environmental test compliance BS EN60068-2-2, BS EN60068-2-1, BS EN60068-2-78 based maintenance strategies transformers decisions.
Vibration test compliance BS EN68-2-6, BS EN68-2-27, BS EN68-2-29
l HV record mode, versatile sync, PD testing and analysis whilst installation and
Immunity EMC test compliance Confirms to relevant specifications for monitoring / control equipment in HV
superior data review method commissioning of HV GIS and transformers.
substations.
BS EN55022 (:2006); BS EN61000-3-2 to -3-3, BS-EN61000-4-2 to -4-6, Quality testing for PD during or after assembling or
BS EN61000-4-8, BS EN61000-4-11, BS EN61000-4-18; IEC 60255-5,
IEC 61180-1 manufacturing of GIS and transformers.
About QUALITROL®
Others EMI / RFI immunity Established in 1945, with continual improvement at the core of our business, QUALITROL® provides smart utility asset Lab measurements of PD on any insulating material for
condition monitoring across the globe. We are the largest and most trusted global leader for partial discharge monitoring,
Mechanical Dimensions and weight 508 mm x 355 mm x 254 mm [20” x 14” x 10”]. 17 kg [37.5 lbs] scientific and research laboratories.
asset protection equipment and information products across generation, transmission and distribution. At QUALITROL®
Display 12” touch screen, (1024 x 768). Rotary / push button we are redefining condition monitoring technology for Electric utilities assets.
©2014 QUALITROL® Company LLC, an ISO 9001 system certified company. QUALITROL is a registered trademark and OTIWTI is a trademark of QUALITROL® Company LLC.
All trademarks are properties of their respective companies, as noted herein. All rights reserved. Information subject to change without notice. PD-D27-10L-02E.

Email: info@qualitrolcorp.com
www.qualitrolcorp.com www.qualitrolcorp.com
QCM-PPDM Portable partial discharge monitor for transformers and GIS

Handy system for precise l


All testing functions integrated into a single, hand-carry system (17kg [37.5 Intelligent customizable Need based customizable reports created automatically in a single
l
System software - LCD display with full touch interface
assessment of partial discharge lbs]) in a compact enclosure with trolley wheels reporting document. These reports indicate possible courses of action for customers
during testing, commissioning l
Wideband measurement across the frequency range of 300 - 1500 MHz Fast and easy access of data in generating reports
l Key features
and periodic inspections l
Clean, intuitive interface
l
Higher data acquisition rate of 15400 samples per second
Smart and quick real time Programmable alarm criteria and rule engines
l
with QWERTY touch
l
UHF technology based proven (for more than 20 years) hardware and
software in identifying partial discharge alarming / alerting mechanism Facility to send alarms / warnings to local user interface
l keyboard
Real-time monitoring of events with time accuracy of 1 millisecond
l l
Display up to 6 UHF
Full characterization and l
Interpretation is based on multiple artificial neural network classification of channels at once
localization of partial discharge events Expandable and field upgradable Expansion of internal storage to 32 GB with ability to use removable /
l
l
View live and recorded
faults to determine the severity l
A reference library from the historic PD data of the same asset stored into without reconfiguration portable media e.g. USB memory stick for backup
of PD and help in scheduling data as POW, PRPD, STT,
real-time database (time stamped events for up to ten years) 2 GB program memory capable of being upgraded if required
l

maintenance history archive and event


l
Ability to detect multiple PD sources simultaneously Supports the addition of future client applications
l

archive
l
Helps in approximate localization of partial discharge by amplitude Facility to link other portables to expand monitoring capabilities
l
l
Easy configuration of all
comparison
parameters
Other key benefits Designed to meet highest security standards, including NERC cyber-security
l

Very rapid and easy deployment l


Pre-installed software - no installation required on site standards l
Built-in self diagnostics
enables maximum time for l
Easy configuration of system (offline / online) using touch screen interface Built-in time synchronization through NTP / SNTP
l

condition assessment of assets l


Sensors can be fitted to any available inspection hatch or manhole as a Provides timely information where needed through its multiple
l

retrofit communication methods (Ethernet, USB)


l
Require only one field engineer / operator with basic knowledge of partial Superior safety in high voltage test setups
l

discharge
Real-time display of
up to 6 UHF channels
Robust and rugged design to l
IP66 rated highly protective case
maximize portable operation life l
Built-in display (no separate laptop) helps in putting system in any
and support inspections / testing environmental condition for longer time
for extended period of time (24 IP-66 rated highly protective case
l
16 GB data storage sufficient to store PD events continuously for 12 months
hours up to 12 months) with trolley wheels
l
Facility to store data into external storage further enhances data storage
capacity
Flight-friendly and lightweight system
(17 kg [37.5 lbs]) and easy to operate
Accurate fault detection l
Outstanding sensitivity and unique accuracy (75 dBm / 5pC) of UHF
by one person
improves reliability of HV testing measurements
ensuring safe and stable HV l
In-built sensitivity of -75 dBm enables better PD analysis
apparatus installed in l
Noise gating by external signal antenna (optional)
substations
l
Cross channel coincidence gating

HVDC compatibility saves cost of l


Live stream data recording up to 3 days
buying different PD testing l
Higher sampling rate (15.4 kS/s per channel) improves the chances of PD
equipment for HVDC apparatuses detection

Advanced HMI provisions l


In-built LCD screen with touch screen based interface
(SMARTSUB Software - intelligent l
Easy to add / modify / delete substation / site location
data handling, display and l
2D and 3D display of PD signals in multiple formats (Single Cycle, Peak Hold,
interpretation)
PRPD and STT)
l
Automatic self-check of PDM with faults logged and alarmed Easy configuration
l
Trend analysis facility on stored PD data of all parameters
l
State of the art data export function for PD results

Minimal installation and Smart inspection... ...from the world leader in PDM

www.qualitrolcorp.com
QCM-PPDM Portable partial discharge monitor for transformers and GIS

Handy system for precise l


All testing functions integrated into a single, hand-carry system (17kg [37.5 Intelligent customizable Need based customizable reports created automatically in a single
l
System software - LCD display with full touch interface
assessment of partial discharge lbs]) in a compact enclosure with trolley wheels reporting document. These reports indicate possible courses of action for customers
during testing, commissioning l
Wideband measurement across the frequency range of 300 - 1500 MHz Fast and easy access of data in generating reports
l Key features
and periodic inspections l
Clean, intuitive interface
l
Higher data acquisition rate of 15400 samples per second
Smart and quick real time Programmable alarm criteria and rule engines
l
with QWERTY touch
l
UHF technology based proven (for more than 20 years) hardware and
software in identifying partial discharge alarming / alerting mechanism Facility to send alarms / warnings to local user interface
l keyboard
Real-time monitoring of events with time accuracy of 1 millisecond
l l
Display up to 6 UHF
Full characterization and l
Interpretation is based on multiple artificial neural network classification of channels at once
localization of partial discharge events Expandable and field upgradable Expansion of internal storage to 32 GB with ability to use removable /
l
l
View live and recorded
faults to determine the severity l
A reference library from the historic PD data of the same asset stored into without reconfiguration portable media e.g. USB memory stick for backup
of PD and help in scheduling data as POW, PRPD, STT,
real-time database (time stamped events for up to ten years) 2 GB program memory capable of being upgraded if required
l

maintenance history archive and event


l
Ability to detect multiple PD sources simultaneously Supports the addition of future client applications
l

archive
l
Helps in approximate localization of partial discharge by amplitude Facility to link other portables to expand monitoring capabilities
l
l
Easy configuration of all
comparison
parameters
Other key benefits Designed to meet highest security standards, including NERC cyber-security
l

Very rapid and easy deployment l


Pre-installed software - no installation required on site standards l
Built-in self diagnostics
enables maximum time for l
Easy configuration of system (offline / online) using touch screen interface Built-in time synchronization through NTP / SNTP
l

condition assessment of assets l


Sensors can be fitted to any available inspection hatch or manhole as a Provides timely information where needed through its multiple
l

retrofit communication methods (Ethernet, USB)


l
Require only one field engineer / operator with basic knowledge of partial Superior safety in high voltage test setups
l

discharge
Real-time display of
up to 6 UHF channels
Robust and rugged design to l
IP66 rated highly protective case
maximize portable operation life l
Built-in display (no separate laptop) helps in putting system in any
and support inspections / testing environmental condition for longer time
for extended period of time (24 IP-66 rated highly protective case
l
16 GB data storage sufficient to store PD events continuously for 12 months
hours up to 12 months) with trolley wheels
l
Facility to store data into external storage further enhances data storage
capacity
Flight-friendly and lightweight system
(17 kg [37.5 lbs]) and easy to operate
Accurate fault detection l
Outstanding sensitivity and unique accuracy (75 dBm / 5pC) of UHF
by one person
improves reliability of HV testing measurements
ensuring safe and stable HV l
In-built sensitivity of -75 dBm enables better PD analysis
apparatus installed in l
Noise gating by external signal antenna (optional)
substations
l
Cross channel coincidence gating

HVDC compatibility saves cost of l


Live stream data recording up to 3 days
buying different PD testing l
Higher sampling rate (15.4 kS/s per channel) improves the chances of PD
equipment for HVDC apparatuses detection

Advanced HMI provisions l


In-built LCD screen with touch screen based interface
(SMARTSUB Software - intelligent l
Easy to add / modify / delete substation / site location
data handling, display and l
2D and 3D display of PD signals in multiple formats (Single Cycle, Peak Hold,
interpretation)
PRPD and STT)
l
Automatic self-check of PDM with faults logged and alarmed Easy configuration
l
Trend analysis facility on stored PD data of all parameters
l
State of the art data export function for PD results

Minimal installation and Smart inspection... ...from the world leader in PDM

www.qualitrolcorp.com
QCM-PPDM Portable partial discharge monitor for transformers and GIS

Handy system for precise l


All testing functions integrated into a single, hand-carry system (17kg [37.5 Intelligent customizable Need based customizable reports created automatically in a single
l
System software - LCD display with full touch interface
assessment of partial discharge lbs]) in a compact enclosure with trolley wheels reporting document. These reports indicate possible courses of action for customers
during testing, commissioning l
Wideband measurement across the frequency range of 300 - 1500 MHz Fast and easy access of data in generating reports
l Key features
and periodic inspections l
Clean, intuitive interface
l
Higher data acquisition rate of 15400 samples per second
Smart and quick real time Programmable alarm criteria and rule engines
l
with QWERTY touch
l
UHF technology based proven (for more than 20 years) hardware and
software in identifying partial discharge alarming / alerting mechanism Facility to send alarms / warnings to local user interface
l keyboard
Real-time monitoring of events with time accuracy of 1 millisecond
l l
Display up to 6 UHF
Full characterization and l
Interpretation is based on multiple artificial neural network classification of channels at once
localization of partial discharge events Expandable and field upgradable Expansion of internal storage to 32 GB with ability to use removable /
l
l
View live and recorded
faults to determine the severity l
A reference library from the historic PD data of the same asset stored into without reconfiguration portable media e.g. USB memory stick for backup
of PD and help in scheduling data as POW, PRPD, STT,
real-time database (time stamped events for up to ten years) 2 GB program memory capable of being upgraded if required
l

maintenance history archive and event


l
Ability to detect multiple PD sources simultaneously Supports the addition of future client applications
l

archive
l
Helps in approximate localization of partial discharge by amplitude Facility to link other portables to expand monitoring capabilities
l
l
Easy configuration of all
comparison
parameters
Other key benefits Designed to meet highest security standards, including NERC cyber-security
l

Very rapid and easy deployment l


Pre-installed software - no installation required on site standards l
Built-in self diagnostics
enables maximum time for l
Easy configuration of system (offline / online) using touch screen interface Built-in time synchronization through NTP / SNTP
l

condition assessment of assets l


Sensors can be fitted to any available inspection hatch or manhole as a Provides timely information where needed through its multiple
l

retrofit communication methods (Ethernet, USB)


l
Require only one field engineer / operator with basic knowledge of partial Superior safety in high voltage test setups
l

discharge
Real-time display of
up to 6 UHF channels
Robust and rugged design to l
IP66 rated highly protective case
maximize portable operation life l
Built-in display (no separate laptop) helps in putting system in any
and support inspections / testing environmental condition for longer time
for extended period of time (24 IP-66 rated highly protective case
l
16 GB data storage sufficient to store PD events continuously for 12 months
hours up to 12 months) with trolley wheels
l
Facility to store data into external storage further enhances data storage
capacity
Flight-friendly and lightweight system
(17 kg [37.5 lbs]) and easy to operate
Accurate fault detection l
Outstanding sensitivity and unique accuracy (75 dBm / 5pC) of UHF
by one person
improves reliability of HV testing measurements
ensuring safe and stable HV l
In-built sensitivity of -75 dBm enables better PD analysis
apparatus installed in l
Noise gating by external signal antenna (optional)
substations
l
Cross channel coincidence gating

HVDC compatibility saves cost of l


Live stream data recording up to 3 days
buying different PD testing l
Higher sampling rate (15.4 kS/s per channel) improves the chances of PD
equipment for HVDC apparatuses detection

Advanced HMI provisions l


In-built LCD screen with touch screen based interface
(SMARTSUB Software - intelligent l
Easy to add / modify / delete substation / site location
data handling, display and l
2D and 3D display of PD signals in multiple formats (Single Cycle, Peak Hold,
interpretation)
PRPD and STT)
l
Automatic self-check of PDM with faults logged and alarmed Easy configuration
l
Trend analysis facility on stored PD data of all parameters
l
State of the art data export function for PD results

Minimal installation and Smart inspection... ...from the world leader in PDM

www.qualitrolcorp.com
QCM-PPDM Portable partial discharge monitor for transformers and GIS QCM-PPDM Portable partial discharge monitor for transformers and GIS
QCM-PPDM
TECHNICAL SPECIFICATIONS Portable partial discharge monitor for transformers and GIS
Power supply Voltage range 90 to 264 VAC, 47-63 Hz; 40 to 290 VDC universal supply
Supply current 110 mA @ 230 VAC
Power 70 W

MCU (Master
Control Unit)
Input 3 UHF channels / (or) 6 UHF channels
1 additional channel for noise antenna
Smart and easy CBM Handy system for precise assessment
Outputs Alarm indications on the screen: - PD fault alarm - PD alarm
- PD warning alarm - System status indicator
of partial discharge during testing,
UHF sensors
MMI

Mounting
LCD display with full touch interface

Internal or External
commissioning and periodic inspections
(optional) Output Communicates to portable Full characterization and localization of partial discharge faults to determine the severity of
l

Bandwidth Wideband 300 - 1500 MHz PD and help in scheduling maintenance


Sensitivity > 6 mm, < 5pC
Very rapid and easy deployment enables maximum time for condition assessment of assets
l
Remote SMARTSUB Operating system Windows XP / Windows 7 compatible
software
Max monitoring locations 100+ Robust and rugged design to maximize portable operation life and support inspections /
l

Memory 1GB, upgradable (if required) testing for extended period of time (24 hours up to 12 months)
Min size for installtion 20 MB
System alarms System fault, channel fault
Accurate fault detection improves reliability of HV testing ensuring safe and stable HV
l

apparatus installed in substations


PD alarms / PD warning Gradient, PD Trend

Performance Sample rate 15.4 KS/s per channel


Total of 107.5 KS/s for 7 channels (simultaneous sampling) Product Summary
Data storage 16 GB Description A self sufficient and portable PDM system
Clock 1.2 GHz for rapid monitoring and analysis of partial discharge in
Time synchronization Yes gas insulated switchgear (GIS) and power
Noise gating coincidence filters Yes transformers. The system is field operated, touch
Comms Ethernet ports - external RJ45 (10/100 Mbps) screen based and gives engineers the tools required
USB One port to facilitate firmware upgrade, configuration upgrade and manual for diagnosing partial discharge with limited or no
download of data access to the main PDM infrastructure.
l Allows the operator to have l Excellent interference immunity for
GPRS Optional
confidence in the reliability and PD measurement under difficult Application Used for low-cost, high performance
Environmental Ambient operating temperature -25ºC to +55ºC continued operation of the plant conditions periodic online and offline PD testing on HV insulating
Storage temperature -25ºC to +75ºC
l Extends residual life of aging plant l Usable for HV GIS commissioning system of GIS and power transformers in transmission
Humidity 5 - 95% non-condensing
and defers capital costs tests installations, power plants and large industrial
Enclosure rating NEMA IP66
consumers. The information gained from the system
Siesmic IEEE C37.98 (Seismic Testing of Relays) l Implementation of efficient, condition- l Retrofits to most major GIS and may be used for condition based maintenance
Environmental test compliance BS EN60068-2-2, BS EN60068-2-1, BS EN60068-2-78 based maintenance strategies transformers decisions.
Vibration test compliance BS EN68-2-6, BS EN68-2-27, BS EN68-2-29
l HV record mode, versatile sync, PD testing and analysis whilst installation and
Immunity EMC test compliance Confirms to relevant specifications for monitoring / control equipment in HV
superior data review method commissioning of HV GIS and transformers.
substations.
BS EN55022 (:2006); BS EN61000-3-2 to -3-3, BS-EN61000-4-2 to -4-6, Quality testing for PD during or after assembling or
BS EN61000-4-8, BS EN61000-4-11, BS EN61000-4-18; IEC 60255-5,
IEC 61180-1 manufacturing of GIS and transformers.
About QUALITROL®
Others EMI / RFI immunity Established in 1945, with continual improvement at the core of our business, QUALITROL® provides smart utility asset Lab measurements of PD on any insulating material for
condition monitoring across the globe. We are the largest and most trusted global leader for partial discharge monitoring,
Mechanical Dimensions and weight 508 mm x 355 mm x 254 mm [20” x 14” x 10”]. 17 kg [37.5 lbs] scientific and research laboratories.
asset protection equipment and information products across generation, transmission and distribution. At QUALITROL®
Display 12” touch screen, (1024 x 768). Rotary / push button we are redefining condition monitoring technology for Electric utilities assets.
©2014 QUALITROL® Company LLC, an ISO 9001 system certified company. QUALITROL is a registered trademark and OTIWTI is a trademark of QUALITROL® Company LLC.
All trademarks are properties of their respective companies, as noted herein. All rights reserved. Information subject to change without notice. PD-D27-10L-02E.

Email: info@qualitrolcorp.com
www.qualitrolcorp.com www.qualitrolcorp.com
QCM-PPDM Portable partial discharge monitor for transformers and GIS QCM-PPDM Portable partial discharge monitor for transformers and GIS
QCM-PPDM
TECHNICAL SPECIFICATIONS Portable partial discharge monitor for transformers and GIS
Power supply Voltage range 90 to 264 VAC, 47-63 Hz; 40 to 290 VDC universal supply
Supply current 110 mA @ 230 VAC
Power 70 W

MCU (Master
Control Unit)
Input 6 UHF channels
1 additional channel for noise antenna
Smart and easy CBM Handy system for precise assessment
Outputs Alarm indications on the screen: - PD fault alarm - PD alarm
- PD warning alarm - System status indicator
of partial discharge during testing,
UHF sensors
MMI

Mounting
LCD display with full touch interface

Internal or External
commissioning and periodic inspections
(optional) Output Communicates to portable Full characterization and localization of partial discharge faults to determine the severity of
l

Bandwidth Wideband 300 - 1500 MHz PD and help in scheduling maintenance


Sensitivity > 6 mm, < 5pC
Very rapid and easy deployment enables maximum time for condition assessment of assets
l
Remote SMARTSUB Operating system Windows XP / Windows 7 compatible
software
Max monitoring locations 100+ Robust and rugged design to maximize portable operation life and support inspections /
l

Memory 1GB, upgradable (if required) testing for extended period of time (24 hours up to 12 months)
Min size for installtion 20 MB
System alarms System fault, channel fault
Accurate fault detection improves reliability of HV testing ensuring safe and stable HV
l

apparatus installed in substations


PD alarms / PD warning Gradient, PD Trend

Performance Sample rate 15.4 KS/s per channel


Total of 107.5 KS/s for 7 channels (simultaneous sampling) Product Summary
Data storage 16 GB Description A self sufficient and portable PDM system
Clock 1.2 GHz for rapid monitoring and analysis of partial discharge in
Time synchronization Yes gas insulated switchgear (GIS) and power
Noise gating coincidence filters Yes transformers. The system is field operated, touch
Comms Ethernet ports - external RJ45 (10/100 Mbps) screen based and gives engineers the tools required
USB One port to facilitate firmware upgrade, configuration upgrade and manual for diagnosing partial discharge with limited or no
download of data access to the main PDM infrastructure.
l Allows the operator to have l Excellent interference immunity for
GPRS Optional
confidence in the reliability and PD measurement under difficult Application Used for low-cost, high performance
Environmental Ambient operating temperature -25ºC to +55ºC continued operation of the plant conditions periodic online and offline PD testing on HV insulating
Storage temperature -25ºC to +75ºC
l Extends residual life of aging plant l Usable for HV GIS commissioning system of GIS and power transformers in transmission
Humidity 5 - 95% non-condensing
and defers capital costs tests installations, power plants and large industrial
Enclosure rating NEMA IP66
consumers. The information gained from the system
Siesmic IEEE C37.98 (Seismic Testing of Relays) l Implementation of efficient, condition- l Retrofits to most major GIS and may be used for condition based maintenance
Environmental test compliance BS EN60068-2-2, BS EN60068-2-1, BS EN60068-2-78 based maintenance strategies transformers decisions.
Vibration test compliance BS EN68-2-6, BS EN68-2-27, BS EN68-2-29
l HV record mode, versatile sync, PD testing and analysis whilst installation and
Immunity EMC test compliance Confirms to relevant specifications for monitoring / control equipment in HV
superior data review method commissioning of HV GIS and transformers.
substations.
BS EN55022 (:2006); BS EN61000-3-2 to -3-3, BS-EN61000-4-2 to -4-6, Quality testing for PD during or after assembling or
BS EN61000-4-8, BS EN61000-4-11, BS EN61000-4-18; IEC 60255-5,
IEC 61180-1 manufacturing of GIS and transformers.
About QUALITROL®
Others EMI / RFI immunity Established in 1945, with continual improvement at the core of our business, QUALITROL® provides smart utility asset Lab measurements of PD on any insulating material for
condition monitoring across the globe. We are the largest and most trusted global leader for partial discharge monitoring,
Mechanical Dimensions and weight 508 mm x 355 mm x 254 mm [20” x 14” x 10”]. 17 kg [37.5 lbs] scientific and research laboratories.
asset protection equipment and information products across generation, transmission and distribution. At QUALITROL®
Display 12” touch screen, (1024 x 768). Rotary / push button we are redefining condition monitoring technology for Electric utilities assets.
©2014 QUALITROL® Company LLC, an ISO 9001 system certified company. QUALITROL is a registered trademark and OTIWTI is a trademark of QUALITROL® Company LLC.
All trademarks are properties of their respective companies, as noted herein. All rights reserved. Information subject to change without notice. PD-D27-10L-02E.

Email: info@qualitrolcorp.com
www.qualitrolcorp.com www.qualitrolcorp.com

You might also like