0% found this document useful (0 votes)
199 views2 pages

Atx 060

The document describes Type ATX thermostatic expansion valves that are used in refrigeration and air conditioning systems. The valves come in different models with varying orifice sizes, refrigerant types, charge types, connection types, and capacities. Key specifications that define each valve model include orifice port size, refrigerant, charge type, connection type, inlet and outlet sizes, capacity, and weight. Capacities are provided for common refrigerants R22, R134a, R404A, and R407C at standard temperature conditions.

Uploaded by

TimmyJuri
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
199 views2 pages

Atx 060

The document describes Type ATX thermostatic expansion valves that are used in refrigeration and air conditioning systems. The valves come in different models with varying orifice sizes, refrigerant types, charge types, connection types, and capacities. Key specifications that define each valve model include orifice port size, refrigerant, charge type, connection type, inlet and outlet sizes, capacity, and weight. Capacities are provided for common refrigerants R22, R134a, R404A, and R407C at standard temperature conditions.

Uploaded by

TimmyJuri
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

EXPANSION VALVES

Type ATX

GENERAL DESCRIPTION
• Application: General refrigeration and air conditioning
systems.
*Note: S–charge valve for low temperature (−40 to 10°C),
unloading, heat pump applications, or hot gas defrost
system. CY–charge valve for extreme low temp. (−70 to
−40°C) application.
• Charge: L (Liquid) charge for refrigeration application.
G (Gas) charge for cooling application with
20°C (standard) MOP.
S (Special) charge for all purpose with 20°C
(standard) MOP.
C (Cross) charge, CL (Cross low) charge and
CY (Extream low) charge for low temp applica-
tion.
• Max. allowable pressure:
1.37 MPa {14kgf/cm2} . . (G, L, C, CL–charge) Type ATX–B

2.75 MPa {28kgf/cm2} . . . . (S, CY–charge)


• Adjustable range of static superheat:
3 to 13°C . . . . . . . . (G, L, CL–charge)
0 to 8°C . . . . . . . . . . . . (S–charge)
0 to 13°C . . . . . . . . . . . (CY–charge)
• Superheat change:
4 to 5°C (R134a) . . . . . . (L or G–charge)
2 to 3°C(R22) . . . . . . . (L or G–charge)
4 to 6°C(R134a, R22) . . . . . . (S–charge)
8 to 12°C(R22) . . . . . . . . (CY–charge)
• Rugged diaphragm element: Best for heat pump units.

Type ATX–D

VALVE NOMENCLATURE
Catalog No. is decided according to the specifications.
Example: ATX Ð 34006 B H L
Ⅰ Ⅱ Ⅲ Ⅳ Ⅴ
Ⅰ: Type...... ATX–Thermostatic expansion valve for general use.
Ⅱ: Model...... The last two figures indicate approximate capacity.
The first and second figures indicate inlet and outlet pipe size respectively.
Ⅲ: Connection...... B–Flare Nut Connection, D–Solder Connection
Ⅳ: Kind of refrigerant...... M=R134a, H=R22, U=R404A, P=R407C, C=Other refrigerant
Ⅴ: Kind of charge...... G=G–charge, L=L–charge, C=C–charge, CL=CL–charge, CY=CY–charge, S=S–charge

TYPE NUMBER SELECTION (SPECIFICATIONS)


Catalog No. Orifice Capacity (U.S.R.T.) {kW} Connection * Capil.
Wt.
Port Tube Length
Type Model Connection Refrigerant Charge R22 R134a R404A R407C Inlet Outlet Equalizer (kg)
(mm) (mm)
1.0 0.7 0.7 1.0
34006 M G 3
(R134a) (Gas) {3.51} {2.46} {2.46} {3.51}

H L 2.1 1.6 1.5 2.2


34013
(R22) (Liquid) {7.39} {5.63} {5.27} {7.74}
4
φ3
B U C 3.6 2.8 2.7 3.7 1/4"
ATX– 34023 3/8" 1/2" × 1.2
(Flare) (R404A) (Cross) {12.7} {9.85} {9.49} {13.0} Flare
1500
P CL 5.5 4.2 4.0 5.7
34035 (R407C) (Cross Low) 5
{19.3} {14.8} {14.1} {20.0}
C S 7.0 5.4 5.1 7.2
34045 (Others) (Special) 5.5
{24.8} {19.0} {17.9} {25.3}
*Capillary tube length: 2000mm for S–charge valve as standard.
・Capacity: Based on condensing temp. 38°C (100°F) and evaporator temp. 5°C (41°F).

59
Catalog No. Orifice Capacity (U.S.R.T.) {kW} Connection * Capil.
Wt.
Port Tube Length
Type Model Connection Refrigerant Charge R22 R134a R404A R407C Inlet Outlet Equalizer (kg)
(mm) (mm)
34006 3 1.0 {3.51} 0.7 {2.46} 0.7 {2.46} 1.0 {3.51}
34013 2.1 {7.39} 1.6 {5.63} 1.5 {5.27} 2.2 {7.74}
4 φ3
34023 M G 3.6 {12.7} 2.8 {9.85} 2.7 {9.49} 3.7 {13.0} 3/8" OD 1/2" OD × 1.1
(R134a) (Gas)
34035 5 5.5 {19.3} 4.2 {14.8} 4.0 {14.1} 5.7 {20.0} 1500

34045 H L 5.5 7.0 {24.6} 5.4 {19.0} 5.1 {17.9} 7.2 {25.3}
57060 (R22) (Liquid) 6 9.7 {34.1} 7.2 {25.4} 6.8 {23.9} 10.0 {35.1}
57080 8 13.0 {45.7} 9.6 {33.7}
9.1 {32.0} 13.4 {47.1} 5/8" OD 7/8" OD
φ3
U C 1/4"
ATX– 71110 D (Solder) 10 17.8 {62.9} 13.2 {46.4} 12.5 {44.0} 18.3 {64.3} or or × 1.3
(R404A) (Cross) Flare
71140 22.6 {79.4} 16.8 {59.1} 16.0 {56.3} 23.3 {81.9} 7/8" ID 1–1/8" ID 2000

71160 P CL 11 26.0 {91.6} 19.2 {67.5} 18.2 {64.0} 26.8 {94.2}


12220 (R407C) (Cross Low) 35.8 {126} 26.4 {92.8} 25.1 {88.3} 37.0 {130}
12270 12 43.5 {154} 32.4 {114} 30.8 {108} 44.9 {158} 1" OD 1" OD φ3
C S
12330 (Others) (Special) 13 53.4 {187} 39.6 {140} 37.6 {132} 54.9 {193} or or × 1.5
12420 15 67.6 {237} 50.4 {177} 47.9 {168} 69.7 {245} 1–1/4" ID 1–1/4" ID 3000

12500 16 81.0 {285} 60.0 {211} 57.0 {200} 83.3 {293}


*Capillary tube length: 2000mm for S–charge valve as standard.
・Capacity: Based on condensing temp. 38°C (100°F) and evaporator temp. 5°C (41°F).

Extreme Low Temperature Model (−70°C to −40°C)


Catalog No. Orifice Capacity (U.S.R.T.) {kW} Connection Capil.
Wt.
Port Tube Length
Type Model Connection Refrigerant Charge R22 Inlet Outlet Equalizer (kg)
(mm) (mm)
34006 3 1.5 {5.27}
B
34013 (Flare) 3.4 {12.0} 1.2
4 (Flare)
34023 5.5 {19.3} 3/8" 1/2"
or CY φ3 1.1
D H 1/4"
ATX– 34035 (Extreme 5 7.8 {27.4} × (Solder)
(Solder) (R22) Low) Flare
34045 5.5 7.0 {24.6} 2000

57060 D 6 9.7 {34.1}


5/8" 7/8" 1.3
57080 (Solder) 8 13.0 {45.7}
・Capacity: Based on condensing temp. 40°C (104°F) and evaporator temp. −50°C (−58°F), sub–cooling 50°C (90°F).
・Contact the company for more detailed information.

DIMENSIONS Catalog No. Unit: mm

Type ATX–B Type Model Connection L H H1 h φD R B


φD 34006
φ3 ×R B
34013 (Flare)
34023 38 77 31 30 1500
34035 D
(Solder)
34045
64 76
H

57060
57080
H1

ATX– 71110 80 34 52 2000


B

φ16 71140
71160 D
51
h

12220 (Solder)
12270
L
12330 82 36 56 68 3000 100
12420
12500
Type ATX–D
φD
φ3 ×R
ACCESSARY Sensing Bulb Mounting Band
14

φ6 12.6 11−φ6
7

16
H

116.6 126
(5.4)
H1

267
B

φ16 t=0.4
Type ATX–34006 to 71160 Bolt
h

14

φ6 12.6 12−φ6
7

16

L
174 138.6
(5.4)
337
Unit: mm Type ATX–12220 to 12500 t=0.4

60

You might also like