6.6Kv Switchgear CFPP 2X30Mw Amurang: Insulation Test, Contact Resistance & Timing

This document summarizes test results for a 12kV switchgear CB panel. Insulation resistance tests found resistances between 16-30 GOhms when closed and 88-97 GOhms when open. Contact resistance tests found values between 15-17 uOhms. Timing tests found close times around 51ms, open times around 39ms, and close-open times around 42ms, all within specification. The tests were performed using calibrated equipment and the switchgear was found to comply with specifications.

Uploaded by

kukuh nug
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
57 views1 page

6.6Kv Switchgear CFPP 2X30Mw Amurang: Insulation Test, Contact Resistance & Timing

This document summarizes test results for a 12kV switchgear CB panel. Insulation resistance tests found resistances between 16-30 GOhms when closed and 88-97 GOhms when open. Contact resistance tests found values between 15-17 uOhms. Timing tests found close times around 51ms, open times around 39ms, and close-open times around 42ms, all within specification. The tests were performed using calibrated equipment and the switchgear was found to comply with specifications.

Uploaded by

kukuh nug
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 1

INSULATION TEST, CONTACT RESISTANCE & TIMING

6.6kV SWITCHGEAR
CFPP 2x30MW AMURANG
Date : / / 2017 Doc : NAMA PANEL / CB / 02

CB NAMA PANEL

1 SPECIFICATION
FEEDER NAME : TRAFO (MVA) OBHB
MANUFACTURE : ABB
TYPE / YEAR : VD4/P 12.32.40 / 2015
RATED VOLTAGE / CURRENT : 12 kV / 1250 A
SERIAL NUMBER : 1YHP000046A1056

2 INSULATION RESISTANCE TEST


TEST POINT TEST VOLTAGE RESULT (OHM) REMARK
L1 - G 5000 VDC 17.2 GΩ CLOSE POSITION
L2 - G 5000 VDC 17.3 GΩ CLOSE POSITION
L3 - G 5000 VDC 16.4 GΩ CLOSE POSITION
L1 - L2 5000 VDC 28.3 GΩ CLOSE POSITION
L2 - L3 5000 VDC 27.5 GΩ CLOSE POSITION
L3 - L1 5000 VDC 30.2 GΩ CLOSE POSITION
L1 TOP - L1 BOTTOM 5000 VDC 97.3 GΩ OPEN POSITION
L2 TOP - L2 BOTTOM 5000 VDC 94.6 GΩ OPEN POSITION
L3 TOP - L3 BOTTOM 5000 VDC 88.5 GΩ OPEN POSITION

3 CONTACT RESISTANCE TEST


TEST POINT TEST CURRENT RESULT (OHM) REMARK
PHASE L1 100 A 15.5 µΩ
PHASE L2 100 A 17.1 µΩ
PHASE L3 100 A 17.2 µΩ

4 TIMMING BREAKER
TEST POINT PHASE R PHASE S PHASE T REMARK
CLOSE TIME 51.2 mS 51.4 mS 51.4 mS
OPEN TIME 39.2 mS 38.8 mS 38.8 mS
51.2 mS 51.6 mS 51.4 mS CLOSE
CLOSE-OPEN TIME
42.4 mS 42.2 mS 42.0 mS OPEN

Instrument tool : Serial Number : Calibration Date :


1 . Megger MIT510/2 (S/N 10003700904091708) 12/9/2015
2 . Megger DLRO 200 (S/N 070607-1341) 7/7/2015
3 . ISA CBA 1000 (S/N 2015/21903) 19/6/2015

Remark : This equitment is comply to the specification


Refrence attachment instrument test result