MR.
ABDUL AZEEZ AL MUHANNADI
                 –PRIVATE VILLA
Water Supply Calculation
     Domestic Cold water system:
     General Description:
     Domestic water supply will be obtained from the main city water network and stored in
     POLYETHYLENE storage tank to be located at ground floor.
     Water will be pumped from storage tank to a roof water tank through transfer water
     pumps. From this roof water tank, water will be distributed for all building facilities by
     means of gravity except for the upper three floors which requires booster pump set to
     achieve the proper water head at these levels.
     Basis of Design
          Design for cold water pipes is based upon diversified load for fixtures used
          intermittently on the system.
          Pipe sizes will be determined by the fixture unit method. The weight in fixtures
          units is tabulated below in accordance with National Plumbing Code Handbook:
                               Fixture Type                        Fixture Unit
                     Water Closet-Public Flush Tank                     5
                     Water Closet-Private Flush Tank                    3
                              Lavatory-Public                           2
                             Lavatory-Private                           1
                            Urinal-Flush Valve                          5
                            Urinal-Flush Tank                           3
                                    Bidet                               2
                            Drinking Fountain                           2
                         Restaurant Kitchen Sink                        4
                                Kitchen Sink                            2
                           Public Shower Head                           4
                          Private Shower Head                           2
                                  Hose Bib                              3
                Laundry (dish washer or washing machine)                2
          Determination of demand and usage will follow the recommendations of the
          National Plumbing Code Handbook.
System will be designed so as to ensure a minimum residual pressure of 20 meter
of water.
Storage water Tanks:
 Residential water demand:
 According to uniform plumbing code, at office building
 Assume 2 person for each bedroom
 No of person=12
 According to uniform plumbing code, water demand = 270 liter/ person/day
 Total residential water demand = (12)X270= 3.24 m3/day
 Use 1 water tank at the roof =1500 gallon(storage 1day)
 Diameter=1.97m ,hight=2.60m
 GYM demand:
 Assume No of person=12
 Total residential water demand = (12)X50= 0.60 m3/day
 Use 1 water tank at the roof floor =400 gallon(storage 1day)
 Diameter=1.25m ,hight=1.33m
 Out.Kit demand:
 Use 1 water tank at the roof floor =400 gallon(storage 1day)
 Diameter=1.25m ,hight=1.33m
 Driver Quarter:
 According to uniform plumbing code, at office building
 Assume 2 person for each bedroom
 No of person=6
 According to uniform plumbing code, water demand = 270 liter/ person/day
 Total residential water demand = (6)X270= 1.62 m3/day
 Use 1 water tank at the roof floor =400 gallon(storage 1day)
 Diameter=1.25m ,hight=1.33m
     Transfer water pumps:
Roof water tank is to be filled in               1Hours
Q=volume / time = 11.73/1 = 11.73 m3/Hr = 3 L/sec
Use two transfer water pumps each of capacity = 3 L/sec                        (one is stand by)
          Static head = 10m                             (from drawings)
          Friction losses = 20% of static head = 10*0.2 = 2 m
Total pumps head = 10+2 = 12m take it =20 m
     Booster pump set calculations:                            (for VILLA)
Booster pump set will serve all villa Total fixture units for these floors is calculated in
the table below
                                        Floors          Total fixtures
                 Fixtures                                                     F.U     T.F.U
                                villa              NO
                  E.W.C                   9              9                     3        27
                   LAV.                   9              9                     1         9
                    SH                    8              8                     2        16
                    K.S                   0              0                     2        12
                    B.T                   2              2                     2         4
                             Total fixture units for main villa                         70
       Total fixture units = 70
       Total Discharge = 37GPM
       Discharge of one pump = 2.30              L/sec
     Booster pump set calculations:                            (for Out.Kit)
Booster pump set will serve all villa Total fixture units for these floors is calculated in the table below
                                        Floors          Total fixtures
                 Fixtures                                                     F.U     T.F.U
                               Out.kit             NO
                   K.S                    1              1                     2        2
                             Total fixture units for main villa                         2
       Total fixture units = 2
       Total Discharge = 2GPM
       Discharge of one pump = 0.50              L/sec
     Booster pump set calculations:                            (for driver quarter)
Booster pump set will serve all villa Total fixture units for these floors is calculated in the table below
                                        Floors          Total fixtures
                 Fixtures                                                     F.U     T.F.U
                                villa              NO
                  E.W.C                   2              2                     3        6
                   LAV.                   2              2                     1        2
                    B.T                   2              2                     2        4
                             Total fixture units for main villa                         12
       Total fixture units = 12
       Total Discharge = 10 GPM
       Discharge of one pump = 0.63              L/sec
     Booster pump set calculations:                            (for GYM)
Booster pump set will serve all villa Total fixture units for these floors is calculated in the table below
                                        Floors          Total fixtures
                 Fixtures                                                     F.U     T.F.U
                                villa              NO
                  E.W.C                   1              1                     3        3
                   LAV.                   1             1                      1        1
                    SH                    1             1                      2        2
                             Total fixture units for main villa                         6
       Total fixture units = 6
       Total Discharge = 7 GPM
       Discharge of one pump = 0.50 L/sec
     Booster pump set calculations:                            (for MAGLIS)
Booster pump set will serve all villa Total fixture units for these floors is calculated in the table below
                                        Floors          Total fixtures
                 Fixtures                                                     F.U     T.F.U
                                villa              NO
                  E.W.C                   1             1                      5        5
                   LAV.                   4             1                      2        8
                    KS                    1             1                      4        1
                                        Total fixture units                             14
          Total fixture units = 14
          Total Discharge = 11 GPM
          Discharge of one pump = 0.80 L/sec
          Use GRP water tanks at BASEMENT FLOOR =20 M3(storage 2days)
          Diameter(4.1X1.8X2.70)
     Domestic Hot water system:
     General Description
          -Domestic Hot Water will be supplied to gym,out kit ,maglis and driver quarter
          will be generated through individual water heaters located at toilets or any
          facility requiring hot water.
          -Domestic Hot Water will be supplied to Main Villa by central water heater