TECHNICAL SPECIFICATION
3B6 Display
Load cell
SHLD
BLACK (-REF1)
BLUE (-IN1)
YELLOW (+OUT1)
GREEN (+OUT1)
RED (+IN1)
WHITE (+REF1)
Pin 18 + GND = 12V in work condition CONNECTOR X1 FOR CHECKS WITH TESTER
0V in overload condition
Electrical power to control unit (DLE)
Pin 7 + GND = feedback ok (12V) Pin 1: 12 V
Pin 2: GND
Pin 9 positive
Pin10 = boom retracted with forks in Overload signal (12V generated by the DLE)
horizontal position, without load: Pin 18: 12 V normal conditions, 0 Valarm overload
1,1÷1,4 mV Pin 7: re-reading overload signal
= boom extended with forks in
horizontal position, without load: Electrical power to load cell equal to 5 V
0,1÷0,4 mV Channel 1: Pin 16:positive Pin 17: negative
Pin 20 + GND = 12V with outriggers down
Pin 21 + GND = 12V with outriggers down Load cell signal in range 0,1 - 2,5 mV
Channel 1: Pin 10: positive Pin 9: negative
TECHNICAL SPECIFICATION
1 2 3
•
NOTICE
During the calibration mode the limiter device
doesn’t block any manoeuvres so the calibration
can be done.
• With outriggers, calibrate the DLE system wi-
4 10 thout load and with load and outriggers fully at
ground.
• The calibration of the machine should be done
after a few minutes of use, in other words with
the machine "warm”.
9
5 6 7 8
TECHNICAL SPECIFICATION
DISPLAY FUNCTION
1 Lower the outriggers to the ground, fully retract the boom holding it slightly above the
horizontal with respect to the ground. DON’T lift loads.
Press to confirm the EMPTY calibration of the machine. The audible alarm will sound
to confirm the command has been executed.
Press to proceed to the next point (2).
2 With outriggers down, place a load on the forks with a known weight, extend the boom
while holding it horizontal till reaching the overturning moment. The overturning distance
is from the front part of the wheels to the center of the load. (see the diagram inside the
cab).
Press to confirm the LOADED calibration of the machine and check that the alarm
triggers. The audible alarm will sound to confirm the command has been executed. Move
the boom fully in while holding the same in the horizontal position.
Press to proceed to the next point (3).
3 With outriggers down, place a load on the forks with a known weight, extend the boom
while holding it horizontal till reaching the overturning moment. The overturning distance
is from the front part of the wheels to the center of the load. (see the diagram inside the
cab).
Press some times to switch off the LED's of the load and press to switch on
them; at the end, all LED's are on from left to right, except the red last one.
The procedure is saved automatically
Press some times to arrive to the point (F).
F Press to exit calibration and to SAVE the changes made (the audible alarm sounds
and the LED’s come on to confirm that data have been saved).
The limiter is no longer in the calibration mode. The LED is not lit fixed any more.
You should turn the machine off and then on again to eliminate any alarm messages.
Starting to work.
TECHNICAL SPECIFICATION
71.6°
13 70° 13 68.8°
12 60° E 12 60° E
kg
11 D 11 D
00
50° 50°
20
kg
10 C 10 C
00
9 40°
g
25
9 40° B B
k
00
8 A
30
kg
8 A
12.80 m
.60 m
00
.60 m 7 30°
12.99 m
7 30°
35
6 kg
6 00
40
kg
5 20°
00
5 20°
1500 kg
2500 kg
3500 kg
2000 kg
3000 kg
40
1000 kg
1500 kg
250 kg
500 kg
4
3
10°
3
1250 kg
10° 2
2 1
0°
1 0
0°
0 -1 -4.18°
-1.43° 10 9 8 7 6 5 4 3 2 1 0
-1
10 9 8 7 6 5 4 3 2 1 0 9.08 m
9.02 m
TECHNICAL SPECIFICATION
FUNZIONE DISPLAY
A-B Display of the value read by the ADC converter-cell channel 1 (A).
This diagnosis function allows you to check proper reading of the load cell.
As you move the boom, you can see the LEDs of the load bar progressively go on/off
(valid if calibration has already been done).
Position the machine for a calibration without load.
If the function A is setted, by a progressive boom extension the LEDs of the load bar
progressively have to go off.
If function A is activated and the LED is completely ON or OFF, there could be a problem
with the connection or in the cell thereof; if it is partly lit but there is no movement in the
boom, make sure the cell is fixed.
C Digital Inputs display: this function allows you to see if the following signals are properly
delivered to the DLE device according to the lighted LEDs of the load bar:
LED3: lit when the load limiter disconnect key is turned.
LED4: ON if the interlock relay is active (machine safe without alarms).
D Software version existing in the DLE unit: this function allows you to see the software
version included in the DLE unit according to the lighted LEDs of the load bar:
No LED: software 0
One LED: software 1 ……
Four LED: software 4
E No function.
ALARM CODES
Alarm code 1
Description E2PROM Error. Internal comparison of data read from E2PROM failed.
Action Switch off and switch on the machine. If the alarm continues, recalibrate the machine,
otherwise replace DLE
Alarm code 2
Description CELL 1 reading out of range.
Action Check if the load cell is fixed well.
Check the connection between DLE and sensor for short circuits or signal interruptions
due to a broken cable.
Check the DLE connector for signs of oxidation, short circuits or absence of electrical
contact in some pins.
If the alarm persists, check if the cell is intact.
TECHNICAL SPECIFICATION
Alarm code 4
Description Block Relay check error during work. Check through.re-reading of the block output
of the congruence with the current state of the limiter.
The alarm triggers even in the absence of malfunctions if the load limiter cutout
key is used.
Action The relay or the cable can be shorted; check.
The limiter’s outputs do not deactivate. Switch off and on the machine and run a complete
test of the outputs.
If the alarm persists, replace the DLE.
Alarm code A
Description RAM data error. Checks that the parameters load in the RAM at start-up remain unal-
tered.
Action Switch off and on the limiter.
Alarm code B
Description Outriggers congruence.
Action Check that the signal of stabilised machine is congruent between the two inputs used
for reading during operation.
Display: until the system is turned off.
Operations: check wiring, power cable, DLE connector. If the alarm persists, change the
DLE (digital input reading malfunction).
Alarm code C
Description A.D.C. reading control error. If the analog/digital converter works fine after special
rereading of the DLE board.
Action Switch off and on the limiter.
If the alarm continues, replace DLE.
Connect the PC to the LMI display (limit moment indicator) using the serial port and the power cord (cod.
07.0736.0014), switch on the board and start the Winscope application.
Below, the list of the parameters and of the variables visualizable on the PC. In bold, the values interesting for the
GTH-4013 SX and GTH-4017 SX.