Vigilohm IM400: Insulation Monitoring Device User Manual
Vigilohm IM400: Insulation Monitoring Device User Manual
DOCA0049EN-02 09/2015
                Vigilohm IM400
                Insulation Monitoring Device
                User Manual
                09/2015
DOCA0049EN-02
                www.schneider-electric.com
    The information provided in this documentation contains general descriptions and/or technical character-
    istics of the performance of the products contained herein. This documentation is not intended as a
    substitute for and is not to be used for determining suitability or reliability of these products for specific user
    applications. It is the duty of any such user or integrator to perform the appropriate and complete risk
    analysis, evaluation and testing of the products with respect to the relevant specific application or use
    thereof. Neither Schneider Electric nor any of its affiliates or subsidiaries shall be responsible or liable for
    misuse of the information contained herein. If you have any suggestions for improvements or amendments
    or have found errors in this publication, please notify us.
    No part of this document may be reproduced in any form or by any means, electronic or mechanical,
    including photocopying, without express written permission of Schneider Electric.
    All pertinent state, regional, and local safety regulations must be observed when installing and using this
    product. For reasons of safety and to help ensure compliance with documented system data, only the
    manufacturer should perform repairs to components.
    When devices are used for applications with technical safety requirements, the relevant instructions must
    be followed.
    Failure to use Schneider Electric software or approved software with our hardware products may result in
    injury, harm, or improper operating results.
    Failure to observe this information can result in injury or equipment damage.
    © 2015 Schneider Electric. All rights reserved.
2                                                                                                  DOCA0049EN-02 09/2015
                        Table of Contents
                    Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                                              5
                    About the Book. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                                             7
          Chapter 1 Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                                          9
                           Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .        10
                           Physical Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .            12
                           Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .       13
          Chapter 2 Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                                      17
                           Safety Measures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .           18
                           Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .        20
                           Flush Mounting and Dismantling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                    21
                           Mounting on and Dismantling from a Grid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                         24
                           Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .        25
                           Typical Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .          26
          Chapter 3 Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                                        31
                           R and C Measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                 32
                           Configuration and Accuracy Zones by Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                               33
                           Monitoring the System Insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                    36
                           Operation on Systems with a Voltage Greater Than 480 Vac/dc . . . . . . . . . . . . . . . . . . . . .                                         46
                           Insulation Fault Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .             47
                           Injection Inhibition Input and Exclusion Management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                               48
                           Self-Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .     53
          Chapter 4 Human Machine Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                                                    55
                           Vigilohm IM400 Menu Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                     56
                           Navigating the Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .             57
                           Status Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .          59
                           Special Status Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .              61
                           Modifying Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .              62
                           Clock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   64
                           Insulation Fault Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .          65
                           Trend Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .         66
          Chapter 5 Communication via Modbus RS-485 . . . . . . . . . . . . . . . . . . . . . . . . . . . .                                                              67
                           Configuring RS-485 Communication Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                           68
                           Table of Modbus Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                 69
                           Modbus Registers Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                 70
          Chapter 6 Maintenance and Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                                                          79
                           Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .            80
                           Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .           81
                           Maintenance and Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                       82
          Chapter 7 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                                         83
                           Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .        83
          Glossary          ......................................................                                                                                       85
DOCA0049EN-02 09/2015                                                                                                                                                     3
4   DOCA0049EN-02 09/2015
                        Safety Information
Important Information
NOTICE
                        Read these instructions carefully, and look at the equipment to become familiar with the device before
                        trying to install, operate, service, or maintain it. The following special messages may appear throughout
                        this documentation or on the equipment to warn of potential hazards or to call attention to information that
                        clarifies or simplifies a procedure.
PLEASE NOTE
                        Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel.
                        No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this
                        material.
                        A qualified person is one who has skills and knowledge related to the construction and operation of
                        electrical equipment and its installation, and has received safety training to recognize and avoid the
                        hazards involved.
DOCA0049EN-02 09/2015                                                                                                             5
FCC Notice
             This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant
             to part 15 of the FCC Rules. These limits are designated to provide reasonable protection against harmful
             interference when the equipment is operated in a commercial environment. This equipment generates,
             uses, and can radiate radio frequency energy and, if not installed and used in accordance with the
             instruction manual, may cause harmful interference to radio communications. Operation of this equipment
             in a residential area is likely to cause harmful interference in which case the user will be required to correct
             the interference at his own expense.
6                                                                                                        DOCA0049EN-02 09/2015
                        About the Book
At a Glance
Document Scope
                        This manual is intended for use by designers, panel builders, installers, system integrators, and
                        maintenance technicians who use ungrounded power systems (IT) with insulation monitoring devices
                        (IMDs).
Validity Note
                        The Vigilohm IM400 is used to monitor lines to earth insulation of ungrounded power systems. This
                        includes industrial and marine electrical systems, infrastructures, and power generation systems such as
                        photovoltaic and wind turbines. Thanks to the adaptive multi-frequency injection signal, the Vigilohm IM400
                        is suitable for power and control circuits that contain switching power electronics (speed drives, motor
                        starters, inverters, thyristors) and DC components. The Vigilohm IM400 allows automatic and manual fault
                        location.
Related Documents
                        You can download these technical publications and other technical information from our website at
                        http://download.schneider-electric.com
DOCA0049EN-02 09/2015                                                                                                            7
8   DOCA0049EN-02 09/2015
                           Vigilohm IM400
                           Vigilohm IM400 - Presentation
                           DOCA0049EN-02 09/2015
                        Chapter 1
                        Presentation
Presentation
DOCA0049EN-02 09/2015                                                                9
Vigilohm IM400 - Presentation
Presentation
Using Ungrounded IT System to Improve Power Availability and Reduce Risk of Fire
                      Continuity of service is an essential operational requirement for power systems, as it helps protecting
                      people and property. The use of ungrounded IT power system is mandatory when power interruption would
                      lead to a hazard for people and equipment. It is the case of medical operating theaters and marine
                      applications.
                      Ungrounded IT system is recommended when unavailability of power would result in losing production, or
                      occur significant downtime costs. When the first insulation fault current can lead to a risk of fire or
                      explosion, it is recommended to limit the first fault current by using ungrounded systems. It is the case in
                      environments such as oil and gas, chemical, or photovoltaic. The IT grounding system is chosen in certain
                      cases because it can help facilitating preventive and corrective maintenance operations.
                      The ungrounded IT system helps making continuity of service. Even after a first insulation fault has
                      occurred, the installation can continue to function without presenting any danger to people or equipment.
                      However, the faulty circuit must be detected and repaired before a second insulation fault occurs. The fact
                      that the IT system can tolerate a first insulation fault means that maintenance operations can be improved,
                      planned, and carried out in good conditions.
                       RA × Id ≤ 50 V
                      Where:
                         RA is the resistance value of the grounding connection of the equipment exposed-conductive-parts.
                         Id is the ground fault current, in A.
                         50 V is the maximal acceptable voltage for indirect contacts.
10                                                                                                                     DOCA0049EN-02 09/2015
                                                                                                     Vigilohm IM400 - Presentation
DOCA0049EN-02 09/2015                                                                                                          11
Vigilohm IM400 - Presentation
Physical Description
Physical Description
                      A   Display
                      B   Contextual menu buttons
                      C   MENU button
                      D   Red indicator light for Vigilohm IM400 product status
                      E   Yellow indicator light for Modbus communication indication
                      F   Green indicator light for correct insulation indication
                      G   White indicator light for preventive insulation alarm
                      H   Yellow indicator light for insulation alarm
                      I   ESC button for returning to previous menu or canceling a parameter entry
                      J   Vigilohm product catalog number
                      K   Vigilohm serial number
                      L   Auxiliary power supply terminal block
                      M   Injection terminal block
                      N   Insulation alarm relay terminal block
                      O   Preventive insulation alarm relay terminal block
                      P   Modbus RS-485 terminal block
                      Q   Injection inhibition input terminal block
12                                                                                                   DOCA0049EN-02 09/2015
                                                                                                           Vigilohm IM400 - Presentation
Accessories
Presentation
                        The following accessories are required depending on the type of installation on which Vigilohm IM400 is
                        installed:
                         A Cardew C surge limiter
                         A ZX impedance
                         A voltage adaptor
ZX impedance 50159
                        (1) Compatible with the Vigilohm IM400 when used with voltage adaptor IM400-1700 or PHT1000.
                        (2) Compatible with all Cardew C catalog numbers.
                        (3) For power systems with Umax > 480 Vac Ph-Neutral, or Umax > 830 Vac Ph-Ph, or Umax > 480 Vdc without
                            insulation fault locator.
                        (4) For power systems with Umax > 480 Vac Ph-Neutral, or Umax > 830 Vac Ph-Ph, or Umax > 480 Vdc with
                            insulation fault locator.
                        NOTE: For information regarding automatic and mobile insulation fault locating accessories, refer to the
                        relevant section (see page 47).
                        Function       The Cardew C is used if the insulation monitoring device is connected to the secondary of an MV/LV
                                       transformer (according to the rules and conventions that apply in the various countries).
                                       It helps protecting the low-voltage (LV) installation against overvoltage hazards.
                                       It is connected to the transformer secondary.
                                       The Cardew C can be used on the following systems:
                                        U < 1000 Vac
                                        U < 300 Vdc
                        Selection      Un: Nominal Phase-to-Phase Voltage of AC          Ui: Arcing Voltage       Type of Cardew C
                        table          System
                                       Accessible neutral       Not accessible neutral
                                       U ≤ 380 V                U ≤ 220 V                400 V < Ui ≤ 750 V       250 V
                                       380 V < U ≤ 660 V        220 V < U ≤ 380 V        700 V < Ui ≤ 1,100 V     440 V
                                       660 V < U ≤ 1,000 V      380 V < U ≤ 660 V        1,100 V < Ui ≤ 1,600 V   660 V
                                       1,000 V < U ≤ 1,560 V    660 V < U ≤ 1,000 V      1,600 V < Ui ≤ 2,400 V   1,000 V
                        Dimensions
DOCA0049EN-02 09/2015                                                                                                                  13
Vigilohm IM400 - Presentation
Connection
ZX Impedance
                       Function     The ZX impedance creates an installation with an impedance grounded neutral system (1500 Ω at
                                    50 Hz).
                                    The ZX remains connected during insulation fault locating at 2.5 Hz:
                                     1,500 Ω at 50 Hz
                                     1 M Ω at 2.5 Hz
14                                                                                                             DOCA0049EN-02 09/2015
                                                                                                          Vigilohm IM400 - Presentation
Voltage Adaptors
                        The optional voltage adaptors are:
                         IM400-1700
                         PHT1000
                        Function       The IM400-1700 and PHT1000 voltage adaptors can be used to connect a Vigilohm IM400 to voltage
                                       systems higher than 480 Vac L-L. The wire connecting IM400-1700 to Vigilohm IM400 must have the
                                       same voltage rating than the monitored network.
                                       The compatibility of voltage adaptors with insulation fault location is as follows:
                                        The IM400-1700 voltage adaptor is not compatible with insulation fault location.
                                        The PHT1000 voltage adaptor is compatible with insulation fault location.
S3 Subassembly (Retrofit)
                        Insulation alarm thresholds of the Vigilohm IM400 must be set higher than 2 kΩ to take into account internal
                        impedance of the no longer commercialized S3 subassembly.
DOCA0049EN-02 09/2015                                                                                                               15
Vigilohm IM400 - Presentation
16                              DOCA0049EN-02 09/2015
                           Vigilohm IM400
                           Vigilohm IM400 - Installation
                           DOCA0049EN-02 09/2015
                        Chapter 2
                        Installation
Installation
DOCA0049EN-02 09/2015                                                                17
Vigilohm IM400 - Installation
Safety Measures
                                                                           DANGER
                        HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
                           Before carrying out work of any kind, disconnect the Vigilohm IM400 from the monitored system by
                            disconnecting wiring terminals 1, 2, and 3 of injection terminal block. Disconnect all the power supplies
                            running to the Vigilohm and the equipment on which it is installed.
                           Always use a correctly calibrated voltage tester to check that the injection wire and power supply have
                            been properly disconnected.
                        Failure to follow these instructions will result in death or serious injury.
                                                                           DANGER
                        HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
                        Connect the ground wiring terminal (4) on the IM400-1700 voltage adaptor to a protective earth ground
                        (PE) conductor.
                        Failure to follow these instructions will result in death or serious injury.
                                                                           DANGER
                        HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
                           Wear suitable personal protective equipment and follow the currently applicable electrical safety
                            instructions.
                           This equipment may only be installed by qualified electricians who have read all the relevant
                            information.
                           NEVER work alone.
                           Before performing visual inspections, tests, or maintenance on this equipment, disconnect all sources
                            of electric power. Assume that all circuits are live until they have been completely de-energized,
                            tested, and tagged. Pay particular attention to the design of the power system. Consider all power
                            supply sources, particularly the potential for backfeed.
                           Before closing protective covers and doors, carefully inspect the work area to ensure that no tools or
                            objects have been left inside the equipment.
                           Take care when removing or replacing panels. Take special care to ensure that they do not come into
                            contact with live busbars. To minimize the risk of injuries, do not tamper with the panels.
                           The successful operation of this equipment depends upon proper handling, installation, and operation.
                            Failure to follow basic installation procedures can lead to personal injury as well as damage to
                            electrical equipment or other property.
                           NEVER shunt an external fuse/circuit breaker.
                           The Vigilohm must be installed in a suitable electrical cabinet.
                        Failure to follow these instructions will result in death or serious injury.
18                                                                                                                DOCA0049EN-02 09/2015
                                                                                                        Vigilohm IM400 - Installation
                        A dielectric test (Hi-Pot) or a Megger test on a device installed in the power system monitored by the
                        Vigilohm IM400 can damage the Vigilohm IM400.
                                                                     NOTICE
                        HAZARD OF PRODUCT DAMAGE
                        Before performing a dielectric test (Hi-Pot) or a Megger test, disconnect the Vigilohm input and output
                        wires.
                        Failure to follow these instructions can result in equipment damage.
DOCA0049EN-02 09/2015                                                                                                             19
Vigilohm IM400 - Installation
Dimensions
                                                                    CAUTION
                        CUTTING HAZARD
                        Trim the edges of the cut-out plates to remove any jagged edges.
                        Failure to follow these instructions can result in injury or equipment damage.
20                                                                                                       DOCA0049EN-02 09/2015
                                                                                                                   Vigilohm IM400 - Installation
Presentation
                        Vigilohm IM400 can be attached to any flat, rigid vertical support using the spring clips supplied. The device
                        must not be tilted following installation.
                        To free up useful space for control gear, you can attach the Vigilohm to the front panel of the floor-standing
                        or wall-mounted enclosure.
                        For USA and Canada, Vigilohm IM400 mounting is to be open type only.
Installing
                        Before attaching the Vigilohm, check the following:
                         The mounting plate must have a thickness of between 0.8 mm (0.03 in) and 3.2 mm (0.12 in).
                         A rectangle measuring 148 x 112 mm (5.83 x 4.41 in) must be cut out from the plate so the device can
                          be installed.
                         No terminal blocks are connected to the unit.
                        Step       Action
                        1          Insert the Vigilohm in the cut-out in the mounting plate by tilting the device forward slightly.
                        2          Depending on the thickness of the mounting plate, clip the spring clips into the mounting slots on the
                                   device as described below. First, clip the spring clip at the top.
                                   If the mounting plate thickness (X) is:     The mounting slot to be used is:
                                   0.8 mm ≤ X ≤ 2 mm
                                   (0.03 in ≤ X ≤ 0.08 in)
                                   If the mounting plate thickness (X) is:     The mounting slot to be used is:
                                   2 mm < X ≤ 3.2 mm
                                   (0.08 in ≤ X ≤ 0.12 in)
DOCA0049EN-02 09/2015                                                                                                                        21
Vigilohm IM400 - Installation
                        Step    Action
                        3       Clip the 2 spring clips on the device sides then the 2 spring clips at the device bottom.
4 Wire up and insert the terminal blocks as shown in the relevant wiring diagram (see page 25).
22                                                                                                                     DOCA0049EN-02 09/2015
                                                                                                                 Vigilohm IM400 - Installation
Removing
                        To remove the Vigilohm from a mounting plate, proceed as follows:
                        Step       Action
                            1      Disconnect the terminal blocks from the Vigilohm.
                            2      Deal with each of the spring clips as follows: insert the blade of a screwdriver between the spring clip
                                   and the device. Then use the screwdriver as a lever to release the spring clip.
                                   Start releasing the spring clips at the top and bottom of the device.
DOCA0049EN-02 09/2015                                                                                                                         23
Vigilohm IM400 - Installation
Presentation
                       To install the Vigilohm on a grid using fixing brackets (reference 01199 Prisma catalog) or equivalent. The
                       device must not be tilted following installation.
                       When mounting the device or dismantling it using clamps, you can keep the terminal blocks connected and
                       wired up, or you can remove them and keep them to hand.
                       For USA and Canada, Vigilohm IM400 mounting is to be open type only.
Mounting
                       To install the Vigilohm on a grid using fixing brackets, proceed as follows:
                        Step        Action
                                1   Position the fixing brackets on the Vigilohm and tighten the screws and washers as described below
                                    (tightening torque: 1.2 N.m (8.85 lb-in.).
Removing
                       To remove the Vigilohm from a grid, unscrew the clamps from the grid to release the device.
24                                                                                                                   DOCA0049EN-02 09/2015
                                                                                                        Vigilohm IM400 - Installation
Connection
Connection Diagram
                        The diagram below illustrates how to connect the Vigilohm to a single-phase or three-phase 3- or 4-wire
                        power system, or a DC power system.
                        The relay operating mode (failsafe or standard) is controlled via the HMI of the Vigilohm device or with
                        Modbus communication.
                        NOTE: Circuit breakers (reference MGN61334 or equivalent) can be used to replace listed fuses.
Connection Characteristics
                        All the Vigilohm IM400 wiring terminals have identical wiring capabilities.
                        The table shows the characteristics of the cables that can be used to connect the wiring terminals:
                        Cross-section area and voltage rating of wires must be suitable to the load current and to the voltage to
                        which it is connected. The following characteristics need to be considered:
                         Auxiliary power supply consumption: 25 VA / 10 Ω
                         Current flowing to the monitoring network wiring terminal: less than 20 mA
                         Current flowing to the injection inhibition wiring terminal: 5 mA
                         Current flowing to the insulation alarm and to the preventive insulation alarm wiring terminals depends
                          on the power rating of the insulation alarm indicator.
DOCA0049EN-02 09/2015                                                                                                               25
Vigilohm IM400 - Installation
Typical Applications
Presentation
                       The following section presents five insulation monitoring applications for an IT power system:
                        One application with a standalone Vigilohm IM400
                        One application with Vigilohm IM400 where the insulation alarm and preventive insulation alarm outputs
                         are sent to a supervisor
                        One application with Vigilohm IM400 where the insulation alarm and preventive insulation alarm outputs
                         are sent to a supervisor, and locating the insulation fault is done using an XD301 or XD312 automatic
                         fault locator and an XRM mobile fault locator
                        One application with a Vigilohm IM400 connected to a communication network
                        One application with a Vigilohm IM400 connected to a communication network, and locating the
                         insulation fault is done using an XD308C insulation fault locator
Monitoring the Insulation of an IT Power System with a Vigilohm IM400 Where the Insulation Alarm Is Sent to a
Supervisor
                       The insulation is monitored by a Vigilohm IM400 whose insulation alarm and preventive insulation alarm
                       outputs are connected to an available input on a networked device (a PLC, for example). This device is
                       itself connected to a supervisor via a communication network.
                       As far as this architecture is concerned, the restriction is that only the insulation fault and preventive
                       insulation alarm information is available at supervisor level.
26                                                                                                                DOCA0049EN-02 09/2015
                                                                                                             Vigilohm IM400 - Installation
Monitoring the Insulation of an IT Power System with a Vigilohm IM400 and Insulation Fault Location Where the
Insulation Alarm Is Sent to a Supervisor
                        The insulation is monitored by a Vigilohm IM400 whose insulation alarm and preventive insulation alarm
                        outputs are connected to an available input on a networked device (a PLC, for example). This device is
                        itself connected to a supervisor via a communication network.
                        Locating the insulation fault is done using XD301 or XD312 devices. The XD301 or XD312 output relay is
                        connected to an available input on a networked device.
                        The XRM mobile insulation fault locator is used to locate accurately the area where the insulation fault is.
                        As far as this architecture is concerned, the restriction is that only the insulation fault information and group
                        of faulty feeder are available at supervisor level.
DOCA0049EN-02 09/2015                                                                                                                  27
Vigilohm IM400 - Installation
Monitoring the Insulation of an IT Power System with a Vigilohm IM400 Connected to a Communication Network
                       When the Vigilohm IM400 insulation monitoring device is linked to the supervisor via a Modbus connection,
                       the following actions are supported:
                        Display:
                           Product status
                           Status of the insulation alarm (active, not active, acknowledged) and status of the preventive
                             insulation alarm
                           Details of the last 30 time-tagged events
                           Values for R and C to create tables or curves for monitoring these values over variable periods
                          Configuring the product remotely: all the settings can be accessed remotely, except for the Modbus
                           parameters (Address, Auto Config, Baudrate, and Parity).
The Ethernet gateway can be an EGX series or Com'X series, for example.
28                                                                                                           DOCA0049EN-02 09/2015
                                                                                                           Vigilohm IM400 - Installation
Monitoring the Insulation of an IT Power System with a Vigilohm IM400 Connected to a Communication Network and
Insulation Fault Location
                        When the Vigilohm IM400 insulation monitoring device is linked to the supervisor via a Modbus connection,
                        the following actions are supported:
                         Display:
                            Product status
                            Status of the insulation alarm (active, not active, acknowledged) and status of the preventive
                              insulation alarm
                            Details of the last 30 time-tagged events
                            Values for R and C to create tables or curves for monitoring these values over variable periods
                           Configuring the product remotely: all the settings can be accessed remotely, except for the Modbus
                            parameters.
                        Using the XD308C insulation fault location device in addition with the XLI300 communication interface
                        allows also the supervisor to monitor remotely all the feeders and so to report precisely any insulation fault
                        location.
                        The XRM mobile insulation fault locator is used to locate accurately the area where the insulation fault is.
DOCA0049EN-02 09/2015                                                                                                                29
Vigilohm IM400 - Installation
30                              DOCA0049EN-02 09/2015
                          Vigilohm IM400
                          Vigilohm IM400 - Functions
                          DOCA0049EN-02 09/2015
                        Chapter 3
                        Functions
Functions
DOCA0049EN-02 09/2015                                                                           31
Vigilohm IM400 - Functions
R and C Measurement
Insulation Measurements
                      Vigilohm IM400 is designed:
                       To monitor the IT power system insulation,
                       To measure:
                          The insulation resistance R (Ω) continuously,
32                                                                                                             DOCA0049EN-02 09/2015
                                                                                                           Vigilohm IM400 - Functions
Configuration by Application
                        Vigilohm IM400 is designed and tested to be compliant with different applications:
                         Power circuits: industrial or marine applications that contain power loads and power electronics such as
                           speed drives, inverters, or rectifiers.
                         Control circuits: auxiliary control circuits used to drive power systems. These circuits contain sensitive
                           loads such as PLCs, IOs, or sensors.
                         Photovoltaic systems: large photovoltaic power generation systems. This application is characterized
                           by high DC rated voltage (1,000 V) and high system leakage capacitance (up to 2,000 µF).
Applications
                        To optimize the measurement performances of Vigilohm IM400 according to the application, set the
                        application parameter by selecting Menu → Settings → Network → App..
                        Set the App. parameter value depending on the type of application on which Vigilohm IM400 is installed:
                        The measurement parameters accessible in the Network menu are automatically preset depending on the
                        application:
                         Filtering
                         Fault Locating
                         V. Adaptor
                         Frequency
                         Injection
                        The Vigilohm IM400 is designed to provide accurate insulation resistance and capacitance measurement
                        on highly disturbed systems with power electronic devices. A filtering function is embedded to improve the
                        measurement stability to avoid display fluctuation, undesired transient insulation, and preventive insulation
                        alarm. The response time associated with this filtering function does not affect the IT power system.
DOCA0049EN-02 09/2015                                                                                                             33
Vigilohm IM400 - Functions
Voltage Adaptors
                      The Vigilohm IM400 can be used with IM400-1700 and PHT1000 voltage adaptors to monitor power
                      systems with a rated voltage higher than 480 Vac L-L.
                      IM400-1700 voltage adaptor can also be used in power systems below 480 Vac/dc to increase the internal
                      impedance of the Vigilohm IM400.
                      Three settings are available for the V. Adaptor parameter.
System Frequency
                      This is the rated frequency of the monitored power system.
                      Four settings are available for the Frequency parameter:
                       DC
                       50 Hz
                       60 Hz
                       400 Hz
34                                                                                                                  DOCA0049EN-02 09/2015
                                                                                                              Vigilohm IM400 - Functions
Injection
                        This is the level of measurement voltage and measurement current that are injected between the
                        monitored power system and ground.
                        Four settings are available for the Injection parameter.
Accuracy by Application
                        The accuracy zones of typical performance for Vigilohm IM400 depend on the application.
                        Example: For photovoltaic systems, the insulation resistance is:
                         ±1 kΩ from 0 to 7 kΩ
                         ±15% from 7 to 50 kΩ with leakage capacitance C = 50 µF
                         ±15% from 7 to 10 kΩ with leakage capacitance C = 500 µF
DOCA0049EN-02 09/2015                                                                                                                   35
Vigilohm IM400 - Functions
Functional Description
                      The Vigilohm monitors the IT system insulation resistance (kΩ) in accordance with the following timing
                      diagram:
                           An insulation decrease is detected on the system. The insulation resistance drops below the
                         preventive insulation alarm threshold. The preventive insulation alarm relay switches and the preventive
                         insulation alarm indicator light lights up.
                             An insulation fault is detected on the system.
                          Once T (insulation alarm delay) has elapsed, Vigilohm IM400 switches to the insulation alarm state.
                         The insulation alarm relay switches and the insulation alarm indicator light lights up.
                           Press the    button to acknowledge the insulation alarm.
                         Both the insulation alarm relay and the preventive insulation alarm relay toggle back to their initial state.
                         Depending on the setup of the I/Os, the preventive insulation alarm relay and the insulation alarm relay
                         may or may not toggle back to their initial states. The timing diagram above represents the case when
                         the I/Os are set up to acknowledge the relays (see page 42).
                             The insulation fault has been corrected or disappeared. Vigilohm IM400 reverts to normal status.
                      When the Vigilohm in the insulation alarm state is not acknowledged by the user, and the insulation rises
                      again above the insulation alarm threshold, then the insulation fault is recorded as transient.
36                                                                                                                DOCA0049EN-02 09/2015
                                                                                                                    Vigilohm IM400 - Functions
Status Information
                        The display and the five indicator lights on Vigilohm IM400 indicate the current status of the product.
The available settings for the insulation alarm and preventive insulation alarm thresholds are as follows:
                        Insulation alarm and preventive insulation alarm thresholds are saved in an internal non-volatile memory.
                        They remain unchanged after a power cut.
                        The preventive insulation alarm threshold must always be set higher than the insulation alarm threshold.
                        An insulation alarm is cleared when the insulation level reaches 20% above the threshold.
DOCA0049EN-02 09/2015                                                                                                                        37
Vigilohm IM400 - Functions
                      NOTE: The preventive insulation alarm time delay setup is not displayed when the preventive insulation
                      alarm threshold value is set to OFF.
38                                                                                                              DOCA0049EN-02 09/2015
                                                                                                           Vigilohm IM400 - Functions
                        On small networks without loads and IT transformer, where the insulation level is high, or during
                        commissioning without loads and without IT transformer, it is recommended to set the parameter to OFF.
                        Detection of disconnection between Vigilohm IM400 and IM400-1700 or PHT1000 voltage adaptors is
                        always active and does not depend on the value of the Disconnect. Inj. parameter.
                        If the injection disconnects, Vigilohm IM400 triggers a product status alarm, described in Disconnected
                        Injection Detection (see page 61). The product status LED becomes red.
To access the insulation alarm relay parameter, select Menu → Settings → I/O Config..
DOCA0049EN-02 09/2015                                                                                                             39
Vigilohm IM400 - Functions
                      When the preventive insulation alarm relay is configured in failsafe (FS) mode:
                       The preventive insulation alarm relay is activated (energized) in the following case:
                         No insulation fault is being detected.
                         The preventive insulation alarm relay is deactivated (de-energized) in the following cases:
                           Preventive insulation fault is being detected.
                           Insulation fault is being detected.
                           A special insulation status is detected (see page 61).
                           The product is inoperative (detected by self-test).
                           The auxiliary power supply is lost.
                           When the user triggers a self-test with relays (selecting Menu → Settings → I/O Config. →
                            Test. w. Relays, set to ON), the preventive insulation alarm relay toggles for 3 seconds
                            (see page 53).
                      When the preventive insulation alarm relay is configured in standard (Std.) mode:
                       The preventive insulation alarm relay is activated (energized) in the following cases:
                         The preventive insulation fault is being detected.
                         Insulation fault is being detected.
                         A special insulation status is detected (see page 61).
                         The product is inoperative (detected by self-test).
                         When the user triggers a self-test with relays (selecting Menu → Settings → I/O Config. →
                          Test. w. Relays, set to ON), the preventive insulation alarm relay toggles for 3 seconds
                          (see page 53).
                         The preventive insulation alarm relay is deactivated (de-energized) in the following cases:
                           No insulation fault is being detected.
                           The auxiliary power supply is lost.
                      When the preventive insulation alarm relay is set up in mirror mode (by selecting Menu → Settings →
                      I/O Config → Prev. Al. Rel → Mirror):
                       The preventive insulation alarm relay mirrors (symmetrically matches) the insulation alarm relay as long
                         as the Vigilohm IM400 is operating correctly (see page 26).
                       The preventive insulation alarm relay stops mirroring the insulation alarms when the Vigilohm IM400 is
                         de-energized or inoperative. This feature can be used to detect an inoperative product.
40                                                                                                              DOCA0049EN-02 09/2015
                                                                                                              Vigilohm IM400 - Functions
The following wiring diagram shows how to wire the Vigilohm IM400 in FS mode:
DOCA0049EN-02 09/2015                                                                                                                 41
Vigilohm IM400 - Functions
                      When the Vigilohm IM400 detects an insulation fault, both the preventive insulation alarm relay and the
                      insulation alarm relay are triggered, depending on the setup.
                       Acknowledgement of relays set to ON
Insulation fault alarm acknowledgement switches back the relays to their initial position.
42                                                                                                               DOCA0049EN-02 09/2015
                                                                                                          Vigilohm IM400 - Functions
Insulation fault alarm acknowledgement does not switch back the relays to their initial position.
DOCA0049EN-02 09/2015                                                                                                               43
Vigilohm IM400 - Functions
                      NOTE: Corrected insulation fault signal is applicable only if the parameter Ack. Al. Relay
                      (acknowledgement insulation alarm relay) is set to ON.
                      In system configurations where the insulation alarm relay is connected to an external signaling device (for
                      example, horns or lamps), the relays are triggered back to their normal position, depending on their setup,
                      when the insulation alarm is acknowledged.
                       Corrected insulation fault signal set to ON
                                After correcting the insulation fault in the power system, the insulation fault alarm relay toggles for
                         3 s.
44                                                                                                                 DOCA0049EN-02 09/2015
                                                                                                            Vigilohm IM400 - Functions
                                 After correcting the insulation fault in the power system, the insulation fault alarm relay does not
                            toggle for 3 s.
DOCA0049EN-02 09/2015                                                                                                              45
Vigilohm IM400 - Functions
Operation
                      A voltage adaptor is required when the device is connected to one of the following systems:
                       system voltage greater than 830 Vac Ph-Ph and the Vigilohm IM400 is connected to an accessible
                         neutral.
                       system voltage greater than 480 Vac and the Vigilohm IM400 is connected to a phase (non-accessible
                         neutral).
                       system voltage greater than 480 Vdc.
                      See the specifications for information about the maximum voltage (see page 84).
                      For Vigilohm IM400 operation without insulation fault location (XD301, XD312, XD308C, or XRM not used),
                      the IM400-1700 voltage adaptor can be used.
                      For Vigilohm IM400 operation with insulation fault location (XD301, XD312, XD308C, or XRM used), the
                      PHT1000 voltage adaptor must be used.
                      NOTE: The V. Adaptor parameter cannot be set up as HV1700 if the parameter Fault locating is set to
                      ON.
V. Adaptor Parameter
                      Configure the V. Adaptor parameter as follows:
                       HV1700 for the IM400-1700 voltage adaptor
                       PHT1000 for the PHT1000 voltage adaptor
46                                                                                                         DOCA0049EN-02 09/2015
                                                                                                          Vigilohm IM400 - Functions
                        The Insulation Fault Locating parameter must be configured to ON for proper operation. The factory
                        value is ON.
                        The signal injected by IM400 is compatible with the XP15, XP50, XP100, and XRM devices. Proceed as
                        follows:
                        1. Use the XRM connected to an XP•• current probe on the injection connection wire close to IM400, and
                            calibrate the XRM to 18.
                        2. Use the XRM on the cables to locate the insulation fault. When the XRM is reporting 18, it means that
                            the insulation fault is on the cable or the load downstream to the clamp.
                        Refer to the Vigilohm Catalog for information about the mobile insulation fault locating devices:
                         XRM locating signal receiver (commercial reference 50278)
                         Open-clamp current probes (commercial references 50494, 50498, and 50499)
                          NOTE: In manual fault location mode with IM400, XGR injector is not necessary.
DOCA0049EN-02 09/2015                                                                                                             47
Vigilohm IM400 - Functions
Exclusion
                      The IMD injects several patented combinations of low frequency voltage into the system. In a system with
                      several incoming feeders, depending on the circuit breaker position, there must be no more than one IMD
                      injecting into the system.
                      The inhibition of injection is managed by the state of inhibition input of Vigilohm IM400, which can, for
                      example, be connected to the auxiliary contacts of the circuit breakers.
                      The injection inhibition input can be configured to use an NO or an NC contact as shown below:
                      Contact type           Injection activated when the contact is...     Injection deactivated when the contact is...
                      NO (factory value)     Open                                           Closed
                      NC                     Closed                                         Open
                      If                     Then
                       If D1 is closed and The two Vigilohm IM400 devices are active:
                       D2 is open           Vigilohm IM400 no.1 monitors the system insulation.
                                             Vigilohm IM400 no.2 only monitors the insulation of the transformer 2 connection as far as D2.
                       If D1 is closed and  Vigilohm IM400 no.1 is active and monitors the system insulation.
                       D2 is closed         Vigilohm IM400 no.2 must be inhibited.
48                                                                                                                      DOCA0049EN-02 09/2015
                                                                                                             Vigilohm IM400 - Functions
                        If                              Then
                        If the coupling (C) is closed   The same applies as in the exclusion example above involving two incoming
                                                        feeders (see page 48).
                         If the coupling is open and   The two Vigilohm IM400 devices are active:
                         D1 is closed                   Vigilohm IM400 no.1 monitors the insulation of system 1.
                         D2 is closed                   Vigilohm IM400 no.2 monitors the insulation of system 2.
                        Vigilohm IM400 no.2 must be inhibited when the following three conditions are met:
                         D1 is closed.
                         D2 is closed.
                         C is closed.
DOCA0049EN-02 09/2015                                                                                                               49
Vigilohm IM400 - Functions
50                                                                                                              DOCA0049EN-02 09/2015
                                                                                                             Vigilohm IM400 - Functions
                        There are two methods to determine the logic driving the injection inhibition input of each IMD:
                        Method 1: Give a priority to each IMD using indexes of incoming feeders. In this example:
                           Priority of IM400 no.1 is 1 (highest priority),
                           Priority of IM400 no.2 is 2,
                           Priority of IM400 no.3 is 3,
                           Priority of IM400 no.4 is 4 (lowest priority).
                           IM400 no.1 with the highest priority is always injecting, its injection inhibition input is left unwired.
                           IM400 no.2 with the priority 2 always injection into the system except when there is a closed path
                            between itself and one IMD with a higher priority, that is, IM400 no.1 in this case. The closed path occurs
                            when D2, C1 and D1 are closed.
                            Therefore:
                            Injection inhibition of IM400 no2 =
                            D2 AND C1 AND D1
                            The representation in Ladder PLC programming language is as follows:
                           IM400 no.3 with the priority 3 always injection into the system except when there is a closed path
                            between itself and one IMD with a higher priority, that is, IM400 no.2 and IM400 no.1 in this case.
                            The closed path occurs when:
                             (D3, C2, and D2) are closed, or
                             (D3, C2, C1, and D1) are closed.
                            Therefore:
                             Injection inhibition of IM400 no.3 =
                              (D3 ANDC2 ANDD2) OR (D3 AND C2 AND C1 AND D1)
                             Injection inhibition of IM400 no.3 =
                              (D3 AND C2) AND (D2 OR (C1 AND D1))
DOCA0049EN-02 09/2015                                                                                                               51
Vigilohm IM400 - Functions
                           IM400 no.4 with the priority 4 always injection into the system except when there is a closed path
                            between itself and one IMD with a higher priority, that is, IM400 no.3, IM400 no.2, and IM400 no.1 in
                            this case.
                            The closed path occurs when:
                             (D4, C3, and D3) are closed, or
                             (D4, C3, C2, and D2) are closed, or
                             (D4, C3, C2, C1, and D1) are closed.
                            Therefore:
                             Injection inhibition of IM400 no.4 =
                              (D4 AND C3 AND D3) OR (D4 AND C3 AND C2 AND D2) OR (D4 AND C3 AND C2 AND C1 AND D1)
                             Injection inhibition of IM400 no.3 =
                              (D4 AND C3) AND (D3 OR (C2 AND D2) OR (C2 AND C1 AND D1))
                            The representation in Ladder PLC programming language is as follows:
52                                                                                                                 DOCA0049EN-02 09/2015
                                                                                                             Vigilohm IM400 - Functions
Self-Test
Description
                        The Vigilohm has a self-test function for testing:
                         The product: indicator lights, internal electronics
                         The measurement system, and the insulation alarm and preventive insulation alarm relays
Self-Test OK
                        If the self-test is successful, the following screen appears for three seconds:
                        After that, a measurement phase shown by a progress bar at the bottom of the screen appears, and then
                        one of the status screens automatically appears (system insulation resistance measurement or insulation
                        fault alarm).
Self-Test Not OK
                        If the self-test is not successful, the product automatically restarts. If the problem persists:
                         The red status indicator LED switches on.
                         The insulation alarm relay is triggered
                         A product inoperative message is displayed.
                        If this happens, briefly disconnect the auxiliary power supply of the Vigilohm. If the problem persists,
                        contact the Schneider Electric Customer Care Center.
DOCA0049EN-02 09/2015                                                                                                               53
Vigilohm IM400 - Functions
54                           DOCA0049EN-02 09/2015
                          Vigilohm IM400
                          Vigilohm IM400 - Human Machine Interface
                          DOCA0049EN-02 09/2015
                        Chapter 4
                        Human Machine Interface
Presentation
                        The Vigilohm features a sophisticated and intuitive human machine interface (HMI) with signaling indicator
                        lights, a graphic display, and contextual menu buttons for accessing the information required to operate
                        the Vigilohm and make parameter settings.
DOCA0049EN-02 09/2015                                                                                                           55
Vigilohm IM400 - Human Machine Interface
56                                         DOCA0049EN-02 09/2015
                                                                                                    Vigilohm IM400 - Human Machine Interface
Presentation
                        The diagram below illustrates the various elements for operating the Vigilohm.
                        1   Screen identification area containing a menu icon, and the name of the menu or parameter
                        2   Information area for displaying screen-specific details (measurement, insulation alarm, setting)
                        3   Navigation buttons
Navigation Buttons
                        The navigation buttons enable quick and intuitive navigation:
                        4                   Contextual menu                  For scrolling down the display or moving to the next item in a list
                                            button 2
                                                                             For moving one digit to the left within a numerical value. If the
                                                                             digit on the far left is already selected, pressing the button loops
                                                                             you back to the digit on the right.
                                                                             For moving 1 digit to the right within a numerical value
DOCA0049EN-02 09/2015                                                                                                                           57
Vigilohm IM400 - Human Machine Interface
Information Icons
                     This table describes the icons provided for information in the information area of the LCD display. Among
                     other things, they indicate which menu is selected or the insulation alarm status.
                      Icon       Description
                                 Main menu
Trend menu
Product identification
58                                                                                                         DOCA0049EN-02 09/2015
                                                                                            Vigilohm IM400 - Human Machine Interface
Status Screens
Presentation
                        The default screen shows the insulation resistance value of the system. This screen is automatically
                        replaced by an alert screen when an insulation alarm occurs.
                        The screen backlight flashes to indicate an insulation alarm.
                        Each insulation measurement screen displays a status bar at the bottom that provides additional
                        information. In general, it shows the date and time of the insulation fault.
                        1 Insulation value
                        2 Progress bar for the refresh time
                        3 Bargraph indicating the insulation level on a logarithmic scale. The      symbol indicates the insulation
                          alarm threshold value.
                        4 Status bar displaying additional information related to the current insulation alarm state. Different types
                          of status bar are available (see note below).
                        5 Contextual buttons for navigating the insulation screens or for launching a manual self-test.
                        NOTE: The different types of status bar are:
                         Current date and time: displayed when product is in normal operation (no insulation fault detected)
                         Insulation alarm active time delay: an insulation fault has been measured and the insulation alarm time
                          delay is active. This bar shows a progress bar for the time delay.
                         Insulation alarm pickup date and time
                         Insulation alarm dropout date and time
                         Insulation alarm relay acknowledgment
DOCA0049EN-02 09/2015                                                                                                             59
Vigilohm IM400 - Human Machine Interface
Acknowledge the transient insulation fault by pressing the contextual menu button.
60                                                                                                             DOCA0049EN-02 09/2015
                                                                                               Vigilohm IM400 - Human Machine Interface
Presentation
                        The special status screens are displayed depending on events that occur during the product life. The
                        screens depend on the event type but always trigger the red product status indicator light and the insulation
                        alarm relay is active. If the preventive insulation alarm relay is configured in mirror mode, it is also triggered
                        and no longer mirrors the insulation alarm relay.
Overvoltage
                        The overvoltage state is triggered when the voltage of the monitored system becomes too high. For details
                        on the Vigilohm IM400 limits, refer to the product performances. In case of overvoltage, the Vigilohm IM400
                        is no longer able to monitor the IT system and automatically disconnects of the power system until the
                        product is manually reset by briefly disconnecting the auxiliary power supply.
If the Disconnect Inj. parameter is set to OFF, the Vigilohm IM400 displays R > 10 MΩ.
Inoperative Product
                        The inoperative product state is triggered when the Vigilohm IM400 is inoperative.
DOCA0049EN-02 09/2015                                                                                                                  61
Vigilohm IM400 - Human Machine Interface
Modifying Parameters
Presentation
                     To modify any of the values, you must be familiar with how the interface menus are structured and the
                     general navigation principles. For more information about how the menus are structured, refer to the
                     Vigilohm IM400 menu structure (see page 56).
                     To modify the value of a parameter, follow either of the two methods described below:
                      Select an item (value plus unit) in a list.
                      Modify a numerical value, digit by digit.
                     The parameters listed below are the only ones where the numerical value can be modified:
                      date
                      time
                      password
                      Modbus address
Saving a Parameter
                     After you have confirmed the modified parameter, one of the two screens appears:
                      If the parameter has been saved correctly, the screen displays Saved and then automatically reverts to
                        the previous display.
                      If the parameter has not been saved correctly, the screen displays Error and the editing screen remains
                        active. It happens when:
                         a value is deemed to be out of range (for example the value is classed as forbidden),
                         there are several interdependent parameters.
Exiting an Entry
                     To exit the current parameter entry, press the ESC button. The screen reverts to the previous display.
                      Step         Action
                          1        Navigate to MENU → Settings → Password.
                          2
                                   Select Modify Password. Press           to edit the new password digit by digit (editing starts from the digit
                                   furthest to the right).
                          3
                                   Use      to increase the value of the digit. It will automatically roll over from 9 to 0.
NOTE: Keep the button pressed down to accelerate scrolling through the values.
62                                                                                                                             DOCA0049EN-02 09/2015
                                                                                                     Vigilohm IM400 - Human Machine Interface
                        Step       Action
                            4
                                   Press      to move to the next digit. Pressing this button on the last digit (furthest left) loops you back to
                                   the first one.
                            5      Repeat steps 3 and 4 for all other digits.
                            6
                                   Press    to save the new password. A message indicates that the password was saved successfully.
                                   The screen reverts to the previous one.
                            7
                                   Select Activation. Press       .
                            8
                                   Change value list to ON by pressing the  or    arrows. Validate the entry by selecting           . A message
                                   indicates that the parameter was saved successfully.
                                   Result: The password protection is now active.
                        Step       Action
                            1      Press the contextual menu navigation keys to navigate to the parameter to edit.
                            2
                                   Press      . The screen to enter the password is displayed.
                                   The first (furthest left) digit is selected and ready to edit.
                            3
                                   Use      to increase the value of the digit. It will automatically roll over from 9 to 0.
                                   NOTE: Keep the          button pressed down to accelerate scrolling through the values.
                            4
                                   Press      to move to the next digit. Pressing this button on the last digit (furthest right) loops you back to
                                   the first one.
                            5      Repeat steps 3 and 4 for all other digits.
                            6
                                   Press      to validate the password entry. If the password has been entered correctly, the protection
                                   system stays unlocked for 30 seconds or as long as you are editing parameters.
                                   If the password has been entered incorrectly, an error message is displayed and you must enter the
                                   password again. Use the ESC button to revert to the previous screen.
DOCA0049EN-02 09/2015                                                                                                                           63
Vigilohm IM400 - Human Machine Interface
Clock
Description
                     Vigilohm IM400 uses the date and time parameter to time-tag the system insulation faults recorded.
                     The time must be set:
                      whenever the power supply is interrupted,
                      when switching from winter to summer time and back.
                     If the auxiliary power supply is interrupted, Vigilohm IM400 retains the date and time setting from
                     immediately before the interruption.
Icon
                     When Vigilohm IM400 is powered up, the clock icon flashes on the system monitoring screens to indicate
                     that the clock needs to be set.
                     Pressing the top contextual button displays the clock setup screen.
Setting
                     To set the date and time, refer to the procedure for modifying a numerical value (see page 62).
Date/Time Format
                     The date is displayed in the format: dd.mm.yyyy.
                     The time is displayed using the 24-hour clock in the format: hh:mm.
64                                                                                                           DOCA0049EN-02 09/2015
                                                                                                  Vigilohm IM400 - Human Machine Interface
Description
                        Vigilohm IM400 records the details of the 30 most recent insulation fault events that have triggered one of
                        the 2 statuses below:
                         preventive insulation alarm
                         insulation alarm
                        Event 1 is the one that was recorded most recently and event 30 is the oldest recorded event.
                        The oldest event is deleted when a new event occurs. Due to the rolling buffer the Vigilohm IM400 may
                        show 28 logs maximum. To reset all the events, select Settings → Reset → Reset Logs.
                        Using this information, the performance of the distribution system can be improved and maintenance work
                        facilitated. It is also available through Modbus (see page 67).
                        Legend         Description
                        1              Insulation fault value recorded
                        2              Type of insulation fault recorded: insulation alarm, preventive insulation alarm, transient insulation
                                       alarm
                        3              Date and time when the insulation alarm fault, preventive insulation alarm, or transient insulation
                                       fault occurred
                        4              Date and time when the event disappeared:
DOCA0049EN-02 09/2015                                                                                                                           65
Vigilohm IM400 - Human Machine Interface
Trend Screens
Presentation
                     Vigilohm IM400 records and can display curves of the average of the system insulation over the following
                     durations:
                      last hour (1 point every 2 minutes)
                      last day (1 point per hour)
                      last week (1 point per day)
                      last month (1 point per day)
                      last year (1 point per month)
                     The chart scale automatically adjusts to the shown data to optimize the display accuracy.
                     The curves show a general trend how the system insulation evolves over time. They are calculated from
                     averages related to shorter or longer durations depending on the charts. So charts may not show transient
                     insulation faults when they are smoothed over time.
Trend Screen
                      Legend          Description
                      1               Trend
                      2               Current value of the insulation alarm threshold
                      3               Vertical dotted line: indicates a power interruption (duration undefined)
                      4               Squared area: indicates that the injection has been inhibited
66                                                                                                                DOCA0049EN-02 09/2015
                          Vigilohm IM400
                          Vigilohm IM400 - Communication
                          DOCA0049EN-02 09/2015
                        Chapter 5
                        Communication via Modbus RS-485
DOCA0049EN-02 09/2015                                                                67
Vigilohm IM400 - Communication
Communication Parameters
                    Before initiating any communication processes, configure the Modbus communication port via the HMI on
                    Vigilohm IM400 selecting Menu → Settings → Modbus.
                    In point-to-point mode, when the device is directly connected to a computer, the reserved address 248 can
                    be used to communicate with the device whatever the device internal address.
The yellow indicator light indicates the status of the activity on the Modbus RS-485 bus as follows:
                     If                                   Then
                     If the indicator light is flashing   Communication on the bus is active.
                     If the indicator light is off        There is no active communication between master and slave.
                    NOTE: The yellow indicator light flashes on every valid Modbus frame even if the Vigilohm IM400 is not
                    addressed directly.
68                                                                                                                 DOCA0049EN-02 09/2015
                                                                                                          Vigilohm IM400 - Communication
Modbus Functions
DOCA0049EN-02 09/2015                                                                                                                69
Vigilohm IM400 - Communication
Table Format
                         Modbus register tables have the following columns:
                            Register address: Address of register encoded in the Modbus frame, in hexadecimal (hex) and decimal
                             (dec) formats
                            Register number: corresponds to the Register Address + 1, in hexadecimal (hex) and decimal (dec)
                             formats
                            RW: Whether the register is read only (R) or read/write (RW)
                            Unit: The unit the information is expressed in
                            Type: The encoding data type
                            Range: The permitted values for this variable, usually a subset of what the format allows
                            Description: Provides information about the register and the values that apply
System Status
Monitoring
70                                                                                                                           DOCA0049EN-02 09/2015
                                                                                                 Vigilohm IM400 - Communication
Trending Data
DOCA0049EN-02 09/2015                                                                                                           71
Vigilohm IM400 - Communication
72                                                                                                    DOCA0049EN-02 09/2015
                                                                                                 Vigilohm IM400 - Communication
Diagnostic
Settings
DOCA0049EN-02 09/2015                                                                                                             73
Vigilohm IM400 - Communication
74                                                                                                  DOCA0049EN-02 09/2015
                                                                                                              Vigilohm IM400 - Communication
Log
DOCA0049EN-02 09/2015                                                                                                                       75
Vigilohm IM400 - Communication
Example of an Event
                      The two records below represent an insulation alarm that occurred at 12:00 on October 1, 2010 and was
                      acknowledged at 12:29.
                      Record number: 1
Record number: 2
76                                                                                                          DOCA0049EN-02 09/2015
                                                                                                       Vigilohm IM400 - Communication
                        b15    b14    b13   b12   b11   b10   b09    b08   b07   b06   b05   b04   b03    b02   b01   b00   Word
                        0      0      0     0     0     0     0      0     R4    Y     Y     Y     Y      Y     Y     Y     Word 1
                        0      0      0     0     M     M     M      M     WD    WD    WD    D     D      D     D     D     Word 2
                        SU     0      0     H     H     H     H      H     iV    0     mn    mn    mn     mn    mn    mn    Word 3
                        ms     ms     ms    ms    ms    ms    ms     ms    ms    ms    ms    ms    ms     ms    ms    ms    Word 4
                           M - Months
                             1 byte
                             Value from 1...12
                           D - Days
                             1 byte
                             Value from 1...31
                           H - Hours
                             1 byte
                             Value from 0...23
                           mn - Minutes
                             1 byte
                             Value from 0...59
                           ms - Milliseconds
                             2 byte
                             Value from 0...59999
                        The following fields are in CP56Time2a standard and are considered as optional:
                         WD - Week Day
                           If not used, set to 0 (1 = Sunday, 2 = Monday...)
                           Value from 1...7
                           SU - Summertime
                             If not used, set to 0 (0 = standard time, 1 = summertime)
                             Value from 0...1
DOCA0049EN-02 09/2015                                                                                                              77
Vigilohm IM400 - Communication
78                               DOCA0049EN-02 09/2015
                          Vigilohm IM400
                          Vigilohm IM400 - Commissioning, Maintenance, and Troubleshooting
                          DOCA0049EN-02 09/2015
                        Chapter 6
                        Maintenance and Troubleshooting
DOCA0049EN-02 09/2015                                                                                       79
Vigilohm IM400 - Commissioning, Maintenance, and Troubleshooting
Safety Precautions
Safety Precautions
                     The following safety precautions must be thoroughly implemented before commissioning or attempting to
                     repair electrical equipment or carry out maintenance. Carefully read and follow the safety precautions
                     described below.
                                                                       DANGER
                      HAZARD OF ELECTRIC SHOCK, ARC FLASH OR BURNS
                         Wear suitable personal protective equipment and follow the currently applicable electrical safety
                          instructions. See, for example, standard NFPA 70E when carrying out work in the USA.
                         Only qualified personnel should maintain this equipment. Such work should be performed only after
                          reading all the installation instructions.
                         Turn off all power supplying this equipment before working on or inside it.
                         NEVER work alone.
                         Beware of potential hazards and wear personal protective equipment.
                      Failure to follow these instructions will result in death or serious injury.
                                                                   NOTICE
                      HAZARD OF PRODUCT DAMAGE
                         Never open the Vigilohm unit.
                         Do not attempt to repair any components in the Vigilohm range, either in the unit or an accessory.
                      Failure to follow these instructions can result in equipment damage.
80                                                                                                           DOCA0049EN-02 09/2015
                                                                     Vigilohm IM400 - Commissioning, Maintenance, and Troubleshooting
Commissioning
DOCA0049EN-02 09/2015                                                                                                              81
Vigilohm IM400 - Commissioning, Maintenance, and Troubleshooting
Self-Test
                        The Vigilohm performs a series of self-tests on start-up, and then at regular intervals during operation to
                        detect any potential inoperations in its internal and external circuits. For more information on the self-test
                        function, refer to the relevant section (see page 53).
Troubleshooting
                        The table describes the potential problems and their probable causes. It also indicates the checks that can
                        be carried out or provides possible solutions for each scenario. If you are still unable to resolve a problem
                        after consulting the table, contact your Schneider Electric regional sales representative for assistance.
The product status indicator light is red    The Vigilohm injection circuit is cut off.          Briefly disconnect the auxiliary power supply for
and the display indicates that an error                                                          the Vigilohm.
occurred during the self-test.
Although the Vigilohm is being supplied      Inoperative indicator light.                        Restart the self-test and check that the product
with power, the product status indicator                                                         status indicator light lights up briefly.
light does not light up.
The insulation alarm indicator light does    Inoperative indicator light.                        Restart the self-test and check that the insulation
not light up in the event of an insulation                                                       alarm indicator light lights up briefly.
fault.
82                                                                                                                             DOCA0049EN-02 09/2015
                           Vigilohm IM400
                           Vigilohm IM400 - Specifications
                           DOCA0049EN-02 09/2015
                        Chapter 7
                        Specifications
Specifications
Specifications
                           Characteristic                                                                        Values
                           AC or mixed                             Phase-to-phase voltage                        ≤ 830 Vac(1)(2) or
                           AC/DC IT systems                  (1)   with IM400 connected to neutral
                                                                                                                 ≤ 1,700 Vac(3)
                                                                   With IM400 connected to phase                 ≤ 480 Vac(1)(2) or
                                                                                                                 ≤ 1,000 Vac(3)
                                                                   Frequency                                     45...440 Hz
                           DC or rectified systems                 Line voltage                                  < 480 Vdc(1)(2) or
                                                                                                                 ≤ 1,200 Vdc(3)(4)
                           (1) When the insulation monitor is linked to a non-insulated inverter, it is necessary to take into account the DC voltage
                               limit rather than the AC limit.
                           (2) IM400 directly connected to the power system.
                           (3) IM400 used with IM400-1700 or PHT1000 subassemblies.
                           (4) 1000 Vdc with IM400-1700 and 1200 Vdc with PHT1000.
Electrical Characteristics
                           Characteristic                                                                        Values
                           Range for insulation resistance readings                                              10 Ω...10 MΩ
                           Range for capacitance readings                                                        0.01...500 µF
                                                                                                                 (2,000 µF for PV applications)
                           Insulation fault signaling              Number of thresholds                          2 (protected password)
                                                                   Threshold settings         Insulation alarm   0.04...500 kΩ
                                                                                              Preventive         1 kΩ...1 MΩ
                                                                                              insulation alarm
                           Hysteresis ont the thresholds of insulation alarm and preventive insulation            Setting threshold when the insulation
                           alarm                                                                                    alarm triggers
                                                                                                                  Setting threshold +20% when the
                                                                                                                    insulation alarm releases
                           Time delay for signaling                                                              0...7,200 s
                           Dielectric strength                                                                   4000 Vac / 5500 Vdc
                                                                                                                 7.3 kV impulse
                           Auxiliary supply voltage                50/60/400 Hz                                  100...440 Vac
                                                                   DC                                            100...440 Vdc
                           Auxiliary supply voltage tolerances                                                   +/-15 %
                           Monitored system voltage                IM400 directly connected                      +5%
                           tolerances
                                                                   IM400 used with IM400-1700                    +15%
                           Maximum device consumption                                                            25 VA / 10 Ω
                           Measurement voltage                     Variable                                      15 Vp, 33 Vp, 120 Vp
                           Measurement current                     Variable                                      375 µAp, 825 µAp, 3 mAp
                           Fault locating current                                                                3.75 mAp
                           Extraneous DC voltage Ufg                                                             506 V
                           Device operating test                                                                 Self-test / manual test
                           Internal impedance                      At 50/60/400 Hz                               40 kΩ
                           Internal resistance Ri of the measuring circuit                                       40 kΩ
DOCA0049EN-02 09/2015                                                                                                                                 83
Vigilohm IM400 - Specifications
                       Characteristic                                                          Values
                       Output contact                  Quantity                                2 (standard and failsafe)
                                                      Type of contact                          SPDT one changeover contact
                                                      Operating principle                      N/O N/C operation
                                                      Electrical endurance                     30,000 cycles
                                                      Breaking capacity      250 Vac           3A
                                                                             48 Vdc            1 A, 10 mA minimum load
                                                      Minimum switching load 24 Vac/dc         2 mA
                       Injection inhibition (voltage supplied by IM400)      Voltage           24 Vdc
                                                                             Current           5 mA
                       Installation category                                                   300 V/OVC III, degree of pollution 2
                                                                                               600 V/OVC II, degree of pollution 2
                       Characteristic                                                          Value
                       Dielectric strength                                                     15.4 kV impulse
                       Measurement current             Variable                                30 µAp, 60 µAp, 220 µAp
                       Extraneous DC voltage Ufg                                               1,150 Vdc
                       Internal impedance             At 50/60/400 Hz                          430 kΩ
                       Internal resistance Ri of the measuring circuit                         430 kΩ
Mechanical Characteristics
                       Characteristic                                                          Value
                       Weight                                                                  0.75 kg
                       Thermoplastic case             Mounting                                 Flush mount or on grid
                       Degree of protection           Front                                    IP54
                                                      Back                                     IP20
Other Characteristics
                       Characteristic                                                          Value
                       Temperature range              For operation                            –25...+55 °C (65 °C)(1)
                                                      For storage                              –40...+70 °C
                       Use                                                                     Indoors
                       Altitude                                                                Up to 3000 m
                       Degree of pollution                                                     2
                       Overvoltage category                                                    300 V / OVCIII, 600 V / OVCII
                       Standards                      Product                                  IEC 61557-8
                                                      Safety                                   IEC 61010-1, UL 508, C22.2 no. 14-05
                                                      Installation                             IEC 60364-4-41
                                                      Output contact                           IEC 61810-2
                       (1) With IM400-1700 voltage adaptor and 230 V ±15 % auxiliary supply.
                       (2) Suitable for use in all climates:
                        Damp heat, equipment not operating (IEC 60068-2-30)
                        Damp heat, equipment operating (IEC 60068-2-56)
                        Salt mist (IEC 60068-2-52)
84                                                                                                                  DOCA0049EN-02 09/2015
                        Vigilohm IM400
                        Glossary
                        DOCA0049EN-02 09/2015
Glossary
                        I
Insulation Alarm
                        The insulation alarm is triggered when the insulation level on the monitored network goes below the
                        configured threshold.
                        P
Preventive Insulation Alarm
                   The preventive insulation alarm is triggered when the insulation level on the monitored network goes below
                   the configured threshold – this value cannot be set lower than the Insulation Alarm threshold.
                        T
Transient Fault
                        The transient fault appears when the insulation alarm triggers and the insulation level on the monitored
                        network has gone back above the configured threshold without user acknowledging the insulation alarm.
DOCA0049EN-02 09/2015                                                                                                         85
DOCA0049EN-02
Schneider Electric Industries SAS   As standards, specifications and designs change from time to time, please ask for confirmation
35, rue Joseph Monier               of the information given in this publication.
CS30323
F - 92506 Rueil Malmaison Cedex
www.schneider-electric.com 09/2015