ONLINE UPS
Master II Series (1P/1P)-Tower
PRO800-QS/QL SERIES 1-10KVA
PROLiNK Master II Series (1P/1P) Tower Type is a new UPS system series with output
power factor 1.0. The UPS design is using true online double-conversion technology
which provides higher charging current and it can be set via LCD display. The system
is designed to provide protection for critical loads such as sensitive networks, small
computer centres, servers, medical equipment, telecom applications as well as
industrial applications. High input power factor correction in the system improves
the efficiency and reduces overall losses.
For 6KVA and 10KVA units, DSP control technology is implemented for the system to
have improve performance and real time harmonic cancellation. UPS is equipped
with 3-stage smart charging design to optimize battery performance. This feature
extends the useful service life of battery and optimizes battery recharge time. External
battery chargers and battery extension assembly are made available for longer
runtime applications.
Users can easily monitor and access to their UPS status from a comprehensive LCD
display. The UPS systems have USB and RS-232 communication ports as standard,
with a built-in intelligent slot for additional adapters, protocol converters and relay
contact cards. SNMP option is also available for power management via SNMP manager
and web browser.
The Master II series (1P/1P) Tower p.f 1.0 Type is available in capacities ranging from
1KVA to 10KVA. For those applications which require longer backup, long run models
with adjustable battery number options are available for 6KVA and 10KVA. Parallel
Redundant configuration (N+X) is available as an option for 6KVA and 10KVA units.
In addition, Emergency Power Off (EPO) function is also available for UPS models and
which is used to protect the personnel and the equipment in case of fire outbreak or
other types of emergency.
• True double-conversion                                      • Low input THDi to reduce power system pollution
• Microprocessor control optimizes reliability*               • Adjustable charging current via LCD panel*
• Output power factor 1                                       • Generator compatible
• Input power factor correction                               • DSP technology guarantees high performance
• Wide input voltage (110V–300V)                              • Wide input voltage range (110-300 VAC)
• 50/60Hz Frequency Converter Mode                            • Active input power factor correction 0.99
• ECO mode energy saving*                                     • SNMP/USB/RS-232 communications
• Emergency power off (EPO) function                          • Optional N+X parallel redundancy
• Provides over voltage cut-off protection and                • Optional OVCD protection
  surge immunity by MOV for full time
  equipment protection*
 *Only available for 1-3KVA models    Only available for 6-10KVA models
 Local Area    Telecommunication        Data         Electro-Medical       Storage         Emergency      E-Business
  Network            Devices           Centre             Device            PLCS             Alarm     (Server Farms,
   (LAN)                                                                                    Devices     ISP/ASP/POP)
                                                                                                                   25
                                                                                                                      ONLINE UPS
Rear Panel
1-3KVA
 1.   Programmable outlets: connect to non-critical loads              6. RS-232 communication port
 2.   Output receptacles: connect to mission-critical loads            7. Intelligent slot
 3.   AC input                                                         8. Emergency power off function connector (EPO)
 4.   Network/Fax/Modem surge protection                               9. External battery connection
 5.   USB communication port                                           10. Cooling fan
               6                                                  6                                         6
 5                                   7            5                                       7        5                              7
                                                  8                                                8
 8                                                                                        4                                       4
 4                                   9                                                    9                                       9
                                                 10
 10                                                                                                10
                                     1
                                                                                          1                                       1
                                     2
 3                                                                                        2
                                                  3                                                3
                                                                                                                                  2
        PRO801-QS/PRO8015-QS                                      PRO802-QS                                 PRO803-QS
 6-10KVA
 1.   RS-232 communication port                                             8. Maintenance bypass switch
 2.   USB communication port                                                9. Input circuit breaker
 3.   Emergency power off function connector (EPO connector)                10. Output receptacles: connect to mission-critical loads
 4.   Share current port (only available for parallel configuration)        11. Output circuit breaker for receptacles
 5.   Parallel port (only available for parallel configuration)             12. Output terminal: connect to mission-critical loads
 6.   Intelligent slot                                                      13. External battery connector
 7.   Cooling fan                                                           14. Utility input terminal
          1   2 3      4        5                             1       2 3    4        5
                                      6                                                       6
                                      7                                                       7
                                     13                                                       13
  8                                                   8
                                      9                                                       9
 11                                                   11
 10                                                   10
                     12    14                                               12   14
          PRO806-QS/PRO810-QS                                 PRO806-QL/PRO810-QL
26
                                                                                                                                                                        ONLINE UPS
Full Specifications
MODEL                                                 PRO801-QS                        PRO8015-QS                              PRO802-QS                               PRO803-QS
PHASE                                                                                                 Single phase with ground
CAPACITY*                                        1000 VA / 1000 W                   1500 VA / 1500W                          2000 VA / 2000 W                     3000 VA / 3000 W
INPUT
Nominal Voltage                                                                     100/110/115/120 /127 VAC or 200/208/220/230/240 VAC
                                                                                     55 - 150 VAC ± 3 % or 110 - 300 VAC ± 3 % at 50% load
Voltage Range
                                                                                    80 - 150 VAC ± 3 % or 160 - 300 VAC ± 3 % at 100% load
Frequency Range                                                                                             40Hz ~ 70Hz
Power Factor                                                                                 ŝ 0.99 @ nominal voltage (100% load)
THDi%                                                                                                          Ŝ5%
OUTPUT
Output Voltage                                                                    100*/110*/115*/120 /127 VAC or 200*/208*/220/230/240 VAC
AC Voltage Regulation (Batt. Mode)                                                                             ± 1%
Frequency Range (Synchronized Range)                                                                   47 ~ 53 Hz or 57~63Hz
Frequency Range (Batt. Mode)                                                                      50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
Current Crest Ratio                                                                                             3:1
Harmonic Distortion                                                                  Ŝ2% THD (Linear Load), Ŝ4 % THD (Non-linear Load)
            AC to DC                                                                                           Zero
Transfer
            Inverter to Bypass                                                                             4 ms (Typical)
Time
            ECO to Battery Mode                                                                     8 ms (Typical), 10 ms (max)
Waveform (Batt. Mode)                                                                                      Pure Sinewave
EFFICIENCY
Line Mode                                                 ŝ89% @ battery fully charged                                              ŝ91% @ battery fully charged
ECO Mode                                                                                          ŝ96% @ battery fully charged
Battery Mode                                                             ŝ88%                                                                     ŝ90%
BATTERY
Battery Type                                12 V / 9 AH       12 V / 7 AH               12 V / 9 AH            12 V / 9 AH     12 V / 7 AH      12 V / 7 AH    12 V / 9AH      12 V / 7AH
Numbers                                          2                 3                        3                         4             6               8              6               8
Typical Recharge Time                                                       3 hours recover to 95% capacity for internal battery@ 2A charging current
                                               100/110/115/120 /127 VAC models: default 2A, max. 8A adjustable
Charging Current                                                                                                                             Default: 2A, Max: 8A adjustable
                                              200/208/220/230/240 VAC models: default 2A, max. 12A adjustable
                                                                                                         54.8VDC                 82.2VDC       109.6VDC ±      82.2VDC         109.6 VDC
Charging Voltage                          27.4VDC ± 1% 41.1VDC ± 1%             41.1VDC ± 1%
                                                                                                           ± 1%                    ± 1%            1%            ± 1%            ± 1%
INDICATORS
LCD Panel                                                              Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicator
ALARM
Battery Mode                                                                                          Sounding every 5 seconds
Low Battery                                                                                           Sounding every 2 seconds
Overload                                                                                               Sounding every second
Fault                                                                                                  Continuously sounding
PHYSICAL
Dimension, D x W x H (mm)                                         397 x 145 x 220                                                            421 x 190 x 318
Net Weight (without battery) (kgs)              6.6                6.6                      7                     9.9              9.9             9.9           12.3            12.3
Net Weight (w/ built-in battery) (kgs)         11.7                13                      14.6                   20.3             23.2            28.5           28               33
ENVIRONMENT
Humidity                                                                                    20-95 % RH @ 0- 45°C (non-condensing)
Noise Level                                                                            Less than 50dBA @ 1 Meter with Fan speed control
MANAGEMENT
Smart RS-232 or USB                                                      Supports Windows 2000/2003/XP/Vista/2008, Windows 7/8/10, Linux and MAC
Optional SNMP                                                                     Power management from SNMP manager and web browser
*Derate capacity to 80% when the output voltage is adjusted to 100VAC/200VAC/208VAC.
                                                                                                                                                                                            27
                                                                                                                                                                         ONLINE UPS
Full Specifications
 MODEL                                                                       PRO806-QS/QL                                                           PRO810-QS/QL
 PHASE                                                                                                     1 phase in / 1 phase out
 CAPACITY                                                                 6000 VA / 6000 W                                                        10000 VA / 10000 W
 INPUT
 Nominal Voltage                                                                                            208/220/230/240 VAC
                                                                                                        110-300 VAC @ 0 ~60% load
 Voltage Range                                                                                         140-300 VAC @ 60 ~ 80% load
                                                                                                       176-300 VAC @ 80 ~ 100% load
 Frequency Range                                                                                           46~54 Hz or 56~64 Hz
 Phase                                                                                                     Single phase with ground
 Power Factor                                                                                                 ŝ 0.99 @ full load
 THDi                                                                                              <4% @100% Load ; <6% @50% Load
 OUTPUT
 Output Voltage                                                                                             208/220/230/240 VAC
 AC Voltage Regulation (Batt. Mode)                                                                                  ± 1%
 Frequency Range (Synchronized Range)                                                                       46~54 Hz or 56~64 Hz
 Frequency Range (Batt. Mode)                                                                         50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
 Current Crest Ratio                                                                                               3:1 (max.)
 Harmonic Distortion                                                                     Ŝ1 % THD (Linear Load) ; Ŝ 4 % THD (Non-linear Load)
 Transfer    AC Mode to Batt. Mode                                                                                    Zero
 Time        Inverter to Bypass                                                                                       Zero
 Waveform (Batt. Mode)                                                                                          Pure Sinewave
             AC Mode                                                                        100%~110% 10min ; 110%~130%: 1min ; >130% : 1sec
 Overload
             Battery Mode                                                                100%~110%: 30sec ; 110%~130%: 10sec ; >130% : 1sec
 EFFICIENCY
 AC Mode                                                                                                              94%
 Battery Mode                                                                                                         91%
 BATTERY
           Battery Type                                                       12 V / 7 Ah                                                             12 V / 9 Ah
           Numbers                                                                                                  16
 Standard
           Typical Recharge Time                                                                      9 hours recover to 90% capacity
 Model
           Charging Current (max.)                                                                                 1.0 A
           Charging Voltage                                                                                  218.4 VDC ± 1%
           Battery Type                                                                                  Depending on applications
 Long-run Numbers                                                                                                 16-20**
 Model     Charging Current (max.)                                                                                 4.0 A
           Charging Voltage                                                                     218.4 VDC ± 1% (Based on 16 pcs batteries)
 INDICATORS
 LCD Display                                                        UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions
 ALARM
 Battery Mode                                                                                            Sounding every 4 seconds
 Low Battery                                                                                             Sounding every 2 seconds
 Overload                                                                                               Sounding twice every second
 Fault                                                                                                    Continuously sounding
 PHYSICAL
 Standard Dimension, D x W x H (mm)                                        369 x 190 x 688                                                          442 x 190 x 688
 Model    Net Weight (kgs)                                                        54                                                                      66
 Long-run Dimension, D x W x H (mm)                                         369 x 190 x 318                                                         442 x 190 x 318
 Model    Net Weight (kgs)                                                         13                                                                     16
 ENVIRONMENT
 Operating Humidity                                                                               20-95 % RH @ 0- 40°C (Non-condensing)
 Noise Level                                                          Less than 50dB @1Meter                                                    Less than 58dB @1Meter
 MANAGEMENT
 Smart RS-232/USB                                                            Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux and MAC
 Optional SNMP                                                                         Power management from SNMP manager and web browser
 * Derate capacity to 60% of capacity in CVCF mode and to 90% when the output voltage is adjusted to 208VAC.
 **When using batteries from 16-19, the unit will de-rate according to below formula: P=Prating x N/20.
 ***If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per 100m.
28