Technical Data
Jan 2017
MTU CGT Stamford Generator
20V 4000 G23 (FO) LVSI 804 Model: G2750SMU5
Power Factor Emissions
50 Hz 3-Phase Cos Φ = 0.8 Non-Certified
PRIME POWER (PRP) STANDBY POWER (ESP)
RATINGS
G2750SMU5
Voltage kVA kWe kVA kWe Amps
415/240 2500 2000 2750 2200 3826
400/230 2500 2000 2750 2200 3969
380/220 2600 2080 2800 2240 4254
Definition of Ratings & Reference Conditions
Prime Power (PRP) is the nominal output continuously available, where the average load (variable) does not exceed 75% of the
prime power rating. 10% overload is available for a maximum of 1 hour in 12 hours of operation.
Standby Power (ESP) is the maximum output available, for up to 500 hours per year, where the average load does not exceed 85%
of the standby power rating. No overload is available.
Standard Reference Conditions: air inlet temperature 25°C (77°F), barometric pressure 100kPa, [100m (328ft) altitude], 30%
relative humidity.
Note: The above ratings may be subject to derate at different operating conditions. Please see the Derate Guidelines on the
Broadcrown website.
All power ratings and reference conditions in accordance with ISO 8528-1 and ISO 3046-1.
Key Features:
● Efficient water cooled diesel engine.
● Single bearing CGT Stamford alternator
● Radiator with pressure cap and drain point
● Fully guarded engine-driven fan
● Fully welded steel baseframe with lifting / jacking points
● Various fuel system options
● Heavy duty rubber anti-vibration mountings
● 24V starter batteries and connecting cables
● Separate engine-driven battery charging alternator
● Spin on oil and fuel filters and dry type air filter element
● Auto Start control system with digital instrumentation
● Factory Test Certificate
● Operation & Maintenance Manual
● Wide range of optional extra features available
Overall Dimensions & Weights - Open Set
Length (L) = 7039mm
H Width (W) = 3192mm
Height (H) = 3090mm
Dry Weight (inc oil) = 20148kg
L W Operating Weight = 21383kg
Typical Open Generator Sound Pressure Level at 1m, Free Field (dB)
Overall dBA 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz
TBA TBA TBA TBA TBA TBA TBA TBA TBA
All specifications and design are subject to change without notice
G2750SMU5
Jan 2017
ENGINE & COOLING SYSTEM MTU 20V 4000 G23 (FO)
SI Units PRIME STANDBY
Engine Speed r/min 1500
Performance
Gross Power kWm 2200 2420
Fan Power kWm 50 50
Net Power kWm 2150 2370
Emissions Certification ―
Altitude Capability m 400 400
Cylinders / Type 20 cyl / Vee form / 4-stroke
Aspiration / Charge Cooling Turbocharged / 2 pump 2 loop
General
Governing / Engine Management "ADEC" Electronic Governor/ECU/CANBus
Bore / Stroke mm 170 / 210
Cubic Capacity litres 95.4
BMEP kPa 1846 2031
Fuel Consumption at 100% Power litres/h 495.2 547.5
Fuel Consumption at 75% Power litres/h 377.2 408.5
Fuel
Fuel Consumption at 50% Power litres/h 272.1 285.1
Total fuel flow litres/h 1620
Standard Fuel Tank Capacity litres N/A
Engine Air Flow m³/s 2.4 2.6
Air
Maximum Air Intake Restriction (used filter) kPa 5
Exhaust Gas Flow m³/s 6.5 7.1
Exhaust
Exhaust Gas Temperature °C 580 600
Maximum Exhaust Back Pressure kPa 8.5
Typical Exhaust Pipe Diameter mm 400
Radiator Cooling Air Flow m³/s 33
Max Restriction to Cooling Air Flow Pa 250
Cooling
Max Radiator Air-On Temperature °C 45
Maximum Coolant Temperature °C 104
Coolant Capacity - Engine Only litres 205
Total Coolant Capacity litres TBA
Total Oil Capacity incl Filters litres 390
Oil
Typical Oil Pressure at Rated Speed kPa 460
Typical Oil Consumption (>250hrs Operation) litres/h 1.56
Heat Rejection to Engine Cooling Water kW 860 910
Thermal
Heat Rejection to Charge Cooler kW 300 350
Heat Radiated From Engine (Typical) kW 105 105
Electrical System Voltage V 24
Elec
Battery Type TBA
Battery Capacity SAE CCA A TBA
ALTERNATOR CGT STAMFORD LVSI 804 S2
SI Units PRIME STANDBY
Manufacturer Cummins Generator Technologies - STAMFORD
Model (may vary with voltage) LVSI 804 S2 LVSI 804 S2
Operating Temperature °C 40 27
General Data
Coupling / No. of Bearings Direct / Single Bearing
Phase / Poles / Winding Type 3-Phase / 4-Pole / Winding 311
Power Factor Cos Φ = 0.8
Excitation Separately excited by PMG
Insulation System Class H
AVR Type MA330
Voltage Regulation ± 0.5%
All specifications and design are subject to change without notice
G2750SMU5
Jan 2017
STANDARD CONTROL SYSTEM BC 7310 Digital Auto Start
The standard control system for this model is BC 7310 (photo), based on the Deep
Sea Electronics DSE7310 Digital Auto Start controller.
This provides for the manual and automatic remote start of the generator, together
with full control and protection of the engine via the ECU. LCD digital display of :
▪ Coolant temperature with high temperature alarm and shutdown
▪ Oil pressure with low pressure alarm and shutdown
▪ Oil temperature, engine operating hours, battery charge volts and amps
▪ Volts, with Under/Over Volts protection
▪ Amps, with Over Current protection
▪ Frequency, kW, kVA, Power Factor
Also featuring :
▪ Full RS485 Telemetry implementation
▪ Automatic cool-down timer function
▪ Emergency Stop button
▪ Ample auxiliary inputs/outputs for optional features
▪ Optional (shown) - battery charger and door mounted illuminated switch.
CONTROL SYSTEM OPTIONS
The BC 7320 control system (just the DSE7320 module is shown here) has an identical feature
set to the BC 7310 but with the addition of full AMF functionality with integrated mains
monitoring.
Finally, BC 8610 & BC 8620 control systems provide the same features as
BC 7310 & BC 7320 respectively, plus :
▪ BC 8610 - Set-to-Set Synchronisation
▪ BC 8620 - Single Set-to-Mains Supply Synchronisation with
integrated mains monitoring
For Multi Set-to-Mains synchronisation, each set requires BC 8610 with the addition
of one mains monitoring panel BC 8660 (not illustrated).
See the Synchronisation Guidelines for further details.
All designs and specifications subject to change without notice