Diesel Generator Set
MTU 16V00 DS2250
380V – 11 kV/50 Hz/data center continuous power/fuel consumption optimized/
16V4000G14F/water charge air cooling
Optional equipment and finishing shown. Standard may vary.
Product highlights
Bene�ts                                                      Performance assurance certi�cation (PAC)
— Low fuel consumption                                       — Engine-generator set tested to ISO 8528-5 for transient
— Optimized system integration ability                         response
— High reliability                                           — 100% load factor
— High availability of power                                 — Verified product design, quality and performance integrity
— Long maintenance intervals                                 — All engine systems are prototype and factory tested
Support                                                      Complete range of accessories available
— Global product support offered                             — Control panel
                                                             — Power panel
Standards                                                    — Circuit breaker/power distribution
— Engine-generator set is designed and manufactured in       — Fuel system
   facilities certified to standards ISO 2008:9001 and       — Fuel connections with shut-off valve mounted to base frame
   ISO 2004:14001                                            — Starting/charging system
— Generator set complies to ISO 8528                         — Exhaust system
— Generator meets NEMA MG1, BS5000, ISO, DIN EN and          — Mechanical and electrical driven radiators
   IEC standards                                             — Medium and oversized voltage alternators
— NFPA 110
                                                             Emissions
Power rating                                                 — Fuel consumption optimized
— System ratings: 2120 kVA - 2160 kVA
— Accepts rated load in one step per NFPA 110                Certi�cations
— Generator set complies to G3 according to ISO 8528-5       — CE certification option
— Generator set exceeds load steps according to ISO 8528-5   — Unit certificate acc. to BDEW (German Grid-Code)
Application data 1)
Engine                                                                                    Liquid capacity (lubrication)
Manufacturer		         MTU                                                                Total oil system capacity: l		                                                    300
Model		 16V4000G14F                                                                       Engine jacket water capacity: l		                                                  175
Type		              4-cycle                                                               Intercooler coolant capacity: l		                                                   50
Arrangement		           16V
Displacement: l		      76.3                                                               Combustion air requirements
Bore: mm 		              170                                                              Combustion air volume: m3/s		                                                      2.1
Stroke: mm 		            210                                                              Max. air intake restriction: mbar		                                                50
Compression ratio		     16.4
Rated speed: rpm		    1500                                                                Cooling/radiator system
Engine governor		    ECU 9                                                                Coolant flow rate (HT circuit): m3/hr		                                           68.5
Max power: kWm 		      1798                                                               Coolant flow rate (LT circuit): m3/hr		                                             30
Air cleaner		           Dry                                                               Heat rejection to coolant: kW		                                                    710
                                                                                          Heat radiated to charge air cooling: kW		                                         260
Fuel system                                                                               Heat radiated to ambient: kW		                                                     90
Maximum fuel lift: m 		                                                            5      Fan power for electr. radiator (40°C): kW		                                         38
Total fuel flow: l/min		                                                          20
                                                                                          Exhaust system
Fuel consumption 2)                                         l/hr             g/kwh        Exhaust gas temp. (after turbocharger): °C		                                      480
At 100% of power rating:                                  407.3                 188       Exhaust gas volume: m3/s		                                                         5.4
At 75% of power rating:                                   310.3                  191      Maximum allowable back pressure: mbar		                                            85
At 50% of power rating:                                    217.7                201       Minimum allowable back pressure: mbar		                                            30
Standard and optional features
System ratings (kW/kVA)
    Generator model                      Voltage                                                    Fuel consumption optimized
                                                                             without radiator                                       with mechanical radiator
                                                            kWel               kVA*                AMPS                 kWel               kVA*               AMPS
                                         380 V              1728               2160                3282                 1688               2110               3206
    Leroy Somer LSA52.3 S7
    (Low voltage                         400 V              1728               2160                3118                 1688               2110               3046
    Leroy Somer standard)
                                         415 V              1728               2160                3005                 1688               2110               2935
                                         380 V              1704               2130                3236                 1672               2090               3175
    Marathon 744RSL7092
                                         400 V              1704               2130                3074                 1672               2090               3017
    (Low voltage Marathon)
                                         415 V              1696               2120                2949                 1672               2090               2908
                                         380 V              1704               2130                3236                 1672               2090               3175
    Marathon 744RSL7093
    (Low voltage Marathon                400 V              1704               2130                3074                 1672               2090               3017
    oversized)
                                         415 V              1696               2120                2949                 1672               2090               2908
    Marathon 1020FDH7097
                                         11 kV              1712               2140                112                  1672               2090               110
    (Medium volt. marathon)
    Leroy Somer LSA53.2 XL9
                                         11 kV              1728               2160                113                  1688               2110               111
    (Medium volt. Leroy Somer)
* cos phi = 0.8
1     All data refers only to the engine and is based on ISO standard conditions (25°C and 100m above sea level).
2     Values referenced are in accordance with ISO 3046-1. Conversion calculated with fuel density of 0.83 g/ml. All fuel consumption values refer to rated engine power.
Standard and optional features
Engine
  4-Cycle                                      Closed crankcase ventilation with           Common rail fuel injection
  Standard single stage air filter             improved oil seperator                      Fuel consumption optimized engine
  Oil drain extension & shut-off valve         Governor-electronic isochronous             Centrifugal oil filter
Generator
  4 pole three-phase synchronous               Radio suppression EN55011, group 1, cl. B   Meets NEMA MG-1, BS 5000,
  generator                                    Short circuit capability 3xIn for 10sec     IEC 60034-1, VDE 0530,
  Brushless, self-excited, self-regulating,    Winding and bearing RTDs                    DIN EN 12601, AS1359 and ISO 8528
  self-ventilated                              (without monitoring)                        requirements
  Digital voltage regulator                    Excitation by AREP                          Leroy Somer low voltage generator
  Anti condensation heater                     Mounting of CT´s: 2 core CT´s               Marathon low voltage generator
  Stator winding Y-connected, accessible       Winding pitch: 2/3 winding                  Oversized generator
  neutral (brought out)                        Voltage setpoint adjustment ± 10%           Medium voltage generator
  Protection IP23
  Insulation class H, utilization acc. to H
Cooling system
  Jacket water pump                            Mechanical radiator
  Thermostat(s)                                Electrical driven front-end cooler
  Water charge air cooling                     Jacket water heater
Control panel
  Pre-wired control cabinet for easy           Mains parallel operation of                 Event recording
  application of customized controller (V1+)   multiple gensets (V7)                       IP 54 front panel rating with
  Island operation (V2)                        Basler controller                           integrated gasket
  Automatic mains failure operation with ATS   Deif controller                             Different expansion modules
  (V3a)                                        Complete system metering                    Remote annunciator
  Automatic mains failure operation            Digital metering                            Daytank control
  incl. control of generator and mains         Engine parameters                           Generator winding temperature
  breaker (V3b)                                Generator protection functions              monitoring
  Island parallel operation of multiple        Engine protection                           Generator bearing temperature
  gensets (V4)                                 SAE J1939 engine ECU                        monitoring
  Automatic mains failure operation with       communications                              Modbus TCP-IP
  short (< 10s) mains parallel                 Parametrization software
  overlap synchronization (V5)                 Multilingual capability
  Mains parallel operation of                  Multiple programmable contact inputs
  a single genset (V6)                         Multiple contact outputs
Power panel
  Available in 600x600 and 600x1000            Supply for anti condensation heating        Supply for electrical driven radiator
  Phase monitoring relay 230V/400V             Plug socket cabinet for 230V                from 45kW – 75kW (PP 600x1000)
  Supply for battery charger                   compatible Euro/USA
  Supply for jacket water heater
    Represents standard features
    Represents optional features
Standard and optional features
Circuit breaker/power distribution
  3-pole circuit breaker                        Manual-actuated circuit breaker               Stand-alone solution in seperate cabinet
  4-pole circuit breaker                        Electrical-actuated circuit breaker
Fuel system
  Flexible fuel connectors mounted to           Switchable fuel filter with water separator   Fuel cooler integrated into cooling
  base frame                                    Switchable fuel filter with water separator   equipment
  Fuel filter with water separator              heavy-duty
  Fuel filter with water separator heavy-duty   Seperate fuel cooler
Starting/charging system
  24V starter                                   Starter batteries, cables, rack,              Battery charger
                                                disconnect switch
Mounting system
  Welded base frame                             Resilient engine and generator mounting       Modular base frame design
Exhaust system
  Exhaust bellows with connection flange        Exhaust silencer with                         Y-connection-pipe
  Exhaust silencer with 10 dB(A) sound          30 dB(A) sound attenuation
  attenuation                                   Exhaust silencer with
                                                40 dB(A) sound attenuation
    Represents standard features
    Represents optional features
Weights and dimensions
Drawing above for illustration purposes only, based on a standard open power 400 Volt engine-generator set. Lengths may vary with other voltages. Do not use for installation
design. See website for unit specific template drawings.
  System                                       Dimensions (L x W x H)                                             Weight (dry/less tank)
  Open power unit (OPU)                        4766 x 1810 x 2330 mm                                              12428 kg
Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specific engine-generator set.
Sound data                                                                               Emissions data
—— Consult your local MTU distributor for sound data.                                    —— Consult your local MTU distributor for emissions data.
Rating definitions and conditions
—— Data Center Continuous Power ratings apply to Data Center
   installations where a reliable utility power is available and comply
   with Uptime Institute Tier III and IV requirements. At constant or
   varying load, the number of generator set operating hours is
   unlimited. A 10% overload capacity is available for one hour in
                                                                                                                                                                                Subject to change. | 3238411 | Edition 01/19 | ESM 2019-08.
   twelve. Ratings are in accordance with ISO 8528-1, ISO 3046-1, BS
   5514 and AS 2789. Average load factor: ≤ 100%..
—— Consult your local MTU distributor for derating information.