BMS BOQ
SL NO DESCRIPTION OF WORK                                                               QTY      UNIT       SUPPLY INR             INSTALLATION INR
                                                                                                        RATE        AMOUNT       RATE        AMOUNT
        Supply, Installation, Testing and Commissioning of the following items with 2
        Years Warranty
  1
        HMI
        HMI display of 4.3" LCD Touch screen display, Panel mounting, with RS232                 No.
        Connection, Local supervisory port, USB, Backlight of LED with Autodim,
        requires 24VAC/DC, operating temperature of 0°C to 45°C, with HMI Software
        to view and adjust operating times, monitor alarms, to display and control the
        parameters and display graphs of logged data, security settings, power failure
        protection. The Display shall be IP50 rating when panel mounted with all other
        mounting accessories complete as required.
 1.1                                                                                        1
        AHU
        DDC
 2
 a      DDC controller supporting TCP/IP over Ethernet protocol or BACnet IP                     Nos
        protocol and I/O's designed as per the IO Summary with necessary expansion
        IO module and VFD Integration modules and BTU Meter integration with all
        other mounting accessories complete as required.
                                                                                            1
 2.1    Control Panel
  a     Control Panel of IP64 protection standard for mounting the DDC with Base                 Nos
        Plate, Cable Truf, Glands for Cable Entry, transformer, relays, Fan, MCB's,
        Switches with all other mounting accessories complete as required.
                                                                                            1
 b      Exposed Area - IP 64
        Non Exposed Area - IP22
 3      Third Party Systems Integration
        Supply, Installation, Testing & Commissioning of Gateway/Router/Converter for            Lot
        Integration of the following third party systems supporting multi protocols like
        BACnet, Modbus, Lonworks, JBUS, RS232, RS485 etc with all other mounting            1
        accessories complete as required.
 a      VFD
 b      BTU meter
        Field Devices
 4
        Immersion Temperature sensor
        Supply, Installation (In co ordination with HVAC Contractor), Testing &
        Commissioning of Immersion type temperature sensor with Thermo well and
        all other accessories. Temperature sensor shall be Pt1000 RTD type/
        Thermistor with 0 to 10v or 4 to 20mA transmitter, NPT Compression/Spring
        compression fitting, Stainless steel/Brass Thermowell, Polycarbonate/Impact
        resistant ABS Housing, IP66/67 rating. The measurement range shall be -10oC
        to +110oC with all other mounting accessories complete as required.
 4.1
4.1.1   Chilled Water Inlet pipe line                                                            Nos
                                                                                            1
4.1.2   Chilled Water Outlet pipe line                                                           Nos
                                                                                            1
 4.2    Differential Pressure Switch for Filter
  a     Supply, Installation, Testing & Commissioning of Filter DPS with all the                 Nos
        mounting accessories included. The DPS shall be with Silicone diaphragm,
        Compatible to Air, non-combustible, non-aggressive gases, SPDT switch type,
        maximum operating temperature range shall be -20 to 85°C, maximum
        operating pressure shall be 10Kpa. IP54 rating. The maximum pr limit shall be
        20-300Pa as technical specification with all other mounting accessories
        complete as required.
                                                                                            1
        Differential Pressure Switch for Fan
 4.3
  a     Supply, Installation, Testing & Commissioning of Filter DPS with all the                 Nos
        mounting accessories included. The DPS shall be with Silicone diaphragm,
        Compatible to Air, non-combustible, non-aggressive gases, SPDT switch type,
        maximum operating temperature range shall be -20 to 85°C, maximum
        operating pressure shall be 10Kpa. IP54 rating. The maximum pr limit shall be
        20-300Pa as technical specification with all other mounting accessories
        complete as required.
                                                                                            1
 4.4    Duct Static pressure sensor
  a     Supply, Installation, Testing & Commissioning of Static pressure sensor with all         Nos
        the mounting accessories included. The sensor shall be Magnetic
        sensing/Piezo-resistive pressure transducer, Compatible to
        air,non-combustible, non-aggressive gases, Stability +/- 1% or 2.5% FS/Year ,
        Temperature limits shall be -18 to 50°C, 40kpa burst pressure, the output shall
        be 0 to 10v or 4 to 20mA transmitter, ABS/POM housing material, IP54/66
        rating. The maximum pr limit shall be 0-500Pa all other mounting accessories
        complete as required.
                                                                                            1
 4.5    Supply air Temperature & RH Sensor
  a     Supply, Installation, Testing & Commissioning of Supply Air Temperature & RH             Nos
        sensor with all the mounting accessories included. The sensor shall be Pt1000
        RTD type/thermistor for temperature measurement with 0 to 10VDC or 4-20mA
        transmitters. The temperature measurement range shall be 0oC to 40oC,
        accuracy ±0.2 °C . RH sensor shall be Capacitance type and measurement
        range 0-100%RH,accuracy ±2 %RH, Drift <1% RH/Year. The sensor shall be
        Polycarbonate/Impact resistance ABS housing, IP65/66 rating.
 4.6    Room Temperature & RH Sensor
  a     Supply, Installation, Testing & Commissioning of Room Temperature & RH                   Nos
        sensor with all the mounting accessories included. The sensor shall be Pt1000
        RTD type/thermistor for temperature measurement with 0 to 10VDC or 4-20mA
        transmitters. The temperature measurement range shall be 0°C to 40°C,
        accuracy ±0.4 °C . RH sensor shall be Capacitance type and measurement
        range 0-100%RH,accuracy ±2 %RH, Drift <1% RH/Year. The sensor shall be
        Polycarbonate/Impact resistance ABS housing, IP20 rating.
                                                                                            1
 4.7    Air Flow measuring Station
  a     Supply, Installation, Testing & Commissioning of Air Flow measuring Station @            Nos
        Fresh Air Duct (1000X350mm) with 0 to 10v or 4 20mA transmitters,
        Rectangular configuration, Galvanized steel casing, Anadized aluminium flow
        sensors, 100 to 10,000FPM,accuracy ±2%,IP65 rating with all the mounting
        accessories included.
                                                                                            1
 b      Supply, Installation, Testing & Commissioning of Air Flow Station @ Supply Air           Nos
        Duct (1500X450mm) with 0 to 10v or 4 20mA transmitters,Rectangular
        configuration, Galvanized steel casing, Anadized aluminium flow sensors, 100
        to 10,000FPM,accuracy ±2%,IP65 rating with all the mounting accessories
        included.
                                                                                            1
        BTU Meter
 4.8
  a     Supply, Installation, Testing & Commissioning of Clamp on BTU meter with less            Nos
        than 2% accuracy on any flow with RS485/Modbus RTU/M-Bus communication
        for BMS integration. The BTU meter shall be for 50mm dia pipe/6mm
        thickness/ms
                                                                                            1
 5      Network switch
 a      Network switch with all other mounting accessories complete as required                  Nos
                                                                                            1
 6      Cable & Conducting
 a      Supply, Laying, Termination of ISI Certified 2 Core 1.5 sq.mm ATC, PVC                    Mtr
        insulated, armored, Tinned Copper, twisted, shielded, PE insulated, Cable with
        proper ferrules, lugs and other necessary accessories. The spec shall meet the
        system manufacturer specifications
                                                                                           300
 b      Supply, Laying, Termination of ISI Certified 3 Core 1.0 sq.mm ATC, PVC                    Mtr
        insulated, armored, Tinned Copper, twisted, shielded, PE insulated, Cable with
        proper ferrules, lugs and other necessary accessories. The spec shall meet the
        system manufacturer specifications                                                  150
 c      Supply, Laying, Termination of ISI Certified 4 Core 1.5 sq.mm ATC, PVC                    Mtr
        insulated, armored, Tinned Copper, twisted, shielded, PE insulated, Cable with
        proper ferrules, lugs and other necessary accessories. The spec shall meet the
        system manufacturer specifications                                                  200
 d      Supply, Laying, Termination of ISI Certified Cat 6 cable and PVC conduit with all         Mtr
        other mounting accessories complete as required.
                                                                                           50
                                            Sub Total                                                               ' '' '' '0               ' '' '' '0
                                          Grand Total                                                                                        ' '' '' '0
                                           GST - 18%                                                                                         ' '' '' '0
                                 Grand Total (Including GST)                                                                                 ' '' '' '0
        Note:
        a. If there is no provision for immersion thermo-wells then surface
        mounted temperature sensor will be selected accordingly.
                                                                             PERFORMANCE MONITOR OF AHU - BMS IO SUMMARY
S.No.   Point Description                                    Qty   AI   AO      DI      DO    Soft IO                      IBMS Vendor Scope                                    Builder/ HVAC / Utility Vendor Scope
 A      AHU                                                   1
        Air Flow Station at Fresh Air Duct for Monitoring                                               BMS Supplier to provide and mount Air flow station with all HVAC Vendor to co-ordinate and confirm the location of
  1                                                                1                                    accessories. Cabling from sensor to DDC under BMS          fixing the sensor.
                                                                                                        Vendor scope
        AHU Filter status via Differential pressure switch                                              BMS Supplier to provide and mount Differential pressure HVAC Vendor to co-ordinate and confirm the location of
                                                                                                        switch with all accessories. Cabling from DP Switch to DDC fixing the DP Switch
                                                                                                        under BMS Vendor scope
 2                                                                               1
        AHU Run status via Differential pressure switch                                                 BMS Supplier to provide and mount Differential pressure HVAC Vendor to co-ordinate and confirm the location of
                                                                                                        switch with all accessories. Cabling from DP Switch to DDC fixing the DP Switch
                                                                                                        under BMS Vendor scope
 3                                                                               1
        Chilled water Inlet & Outlet temperature sensor                                                 BMS Supplier to provide and mount Immersion temperature HVAC Vendor to co-ordinate and confirm the location of
                                                                                                        sensor with all accessories. Cabling from temperature   fixing the sensor.
 4                                                                 2                                    sensor to DDC under BMS Vendor scope
        2 way modulating valve control & Feedback (Cooling                                              Cabling from DDC to Valve actuator - BMS Vendor scope        HVAC Vendor to provide the required Valve with actuator
        Coil)                                                                                                                                                        of 0-10 VDC/ 4-20mA analog input/ output for control &
 5                                                                 1    1                                                                                            monitoring in BMS. HVAC Vendor to supply and mount the
                                                                                                                                                                     valve with actuator.
        Air Flow Station at Supply Air Duct for Monitoring                                              BMS Supplier to provide and mount Air flow station with all   HVAC Vendor to co-ordinate and confirm the location of
 6                                                                 1                                    accessories. Cabling from sensor to DDC under BMS            fixing the sensor.
                                                                                                        Vendor scope
        Duct Static pressure sensor                                                                     BMS Supplier to provide and mount Duct static pressure       HVAC Vendor to co-ordinate and confirm the location of
                                                                                                        sensor with all accessories. Cabling from sensor to DDC      fixing the sensor.
                                                                                                        under BMS Vendor scope
 7                                                                 1
        Supply air Temperature and RH                                                                   BMS Supplier to provide and mount Supply air temperature HVAC Vendor to co-ordinate and confirm the location of
                                                                                                        & RH sensor with all accessories. Cabling from sensor to fixing the sensor.
                                                                                                        DDC under BMS Vendor scope
 8                                                                 2
        Room T & RH sensor                                                                              BMS Supplier to provide and mount Room temperature &         HVAC Vendor to co-ordinate and confirm the location of
                                                                                                        RH sensor with all accessories. Cabling from sensor to       fixing the sensor.
 9                                                                 2                                    DDC under BMS Vendor scope
        VFD integration                                                                                 BMS vendor to consider 10 software points for each VFD.      HVAC Vendor to provide RS 485 MODBUS/Bacnet interface
                                                                                                                                                                     in each VFD panel. HVAC Vendor to show the parameters
                                                                                                                                                                     on the MODSCAN / Bacstack /Cimetrics software before
                                                                                                                                                                     integrating to BMS. All mapping details & ID setting in the
                                                                                                                                                                     VFD to be done by the VFD vendor
 10                                                           1                                 10
        BTU Meter integration                                                                           BMS vendor to consider 5 software points for BTU meter.      HVAC Vendor to provide RS 485 MODBUS/M-Bus interface
                                                                                                                                                                     in BTU meter. All mapping details & ID setting in the BTU
                                                                                                                                                                     meters to be shown to BMS Vendor before integrating.
 11                                                           1                                  5
        Total for A                                                10   1        2      0       15
        Note:
        Consider 15 to 20% spare I/Os in each DDC Panel