MICROBIOLOGY -2 HVAC BOQ 22.07.
2025
DATE:
HVAC SYSTEM
19.07.2025
Sl
Description Unit Qty RATE AMT
No
Supply, installation, assembly, testing, commissioning and 24 months warranty from the
date of acceptance by Clients & Consultants for the following equipment
AIR HANDLING UNITS
1 Air Handling Units
Double Skin Horizontal Air Handling Units, complete with double skin (45±2 mm)
insulated with CFC free polyurethane foam (PUF) panels of 42 Kg/cum density
sandwitched between 0.8 mm thick G.I. Sheets inside AND 0.6 MM outside. Both the
sides of the panels are powder coated.
Food grade self adhesive coated neoprene gasket to be provided between panels and
structure of the AHU to ensure the entire housing is airtight didw fans to be supplied along
with motor
SS 304 insulated Drain Tray with 50mm slope.3 mm thick
DX coil shall be of 6 Row deep. (Refer Schedule of equipment for each AHU). Face
Velocity across the coils should not exceed 500 FPM. cooling coils shall be
constructed from premium quality seamless copper tubes and aluminum fins.
Doors: All lockable doors. Pressure closing type.and vacuum sealing type for suction side
Baseframe height (part of the AHU) shall be made up of MS painted steel channels of
height 300mm.
All outlets of the AHU shall have a Aluminum Opposed Blade Dampers.Return air and
fresh air connections shall be provided with opposed blade aluminium motorised dampers
Pre-Filters Section: Made up of 2mm thick 50X25mm rectangular tubes to house 100 mm
thick washable panel type G4 filters. Filter prices shall be included in the AHU price.
Fine-Filters Section: Made up of 2mm thick 50X25mm rectangular tubes to house 300
mm thick F9 filters. Filter prices shall be included in the AHU price.
Bleed off dampers shall be inlcuded
All the sections (prefilter, finefilter, Fan/Motor section, ) shall have lights installed with a
on-off switch outside the section.
Fan/Motor Arrangement: Fan - Nicotra./KRUGER Motor - ABB/Siemens/CG Shall be
aerofoil backward curved plug type direct driven fans
Mixing box shall be included.
Fire resistant flexible duct connection shall be included
Magnehelic gauges across filters and fan shall be provided
VFD to be included 5.5 kw each (Mitsubishi /siemens/MG -MMWC-Heavy Duty-High
Overload Ability)
1.1 AHU - 01
5000 CFM @ 5 Inches Water Gauge TSP, 12 fpi, 15 TR , Set 1
1.2 AHU - 02
5000 CFM @ 5 Inches Water Gauge TSP, 12 fpi, 15 TR , Set 1
2 VRF OUT DOOR UNITS FOR AHU
VRV out door units complete with AHU
expansion valve kit, multiple inverter
compressor,condenser coil and fans, .Anti corrossive coating is
required on condenser coil fins.Refrigerant R410A shall be included
VRV / VRF Outdoor unit of actual capacity shown below @ 38° C ambient and 24° C
indoor temperature
15TR/20 HP ,expansion valve to suit the DX coil circuits nos 2
Refrigerant piping for indoor and outdoor unit interconnection (Rate to be inclusive of Both
Lines-180M+180M) Mtrs 180
Control cabling Mtrs 180
Refnet joints for refrigerant piping lot 9
control panel for common control of out door units nos 3
MAKE: DAIKIN/TOSHIBA
4 HDPE CPVC drain pipe with 6 mm closed cell foam class 0 insulation
40 mm dia Mtrs 60
32 mm dia Mtrs 80
25 mm dia Mtrs 90
8 SHEET METAL DUCTING
Factory fabricated GSS Ducting (Box ducts only) with TDF Flanges, supports, cleat
joints, gaskets, bolts & nuts. GSS ducting shall meet the requirements of Class VIII. No
fabrication at site. Ducts should be supplied covered using polythene sheets from factory.
Make: Radiant / Rolastar / Camduct
a 24 G Sqm 300
b 22 G Sqm 200
c 20 G Sqm 0
9 Duct thermal insulation class o closed cell - TROCELLEN/armacell Make
a 13mm thick Sqm 300
b 9mm thick Sqm 200
GI volume control damper ( Quadrant type and Opposed blade construction) with
matching flanges on both side. The space between the bolts should be not more than 100
8 mm. Make:Ravi Star / Cosmos Sqm 8
TERMINAL HEPA FILTER BOX
Terminal HEPA filer box size 600x600 ,900 cfm,300mm deep complete with filter box and
i nos 18
fixing arrngement with spigot,perforated plate aluminium with DOP port on the upstream
Fire dampers for with fusible link type fire dampers and limit switch for position feedback.
The dampers to be rated for 90 minutes fire rating and the dampers shall be of spring
return type. Fire damper to be provided with matching flanges on both sides. Fire
dampers should be supplied with extended fire rated sleeves.Fire damper to be provided
10 with matching flanges on both sides. Make: Ravistar / Greenheck sqm 2
11 Elctrical Works
Supply, installation, testing and commissioning of wall mounting type distribution board
(concealed/ partly concealed) for lighting control/small power control. The DB shall
comprise of SPN or TPN copper busbars as applicable, busbars of adequate size and
brass neutral link with suitable number of taps and screws. The board shall be made
out of 16 SWG sheet steel suitably reinforced. The distribution board shall be equipped
with incoming and outgoing MCB's & Circuit identification tags/cable markers etc. The
distribution board shall be as per relevant IS & CEIG requirements .An extra link shall be
provided inside the DB for earthing purpose. An over all cover made out of 16 SWG
sheet steel with flush type screws / lockable arrangement. The rate for board shall
include supply and installation of all components, with MS doors such that MCB's are not
visible, hardware's, etc. including all connected civil works, equipped with the following.
Suitable size MS adaptor box shall be provided above the DB location to terminate the
incoming conduits to DB. All Lighting DBs shall be comply with curve 'B' tripping
characteristics and Power DBs of curve C' tripping characteristics.
b 4C x 16 Sqmm Cu XLPE armoured cable (Copper) VRV Rmt 180
d 4C x 2.5 sqmm Cu XLPE Armoured cable (Copper) AHU Rmt 120
e 4C x 1.5 sqmm Cu XLPE Armoured cable (Copper) Rmt 60
GI Earthing
a 25 x 3mm GI Strip Rmt 30
b 10 Gage GI Wire Rmt 300
Cable Trays:
Suply, Installation, Testing, Commissioning of Cable tray with necessary supports and
perforated steel with all accessories,. Refer drawings for the estimation purpose. AHU &
Other equipments.
a 150 mm wide Rmt 60
b 300 mm wide Rmt 20
c 450 mm wide Rmt 60
12 CONTROLS
Supply and installation of DDC Panels: Automation stations / DDC Controller with I/O
module etc...The controllers shall be 32 bit microprocessor based standalone and
networkable type with real time clock and historical database of min 3600 events , with
port for POT (Portable Operator Unit). Controllers shall be with embedded webservers
and BTL listed. Controllers shall comply with BACNET IP Protocol. The controllers shall
be designed to cater the given I/O Summary. The required enclosures for DDC controllers
1 shall be included (preferred IP 65).
AHU Sets 2
2 Supply,installation,commissioning of following sensors and actuators
i Differential pressure Transmitter For HEPA filter Nos 3
ii Differential pressure switch (Air)AHU Nos 4
iii Duct type temperature/RH sensors complete with all accessories Nos 4
iv Duct mounted velocity sensor for Supply air for each AHU Nos 2
Supply, installation, testing and commissioning of following cables and conduits :
Communication cabling from DDC panels, Sensor cabling from sensors to DDC, Data
interface cabling for software interface with chillers and pumps, Interlock cabling from
fire alarm control element to the DDC panel, Power wiring for DDC panel from the
nearest electrical DB and UPS point, Conduit for communication/ sensor and power
3 cabling.
i 2C X 1.0 SQ.MM -Unscreened Mts 300
ii 2C X 1.0 SQ.MM -screened Mts 200
iii 3C X 1.0 SQ.MM -screened Mts 200
iv 4C X 1.0 SQ.MM -screened Mts 200
v 1" GI Conduit (for exposed areas) Mts 100
vi 1.5 SQ.MM -screened, twisted bus cable for communication Mts 400
TOTAL
APEPL