cpc9 setting amended     4/11/05     11:24 AM     Page 1
TECHNICAL SPECIFICATION
       Coltman Floors And Roofs                                              The gap between the top of the wall/steel beam and the
           Units comprise of hollow and solid prestressed concrete,      soffit of the floor unit due to camber is to be filled solid with
       normally 1200mm wide placed side by side with a grouted           mortar by the Principal Contractor before construction above
       joint. The units are manufactured with a concrete having a        the slab proceeds.
       minimum cube strength of 30 N/mm2 at transfer and                 Side Bearings
       50N/mm2 at 28 days. Prestressing wire is stress relieved and
       treated for low relaxation.
           The Coltman flooring units are manufactured by the long
       line prestressed method using slip form techniques on heated
       steel beds within a factory environment. Coltman units are
       sawn to length on the manufacturing bed and are supplied
       as standard with plain sawn ends and open cores.
           Cross sectional and length tolerances are within the limits
       set out in BS 8110 and are subject to stringent quality
       control checks.
           Structural design is in accordance with the                                 Gap due to camber to be solidly filled
       recommendations of BS 8110 “The Structural Use Of                                 with mortar before construction
       Concrete”.                                                                            above the slab proceeds
           The standard Coltman floor unit is designed for a mild
       exposure condition as defined in BS 8110, other exposure          Internal Load Bearing Wall
       conditions can be considered subject to consultation with the
       Coltman Technical Department.
           The standard Coltman floor unit is designed to meet
       Class 3 serviceability requirements as described in BS 8110.
       Designs to Class 1 and Class 2 are available if required.                                       Gap due to camber to be filled with
       Camber                                                                      100                'Dry pack' mortar before construction
                                                                                minimum                      above the slab proceeds
           Prestressed units have an inherent upward camber and
       due allowance should be made in any finishes to cater for
       this particularly where a rigid insulation board or a floating
       timber floor is to be placed onto the top of the floor unit. In
                                                                         Supports
                                                                              Structural supporting walls for Coltman units are to rise
       these situations a levelling screed will need to be applied by
                                                                         from proper foundations and the adequacy of all bearings is
       the Principal Contractor prior to the laying of the finish.
                                                                         the responsibility of the Principal Contractor.
           Differential camber between adjacent units should be
                                                                              The stability of the supporting structure must not be
       within the tolerances set out in BS 8110 except for areas of
                                                                         adversely affected by the installation of the precast concrete
       floor where the adjacent spans of the units are of different
                                                                         units.
       lengths or where large holes are to be formed within the
                                                                              When designing bearings consideration must be given to
       middle third of the unit.
                                                                         the standard method of fixing precast concrete units,
           Consideration must also be given to both floor and ceiling
                                                                         particularly the operation of final alignment. Construction
       finishes where floor spans are perpendicular as steps will
                                                                         loading arrangement/forces may be more onerous than the
       occur between units.
                                                                         final working condition.
           The camber of Coltman units will generally comply with
                                                                              Where masonry supports are provided the Principal
       the recommendations of BS 8110 and are predicted to be
                                                                         Contractor should ensure that the mortar is fully cured before
       approximately 1/300th of the span.
                                                                         the floor units are placed into position. This is particularly
                                                                         relevant where retarded mortars are being used. A curing
                                                                         period of 3 to 7 days should be allowed for traditional
                                                                         mortars and advice of curing times should be confirmed with
                                                                         manufacturer where retarded mortars are used. Accurate and
                                        Camber                           level structural seating shall be prepared by the Principal
                                        L/300                            Contractor.
                                                                              Lightweight blocks are not suitable to provide bearings for
                                                                         precast concrete units and their use in this situation should
                                                                         be avoided. Where steel sections are to be utilised within
                                 Length (L)                              masonry structures suitable arrangements must be made to
                                                                         fix the steel beams down to padstones to prevent movement
cpc9 setting amended            4/11/05       11:24 AM            Page 2
       and rotation during installation. If this is not practical,                           Any material placed between the structural seating and
       temporary props are to be provided to ensure stability. In                        the unit soffit may result in a variation to our estimate.
       certain instances it may be necessary to utilise both a bolted                        Normal bearing requirements for Coltman units are
       fixing and propping particularly where eccentric loads are to                     100mm on brickwork and 75mm on steel and concrete but
       be placed on a support beam.                                                      these may be reduced in certain circumstances subject to
            Where precast units are supported on a cavity wall the                       design criteria.
       outer leaf of the wall must be built upto within 225mm of                             Where precast concrete units are supported on steel shelf
       the bearing level to maintain stability.                                          angles then the outstanding leg of the angle should not be
            In locations where the precast concrete units are to be                      less than 150mm and should project a minimum of 50mm
       supported on walls less than 190mm thick then temporary                           beyond the top flange of the beam.
       props or other means of bearing enhancement must be
       employed, designed and erected by competent persons.                              Steel Shelf Angle Bearing
       Props and timber runners are to be positioned at bearing
       level to give lateral support to the wall during installation.
                                                                                                                                             30
       Dual Bearing                                                                                                            Minimum clearance
                                 140                  In situ infill and
             Minimum width of wall                    reinforcement by Coltman
                                                              Props to provide lateral
         Timber just below
         bearing level
                                                              stability to single skin               50                                    150
                                                              load bearing wall                     Shelf angles to project      150mm minimum
                                                                                                    a minimum of 50mm beyond         outstand leg
                                                                                                    top flange
           Consideration must also be given to the design and
       stability of lintels during the construction phase. It may be                              Contact Coltman Technical Department
       necessary dependent on type of lintels to prop the inner skin                                at an early stage if any variation to
       until the construction is complete.                                                             this detail is to be considered
       Propping                                                                                      Infill concrete           Infill concrete
                                                                                                       Flange flush with top of slab
                Lintel
                                          The inner skin should be propped
                                          where there is insufficent masonry
                                          to counterbalance the load imposed
                                          during the construction phase.                             75
                                                                                                    Minimum Bearing
                                          Lintels should be designed with the
                         Prop
                                          construction phase loading in mind, as
                                          this type of lintel does not achieve
                                          full load capacity until construction
                                                                                         Fixing
                                          is complete.
                                                                                             Coltman installation gangs are fully experienced and
                                                                                         trained to handle and place precast concrete in accordance
                                                                                         with the Code of Practice For The Safe Erection Of Precast
                                                                                         Concrete.
           The foregoing comments apply equally to other types of
                                                                                             Where erection is to be carried out by others than
       structures with particular attention being required in the case
                                                                                         Coltman it is the responsibility of the Principal Contractor to
       of isolated piers and walls or toothed walls where temporary
                                                                                         ensure that the fixing gang is competent and capable of
       means of support may be required.
                                                                                         carrying out the work in accordance with the Code of
           In all instances the temporary supports/propping should
                                                                                         Practice For The Safe Erection Of Precast Concrete. Copies of
       be designed by a competent person and must be in position
                                                                                         this code are available upon request.
       prior to the installation of the precast concrete units.
                                                                                             Layout drawings are prepared for use during site erection
           Where precast concrete units are to be fixed within a
                                                                                         and these should be followed carefully and accurately.
       steel frame building it is essential that sufficient structural
       steelwork, sheeting rails, purlins, bracings, etc., are omitted
       to allow for our standard fixing procedures.                                      Grouting
           Additional steel supports may be required where floor                             When fixing we include for filling the joints between units
       units are required to notch around columns, particularly                          with Grade C25 concrete, but not for screed or other
       around the perimeter of the building.                                             finishes.
cpc9 setting amended       4/11/05       11:24 AM     Page 3
       Make Up                                                                    The visual effect of differential camber as previously
           Each area of flooring is set out using standard units and          described should be considered when an exposed soffit finish
       may incorporate reduced width units or in situ concrete strips         or direct decoration is to be utilised.
       to make up. Any strips should be cast in situ during site                  The application of plaster should be carried out in
       erection, unless otherwise specified. Stripping and disposal           accordance with the recommendations of British Gypsum.
       of formwork to be carried out by others at no cost to                  We do not recommend direct plastering to units exceeding
       Coltman.                                                               7.0m span.
           Our estimate does not include for any in situ strips that              The application of Artex to the soffits of our units should
       may be required adjacent to steel beams, or to the edge of             be carried out in accordance with the Artex specification
       any bay of units, or for making good around pipes,                     which is available from us upon request.
       stanchions or making up faces of large openings.                           Units with closed ends may accumulate water within the
                                                                              cores due to exposure to weather or from subsequent
       Holes                                                                  building operations. The Principal Contratctor should drill
           Small holes up to 50mm dia can be drilled on site on the           weep holes to release any trapped water or keep the weep
       centre lines of the hollow cores, care being taken to avoid            holes clear where they are provided by Coltman. The
       cutting or exposing reinforcement. The spacing of these holes          Principal Contractor should be satisfied that all trapped water
       should be limited to 400mm centres in each direction.                  has been released prior to the application of finishes.
       Larger holes can be formed during manufacture, dependent
       upon design criteria. The edge of the hole may be located at
       70mm plus increments of 100mm from the side of the unit.                Recommended type of fixing for heavier loads.
                                                                               (Fire protection may required by others)
       Service Ducts
                   Metal Trimmer strap
                                                                                                                      Fixing zone
                                                                                                                                         Tapcon or similar fixings
                                                                                                                                         may be drilled into the
                                                                               Toggle or similar type fixings may                        area's directly below the
                                                                               be made into the areas directly                           cores to provide fixings
                                                                               below the cores. Expanding bolt type                      for batten and plasterboard
                                                                               fixings are not recommended.                              ceilings.
                                                                              Ceiling Fixings
                                                                                             100          100
                                                                                                                                    26
                                                                                                                                            (148/198)
                                                                                                                                                              (200/250)
       Holes for large services , flues , soil and vent pipes and the like
                                                                                                     70
                                                                                                                                                        150
                                                                                                                                    98
       may be formed during manufacture. Small holes may be drilled
       on site through the cores of the units.
       Metal straps are used to trim larger duct openings subject to design
       criteria and should be fire protected by the Principal Contractor.
                                                                                                                                    26
                                                                                  Prestressed wire locations
       Screed                                                                     1. Shot fired fixings are not permitted.
           A non-structural sand and cement or grano screed is                    2. Service and ceiling loads must not exceed those shown
       normally laid by the Principal Contractor over the floor                      on the slab general arrangement drawings.
                                                                                  3. Fire protection may be required where a fixing
       (before plastering the soffit) to provide a level surface for                 penetrates the floor slab.
       finishes. A minimum screed thickness of 40mm is suggested                  4. The adequacy of the fixing is the responsibilty of others.
       with due allowance being made for the camber of units. It is
       strongly recommended that a light two-way reinforcing fabric
       is incorporated in the screed. Anti-crack reinforcement in the
                                                                              Fire Resistance
                                                                                  Coltman units are designed in accordance with BS 8110
       screed should always be provided by the Principal Contractor
                                                                              to provide a minimum fire resistance of 1 hour. 1.5 and 2
       over supporting beams and walls.
                                                                              hour fire resistance elements as defined in BS 8110 are also
       Soffit                                                                 available. The fire resistance may be enhanced further by the
           Soffits of Coltman units are suitable for the application of       application of appropriate finishes.
       plaster finishes. Small surface blemishes may be expected
       but the surface will be free from large voids. Stopping off of         Sound Insulation
       air holes and rubbing down of any casting bed marks are not            (See Building Regulations Approved Document E and Robust
       included within our offer.                                             Details Ltd Publication: Robust Details Part, “Resistance To
           The Principal Contractor is responsible for ascertaining           The Passage Of Sound”.)
       the suitability of our floor units, by inspection at our factory if       Where the precast concrete units are forming a floor
       an exposed soffit is required or if the soffit is to receive direct    which is separating individual dwellings, the following points
       decoration in the form of paint, Artex, etc.                           should be considered:
cpc9 setting amended      4/11/05         11:24 AM           Page 4
           It is important that the project Architect ensures the PC     Coltman Precast Concrete Staircases
       floor depth and average density is compatible with the
       intended floor and ceiling finish, if full compliance with
       Building Regulations Part E and or Robust Details Ltd
       Publication: Robust Details Part E, “Resistance To The                                                    Applied finish to landing area
                                                                                                                 by others to accommodate
       Passage Of Sound” is to be achieved.                                                                      manufacturing , building and
                                                                                                                 fixing tolerances.
       Typical End Bearing
                                               Finish
                                               PC concrete floor plank
                                               Ceiling
                           Dry bearing                                                           SECTION A - A
                           Any resulting voids between the top
                           of the inner leaf and the underside
                           of the plank to be filled with a
                           flexible sealant (sealant provided
                           and installed by General Contractor).
       Typical End Bearing
                                                                                   P.C Landing
                                                                                                                           P.C Landing
       Typical Side Bearing
                                                                            A                                                               A
                                               Finish
                                               PC concrete floor plank
                                               Ceiling
                          Gap due to camber to be solidly
                          filled with mortar before the                       Units comprise of bar reinforced concrete stairflights and
                          construction above slab proceeds.              landing slabs, manufactured with concrete having a
                          Where the gap becomes too small
                          to be filled with mortar it should be
                                                                         minimum cube strength of 35N/mm2 at 28 days. The
                          filled with a flexible sealant (mortar         staircase units are cast from steel or high quality timber
                          and sealant provided and installed             moulds. Treads, risers and strings of flights, sides and soffits
                          by the General Contractor).
                                                                         of landing slabs will be as cast from the mould to produce a
                                                                         type “A” finish, as described in BS 8110. Soffits to
       Composite                                                         stairflights will be trowelled smooth and tops of landing slabs
          In composite construction, where a structural concrete         left to receive screed by others.
       topping acts in conjunction with the precast units, the units          The exposed concrete surfaces will be left suitable to
       may require to be supported on a pre-erected, fully braced        receive Artex or similar direct, but further surface preparation
       propping system at centres defined on the layout drawings.        may be required by others if a paint finish is to be applied.
       Props should remain in position until the structural topping           As soon as the staircases have been installed they should
       has reached its design strength or as stated on the layout        be protected from damage by following trades. In the case of
       drawings. The concrete topping should be placed in                supply only contracts the Principal Contractor should satisfy
       accordance with BS 8204 Parts 1 and 2. A structural               himself of the quality prior to offloading. We cannot accept
       topping specification is available from our Technical             responsibility for damage reported to us after the staircase
       Department upon request.                                          units have been offloaded.
                                                                              Balustrade fixings can be provided in the form of pockets.
       Disproportionate Collapse                                         However we would generally recommend that fixings for the
           Requirements for disproportionate collapse must be            balustrade be drilled on site by others.
       specified by the Project Engineer responsible for the overall          All lifting pockets used during installation to be filled in
       design of the structure. Where structural ties are specified,     by others than Coltman.
       they should be designed and detailed by the Project                    The staircase units have lifting anchors cast in during
       Engineer. If the proposed ties are to be cast into details pre-   manufacture. Where installation is not being carried out by
       formed within the PC floor, it is important that the Project      Coltman then lifting eyes need to be obtained from an
       Engineer checks with Coltman that the proposed details are        approved supplier. Our Design Department will advise you of
       achievable.                                                       the type and number required.
cpc9 setting amended                     4/11/05        11:24 AM             Page 5
        LOAD SPAN TABLES
        Coltman Hollow Core Slabs
        These tables are for guidance purposes only. Where deflections natural frequency etc require consideration please contact our Technical Department.
                                                                           2
        (The design includes for self weight and an allowance of 1.75 Kn/m for finishes, but does not include for any partition allowance or the effect of any service holes)
                                                          Maximum Permissible Spans In Metres
                                                           Live Loading (Kn/m2)
           Unit Cross Section
                                                              0.75         1.50          2.00          2.50          3.00          3.50          4.00          5.00             7.50     10.00       12.50   15.00
           Depth - Self Weight
                      (Solid slab)
                                                              5.00         5.00          5.00          5.00          4.88          4.70          4.55          4.27             3.76     3.40         3.12   2.91
              100mm Deep - 2.36 Kn/m2
                                                              7.50         7.50          7.50          7.50          7.26          7.00          6.77          6.36             5.60     5.06         4.65   4.32
              150mm Deep - 2.35 Kn/m2
              (Sound slab - 300 kg/m2)
                                                              7.50         7.50          7.50          7.35          7.08          6.85          6.63          6.26             5.54     5.03         4.63   4.32
              150mm Deep - 2.94 Kn/m2
                                                              10.00        10.00         9.86          9.48          9.14          8.84          8.56          8.07             7.15     6.49         5.98   5.57
              200mm Deep - 2.94 Kn/m2
                                                              12.50        12.05         11.64         11.24         10.87         10.53         10.23         9.69             8.64     7.87         7.28   6.80
              250mm Deep - 3.66 Kn/m2
        Coltman Composite Slabs
        Hollow Core Slab                                                                                                         Solid Plank And                        Grade 35 concrete with A142 mesh
                                                                                                                                                                        reinforcement placed directly onto
        And Structural                                                                                                           Structural Topping                     the floor slabs
        Topping
                                                                                               2
        (The design includes for self weight and an allowance of 1.75 Kn/m for finishes but does not include for any partition allowance or the effect of any service holes)
                                                          Maximum Permissible (Unpropped) Spans In Metres
                                                          Live Loading (Kn/m2)
                                         Total      Total
          Depth of      Depth of
                                         Struct      self
          P.C unit      topping
                                         depth     weight         0.75          1.50         2.00          2.50         3.00          3.50         4.00          5.00            7.50    10.00       12.50   15.00
           (mm)           (mm)                            2
                                         (mm)       (Kn/m )
             75            75             150        3.75         3.75          3.75         3.75         3.75          3.75          3.75         3.75          3.75           3.75      3.73        3.57   3.43
             75           125             200       4.95          3.75          3.75         3.75         3.75          3.75          3.75         3.75          3.75           3.75      3.75        3.67   3.59
            100            50             150       3.79          5.00          5.00         5.00         5.00          5.00          5.00         5.00          5.00           4.69      4.36        4.04   3.54
            100           100             200       5.00          5.00          5.00         5.00         5.00          5.00          5.00         5.00          5.00           4.89      4.70        4.52   4.37
            150            50             200        3.83         7.50          7.50         7.50         7.50          7.50          7.40         7.25          6.98           6.40      5.86        5.43   4.95
            150            75             225       4.43          7.50          7.50         7.50         7.50          7.50          7.39         7.27          7.04           6.56      6.16        5.82   5.54
            200            50             250        4.49         10.0          9.80         9.58         9.37          9.18          9.00         8.82          8.50           7.82      7.22        6.71   6.06
            200            75             275       5.09          9.90          9.61         9.44         9.27          9.10          8.95         8.80          8.53           7.94      7.46        7.05   6.70
            250            50             300        5.25         11.42        11.06         10.82        10.61         10.41        10.21         10.03         9.68           8.93      8.23        7.68   7.22
            250            75             325        5.85         11.15        10.84         10.65        10.47         10.29        10.13         9.97          9.67           9.03      8.50        8.05   7.62
        Partition loadings should be determined in accordance with clause 5.2.2.2 of BS 8110. Line loads should be converted to imposed blanket loads for preliminary design
        purposes. Minimum topping depths are taken at centre of span therefore due allowance should be made for camber when determining overall floor depth.
cpc9 setting amended                4/11/05    11:24 AM    Page 6
       Site Dimensions                                                               Physical
           We do not allow for taking site dimensions. It is the                     Appearance -          Prestressed Floor Units: Grey solid
       Principal Contractor’s responsibility to provide all necessary                                      or with longitudinal hollow cores
       information and ensure that the dimensions on our approved                                          within depth of unit.
       drawings are compatible with the physical dimensions of the                                         Stair/General Precast Items: Grey
       structure as built on site.                                                                         solid units occasional protruding
                                                                                                           steel bearing cleats.
       Testing
           We shall be pleased to provide test cubes, samples of                     Hazards -             Skin irritation or dermatitis unlikely when
       materials etc., for collection by the Principal Contractor from                                     handling the product in its solid form.
       our works for delivering to an approved testing laboratory.                                         Operatives should be aware of the abrasive
           The cost of collection, delivery and testing to be borne by                                     nature of the product. During cutting,
       the Principal Contractor.                                                                           drilling and other operations where dust is
                                                                                                           created there is a risk of inhaling dust
       Inspection Of Finished Work                                                                         containing silica compounds and steel
           The Contractor should ensure that our products and                                              filings, which if inhaled can lead to long
       workmanship are to the satisfaction of all concerned whilst                                         term health hazards. The airborne dust will
       our men are on site. Liability will not be accepted for defects                                     irritate the eyes.
       not notified to us within three days of erection.
                                                                                     PPE/Precautions - Gloves, suitable for handling abrasive
       Health & Safety File Information                                                                material. Eye protection to prevent dust or
          Coltman Precast Concrete Ltd will provide ”As Installed”                                     splinters getting into the eyes. Respiratory
       drawings and calculations at completion of the installation                                     protection to be worn at all times when
       these will include any changes from the original floor layout.                                  carrying out operations that generate dust.
       The Principle Contractor will be responsible for recording any                                  Selection of respirator will depend upon
       amendment to the installed drawings thereafter.                                                 proximity and concentration of dust. Dust
                                                                                                       masks will normally be adequate unless
       Loadings                                                                                        working in confined spaces.
           The floor unit layout drawings and calculations detail the
       loads for which the floor has been designed. Care should be                   Area of Use -         Precast concrete flooring, stair components
       taken to ensure that during construction and during the life                                        and other general precast concrete
       of the building that both the design loads are not exceeded                                         products for use in the construction
       and that additional holes are not introduced without the                                            industry.
       approval of the Coltman Design Department. No further
       partitions other than those shown on the Coltman drawings                     Spillage Requirements -        Not applicable.
       should be built off the floor units again without prior
       consultation with the Coltman Design Department.                              Storage Requirements -         Not applicable.
       Maintenance                                                                   Special First Aid -            Not applicable.
             There are no maintenance requirements.
                                                                                     General
       Demolition                                                                        The illustrations shown and details given in other parts of
          Advice on demolition should be sought from a competent                     this brochure also constitute part of the Standard Technical
       person who has access to the Health & Safety file.                            Specification. For further details, please contact our Technical
                                                                                     Department.
       COSHH Assessment                                                                  Our policy is one of continious improvement, and we
                                                                                     reserve the right to change the specification without notice.
       Product -                    Precast concrete products consisting of
                                    Portland cement, sand, limestone and
                                    quartz aggregates. Can contain calcium              (All illustration dimensions are mm)
                                    silicates and quartz particles.                     Published October 2005.
        BS EN ISO 9001:2000                                                                                                                          ISO 14001
           Registered Firm                                                                                                                       REGISTERED FIRM
      Coltman Precast Concrete Limited London Road Canwell Sutton Coldfield West Midlands B75 5SX. Tel: 01543 480482 Fax: 01543 481587
                                             Website: www.coltman.co.uk E-mail: general@coltman.co.uk
                              Registered Address: Melsonby Terrace 31 Chorley Old Road Bolton Lancs BL1 3AD Registered No. 1032721 London