Mircom Fire Alarm Panels: Device Compatibility Guide
Mircom Fire Alarm Panels: Device Compatibility Guide
sm
                                                                                                                                     i
                                                               FA-100 & FA-1000 Series UL Listed Two-Wire Smoke Detectors
       Notes: Whether mixing different models of compatible smoke detectors or using the same model on the
              same circuit, total standby current of all detectors must not exceed 3 mA.
                                                                                                 Maximum # of
                                             Compatibility Identifier      Rated Standby
   Smoke Detector Make Model / Base                                                               devices per
                                                 Head / Base                  Current
                                                                                                    circuit
Mircom
Apollo
55000-225 / 45681-251, -255, -256, -258 225 / 251, 255, 256, 258 0.045 mA 30
55000-325 / 45681-251, -255, -256, -258 325 / 251, 255, 256, 258 0.045 mA 30
Edwards
C2M-PD/CM2M-PD
EC-103-3/CSBU
Hochiki
                                                                                                                       1
FA-100 & FA-1000 Series UL Listed Two-Wire Smoke Detectors
                                                                                                        Maximum # of
                                                             Compatibility Identifier   Rated Standby
     Smoke Detector Make Model / Base                                                                    devices per
                                                                 Head / Base               Current
                                                                                                           circuit
Hochiki continued
Napco
Sentrol - ESL
System Sensor
2
                                                   FA-100 & FA-1000 Series UL Listed Two-Wire Smoke Detectors
                                                                                     Maximum # of
                                   Compatibility Identifier    Rated Standby
Smoke Detector Make Model / Base                                                      devices per
                                       Head / Base                Current
                                                                                        circuit
                                                                                                           3
FA-100 & FA-1000 Series UL Listed Compatible Four-Wire Smoke Detectors
Mircom
MIR-545U 30
MIR-545TU 30
Sentrol-ESL
541C N/A
541CXT N/A
709-MV-21 N/A
709-24V-21 N/A
System Sensor
1424 25
6424 30
6424A 30
A77-716B
DH400ACDCI 8
DH400ACDCP 8
DH400ACDCIHT 8
4
                                               FA-100 & FA-1000 Series UL Listed Compatible Signaling Devices
S2415 NS-2475W-FR
S2415W NS-24110W-FR
S241575 NS4-2415W-FR
S241575W NS4-241575W-FR
S2475 NS4-2430W-FR
S2475W NS4-2475W-FR
S24110 NS4-24110W-FR
S24110W RS-2415W-FR
H12/24 RSS-241575W-FR
H12/24W RSS-2415W-FR
MDL RSS-241575W-FR
MDLW RSS-2430W-FR
Wheelock RSS-2475W-FR
AS-2415W-24-FR RSS-24110W-FR
AS-241575W-FR RSS-2415C-FW
AS-2430W-FR RSS-2430C-FW
AS-2475W-FR RSS-2475C-FW
AS-24110W-FR RSS-24100C-FW
AS-2415C-FW MT-12/24-ULC
                                                                                                           5
FA-100 & FA-1000 Series ULC Listed Compatible Hardwire Smoke Detectors
FA-100 & FA-1000 Series ULC Listed Compatible Hardwire Smoke Detectors
           Notes: Whether mixing different models of compatible smoke detectors or using the same model on the
                  same circuit, the total standby current of all detectors must not exceed 3 mA.
                                               Maximum # of                                       Maximum # of
        Make & Model/Circuit                                               Make & Model/Circuit
                                                 Devices                                            Devices
C2M-PD/CM2M-PD Hochiki
EC-103-3/CSBU DCD-135/NS6-220 30
Fenwal DCD-135/NS4-220 30
6
                                        FA-100 & FA-1000 Series ULC Listed Compatible Hardwire Smoke Detectors
                         Maximum # of                                        Maximum # of
  Make & Model/Circuit                     Make & Model/Circuit
                           Devices                                             Devices
DCD-190/NS4-220 30 1400-A 30
DCD-190/HSC-220R 30 2400-A 25
SIJ-24/NS6-220 30 1451-A/B401B 25
SIJ-24/NS4-220 30 1451-A/B406B 25
SIJ-24/HSC-220R 30 2451-A/B401B 25
SLR-24/NS6-220 30 2451-A/B406B 25
SLR-24/HSC-220R 30 1451DH/DH400A 30
SLR-24H/NS6-220 30 2451-A/DH400A 25
SLR-24H/NS4-220 30 1151A 30
SLR-24H/HSC-220R 30 2151A 30
SLR-835/NS6-220 30 C2W-BA/C2WT-BA 30
SLR-835/NS4-220 30 C2WTR-B 1
SLR-835/HSC-220R 30 C2WTA-BA 1
SLR-835B-2 30
Mirtone
73471 base
73494 base
73575 base
73495/73486 base
73495/73487 base
73595/73486 base
73595/73497 base
73594/73400 base
73405/73400 base
73594/73401 base
73405/73401 base
NAPCO
FW-2 30
Simplex
2098-9110 base
                                                                                                            7
FA-200 Series UL Listed Two-Wire Smoke Detectors
Mircom
Hochiki
8
                                                              FA-200 Series UL Listed Two-Wire Smoke Detectors
NAPCO
Sentrol - ESL
System Sensor
                                                                                                            9
FA-200 Series UL Listed Four-Wire Smoke Detectors
709-MV-21 6424A
709-24V-21 A77-716B
DH400ACDCIHT
10
                                                                    FA-200 Series UL Listed Signaling Devices
GOS24-15-1 NS4-24110W-FR
GOS24-15/75 RS-2415W-FR
GOS24-15/75 RSS-241575W-FR
GOS24-30/75 RSS-2415W-FR
GOS24-110-1 RSS-241575W-FR
GMH-24 RSS-2430W-FR
GMS-24-15-1 RSS-2475W-FR
GMS-24-15/75-W RSS-24110W-FR
GMS-24-30/75-W RSS-2415C-FW
GMS-24-15/75-C RSS-2430C-FW
GMS-24-110-1 RSS-2475C-FW
WGMS-4/75 RSS-24100C-FW
                                                                                                          11
FA-200 Series UL Listed Signaling Devices
MT-12/24-ULC
MT-24-LS-VFR-ULC
MT-24-WS-VFR-ULC
AMT-12/24-R-ULC
AMT-24-LS-VFR-ULC
MB-G6-24-R
MB-G10-24-R
SM-12/24-R
DSM-12/24-R
12
                                                 FA-260 Series UL/ULC Compatible Two-Wire Smoke Detectors
Mircom
                                                                                                      13
FA-260 Series UL/ULC Listed Smoke Detector Bases
System Sensor
14
                                                   FA-260 Series UL/ULC Listed Smoke Detector Bases
Manufacturer Base
System Sensor
1124B
2124B
2124TB
2124S
2124TS
2124R
2124TR
2124AT
2124ATR
2124AITR
1424
2424
2424TH
2424AT
2424AIT
6424
1151 B112LP
2151 B112LP
1451 B402B
2451 B402B
22451TH B402B
                                                                                                15
FA-260 Series UL/ULC Listed Smoke Detector Bases
                                                                        Voltage
              Manufacturer                         Type     Cd
                                                                        (FWR)
Gentex
GEH24 H - 20-31
GES24-15 S 15 20-31
GES24-30 S 30 20-31
GES24-60 S 60 20-31
GES24-75 S 75 20-31
System Sensor
S2415(W)(A) S 15 20-30
S2475(W)(A) S 75 20-30
H24(W)(A) H - 20-30
16
                                                   FA-260 Series UL/ULC Listed Smoke Detector Bases
                                                 Voltage
      Manufacturer                Type    Cd
                                                 (FWR)
Wheelock
Note: NS = 2-wire, NS4 = 4-wire
AS-2415W-FR(W) S 15 20-31
AS-2430W-FR(W) S 30 20-31
AS-2475W-FR(W) S 75 20-31
AS4-2415C-FR(W) S 15 20-31
AS4-2430C-FR(W) S 30 20-31
AS4-2475C-FR(W) S 75 20-31
AH-24-R H - 20-31
AH-24-WP-R H - 20-31
MT-24-R H 20-31
MT4-24-R H 20-31
                                                                                                17
FA-300, FA-300-6L Series UL Listed Compatible Two-Wire Smoke Detectors
                                                                          Compatibility                     Maximum # of
                                                                                            Rated Standby
                     Make Model / Base                                   Identifier Head/                    devices per
                                                                                            Current (mA)
                                                                               Base                            circuit
Mircom
18
                                        FA-300, FA-300-6L Series UL Listed Compatible Two-Wire Smoke Detectors
                                        Compatibility                                   Maximum # of
                                                                 Rated Standby
           Make Model / Base           Identifier Head/                                  devices per
                                                                 Current (mA)
                                             Base                                          circuit
Hochiki
DCD-135/HSC-220R                      HD-3/HB-72                       0.035                    12
DCD-135/NS6-220                       HD-3/HB-3                        0.035                    12
DCD-190/HSC-220R                      HD-3/HB-72                       0.035                    12
DCD-190/NS4-220                       HD-3/HB-3                        0.035                    12
DCD-190/NS6-220                       HD-3/HB-3                        0.035                    12
SIJ-24/HSC-220R                       HD-3/HB-72                        0.04                    12
SIJ-24/NS4-220                        HD-3/HB-3                         0.04                    12
SIJ-24/NS6-220                        HD-3/HB-3                         0.04                    12
SLR-24/HSC-220R                       HD-3/HB-72                       0.045                    12
SLR-24/NS4-220                        HD-3/HB-3                        0.045                    12
SLR-24/NS6-220                        HD-3/HB-3                        0.045                    12
Sentrol-ESL
429C / (701E, 701U, 702E, 702U)       S10A-S00                          0.1                     30
429CRT / (702E, 702RE, 702RU, 702U)   S11A-S00                          0.1                     30
429CST / (702E, 702RE, 702RU, 702U)   S11A-S00                          0.1                     30
429CT / (701E, 701U, 702E, 702U)      S10A-S00                          0.1                     30
711U / (701E, 701U, 702E, 702U)       S10A-S00                          0.1                     30
713-5U / (701E, 701U, 702E, 702U)     S10A-S00                          0.1                     30
713-6U / (701E, 701U, 702E, 702U)     S10A-S00                          0.1                     30
721U / (701E, 701U, 702E, 702U)       S10A-S00                          0.1                     30
721UT / (701E, 701U, 702E, 702U)      S10A-S00                          0.1                     30
722U / (701E, 701U, 702E, 702U)       S10A-S00                          0.1                     30
731U / (702E, 702RE, 702RU, 702U)     S11A-S00                          0.1                     30
732U / (702E, 702RE, 702RU, 702U)     S11A-S00                          0.1                     30
System Sensor
1100                                  A-N/A                             0.12                    25
1400                                  A-N/A                             0.1                     25
2100                                  A-N/A                             0.12                    25
2400                                  A-N/A                             0.12                    25
1151/B110LP                           A-A                               0.12                    25
1151/B116LP                           A-A                               0.12                    25
                                                                                                           19
FA-300, FA-300-6L Series UL Listed Compatible Two-Wire Smoke Detectors
                                                                          Compatibility                     Maximum # of
                                                                                            Rated Standby
                     Make Model / Base                                   Identifier Head/                    devices per
                                                                                            Current (mA)
                                                                               Base                            circuit
20
                                                       FA-300, FA-300-6L Series ULC Listed Two-Wire Smoke Detectors
MIR-525 30 SLR-24/NS4-220 12
MIR-525T 30 SLR-24/NS6-220 12
55000-225 30 2400A
55000-226 30 1451/B401B
55000-227 30 2451/B401B
55000-325 30
55000-326 30
55000-327 30
55000-328 30
55000-138 30
55000-139 30
55000-140 30
Hochiki
DCD-135/HSC-220R 12
DCD-135/NS6-220 12
DCD-190/HSC-220R 12
DCD-190/NS4-220 12
DCD-190/NS6-220 12
SIJ-24/HSC-220R 12
SIJ-24/NS4-220 12
SIJ-24/NS6-220 12
SLR-24/HSC-220 12
                                                                                                                21
FA-300 and FA-300-6L Series UL and ULC Listed Supported Synchronous Horn/Strobes
FA-300 and FA-300-6L Series UL and ULC Listed Supported Synchronous Horn/Strobes
           Device               Mircom Equivalent Part #                           Amseco Part #
Mircom
FHS-240-110 20
Faraday
6234 Series 16
Gentex
MRA-HS3-24 32
System Sensor
P1224 MC 32
Wheelock
NS-24MCW-FW 40
SurGard MLR2 Multi-Line Receiver (ULC, ULI approved) SIA-DCS and Ademco Contact ID
SurGard SLR Single-Line Receiver (ULC, ULI approved) SIA-DCS and Ademco Contact ID
Silent Knight Model 9500 Receiver (ULI Approved) SIA-DCS and Ademco Contact ID
Radionics Model D6500 Receiver (ULI Approved) SIA-DCS and Ademco Contact ID
Radionics Model D6600 Receiver (ULI Approved) SIA-DCS and Ademco Contact ID
22
                                                                FR-320 Compatible UL Listed Two-Wire Smoke Detectors
                                                Compatibility                             Maximum # of
                                                                   Rated Standby
               Make Model / Base                  Identifier                               devices per
                                                                   Current (mA)
                                                 Head/Base                                   circuit
Mircom
Apollo
Hochiki
                                                                                                                 23
FR-320 Compatible UL Listed Two-Wire Smoke Detectors
                                                        Compatibility                   Maximum # of
                                                                        Rated Standby
                     Make Model / Base                    Identifier                     devices per
                                                                        Current (mA)
                                                         Head/Base                         circuit
Hochiki continued
Sentrol-ESL
System Sensor
24
                                                 FR-320 Compatible UL Listed Two-Wire Smoke Detectors
                                 Compatibility                             Maximum # of
                                                    Rated Standby
            Make Model / Base      Identifier                               devices per
                                                    Current (mA)
                                  Head/Base                                   circuit
System Sensor i3
                                                                                                  25
FR-320 Series ULC Listed Compatible Two-Wire Smoke Detectors
                                                Maximum # of                          Maximum # of
          Make Model / Base                      devices per      Make Model / Base    devices per
                                                   circuit                               circuit
MIR-525 30 SLR-24/HSC-220 12
MIR-525T 30 SLR-24/NS4-220 12
MIR-1400A 30 SLR-24/NS6-220 12
55000-225 30 1400A 20
55000-226 30 2400A 20
55000-227 30 1451/B401B 20
55000-325 30 2451/B401B 20
55000-326 30
55000-327 30
55000-328 30
55000-138 30
55000-139 30
55000-140 30
Hochiki
DCD-135/HSC-220R 12
DCD-135/NS6-220 12
DCD-190/HSC-220R 12
DCD-190/NS4-220 12
DCD-190/NS6-220 12
SIJ-24/HSC-220R 12
SIJ-24/NS4-220 12
SIJ-24/NS6-220 12
26
                                                         FR-320 Series ULC Listed Compatible Two-Wire Smoke Detectors
Manufacturer Description
T8210A107 24VDC
R8210A107 24VDC
8210A107 24VDC
AMEREX
17014 Actuator
BSCO
510006 Actuator
486500-01 Actuator
Parker
SIEMENS
CPYEC-24
TSP
17842 Actuator
                                                                                                                  27
FR-320 Series ULC Listed Compatible Two-Wire Smoke Detectors
                                                               Maximum # of
                        Manufacturer
                                                               Horn/Strobes
Wheelock
NS-24MCW-FW 13
Gentex
MRA-HS3-24 8
System Sensor
P1224 MC 12
Mircom
FHS-240-110 9
Faraday
6234 Series 9
28
                                                              FR-320 Series ULC Listed Compatible Two-Wire Smoke Detectors
Model Description
Detectors
  Note: * Unit employs an integral heat sensor; however it must not be used as a regular heat detector.
        Refer to the product data sheet for detailed functionality, operation and application. Manual
        configuration for the MIX-3200 is NOT PERMITTED. This device must be configured via
        the AUTO CONFIG.
Bases
Ancillary Modules
                                                                                                                       29
FX-350 Compatible Receivers
SurGard MLR2 Multi-Line Receiver (ULC, ULI approved) SIA-DCS and Ademco Contact ID
SurGard SLR Single-Line Receiver (ULC, ULI approved) SIA-DCS and Ademco Contact ID
Silent Knight Model 9500 Receiver (ULI Approved) SIA-DCS and Ademco Contact ID
Radionics Model D6500 Receiver (ULI Approved) SIA-DCS and Ademco Contact ID
Radionics Model D6600 Receiver (ULI Approved) SIA-DCS and Ademco Contact ID
30
                                                        FX-2000 Series UL Listed Compatible Addressable Loop Modules
Mircom
MIX-B501BHT 200 Series Low Profile Intelligent Base with Horn (Temporal Code)
System Sensor
                                                                                                                 31
FX-2000 Series UL Listed Compatible Addressable Loop Modules
B501BHT 200 Series Low Profile Intelligent Base with Horn (Temporal Code)
32
                                                                FX-2000 Series UL Listed Compatible Two-Wire Smoke Detectors
       Notes:
                1.Whether mixing different models of compatible smoke detectors or using the same model on the
                  same circuit, total standby current of all detectors must not exceed 3 mA.
             2. The below listed smoke detectors are compatible with initiating circuits having Compatibility
                Identifier "A".
                                                                                                       Maximum # of
      Smoke Detector Manufacturer               Compatibility Identifier         Rated Standby
                                                                                                        devices per
             Model / Base                           Head / Base                     Current
                                                                                                          circuit
Mircom
Apollo
55000-225 / 45681-251, -255, -256, -258 225 / 251, 255, 256, 258 0.045 mA 30
55000-325 / 45681-251, -255, -256, -258 325 / 251, 255, 256, 258 0.045 mA 30
Hochiki
                                                                                                                         33
FX-2000 Series UL Listed Compatible Two-Wire Smoke Detectors
                                                                                                           Maximum # of
         Smoke Detector Manufacturer                            Compatibility Identifier   Rated Standby
                                                                                                            devices per
                Model / Base                                        Head / Base               Current
                                                                                                              circuit
Hochiki continued
NAPCO
Sentrol - ESL
System Sensor
34
                                              FX-2000 Series UL Listed Compatible Two-Wire Smoke Detectors
                                                                                     Maximum # of
  Smoke Detector Manufacturer    Compatibility Identifier      Rated Standby
                                                                                      devices per
         Model / Base                Head / Base                  Current
                                                                                        circuit
                                                                                                       35
FX-2000 Series UL Listed Compatible Four-Wire Smoke Detectors
                                                                               Maximum # of
                                           Manufacturer & Model/Circuit
                                                                                 Devices
Mircom
MIR-545U 30
MIR-545TU 30
Sentrol-ESL
541C N/A
541CXT N/A
709-MV-21 N/A
709-24V-21 N/A
     449AT, 449C, 449CT, 449CRT, 449CST, 449CSTE, 449CSRT, 449CSRH, 449CSST,       N/A
     449CSSTE, 449CTE, 449CSLT
System Sensor
1424 25
6424 30
6424A 30
A77-716B
DH400ACDCI 8
DH400ACDCP 8
DH400ACDCIHT 8
36
                                                      FX-2000 Series UL Listed Compatible Signalling Devices
P24110 NS-2430W-FR
P24110W NS-2475W-FR
S2415 NS-24110W-FR
S2415W NS4-2415W-FR
S241575 NS4-241575W-FR
S241575W NS4-2430W-FR
S2475 NS4-2475W-FR
S2475W NS4-24110W-FR
S24110 RS-2415W-FR
S24110W RSS-241575W-FR
H12/24 RSS-2415W-FR
H12/24W RSS-241575W-FR
MDL RSS-2430W-FR
   MDLW                          RSS-2475W-FR
   Wheelock                      RSS-24110W-FR
AS-2415W-24-FR RSS-2415C-FW
AS-241575W-FR RSS-2430C-FW
AS-2430W-FR RSS-2475C-FW
AS-2475W-FR RSS-24100C-FW
AS-24110W-FR MT-12/24-ULC
AS-2415C-FW MT-24-LS-VFR-ULC
AS-2430C-FW MT-24-WS-VFR-ULC
                                                                                                         37
FX-2000 Series ULC Listed Compatible Addressable Loop Modules
Mircom
MIX-B501BHTA 200 Series Low Profile Intelligent Base with Horn (Temporal Code)
System Sensor
38
                                                           FX-2000 Series ULC Listed Compatible Hardwire Smoke Detectors
       Notes: Whether mixing different models of compatible smoke detectors or using the same model on the
              same circuit, total standby current of all detectors must not exceed 3 mA.
                                    Maximum # of                                               Maximum # of
      Manufacturer & Model            Devices/            Manufacturer & Model                   Devices/
                                       Circuit                                                    Circuit
Fenwal DCD-190/NS6-220 30
                                                                                                                     39
FX-2000 Series ULC Listed Compatible Hardwire Smoke Detectors
                                                    Maximum # of                               Maximum # of
          Manufacturer & Model                        Devices/          Manufacturer & Model     Devices/
                                                       Circuit                                    Circuit
SLR-24/NS4-220 30 1451DH/DH400A 30
SLR-24/HSC-220R 30 2451-A/DH400A 25
SLR-24H/NS6-220 30 1151A 30
SLR-24H/NS4-220 30 2151A 30
SLR-24H/HSC-220R 30 C2W-BA/C2WT-BA 30
SLR-835/NS6-220 30 C2WTR-B 1
SLR-835/NS4-220 30 C2WTA-BA 1
SLR-835/HSC-220R 30 NAPCO
SLR-835B-2 30 FW-2 30
Mirtone
73471 base
73494 base
73575 base
73495/73486 base
73495/73487 base
73595/73486 base
73595/73497 base
73594/73400 base
73405/73400 base
73594/73401 base
73405/73401 base
Simplex
2098-9110 base
System Sensor
1400-A 30
2400-A 25
1451-A/B401B 25
1451-A/B406B 25
2451-A/B401B 25
2451-A/B406B 25
40
                                                                FX-2000 Series Compatible Synchronized Modules and Strobes
       Notes:
             1. * Strobes and horns must be connected to separate circuits since the horn is a non-synchronized
                audible appliance.
             2. Do not mix and match sync module with strobes from different manufacturers because each
                manufacturer uses different synchronization protocols.
                                                                                                         Max. Strobe /
      Manufacturer                  Brand             Sync. Module              Strobe Model
                                                                                                             NAC
                                                                                                                       41
FX-2200 Compatible Addressable Devices
 MRI-M502M                 Monitor Module for 2- wire smoke detectors Classes A/B        200
                           initiating
42
                                                 FX-2200 Compatible Synchronized Notification Appliances
                                                                         # of
     Manufacturer          Appliance Module      Candela
                                                                      Appliances
Mircom                 FHS-210-110                  75                      18
Secutron               MRA-24 WW                    15                      24
System Sensor          P12224MC                     15                      30
Wheelock               NS-24 MCW-FW                 15                      38
Amseco                 SH24W-75110                  75                      18
Gentex                 GEC3-24WW                    15                      24
                                                                                                     43
Canada                                U.S.A.                                    © Mircom 2009
                                      4575 Witmer Industrial Estates            Printed in Canada
25 Interchange Way
                                                                                Subject to change without prior notice
Vaughan, ON L4K 5W3                   Niagara Falls, NY 14305
Tel: 905-660-4655 Fax: 905-660-4113   Tel: 1-888-660-4655 Fax: 1-888-660-4113   www.mircom.com