035-23572-100
                             YLAA0041 - YLAA0230
                        AIR-COOLED SCROLL CHILLERS
                     WITH BRAZED PLATE HEAT EXCHANGER
                           STYLE B (60 HZ) 4-12 FAN
                                 40 - 230 TON
                                140 - 800 KW
R-410A
                                     IMPORTANT!
                         READ BEFORE PROCEEDING!
                                 GENERAL SAFETY GUIDELINES
This equipment is a relatively complicated apparatus.        which it is situated, as well as severe personal injury or
During rigging, installation, operation, maintenance,        death to themselves and people at the site.
or service, individuals may be exposed to certain com-
ponents or conditions including, but not limited to:         This document is intended for use by owner-authorized
heavy objects, refrigerants, materials under pressure,       rigging, installation, and operating/service personnel. It
rotating components, and both high and low voltage.          is expected that these individuals possess independent
Each of these items has the potential, if misused or         training that will enable them to perform their assigned
handled improperly, to cause bodily injury or death. It      tasks properly and safely. It is essential that, prior to
is the obligation and responsibility of rigging, instal-     performing any task on this equipment, this individual
lation, and operating/service personnel to identify and      shall have read and understood the on-product labels,
recognize these inherent hazards, protect themselves,        this document and any referenced materials. This in-
and proceed safely in completing their tasks. Failure        dividual shall also be familiar with and comply with
to comply with any of these requirements could result        all applicable industry and governmental standards and
in serious damage to the equipment and the property in       regulations pertaining to the task in question.
                                            SAFETY SYMBOLS
The following symbols are used in this document to alert the reader to specific situations:
             External wiring, unless specified as an optional connection in the manufacturer’s product line, is not
             to be connected inside the control cabinet. Devices such as relays, switches, transducers and controls
             and any external wiring must not be installed inside the micro panel. All wiring must be in accor-
             dance with Johnson Controls’ published specifications and must be performed only by a qualified
             electrician. Johnson Controls will NOT be responsible for damage/problems resulting from improper
             connections to the controls or application of improper control signals. Failure to follow this warn-
             ing will void the manufacturer’s warranty and cause serious damage to property or personal injury.
2                                                                                                 JOHNSON CONTROLS
FORM 150.72-ICOM6
                                                                                                                      
ISSUE DATE: 10/24/2019
                                        ASSOCIATED LITERATURE
                                        Manual Description                                          Form Number
 Start-Up Checklist - Style A and B, 60 Hz                                                           150.72-CL1
 Limited Warranty Engineered Systems Equipment                                                       50.05-NM2
JOHNSON CONTROLS                                                                                                     3
                                                                                              FORM 150.72-ICOM6
                                                                                           ISSUE DATE: 10/24/2019
NOMENCLATURE
YL A A 0125 H 46 X C B
DESIGN SERIES
REFRIGERANT = R-410A
A = DESIGN SERIES
A = AIR COOLED
YL = YORK CHILLER
4                                                                                            JOHNSON CONTROLS
FORM 150.72-ICOM6
                                                                                                                                                                          
ISSUE DATE: 10/24/2019
                                                            TABLE OF CONTENTS
SECTION 1 – GENERAL CHILLER INFORMATION AND SAFETY...................................................................... 11
    Introduction...................................................................................................................................................... 11
    Warranty.......................................................................................................................................................... 11
    Handling.......................................................................................................................................................... 11
    Safety and Quality........................................................................................................................................... 11
    About this Manual............................................................................................................................................ 12
    Misuse of Equipment....................................................................................................................................... 12
SECTION 4 – INSTALLATION.................................................................................................................................37
    Installation Checklist........................................................................................................................................ 37
    Startup/Commissioning................................................................................................................................... 37
    Location and Clearances................................................................................................................................. 37
    Spring Isolators (Optional)............................................................................................................................... 38
    Compressor Mounting..................................................................................................................................... 38
    Chilled Liquid Piping........................................................................................................................................ 38
    Pipework Arrangement.................................................................................................................................... 39
    Wiring.............................................................................................................................................................. 39
    Relief Valves.................................................................................................................................................... 40
    High Pressure Cutout...................................................................................................................................... 40
    Single-Point Supply Connection – Terminal Block, Non-Fused
    Disconnect Switch or Circuit Breaker.............................................................................................................. 41
JOHNSON CONTROLS                                                                                                                                                        5
                                                                                                                                              FORM 150.72-ICOM6
                                                                                                                                           ISSUE DATE: 10/24/2019
6                                                                                                                                            JOHNSON CONTROLS
FORM 150.72-ICOM6
                                                                                                                                                                    
ISSUE DATE: 10/24/2019
SECTION 10 – MAINTENANCE............................................................................................................................197
    Compressors................................................................................................................................................. 197
    Condenser Fan Motors.................................................................................................................................. 197
    Condenser MCHX Cleaning.......................................................................................................................... 197
    Operating Parameters................................................................................................................................... 198
    On-Board Battery Back-Up............................................................................................................................ 198
    Thermal Dispersion Flow Switch................................................................................................................... 198
    Brazed Plate Heat Exchanger (Evaporator) Heater...................................................................................... 198
    Overall Unit Inspection.................................................................................................................................. 198
    Temperature.................................................................................................................................................. 201
JOHNSON CONTROLS                                                                                                                                                  7
                                                                                                                                         FORM 150.72-ICOM6
                                                                                                                                      ISSUE DATE: 10/24/2019
LIST OF FIGURES
8                                                                                                                                       JOHNSON CONTROLS
FORM 150.72-ICOM6
                                                                                                                                                                   
ISSUE DATE: 10/24/2019
LIST OF TABLES
JOHNSON CONTROLS                                                                                                                                                 9
                                             FORM 150.72-ICOM6
                                          ISSUE DATE: 10/24/2019
10                                         JOHNSON CONTROLS
FORM 150.72-ICOM6
ISSUE DATE: 10/24/2019
The warranty is limited to parts only replacement and           •	 ANSI/ASHRAE Standard 15 - Safety Code for
shipping of any faulty part, or sub-assembly, which has            Mechanical Refrigeration.
failed due to poor quality or manufacturing errors. All         •	 ANSI/NFPA Standard 70 - National Electrical
claims must be supported by evidence that the failure              Code (NEC).
has occurred within the warranty period, and that the
unit has been operated within the designed parameters           •	 ASME Boiler and Pressure Vessel Code - Section
specified.                                                         VIII Division 1.
All warranty claims must specify the unit model, serial         •	 ARI Standard 550/590 - Positive Displacement
number, order number, and run hours/starts. Model and              Compressors and Air Cooled Rotary Screw Water
                                                                   Chilling Packages.
JOHNSON CONTROLS                                                                                                     11
                                                                                                    FORM 150.72-ICOM6
SECTION 1 – GENERAL CHILLER INFORMATION and SAFETY
                                                                                                 ISSUE DATE: 10/24/2019
12                                                                                                 JOHNSON CONTROLS
FORM 150.72-ICOM6
                                                             SECTION 1 – GENERAL CHILLER INFORMATION and SAFETY
ISSUE DATE: 10/24/2019
JOHNSON CONTROLS                                                                                                13
                                             FORM 150.72-ICOM6
                                          ISSUE DATE: 10/24/2019
14                                         JOHNSON CONTROLS
FORM 150.72-ICOM6
ISSUE DATE: 10/24/2019
JOHNSON CONTROLS                                                                                                15
                                                                                                   FORM 150.72-ICOM6
SECTION 2 – PRODUCT DESCRIPTION
                                                                                                ISSUE DATE: 10/24/2019
16                                                                                               JOHNSON CONTROLS
FORM 150.72-ICOM6
                                                                                   SECTION 2 – PRODUCT DESCRIPTION
ISSUE DATE: 10/24/2019
JOHNSON CONTROLS                                                                                               17
                                                                                                   FORM 150.72-ICOM6
SECTION 2 – PRODUCT DESCRIPTION
                                                                                                ISSUE DATE: 10/24/2019
The operating program is stored in non-volatile memo-        Single-Point Supply Terminal Block
ry battery backed RAM to eliminate chiller failure due       Includes enclosure, terminal-block, and interconnect-
to AC powered failure/battery discharge. Programmed          ing wiring to the compressors. Separate external pro-
set points are retained in lithium battery-backed RTC        tection must be supplied, by others, in the incoming
memory for 5 years minimum.                                  compressor-power wiring. (Do not include this op-
                                                             tion if either the Single-Point Non-Fused Disconnect
COMMUNICATIONS
                                                             Switch or Single-Point Circuit Breaker options have
     •	 Native communication capability for BACnet           been included.)
        (MS/TP) and Modbus.
     •	 Optional communication available for N2 and          Single-Point Non-Fused Disconnect Switch
        LON via eLink Gateway option.                        Unit-mounted disconnect switch with external, lockable
                                                             handle (in compliance with Article 440-14 of NEC), can
BUILDING AUTOMATION SYSTEM                                   be supplied to isolate the unit power voltage for servic-
INTERFACE                                                    ing. Separate external fusing must be supplied, by others
The Microprocessor Board can accept a 4 mA to 20             in the power wiring, which must comply with the Na-
mA, or 0 VDC to 10 VDC input to reset the leaving            tional Electrical Code and/or local codes.
chiller liquid temperature from a Building Automation
System.                                                      Single-Point Circuit Breaker
                                                             A unit mounted circuit breaker with external, lockable
     •	 The standard unit capabilities include remote        handle (in compliance with NEC Article 440-14), can be
        start-stop, remote water temperature reset via a     supplied to isolate the power voltage for servicing. (This
        PWM 4 mA to 20 mA or 0 VDC to 10 VDC input           option includes the Single-Point Power connection.)
        signal or up to two stages of demand (load) limit-
        ing depending on model.                              Control Transformer
     •	 The standard control panel can be directly con-      Converts unit power voltage to 115-1-60 (2.0 or 3.0
        nected to a Johnson Controls Building Automated      KVA capacity). Factory mounting includes primary
        System.                                              and secondary wiring between the transformer and the
                                                             control panel. (Factory-mounted)
POWER PANEL
Each panel contains:                                         Control Options
                                                             Ambient Kit (Low)
     •	 Compressor power terminals
                                                             Units will operate to 30°F (-1.1°C). This accessory in-
     •	 Compressor motor starting contactors per I.E.C.**    cludes all necessary components to permit chiller op-
     •	 Control power terminals to accept incoming for       eration to 0°F (-18°C) or -10°F (-23°C) with variable
        115-1-60 control power                               speed fans. (This option includes the Discharge Pressure
     •	 Fan contactors and overload current protection       Transducer / Readout Capability option.) For proper
                                                             head pressure control in applications below 30°F (-1°C)
The power wiring is routed through liquid-tight con-         where wind gusts may exceed 5 mph, it is recommend-
duit to the compressors and fans.                            ed that Optional Condenser Louvered Enclosure Panels
                                                             also be included. (Factory-mounted)
ACCESSORIES AND OPTIONS
                                                             High Ambient Kit With Sunshield
Power Options
                                                             Allows units to operate when the ambient temperature
Compressor Power Connections                                 is above 115°F (46°C). Includes sun shield panels and
Single-point terminal block connection(s) are provid-        discharge pressure transducers.
ed as standard. The following power connections are
available as options. (See electrical data for specific      Language LCD and Keypad Display
voltage and options availability.) (Factory-mounted)         Spanish, French, German, and Italian unit LCD con-
                                                             trols and keypad display available. Standard language
                                                             is English.
18                                                                                                JOHNSON CONTROLS
FORM 150.72-ICOM6
                                                                                    SECTION 2 – PRODUCT DESCRIPTION
ISSUE DATE: 10/24/2019
Compressor, Piping, Evaporator Options                        to capture the maximum amount of heat. Capable of
Low Temperature Glycol                                        recovering up to 85% total heat of rejection (cooling
                                                              load plus work input); temperatures as high as 140°F
Replaces standard Thermostatic Expansion Valves
with Electronic Expansion Valves to achieve leaving
                                                              (60°C) are possible.                                         2
glycol temperatures as low as 10°F (-12°C). Required          Hydro-Kit
for any leaving liquid temperature below 30°F (-1°C).
                                                              Factory installed Hydro-Kit suitable for water and gly-
Electronic Expansion Valves permit operation at both
                                                              col systems with up to 35% glycol at leaving tempera-
low temperatures and comfort cooling applications
                                                              tures down to 20°F. The hydro-kit option is available
without a capacity loss or derate at either condition.
                                                              in a single or dual configuration (dual as standby duty
(Factory installed)
                                                              only), with totally enclosed permanently lubricated
Chicago Code Relief Valves                                    pump motors.
Unit will be provided with relief valves to meet Chi-         The hydro-kit option comes standard with a balancing
cago code requirements. (Factory-Mounted)                     valve, discharge check valve, discharge shutoff valve,
                                                              thermal dispersion flow switch, pressure ports, inlet
Service Suction Isolation Valve                               wye-strainer, bleed and drain valves and frost protection.
Service suction (ball-type) isolation valves are added
                                                              Service shut off valves, additional pressure ports and ex-
to unit per system (discharge service ball-type isolation
                                                              pansion tanks are optional within the hydro-kit option.
valve is standard on each circuit). (Factory-Mounted)
                                                              Condenser and Cabinet Options
Hot Gas By-Pass
                                                              MCHX Condenser protection against corrosive envi-
Permits continuous, stable operation at capacities below
                                                              ronments is available by choosing any of the following
the minimum step of compressor unloading to as low
                                                              options. For additional application recommendations,
as 5% capacity (depending on both the unit and operat-
                                                              Refer to FORM 150.12-ES1. (Factory-Mounted)
ing conditions) by introducing an artificial load on the
cooler. Hot gas by-pass is installed on only refrigerant      Post-Coated Dipped MCHX Condenser
system #1 on two-circuited units. (Factory-Mounted)
                                                              The unit MCHX is constructed with post dipped-epoxy
Flanges (ANSI/AWWA C-606 couplings Type)                      MCHX condenser. This is recommended for seashore
                                                              and other corrosive applications (with the exception of
Consists of (2) Flange adapter for grooved end pipe (stan-
                                                              strong alkalies, oxidizers and wet bromine, chlorine
dard 150 psi [10.5 bar] cooler). (Not available on optional
                                                              and fluorine in concentrations greater than 100 ppm).
DX cooler 300 psig DWP waterside.) (Field-mounted)
                                                              Enclosure Panels (Unit)
Flow Switch
                                                              Tamper proof Enclosure Panels prevent unauthorized
A thermal dispersion type flow switch provides ac-
                                                              access to units. Enclosure Panels can provide an aes-
curate, low maintenance flow proving and is included
                                                              thetically pleasing alternative to expensive fencing.
standard. It is factory wired and installed in the exten-
                                                              Additionally, for proper head pressure control, Johnson
sion pipe between evaporator outlet and edge of chill-
                                                              Controls recommends the use of Condenser Louvered
er. The extension pipe is secured to the chiller frame
                                                              Panels for winter applications where wind gusts may
for shipping to avoid risk of damage to evaporator
                                                              exceed five miles per hour. The following types of en-
and is easily attached to the evaporator at startup us-
                                                              closure panels are available:
ing the supplied ANSI/AWWA C-606 connector. The
flow switch can be deleted if alternate or existing flow        •	 Wire Panels (Full Unit) - Consists of welded
switch is field supplied.                                          wire-mesh guards mounted on the exterior of the
                                                                   unit. Prevents unauthorized access, yet provides
Heat Recovery Condenser                                            free air flow. (Factory-Mounted)
A partially condensing refrigerant to liquid condenser          •	 Wire/Louvered Panels - Consists of welded
recovers heat off both refrigerant circuits and rejects            wire-mesh panels on the bottom part of unit and
into a single liquid circuit. Factory installed between            louvered panels on the condenser section of the
the compressor discharge and the condenser (air) coils             unit. (Factory-Mounted)
JOHNSON CONTROLS                                                                                                     19
                                                                                                 FORM 150.72-ICOM6
SECTION 2 – PRODUCT DESCRIPTION
                                                                                              ISSUE DATE: 10/24/2019
20                                                                                             JOHNSON CONTROLS
FORM 150.72-ICOM6
                                                                               SECTION 2 – PRODUCT DESCRIPTION
ISSUE DATE: 10/24/2019
                                                                                                   3
                                                            POWER               POWER
                                                            PANEL               PANEL
4 6
                             ITEM                       DESCRIPTION
                              1         Fan assemblies
                              2         MCHX condenser
                              3         Control panel
                              4         Compressors
                                        Receiver included with optional heat
                              5
                                        recovery condenser
                              6         Filter driers
JOHNSON CONTROLS                                                                                           21
                                                                                        FORM 150.72-ICOM6
SECTION 2 – PRODUCT DESCRIPTION
                                                                                     ISSUE DATE: 10/24/2019
7 6
                                  ITEM                  DESCRIPTION
                                   1     Fan deck
                                   2     MCHX condenser
                                   3     Coil headers
                                   4     Control and power panels
                                   5     Compressors
                                   6     Brazed plate evaporator
                                   7     Formed steel base rails
                                   8     Hydro-kit pumps and motors (optional)
22                                                                                    JOHNSON CONTROLS
FORM 150.72-ICOM6
                                                                       SECTION 2 – PRODUCT DESCRIPTION
ISSUE DATE: 10/24/2019
1 2 3 4
           5                   6
                                                                                           LD13248
                             ITEM                   DESCRIPTION
                              1     Fan contactor
                              2     Fan fuses
                              3     Fan contactor
                              4     Disconnect switch (optional)
                              5     XTBF1
                              6     Compressor contactors
                              7     Compressor overloads
JOHNSON CONTROLS                                                                                     23
                                                                             FORM 150.72-ICOM6
SECTION 2 – PRODUCT DESCRIPTION
                                                                          ISSUE DATE: 10/24/2019
                                        2
                                  1
                                                 3          4
12
                                                                      8
                                                                9
                         11
                                            10
                                                                                          LD13248
                              ITEM                     DESCRIPTION
                                  1    Fan contactor
                                  2    Fan fuses
                                  3    Control relay
                                  4    Microcomputer control center
                                  5    Display
                                  6    Keypad
                                  7    XTBC1
                                  8    Microboard
                                  9    XTCB2
                                  10   XTBF2
                                  11   Compressor contactors
                                  12   Compressor overloads
24                                                                         JOHNSON CONTROLS
FORM 150.72-ICOM6
                                                                                    SECTION 2 – PRODUCT DESCRIPTION
ISSUE DATE: 10/24/2019
    FEATURE
                             FEATURE
                                                OPTION                       OPTION DESCRIPTION
                                                                                                                         2
                           DESCRIPTION
     MODEL                 Model (PIN 1-4)               YLAA
                                                 0041    0041
                                                 0048    0048
                                                 0058    0058
                                                 0065    0065
                                                 0070    0070
                                                 0080    0080
                                                 0081    0081
                                                 0089    0089
                                                 0092    0092
                                                 0100    0100
                              Capacity           0101    0101
    CAPACITY
                              (PIN 5-8)          0115    0115
                                                 0120    0120
                                                 0125    0125
                                                 0136    0136
                                                 0142    0142
                                                 0150    0150
                                                 0155    0155
                                                 0156    0156
                                                 0170    0170
                                                 0175    0175
                                                 0200    0200
                                                 0230    0230
                           Unit Designator        S      Standard Efficiency
       UNIT
                               (PIN 9)            H      High Efficiency
       REF.              Refrigerant (PIN 10)     E      R-410A
                                                  17     200/3/60
                                                  28     230/3/60
                               Voltage            40     380/3/60
      VOLTS
                            (PIN 11 & 12)         46     460/3/60
                                                  50     380-415/3/50
                                                  58     575/3/60
                               Starter            X      Across the Line starter
    STARTER
                              (PIN 13)            T      Soft Start
                                                  A      Design Series A (MicroChannel) Copeland Compressor
                                                         Design Series C (MicroChannel CE/ETL Panel) Copeland Com-
                            Design Series         C
     DESIGN                                              pressor
                              (PIN 14)
                                                  D      Design Series D (MicroChannel) Bitzer Compressor
                                                  F      Design Series F (MicroChannel CE/ETL Panel) Bitzer Compressor
                         Development Level
       DEV                                        B      Development Level B
                             (PIN 15)
                                                 SX      SP Supply TB
                                                 SD      SP NF Disconnect Switch
                             Power Field
     POWER                                       BC      SP Circuit Breaker w/ Lockable Handle, 65 kA SCWR
                            (PIN 16 &17)
                                                 BX      SP Circuit Breaker w/ Lockable Handle
                                                 MB      MP Supply w/Ind Sys CB&L Ext Handles
JOHNSON CONTROLS                                                                                                   25
                                                                                                FORM 150.72-ICOM6
SECTION 2 – PRODUCT DESCRIPTION
                                                                                             ISSUE DATE: 10/24/2019
26                                                                                             JOHNSON CONTROLS
FORM 150.72-ICOM6
                                                                                  SECTION 2 – PRODUCT DESCRIPTION
ISSUE DATE: 10/24/2019
JOHNSON CONTROLS                                                                                              27
                                                                                                FORM 150.72-ICOM6
SECTION 2 – PRODUCT DESCRIPTION
                                                                                             ISSUE DATE: 10/24/2019
28                                                                                            JOHNSON CONTROLS
FORM 150.72-ICOM6
                                                                                       SECTION 2 – PRODUCT DESCRIPTION
ISSUE DATE: 10/24/2019
JOHNSON CONTROLS                                                                                                      29
                                                                                       FORM 150.72-ICOM6
SECTION 2 – PRODUCT DESCRIPTION
                                                                                    ISSUE DATE: 10/24/2019
30                                                                                      JOHNSON CONTROLS
FORM 150.72-ICOM6
                                                                                                    SECTION 2 – PRODUCT DESCRIPTION
ISSUE DATE: 10/24/2019
                                                                                                                                                     2
     Control Functions:
     DV - Display Value                              Fans                         Fans
     CHT - Chilled Liquid Temperature                                                                          Components:
     HPC - High Pressure Cutout
     LPC - Low Pressure Cutout                                                                                 Pressure Relief Valve
     HPL - High Pressure Load Limiting
     LTC - Low Temperature Cutout                                                                              Service (Ball) Valve
                                                                                                               Expansion Valve
                                                            Condenser                                     S
                                                                                                               Solenoid Valve
Sight Glass
                                                                                                               Sensor Pressure
                                                                                                               or Temperature
                                                             DV
                                          585 PSIG           HPL         P                                     Service (Stop) Access Valve
                                            PS               HPC
                                                                                                               Filter Drier
                                                                                                               (Removable Core)
                                                                    See P.R.V.
                                                                    Options
      ZCPR-3       ZCPR-2       ZCPR-1
                                                                                                                                      Chilled
                                                                                                                                      Liquid
                                                                                               450 PSIG
Compressors Evaporator
                                    DV
                                    LPC      P               Ambient Air Sensor
                                                                   DV
                                                                   HTC        T
                                                                   LTC
                                                                                                                  T
                                                                                                    Chilled
                                                                                                    Liquid
                                                                                                                 DV
                                    S
                                                                                                                 CHT
                                                                                                                 LTC
                                -YLLSV
                                                                                                                                           LD13139
Low pressure liquid refrigerant enters the cooler and                        high pressure vapor is fed to the air cooled condenser
is evaporated and superheated by the heat energy ab-                         coil and fans where the heat is removed. The fully con-
sorbed from the chilled liquid passing through the                           densed and subcooled liquid passes through the expan-
cooler shell. Low pressure vapor enters at the compres-                      sion valve where pressure is reduced and further cool-
sor where pressure and superheat are increased. The                          ing takes place before entering to the cooler.
JOHNSON CONTROLS                                                                                                                                31
                                             FORM 150.72-ICOM6
                                          ISSUE DATE: 10/24/2019
32                                         JOHNSON CONTROLS
FORM 150.72-ICOM6
ISSUE DATE: 10/24/2019
LD18119
             Read carefully the rigging warning label   Rigging and lifting should only be done by
             on the chiller packaging.                  a professional rigger in accordance with a
                                                        written rigging and lifting plan. The most
                                                        appropriate rigging and lifting method
                                                        will depend on job specific factors, such
                                                        as the rigging equipment available and
                                                        site needs. Therefore a professional rig-
                                                        ger must determine the rigging and lifting
                                                        method to be used and it is beyond the
                                                        scope of the manual to specify rigging
                                                        and lifting details.
JOHNSON CONTROLS                                                                               33
                                                                                                        FORM 150.72-ICOM6
SECTION 3 – HANDLING AND STORAGE
                                                                                                     ISSUE DATE: 10/24/2019
34                                                                                                    JOHNSON CONTROLS
FORM 150.72-ICOM6
                                                                                                                      SECTION 3 – HANDLING AND STORAGE
ISSUE DATE: 10/24/2019
C D D E F
Control Panel
                                                                                              Control Panel
                                                                                                                                                         3
   Y                                                                                      Y
                                 A                                      B                                         A                 B         C
X X LD18121
LD18120
                                                                        E             F       G                           H
                                                Control Panel
Y A B C D
LD27282
10 Fan Units
                                                                F           G             H                       I                 J
                                Control Panel
                           Y
                                                                A           B             C                       D                 E
                                                                                                                                    LD27283
                                                X
12 Fan Units
JOHNSON CONTROLS                                                                                                                                    35
                                                                                                FORM 150.72-ICOM6
SECTION 3 – HANDLING AND STORAGE
                                                                                             ISSUE DATE: 10/24/2019
                                                 LUG
LUG                LIFTING HOLE
                   IN BASE FRAME          FLANGE
                      FLANGE
LOCKING PIN
                                   LIFTING HOLE
  LOCKING PIN                      IN BASE FRAME
LUG
          LOCKING
          PIN
FLANGE
36                                                                                             JOHNSON CONTROLS
FORM 150.72-ICOM6
ISSUE DATE: 10/24/2019
SECTION 4 – INSTALLATION
             To ensure warranty coverage, this equip-        In installations where winter operation is intended and
             ment must be commissioned and serviced          snow accumulations are expected, additional height
             by an authorized Johnson Controls               must be provided to ensure normal condenser air flow.
             service mechanic or a qualified service
             person experienced in chiller installation.     Clearances are listed in Figure 34 on page 100.
             Installation must comply with all appli-
                                                             Foundation
             cable codes, particularly in regard to elec-
             trical wiring and other safety elements         The unit should be mounted on a flat and level founda-
             such as relief valves, HP cutout settings,      tion, floor, or rooftop capable of supporting the entire
             design working pressures, and ventilation       operating weight of the equipment. See Physical Data
             requirements consistent with the amount         YLAA0041 – YLAA0230 60 Hz on page 50 for oper-
             and type of refrigerant charge.                 ating weight. If the unit is elevated beyond the normal
JOHNSON CONTROLS                                                                                                   37
                                                                                                   FORM 150.72-ICOM6
SECTION 4 – INSTALLATION
                                                                                                ISSUE DATE: 10/24/2019
CHILLED LIQUID PIPING                                        3.	 A 1/16 in. mesh strainer is provided at the cooler
                                                                 inlet line just ahead of the cooler. This is important
General – When the unit(s) has been located in its fi-           to protect the cooler from entrance of large particles
nal position, the unit water piping may be connected.            which could cause damage to the evaporator.
Normal installation precautions should be observed in
order to receive maximum operating efficiencies. Pip-        4.	 All chilled liquid piping should be thoroughly
ing should be kept free of all foreign matter. All chilled       flushed to free it from foreign material before the
water evaporator piping must comply in all respects              system is placed into operation. Use care not to
with local plumbing codes and ordinances.                        flush any foreign material into or through the cooler.
Since elbows, tees and valves decrease pump capacity,        5.	 As an aid to servicing, thermometers and pressure
all piping should be kept as straight and as simple as           gauges should be installed in the inlet and outlet wa-
possible. All piping must be supported independent               ter lines.
of the chiller.                                              6.	 The chilled water lines that are exposed to outdoor
             Consideration should be given to com-               ambients should be wrapped with supplemental
             pressor access when laying out water pip-           heater cable and insulated to protect against freeze-
             ing. Routing the water piping too close to          up during low ambient periods, and to prevent for-
             the unit could make compressor servicing/           mation of condensation on lines in warm humid
             replacement difficult.                              locations. As an alternative, ethylene glycol should
                                                                 be added to protect against freeze-up during low
Hand stop valves should be installed in all lines to fa-         ambient periods.
cilitate servicing.                                          7.	 A chilled water flow switch, (either by YORK or
                                                                 others) MUST be installed in the leaving water pip-
Piping to the inlet and outlet connections of the chiller
                                                                 ing of the cooler. If the factory wired flow switch
should include high-pressure rubber hose or piping
                                                                 and extension pipe kit is not selected, the field in-
loops to ensure against transmission of water pump vi-
                                                                 stalled flow switch must be installed so that there
bration. The necessary components must be obtained
                                                                 is a straight horizontal run of at least 5 diameters
in the field.
                                                                 on each side of the switch. Adjust the flow switch
Drain connections should be provided at all low points           paddle to the size of the pipe in which it is to be in-
to permit complete drainage of the cooler and system             stalled (refer to the manufacturer’s instructions fur-
water piping.                                                    nished with the switch). The switch is to be wired
                                                                 to Terminals 13 and 14 of XTBC1 located in the
A small valve or valves should be installed at the high-         control panel, as shown on the unit wiring diagram.
est point or points in the chilled water piping to allow
                                                                          The Flow Switch MUST NOT be used
any trapped air to be purged. Vent and drain connec-
                                                                          to start and stop the chiller (i.e. starting
tions should be extended beyond the insulation to make
                                                                          and stopping the chilled water pump). It
them accessible.
                                                                          is intended only as a safety switch.
The piping to and from the cooler must be designed to
suit the individual installation. It is important that the
following considerations be observed:
38                                                                                                JOHNSON CONTROLS
FORM 150.72-ICOM6
                                                                                              SECTION 4 – INSTALLATION
ISSUE DATE: 10/24/2019
JOHNSON CONTROLS                                                                                                     39
                                                                                                  FORM 150.72-ICOM6
SECTION 4 – INSTALLATION
                                                                                               ISSUE DATE: 10/24/2019
40                                                                                              JOHNSON CONTROLS
FORM 150.72-ICOM6
                                                                                                  SECTION 4 – INSTALLATION
ISSUE DATE: 10/24/2019
14
                                                                                                        13 XTBC1                 4
                          Terminal Block,                                      MICROPANEL
                         NF Disconnect SW
                         or Circuit Breaker
                                                                                                             Flow Switch
                           1L1 1L2 1L3
                                         GRD
                                                                                            L 2
                                                                                    XTBC2
             It is possible that multiple sources of                        The unit evaporator heater uses 120 VAC.
             power can be supplying the unit power                          Disconnecting 120 VAC power from the
             panel. To prevent serious injury or death,                     unit, at or below freezing temperatures,
             the technician should verify that NO                           can result in damage to the evaporator
             LETHAL VOLTAGES are present inside                             and unit as a result of the chilled liquid
             the panel AFTER disconnecting power,                           freezing.
             Before working on equipment.
JOHNSON CONTROLS                                                                                                           41
                                                                                       FORM 150.72-ICOM6
SECTION 4 – INSTALLATION
                                                                                    ISSUE DATE: 10/24/2019
     A-
                                          INTERNAL
                                           INTERNALWIRING
                                                    WIRINGTO
                                                           TOOPTIONAL
                                                              OPTIONALREMOTE
                                                                       REMOTETEMP.
                                                                              TEMP.RESET
                                                                                    RESETBOARD
                                                                                          BOARD
     A+
     14
                                    FLOW SWITCH
     13
     50
     13
     21
                                    REMOTE UNLOAD STEP 1
     13
     20
                                    PWM REMOTE TEMP RESET
     13
     19                             INTERNAL WIRING TO 2-KCR CONTROL RELAY
     13
     18                             INTERNAL WIRING TO 1-KCR CONTROL RELAY
     13
     51
                                    REMOTE START / STOP
     13
XTBC1                                                                             LD13130
            All externally supplied contacts must be            The unit evaporator heater uses 120 VAC.
            capable of switching 24 VDC / 115 VAC.              Disconnecting 120 VAC power from the
            Gold contacts are recommended. If sup-              unit, at or below freezing temperatures,
            plied contacts are from a Relay / Contac-           can result in damage to the evaporator
            tor (Inductive Load), the coil of the Relay         and unit as a result of the chilled liquid
            / Contactor must be suppressed. Typical             freezing.
            suppressor is P/N 031-00808-000.
            It is possible that multiple sources of
            power can be supplying the unit power
            panel. To prevent serious injury or death,
            the technician should verify that NO
            LETHAL VOLTAGES are present inside
            the panel AFTER disconnecting power,
            Before working on equipment.
42                                                                                    JOHNSON CONTROLS
FORM 150.72-ICOM6
                                                                                             SECTION 4 – INSTALLATION
ISSUE DATE: 10/24/2019
Specification of Water
The water side channels in a BPHE may clog if parti-          Back flushing is an ideal method to clear out the block-
cles such as silt, pipe slag, biological matter, and so on,   age. Contact a professional company if a chemical
are not prevented from entering the unit. These matters       cleaning to BPHE is required. Chemical cleaning is
could otherwise block the channels, causing bad per-          one of the high risks of BPHE corrosion, any chemical
formance and increased pressure drop. Under extreme           corrosion will void the warranty.
conditions, they may lead to BPHE freezing.                   No muddy water is permitted for use in this chiller.
The piping system must be properly flushed to clean           Check the chemical specification of water in the table
out the debris and particles generated in the piping          below for chemical consideration.
welding and process before the BPHE is connected.
Strainers can prevent BPHE from blocking. If any of
the media contains particles larger than 1 mm, a strain-
er with a size of 20 mesh is recommended at the up-
stream of the BPHE.                                                                                                       4
Table 3 - CHEMICAL SPECIFICATION OF WATER
                                                                 CONCENTRATION                   TIME LIMIT
      WATER CONTENT                         UNIT
                                                                   (mg/l or ppm)               (analyze before)
     Alkalinity (HCO3-)                     ppm                      70–300                      Within 24 hrs
       Sulfate (SO42-)                      ppm                        < 70                        No Limit
       HCO3- / SO42-                         -                         > 1.0                       No Limit
   Electrical Conductivity                 μS/cm                     10–500                        No Limit
              pH                             -                        7.5–10                     Within 24 hrs
     Ammonium (NH4+)                        ppm                         <2                       Within 24 hrs
       Chlorides (Cl-)                      ppm                       < 100                        No Limit
     Free Chlorine (Cl2)                   mg/L                         <1                       Within 5 hrs
            Oxygen                         mg/L                       < 0.02                     Within 5 hrs
   Hydrogen Sulfide (H2S)                  mg/L                       < 0.05                       No Limit
 Free Carbon Dioxide (CO2)                 mg/L                         <5                         No Limit
    Total Hardness (odH)                   mg/L                      4.0–8.5                       No Limit
        Nitrate (NO3-)                      ppm                       < 100                        No Limit
           Iron (Fe)                       mg/L                        < 0.2                       No Limit
       Aluminum (Al)                       mg/L                        < 0.2                       No Limit
      Manganese (Mn)                       mg/L                        < 0.1                       No Limit
JOHNSON CONTROLS                                                                                                     43
                                                                                                FORM 150.72-ICOM6
SECTION 4 – INSTALLATION
                                                                                             ISSUE DATE: 10/24/2019
44                                                                                            JOHNSON CONTROLS
FORM 150.72-ICOM6
                                                                                          SECTION 4 – INSTALLATION
ISSUE DATE: 10/24/2019
JOHNSON CONTROLS                                                                                                 45
                                                                                                 FORM 150.72-ICOM6
SECTION 4 – INSTALLATION
                                                                                              ISSUE DATE: 10/24/2019
                All chiller supplied contacts are rated at               It is possible that multiple sources of
                115 VAC, 100 VA, resistive load only, and                power can be supplying the unit power
                must be suppressed at the load by user                   panel. To prevent serious injury or death,
                if powering an inductive load (Relay /                   the technician should verify that NO
                Contactor Coil). Typical suppressor P/N                  LETHAL VOLTAGES are present inside
                is 031-00808-000.                                        the panel AFTER disconnecting power,
                                                                         Before working on equipment.
                The unit evaporator heater uses 120 VAC.
                Disconnecting 120 VAC power from the
                unit, at or below freezing temperatures,
                can result in damage to the evaporator
                and unit as a result of the chilled liquid
                freezing.
46                                                                                              JOHNSON CONTROLS
FORM 150.72-ICOM6
ISSUE DATE: 10/24/2019
STANDARD EFFICIENCY
HIGH EFFICIENCY
NOTES:
  1.	 For leaving liquid temperature below 40°F (4°C) (to 10°F [-12°C]) optional low temperature glycol kit required. Contact your
      nearest Johnson Controls Office for application requirements.
  2.	 For leaving liquid temperature higher than 55°F (13°C), contact the nearest Johnson Controls Office for application guidelines.
  3.	 The evaporator is protected against freezing to -20°F (-29°C) with an electric heater as standard.
  4.	 For operation at temperatures below 30°F (-1°C), install the optional Low Ambient Kit on the system.
  5.	 For operation at temperatures below 0°F (-18°C), install the optional Low Ambient Kit with Variable Speed Fans on the system.
                Excessive flow will cause damage to the
                cooler. Do not exceed maximum cooler
                flow. Special care should be taken when
                multiple chillers are fed by a single pump.
JOHNSON CONTROLS                                                                                                                        47
                                                                                                                             FORM 150.72-ICOM6
SECTION 5 – TECHNICAL DATA
                                                                                                                          ISSUE DATE: 10/24/2019
40
                                   35
       Water Pressure Drop (psi)
30
25
20
15
10
A B C D E F G H I J LD28292a
48                                                                                                                         JOHNSON CONTROLS
FORM 150.72-ICOM6
                                                                                               SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/24/2019
JOHNSON CONTROLS                                                                                                         49
                                                                                                                       FORM 150.72-ICOM6
SECTION 5 – TECHNICAL DATA
                                                                                                                    ISSUE DATE: 10/24/2019
NOTES:
1. kW = Compressor Input Power.
2. EER = Chiller EER (includes power from compressors, fans, and the control panels 0.8 kW).
3. Rated in accordance with AHRI Standard 550/590 at an air on condenser temperature of 95°F and a leaving chilled water temperature of 44°F.
4. Additional rating information can be provided by your local Johnson Controls Sales Office.
50                                                                                                                   JOHNSON CONTROLS
FORM 150.72-ICOM6
                                                                                                            SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/24/2019
NOTES:
1. kW = Compressor Input Power.
2. EER = Chiller EER (includes power from compressors, fans, and the control panels 0.8 kW).
3. Rated in accordance with AHRI Standard 550/590 at an air on condenser temperature of 95°F and a leaving chilled water temperature of 44°F.
4. Additional rating information can be provided by your local Johnson Controls Sales Office.
JOHNSON CONTROLS                                                                                                                           51
                                                                                                                       FORM 150.72-ICOM6
SECTION 5 – TECHNICAL DATA
                                                                                                                    ISSUE DATE: 10/24/2019
NOTES:
1. kW = Compressor Input Power.
2. EER = Chiller EER (includes power from compressors, fans, and the control panels 0.8 kW).
3. Rated in accordance with AHRI Standard 550/590 at an air on condenser temperature of 95°F and a leaving chilled water temperature of 44°F.
4. Additional rating information can be provided by your local Johnson Controls Sales Office.
52                                                                                                                   JOHNSON CONTROLS
FORM 150.72-ICOM6
                                                              SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/24/2019
JOHNSON CONTROLS                                                                     53
                                                                                                               FORM 150.72-ICOM6
SECTION 5 – TECHNICAL DATA
                                                                                                            ISSUE DATE: 10/24/2019
ELECTRICAL DATA
               It is possible that multiple sources of                                 The unit evaporator heater uses 120 VAC.
               power can be supplying the unit power                                   Disconnecting 120 VAC power from the
               panel. To prevent serious injury or death,                              unit, at or below freezing temperatures,
               the technician should verify that NO                                    can result in damage to the evaporator
               LETHAL VOLTAGES are present inside                                      and unit as a result of the chilled liquid
               the panel AFTER disconnecting power,                                    freezing.
               Before working on equipment.
Voltage Limitations
The following voltage limitations are absolute and
operation beyond these limitations may cause serious
damage to the compressor.
COMPRESSOR HEATERS
Compressor heaters are standard. ZP180 compres-                        crankcase heaters must be energized for 18 hours to 24
sors utilize 70W heaters; ZP235, compressor use 120                    hours before restarting a compressor. This will assure
W heaters and ZP285, ZP385, and ZP485 utilize 150                      that liquid slugging and oil dilution does not damage
W heaters. If power is OFF more than two hours, the                    the compressors on start.
54                                                                                                           JOHNSON CONTROLS
FORM 150.72-ICOM6
                                                                                                              SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/24/2019
NOTE:
Reference PIN 59 for Pump Model.
Use this table along with Table 11 - Electrical Data Without Pumps on page 56 to determine electrical data of the unit plus the pump.
JOHNSON CONTROLS                                                                                                                            55
                                                                      FORM 150.72-ICOM6
SECTION 5 – TECHNICAL DATA
                                                                   ISSUE DATE: 10/24/2019
56                                                                  JOHNSON CONTROLS
FORM 150.72-ICOM6
                                                                                         SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/24/2019
JOHNSON CONTROLS                                                                                                 57
                                                                        FORM 150.72-ICOM6
SECTION 5 – TECHNICAL DATA
                                                                     ISSUE DATE: 10/24/2019
58                                                                    JOHNSON CONTROLS
FORM 150.72-ICOM6
                                                                                           SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/24/2019
JOHNSON CONTROLS                                                                                                   59
                                                                         FORM 150.72-ICOM6
SECTION 5 – TECHNICAL DATA
                                                                      ISSUE DATE: 10/24/2019
60                                                                     JOHNSON CONTROLS
FORM 150.72-ICOM6
                                                                                                              SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/24/2019
JOHNSON CONTROLS                                                                                                                          61
                                                                                           FORM 150.72-ICOM6
SECTION 5 – TECHNICAL DATA
                                                                                        ISSUE DATE: 10/24/2019
62                                                                                         JOHNSON CONTROLS
FORM 150.72-ICOM6
                                                                                     SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/24/2019
JOHNSON CONTROLS                                                                                                63
                                                                                            FORM 150.72-ICOM6
SECTION 5 – TECHNICAL DATA
                                                                                         ISSUE DATE: 10/24/2019
64                                                                                        JOHNSON CONTROLS
FORM 150.72-ICOM6
                                                                                          SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/24/2019
ELECTRICAL NOTES
NOTES                                                             the rated load amps for all other loads included in
  1.	 Minimum Circuit Ampacity (MCA) is based on                  the circuit. Otherwise, HACR‑type circuit breakers
      125% of the rated load amps for the largest mo-             must be used. Maximum HACR circuit breaker rat-
      tor plus 100% of the rated load amps for all other          ing is based on 225% of the rated load amps for the
      loads included in the circuit, per NEC Article              largest motor plus 100% of the rated load amps for
      430‑24. If the optional Factory Mounted Control             all other loads included in the circuit.
      Transformer is provided, add the following MCA
                                                                6.	 The “INCOMING WIRE RANGE” is the mini-
      values to the electrical tables for the system pro-
                                                                    mum and maximum wire size that can be ac-
      viding power to the transformer: ‑17, add 2.5 A;
                                                                    commodated by the unit wiring lugs. The (2)
      ‑28, add 2.3 A; ‑40, add 1.5 A, ‑46, add 1.3 A; ‑58,
                                                                    preceding the wire range indicates the number of
      add 1 A.
                                                                    termination points available per phase of the wire
  2.	 The minimum recommended disconnect switch is                  range specified. Actual wire size and number of
      based on 115% of the rated load amps for all loads            wires per phase must be determined based on the
      included in the circuit, per NEC Article 440.                 National Electrical Code, using copper connec-
                                                                    tors only. Field wiring must also comply with lo-
  3.	 Minimum fuse size is based upon 150% of the rat-
                                                                    cal codes.
      ed load amps for the largest motor plus 100% of the
      rated load amps for all other loads included in the       7.	 A ground lug is provided for each compressor sys-
      circuit to avoid nuisance trips at start‑up due to lock       tem to accommodate a field grounding conductor
      rotor amps. It is not recommended in applications             per NEC Table 250‑95. A control circuit ground-      5
      where brown outs, frequent starting and stopping              ing lug is also supplied.
      of the unit, and/or operation at ambient tempera-
                                                                8.	 The supplied disconnect is a “Disconnecting
      tures in excess of 95ºF (35ºC) is anticipated.
                                                                    Means” as defined in the NEC 100, and is intend-
  4.	 Maximum fuse size is based upon 225% of the                   ed for isolating the unit for the available power
      rated load amps for the largest motor plus 100%               supply to perform maintenance and troubleshoot-
      of the rated load amps for all other loads included           ing. This disconnect is not intended to be a Load
      in the circuit, per NEC Article 440-22.                       Break Device.
  5.	 Circuit breakers must be UL listed and CSA certi-         9.	 Field Wiring by others which complies to the Na-
      fied and maximum size is based on 225% of the                 tional Electrical Code and Local Codes.
      rated load amps for the largest motor plus 100% of
JOHNSON CONTROLS                                                                                                   65
                                                                                    FORM 150.72-ICOM6
SECTION 5 – TECHNICAL DATA
                                                                                 ISSUE DATE: 10/24/2019
66                                                                                 JOHNSON CONTROLS
FORM 150.72-ICOM6
                                                                                                       SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/24/2019
JOHNSON CONTROLS                                                                                                                    67
                                                                                                                  FORM 150.72-ICOM6
SECTION 5 – TECHNICAL DATA
                                                                                                               ISSUE DATE: 10/24/2019
68                                                                                                               JOHNSON CONTROLS
FORM 150.72-ICOM6
                                                              SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/24/2019
JOHNSON CONTROLS                                                                     69
                                                                                                                                                                                                                                   FORM 150.72-ICOM6
SECTION 5 – TECHNICAL DATA
                                                                                                                                                                                                                                ISSUE DATE: 10/24/2019
                                                                              WIRING DIAGRAMS
                                                                         ELEMENTARY WIRING DIAGRAMS
                                                                                                                                                                                                                        1L1/1.1
                                                        1L1/1.1
                                                        1L2/1.1
                                                        1L3/1.1
                                                                         2L1/1.4
                                                                         2L2/1.5
                                                                         2L3/1.5
1L3/1.1
2L1/1.4
                                                                                                                                                                                                                                               2L3/1.5
                                                                                                                                                                                                                        1L2/1.1
                                                                                                                                                                                                                                               2L2/1.5
                                                                                                                      1 3 5                            1 3 5                                                                                                     NB31
          1L1          1L2        1L3                                                                  =1-QCB                         =2-QCB
2L1
                                                                                                                                                                                                      2L3
                                                                                                                                                                                            2L2
                               1L3
        1L1
1L2
                                                                                                                      2 4 6                            2 4 6
                                            1L1                                                                                                                                                                       2L1
                                            1L2                                                                                                                            NB20                                       2L2
                                                                                                                                                      2L1/1.4
                                                                                                                                                      2L2/1.5
                                                                                                                     1L2/1.1
                                                                                                                     1L3/1.1
                                                                                                                                                      2L3/1.5
                                                                                                                     1L1/1.1
                                            1L3                                                                                                                                                                       2L3
                                                                                                                                                                                =2-TC
                                                            =1-TC                                                                                                               .11
                                                              .9          NB20
                                        115V-1-50/60HZ
                 -F3                        L1 N PE                                          NB23                                                                                           NB23
                                                                                  2 4 6                              2 4 6                                2 4 6                                                  2 4 6                        2 4 6
                                             L 2 GND
                   90
91
                 -T2                                                              1 3 5                              1 3 5                                1 3 5                                                  1 3 5                        1 3 5
                                           -XCTB2
                 +EXT                                            =1-KM1                         NB56A =1-KM2                               =1-KM3                 NB57A                           =2-KM1                        =2-KM2                  NB58A
       NB18                                    NB18                  /2.5         2 4 6                   /2.6       2 4 6                     /2.6       2 4 6                                       /2.9       2 4 6            /2.10       2 4 6
                            115V
                                                                            1     3 5                            1    3 5                             1   3 5                                                1    3 5                     1   3 5
                   L
                                                                                                                                                                                                                                                      GND
                                                                                                                            GND
GND
                                                                                                                                                                                                                        GND
                                                                                                                 103
                                                                                                                 104
                                                                                                                 105
                                                                                                                                                      106
                                                                                                                                                      107
                                                                                                                                                      108
                                                                            100
                                                                                                                                                                                                             200
                                                                                                                                                                                                             201
                                                                                                                                                                                                             202
                                                                                                                                                                                                                                          203
                                                                                                                                                                                                                                          204
                                                                                                                                                                                                                                          205
        NB9      2
                                                                                     101
                                                                                                                                             NB2
              5                                                                                                      L1 L2 L3 PE                          L1 L2 L3 PE                                            L1 L2 L3 PE                  L1 L2 L3 PE
                                                                                   102
                                                                                  GND
         -XTBC2               5                 NB10
                  5
                                                                                  L1 L2 L3 PE                                =1-M2                               =1-M3                                                  =2-M1                         =2-M2
                                                                                                                            +EXT                                +EXT                                                     +EXT                          +EXT
                                                                    -XP1                                                                                                                                                      NB37
                                        -XP2                         2            2
                                                                                                                                                                13
                                                      GND                                                                                                                                                                                      =2-SZT
                                                      POWER                                                                                                                                                                                     NB37
                              2
             1
                                                                                                                                                                                                                                20      21 51 -XTBC1
                                                 BRN-POS
                                                                                            -ADIS
                                                BRN-NEG
                                                                                                                                                                -SKP                                                                             50
                                     -T1
                 40         24V
                                                                 LED PWR
                                                                                                                                           ROW1
                                                                                                                                           ROW2
                                                                                                                                           ROW3
                                                                 LED GND
                                                                                                                                           COL1
                                                                                                                                           COL2
                                                                                                                                           COL3
                                                                                                                                           COL4
                                                                                                                                           GND
                                                                                                                                                                                                                              12
                                                                 GND
GND
20
                                                                                                                                                                                                                                                       50
                                                                                                                                                                                                                              21
                                                                                                                                                                                                                              51
                 41
                                                                 R/W
                                                                 DB0
                                                                 DB1
                                                                 DB2
                                                                 DB3
                                                                 DB4
                                                                 DB5
                                                                 DB6
                                                                 DB7
                                                                 +5V
                                                                                                                                           NC
                                                                                                                                           NC
                                                                                                                                           NC
                                                                                                                                           NC
                                                                                                                                           NC
                                                                                                                                           NC
                                                                                                                                           NC
                                                                                                                                           NC
                                                                                                                                           NC
                                                                                                                                           NC
                                     -GND
                                                                 RS
             40                                     - +
                            1 2 3                                1 2 3 4              5 6 7 8       9 10 11 12 13 14 15 16                 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18                                     1 2 3 4 5                        6
       BRN
                                                  -XTB4
             1
                            1 2 3                     NB6                                                                                                                                                                     1 2 3 4 5                      6
             1
                            -J14                                                             J1                                                                           J2                                                                                     -J13
                        -AMB
         .7                                       -K1              -K2                -K3            -K4              -K5              -K6                -K7             -K8            -K9                 -K10             -K11            -K12               -K13
     -SFE 3
     +EXT
            3
                  NB50
       BLU
41
LD29089a
70                                                                                                                                                                                                                                   JOHNSON CONTROLS
FORM 150.72-ICOM6
                                                                                                                                                                                                                                                      SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/24/2019
                                                                                                                                                                                                                                                                                                   035-21583-101
                                                                                                                                                                                                                                                                                                      REV. R
                                                                                                                          23
                                                                       380/415V-3-50/60HZ                                                                              13                      13                          13                                                   23
                                                                                                                                                                                                                                                                                                     /32.10
                                             2 4 6                                                                -XTB8                                   =1-KM3            =1-KM2                                         =1-KM1                                                =1-KCR
                                                                                                                                  6                                                                                                                         NB1                     /2.1                                    NB1
                                                                                                                                                             /2.6      14       /2.6           14                          14 /2.5                                              24
                                     -QCB                                    2 4 6
                                                               -QSD                                                                     NB1
                                                                                                                  -K13
                                                                                                   PE                .6                                                                                                                -XP2                                                           -XP2
                                                                                                                                                                                                                                                     -XTBC2                                   30                         -XTBC2
                                             1 3 5
                                                               NB16          1 3 5                                                                                                                                                        13             26                                                   15             30
                                                                                                                  -XTB8
                                                                                                                                                            NB61
                                                                                                                                  7
                                                                                                                                      -XTBC2                                  27                                                      -XP3           -XTBC2                                   31     -XP3                -XTBC2
                                                                                                                          24
                                                                                                                                          24                                                                                         10                  27                                          12                      31
                                                                                                                                                                       13                      13                          13                                                   23
                                                                                                                                                      =2-KM3             =2-KM2                                            =2-KM1                                               =2-KCR
                                                               1L1/1.1
                                                               1L2/1.1
                                                               1L3/1.1
                                                                                             2L1/1.4
                                                                                             2L2/1.5
                                                                                             2L3/1.5
                                                                                                                                                                                                                               /2.9                         NB1                                                            NB1
                                                                                                                                                        /2.10          14 /2.10                14                          14                                                   24 /2.1
                                                                                                                                                                                                                                                                          PORT 1
                                                                                                                                                                                                                                                                        COM REF
                                                                                                                                                                            2/1.1         2         -T5                          WHT
                                                                                                                                                                                                                                                                              PORT 2A RS485
           =2-QMMSC3            1 3 5                                                                                     NB42                                                                                                                               COM                         SHD
                                                                                                                                                                                                           24                                                   TB5                                                BLK
                                                                                       NB37                                                                                                                VAC                                                        -
                                                                                                                                                                            5/1.1         5                                       BLK                                                                 RED
                                                                                                                                                                                                                                                             HOT      +
                                                                                                                                                                                                                                                               -ELINK
                                                                                                                                                                                                                                                                                                                   SCR
                                                                                                                                                                                                                       R
                                                                +5V
+5V
                                                                                                                                        +5V
                                                                      SIG
SIG
SIG
2 4 6
                =2-KM3
                                1 3 5
                                        NB59A
                                                                            -8                                         -9                           -10
                                                                                                                                                                           HOT           COM
                                                                                                                                                                                                          COM
                                                                                                                                                                                                                                                                                                                                        5
                                                                                                                                                                                                                                                                                                                          RED
                                                                                   LK1
                                                                                                                                                                                                                                                                                                                          BLK
                                                               SCR
                                                               RED
                                                                                                         SCR
                                                                                                         RED
                                                                                                                                       SCR
                                                                                                                                       RED
                                                                                                                                                                                   J10
                                                               BLK
BLK
BLK
                  /2.10         2 4 6                                                                                                                                                               J12
                                                                                                                                                                                                          SHD
                           1    3 5                                                                                                                                                                                                                                     -AMB
                =2-SS3
                                                                                                                                                                                                                   -
                           2    4 6                             2 5 8                  7 12                1 4 7                        1 4 7                                                             J8                                                                                                       4 3 2 1
                                                                                                                                                                                                                   +                                                                                                 -TB1
                                                                                                                                                                                       SC-EQ
                                      GND
                           206
                           207
                           208
                                                                2 5 8                  7 12                1 4 7                        1 4 7
                                L1 L2 L3 PE
                NB2                                              -J6              -J11                      -J8                         -J10                                                         =1-UBR                                                                                        =2-UBR
                                                                                                                                                                               NB20                                                                               NB20
                                       =2-M3                                                                                              -AMB
                                        +EXT                                                                                                                                  =1-TC                                                                               =2-TC
                                                                                                                                                                                  .2                                                                                  .4
                      13                      13                                              NB32
                                                                              -BECT                  -BLCT                -BAMB
                                              WHT
                                                    2                                                                                                                                                              =1-R                                                                                       =2-R       A-    A+
          33               33                            -SF
                                       -SFE
                                                                                                                                                                                                               2                                                                                          2
                                       +EXT 2
                                                                                                                                                                                                    GND
                                                                                                                                                                                                                                                                                                   GND
          =1-KCR           =2-KCR                       +EXT
                                                                                                                                                                                                    SIG
                                                                                                                                                                                                                                                                                                   SIG
              /2.1         34 /2.1
           34
                                                                                                                                                      B A C                     B A C                                                 B A C                        B A C
                                               4                                                                                                      1 2 3                     1 2 3                                                 1 2 3                        1 2 3
          18
19
                                                        NB50
                                                                                 +5V
                                                                                                                                                                                                                                                                                                                          A-NEG
                                                                                                                                                                                                                                                                                                                          A-POS
                                                                                       SIG
+5V
                                                                                                                            +5V
                                                                                                           SIG
SIG
GND
GND
                                                                                                                                                                                                                                                                        GND
                                                                                                                                                                                   GND
                                                                                                                                                    +5V
SIG
+5V
                                                                                                                                                                                                                                                              +5V
                                                                                                                                                                                                                                               SIG
                                                                                                                                                                                                                                                                              SIG
                                                                                                                                                                             +5V
SIG
           -XP4             -XP4                    4
                                                                                              -3                 -1                     -2                            -4                       -6
                                                                                                                                                                                                                                                                                              -7
                                              BLK
          2                3                                                                                                                                                                                                                           -5
                                                                                                                                                                                                      BRN 53
                                                                                                                                                                                                      PNK 52
                                                                                                                                                                                                                                                                                                    BRN 55
                                              14                                                                                                                                                                                                                                                    PNK 54
                                                                                                           RED
                                                                                                                                  RED
                                                                                                   SCR
                                                                                                                       SCR
                                                                                                           BLK
BLK
WHT
WHT
WHT
WHT
                                                                                                                                                                                                                                                                                                                          GND
                                                                            SCR
                                                                            RED
                                                                                                                                                SCR
                                                                                                                                                RED
                                                                                                                                                                           SCR
                                                                                                                                                                           RED
                                                                                                                                                                                                                               SCR
                                                                                                                                                                                                                               RED
                                                                                                                                                                                                                                                             SCR
                                                                                                                                                                                                                                                             RED
                                                                            BLK
BLK
BLK
BLK
BLK
                                                                                                                                                                                                                                                                                                                          SIG
     18           19 -XTBC1
                                              14
8 10 9 2 5 8 1 4 7 3 6 9 1 5 9 10 2 6 7 11 4 12 1 5 9 10 2 6 7 11 4 12 6 11
          8                10                       9                        2 5 8                  1 4 7                 3 6 9                     1 5 9 10                2 6 7 11                  4 12                      1 5 9 10                      2 6 7 11                              4 12                     6 11
                                                                                                     -J6                                                                     -J7                                                                              -J9                                                           -J11
                                                                                                                                                                                                                                             -TB1 RS485                            -TB3    RS232
                           -K14             -K15           -K16              -K17                   -K18                  -K19                      -K20               -K21                    -K22                    -K23               -K24 1 2 3 4                                1 2 3 4 5 6
                                                                                                                                                                                                                                                      485+
                                                                                                                                                                                                                                                                                              GND
                                                                                                                                                                                                                                                      SCR
                                                                                                                                                                                                                                                                                              RXD
                                                                                                                                                                                                                                                      485-
                                                                                                                                                                                                                                                      REF
                                                                                                                                                                                                                                                                                              RTS
                                                                                                                                                                                                                                                                                              CTS
                                                                                                                                                                                                                                                                                              TXD
+5V
NB7 NB8
LD29089b
DWG. 1
JOHNSON CONTROLS                                                                                                                                                                                                                                                                                                                   71
                                                                                                                                                                                                                                                            FORM 150.72-ICOM6
SECTION 5 – TECHNICAL DATA
                                                                                                                                                                                                                                                         ISSUE DATE: 10/24/2019
231
1/1.1
             =1-XTBF                        =2-XTBF
                 131                            231
                                3                              3
        =1-FHP                         =2-FHP                                                                                                          -XP3
         +EXT 3                         +EXT 3                           =1-FHP                  =2-FHP                                               14
                                                                           +EXT                    +EXT
            P>                          P>
                                                                               P>                      P>                                                              -XP2
                   1                              1                                                                                                                    1                                                                                                -XP2                -XP2
                                                                   OR
                          1                              1                                                                                                                                                                                                              4                   6
        =1-XTBF                       =2-XTBF                                                                                                                                       1
            132                           232
                                                                                                                                                                                 -XP1
        =1-BMP1                       =2-BMP1
           +EXT M1(11)                   +EXT M1(11)
            >                           >
             .3           M2(14)            .8           M2(14)
                                                                               3/1.1
                                                                                                                                                                                           =1-XTBF
                                                      232
                       132
        =1-XTBF                       =2-XTBF                                                                                                                                                   1
            133                           233
                                                                                         3
                                                                                                                                                                                                                         =1-XTBF
        =1-BMP2                       =2-BMP2
           +EXT M1(11)                   +EXT M1(11)                                                                                                                                                                           1
233
            134                           234
                                NB2
                       134
234
                                                                                                                                                                                                                   125
                                                                                                                                                                                    124
126
119
                                                                                                                                                                                                                                                                                      121
        =1-BMP3                       =2-BMP3
           +EXT M1(11)                   +EXT M1(11)                                                                                                      =1-XTBF              =1-XTBF                        =1-XTBF                        =1-XTBF
            >                           >                                                                                                                      1                 124                             125                            126
             .5           M2(14)            .9           M2(14)
                          43                             43
        QMMSC                         QMMSC
        -AUX1             44          -AUX4              44
                                                                                                                                  149                                  =1-SCH1                         =1-SCH2                        =1-SCH3
                          43 NB69                        43                                                                                                               +EXT                            +EXT                           +EXT
        QMMSC                    QMMSC                                                                                                                                                                                                                                                           NB35
        -AUX2             44     -AUX5                   44
                                                                               =1-XTBF            =1-XTBF                   149                                                 >                              >                              >
                          43                             43                    149                149
                               NB70
        QMMSC                         QMMSC
        -AUX3             44          -AUX6              44                                   -XTB2
                                                                                          149 +EXT
                                                                                                                                  NB32                                  NB11                           NB11                           NB11
        =1-XTBF               NB11 =2-XTBF
            135                        235                                                                                                                            =1-BMP1                         =1-BMP2                        =1-BMP3                            NB62B1
                                                                        NB36             NB47                    NB51             NB48                                                                                                                                                      NB62B2
                                                                                                                                                                      +EXT                            +EXT                           +EXT
                       135
235
            =1-KCR A2                   =2-KCR A2 -EHRH1 -EHRH2 -EEH1                     -EEH2                                             -KH A2                      (2)                            (2)                            (2)                  =1-KM1 A2           =1-KM2 A2
                                                    +EXT +EXT +EXT                         +EXT                                                                  .1     S2                      .1     S2                      .1     S2
                                                                                               -XTB2                                                                        =1-ECH1                            =1-ECH2                         =1-ECH3
                                                                                             2 +EXT                                                                   T2(N) +EXT                     T2 (N)      +EXT               T2 (N)      +EXT
                                                                                                  2                                                                           =1-XTBF                                               =1-XTBF
                                                                                                                                                                                                                                                  2
                  2                                                                    =1-XTBF                                                                                      2                                         2
2/1.2
NB2
NB56C
                                                                                                                                                                                                                                                                                        LD29243a
 2/1.2 What these numbers mean. Example:
 2 = follow wire no.2
 1. = is the drawing number on the bottom center of each page.
 .2 = is the locator number across the top of the page.
 At the top of the pages the numbers 1 to 11 go from left to right. Find drawing number 1 and in                                                                                                                                             DWG. 2
 column number 2 across the top of the page, locate wire number 2.
72                                                                                                                                                                                                                                                        JOHNSON CONTROLS
FORM 150.72-ICOM6
                                                                                                                                                                                                                              SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/24/2019
X Y
118 218
                                                                                                                                                            -XP3
                                                                                                    -XP2                                                   1
                                                                                                    3
                                                                                                14                                                         14
             -XP2                     -XP2                                        =1-KCR                                                     =2-KCR                               -XP3                  -XP3                   -XP3                        -XP3
             7                        5                                                .1       13                                                .1       13                    2                     4                      5                           3
                                                                                                                =2-XTBF
                                                                                                           1
                                             120                                                                                              =2-XTBF                                                                                                              220
                                                                                                                                        1
                                                                                                      21                           21                            21
                                                                                                                                                                                                                                                                                                   5
                                                                                                                                                                                                                                                    220
                                                                                          =2-KM1                 NB58B =2-KM2                 NB59B =2-KM3
                                                            123
                                                                                               .9     22               .10 22                        .10
                                                                                                                                                                 22
                                120
                                                                                                                             225
                                                                                                224
                                                                                                                                                           226
       122
219
221
                                                                                                                                                                                                                        222
                                              NB46                                                                                                                                                                                                                NB46
                    =1-XTBF                                           =2-XTBF             =2-XTBF                       =2-XTBF                      =2-XTBF                                                                             =2-XTBF
                                               120                                                                                                                                                                                                                 220
                        120                                                1                224                            225                          226                                                                                  220
                                                                                                                                                                                                                                                                                 223
                                                                                   =2-SCH1                       =2-SCH2                      =2-SCH3
                                                                                      +EXT                          +EXT                         +EXT
NB2
LD29243b
DWG. 2
JOHNSON CONTROLS                                                                                                                                                                                                                                                                           73
                                                                                                                                                                           FORM 150.72-ICOM6
SECTION 5 – TECHNICAL DATA
                                                                                                                                                                        ISSUE DATE: 10/24/2019
                                                                                       FAN WIRING
035-21583-125
    Rev C
                 1L1
     1L1/1.1
                 1L2
     1L2/1.1
                 1L3
     1L3/1.1
=1-F4
          NB21                                  350
                                                   351
                                                      352
NB15
                                                                                                                                                              1L1
                                                                                                                                                              1L2
                                                                                                                                                              1L3
                                                                                                                                                                           NB27
                                                                                                                                                           =1-F5
                                                                                                                                                              360
                                                                                                                                                              361
                                                                                                                                                              362
                                 1 3 5                                 1 3 5                                                        1 3 5
                   =1-KF1                                  =1-KF2                                                  =1-KF3
                        .3       2 4 6                          .3     2 4 6                                            .4          2 4 6
                             150
                             151
                             152
155
158
158
                                                                                                                                                                                     158
                                                                      154
154
157
157
                                                                                                                                                                                   157
                                                                     153
153
156
156
                                                                                                                                                                                  156
                                T1 T2 T3 PE                            T1 T2 T3 PE                   T1 T2 T3 PE                    T1 T2 T3 PE                T1 T2 T3 PE          T1 T2 T3 PE
X/2.8 -AMB
                                                                                                                                           -XTB7
                                                      8                                     9                                             10
128
129
A1 A1 A1
                                         2
                               2/1.2
LD27947a
74                                                                                                                                                                        JOHNSON CONTROLS
 FORM 150.72-ICOM6
                                                                                                                                                         SECTION 5 – TECHNICAL DATA
 ISSUE DATE: 10/24/2019
             2L1
2L1/1.5
             2L2
2L2/1.5
             2L3
2L3/1.5
=2-F4
                                           450
                                              451
                                                 453
                                                                                                                                                  2L1
                                                                                                                                                  2L2
                                                                                                                                                  2L3
                                                                                                                                                              NB27
                                                                                                                                               =2-F5
                                                                                                                                                  460
                                                                                                                                                  461
                                                                                                                                                  462
                            1 3 5                            1 3 5                                                         1 3 5
              =2-KF1                             =2-KF2                                                      =2-KF3
                   .7       2 4 6                     .8     2 4 6                                                .9       2 4 6
                                                                                                                                                                                               5
                        250
                        251
                        252
255
258
258
                                                                                                                                                                        258
                                                            254
254
257
257
                                                                                                                                                                      257
                                                           253
253
256
256
                                                                                                                                                                     256
                            T1 T2 T3 PE                     T1 T2 T3 PE                    T1 T2 T3 PE                     T1 T2 T3 PE          T1 T2 T3 PE           T1 T2 T3 PE
Y/2.8
                                                                                                                    -XTB10
                                  8                                         9                                      10
228
229
A1 A1 A1
LD27947b
 FIGURE 17 - F
              AN WIRING, STANDARD AIR FLOW (CONT’D)
 JOHNSON CONTROLS                                                                                                                                                                         75
                                                                                                                                                                                                                         FORM 150.72-ICOM6
SECTION 5 – TECHNICAL DATA
                                                                                                                                                                                                                      ISSUE DATE: 10/24/2019
                                                                                                  FAN WIRING
 035-21583-118
     Rev H
                    1L1
       1L1/1.1
NB40                 1L2
       1L2/1.1
                     1L3
       1L3/1.1
                             1 3 5                        1 3 5                                   1 3 5                                        1 3 5                                   1 3 5                                       1 3 5
                 =1-KF1                       =1-KF2                                 =1-KF3                                  =1-KF4                                    =1-KF5                                          =1-KF6
                      .2     2 4 6                 .4     2 4 6                           .5      2 4 6                           .6           2 4 6                        .4         2 4 6                                .3     2 4 6
                           150
                           151
                           152
                                                        153
                                                        154
                                                        155
                                                                                               156
                                                                                               157
                                                                                               158
                                                                                                                                         159
                                                                                                                                         160
                                                                                                                                         161
                                                                                                                                                                                  162
                                                                                                                                                                                  163
                                                                                                                                                                                  164
                                                                                                                                                                                                                                 165
                                                                                                                                                                                                                                 166
                                                                                                                                                                                                                                 167
                                   GND
GND
GND
GND
GND
                                                                                                                                                                                                                                             GND
                           L1 L2 L3 PE                  L1 L2 L3 PE                            L1 L2 L3 PE                                   L1 L2 L3 PE                           L1 L2 L3 PE                                   L1 L2 L3 PE
.2 .4 .5 .6 .4 .3
X/2.8 -AMB
                                                                                                                                                                                                                  -XTB7
                                                                              8                                                          9                                                                       10
82
84
85
87
88
A1 A1 A1 A1 A1 A1
LD27948a
76                                                                                                                                                                                                                     JOHNSON CONTROLS
FORM 150.72-ICOM6
                                                                                                                                                                                                SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/24/2019
                 2L1
   2L1/1.5
                 2L2
   2L2/1.5
                 2L3
   2L3/1.5
                         1 3 5                               1 3 5                                 1 3 5                               1 3 5                           1 3 5                                   1 3 5
             =2-KF1                            =2-KF2                                    =2-KF3                             =2-KF4                      =2-KF5                                    =2-KF6
                  .7     2 4 6                      .9       2 4 6                         .10  2 4 6                         .11      2 4 6               .9          2 4 6                           .8      2 4 6
                       250
                       251
                       252
                                                         253
                                                         254
                                                         255
                                                                                            256
                                                                                            257
                                                                                            258
                                                                                                                                259
                                                                                                                                260
                                                                                                                                261
                                                                                                                                                               262
                                                                                                                                                               263
                                                                                                                                                               264
                                                                                                                                                                                                            265
                                                                                                                                                                                                            266
                                                                                                                                                                                                            267
                                                                                                                                                                                                                                             5
                               GND
GND
GND
GND
GND
                                                                                                                                                                                                                     GND
                       L1 L2 L3 PE                        L1 L2 L3 PE                        L1 L2 L3 PE                           L1 L2 L3 PE                  L1 L2 L3 PE                                  L1 L2 L3 PE
.7 .9 .10 .11 .9 .3
Y/2.8
                                                                                                                                                                              -XTB10
                                                    8                                                           9                                                            10
182
183
184
186
187
A1 A1 A1 A1 A1 A1
LD27948b
JOHNSON CONTROLS                                                                                                                                                                                                                      77
                                                                                                                                                     FORM 150.72-ICOM6
SECTION 5 – TECHNICAL DATA
                                                                                                                                                  ISSUE DATE: 10/24/2019
     035-21583-116
         Rev E
                      208/230V-3-60HZ                                 208/230V-3-60HZ
                                                                         460V-3-60HZ                                                                208/230V-3-60HZ
                         460V-3-60HZ                                      575V-3-60HZ                                                                  460V-3-60HZ
                         575V-3-60HZ                                 380/415V-3-50/60HZ                                                    NB1          575V-3-60HZ
                    380/415V-3-50/60HZ                                                                                                             380/415V-3-50/60HZ
                                                NB1                                                                               2 4 6
        NB1                                                -QSD             2 4 6
                                                                                                                           -QCB
              -XTBC                                                                                                                         -QSD       2 4 6
                      U V W          PE                                                     PE
                                               NB17                                                                                                                PE
                                                                            1 3 5
                             1L1
                                                              L1                                                                  1 3 5
                                                                                                                                           NB16        1 3 5
                          1L2
                                                                    L2
                       1L3
L3
                                                                                                                                                1L1
               1L1/1.1
               1L2/1.1
               1L3/1.1
                                   2L1/1.4
                                   2L2/1.5
                                   2L3/1.5
1 3 5 1 3 5
                                                                                                                                             1L2
                                             =1-QCB                      =2-QCB
                                                                                                                                          1L3
                                                                                                                                           1L1/1.1
                                                                                                                                           1L2/1.1
                                                                                                                                           1L3/1.1
                                                                                                                                                                2L1/1.4
                                                                                                                                                                2L2/1.5
                                                                                                                                                                2L3/1.5
                                                         2 4 6                              2 4 6
                                                      1L1/1.1 1L1
                                                              1L2
                                                              1L3
                                                                                             2L1
                                                                                            2L2
                                                       1L3/1.1
                                                                                       2L3/1.5
                                                      1L2/1.1
                                                                                    2L1/1.4
                                                                                    2L2/1.5
                                                                                         208/230V-3-60HZ
                                                                                            460V-3-60HZ
                                                                                             575V-3-60HZ
                                                                                        380/415V-3-50/60HZ
NB31
                                                                               1 3 5         PE             1 3 5     PE
                                                           =1-QCB                            =2-QCB
                                                                               2 4 6                        2 4 6
                                                                                                      2L1
                                                                                      1L1
                                                                                     1L3
                                                                         1L2/1.1 1L2
                                                                                                       2L2/1.5 2L2
                                                                              1L3/1.1
2L1/1.4
                                                                                                            2L3/1.5
                                                                         1L1/1.1
DWG. 16
78                                                                                                                                                    JOHNSON CONTROLS
FORM 150.72-ICOM6
                                                              SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/24/2019
JOHNSON CONTROLS                                                                     79
                                                                                                                                     FORM 150.72-ICOM6
SECTION 5 – TECHNICAL DATA
                                                                                                                                  ISSUE DATE: 10/24/2019
PUMP WIRING
     035-21583-105
         Rev G
                        1L1
              1L1/1.1
                         1L2
              1L2/1.1                                                                                        -J11
                           1L3                                                          -AMB
              1L3/1.1
                                                                                                     J11 J11                        J11 J11 J11
                                                                                                  4 9 14                           5 10 15
                                                                                                 -W1                               W2
                                  1 3 5                           1 3 5
2 4 6 2 4 6
                NB19
                                                 GND                           GND
                                 300
                                 301
                                 302
                                                                 303
                                                                 304
                                                                 305
                                                                                          -QMMSP1                           -QMMSP2
                                                                                                .2                                .3
                             1
               1/1.1
                                                                                               149/2.3
                                         23
                                               -XTB8
                                              6            -AMB
                                                         V/2.3
                                                                                                               149
                                 -K13                             -K11
                                  /1.6                             /1.5
                                               -XTB8
                                                                               -XTB8
                                              7                            4
33
NB52
                                                                                                                     +EXT
                             2
              2/1.2                                                                                  2/2.5
LD27950a
                                                             DWG. 5
Figure 20 - PUMP WIRING
80                                                                                                                                     JOHNSON CONTROLS
FORM 150.72-ICOM6
                                                                                                                                                     SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/24/2019
PUMP WIRING
                                                                                         1L1
                                                                              1L1/1.1
                                                                                         1L2
                                                                              1L2/1.1
                                                                                         1L3
                                                                              1L3/1.1
                                           -J11
            -AMB
                                     J11               J11 J11
                                  9 14               10 15
                                                                                                                                      -F7
                                                                                         -F6
GND
                                                                                                                                                                                  BLK
                                                                                                                                                                     -KP2
                                                                                                                          BLK
                                                                                                             -KP1
                                                                                                                                                                          RED
                                                                                                                RED
                                                                                                                                            91 92 93 95                     12      18
                                                                                               91 92 93 95          12      18                                              DI1     DI4
                                                                                                                    DI1     DI4
                                                                                                                                                                                  -UFSC2
                                                                                                                          UFSC2
                                                                                                                                                          E
                                                                                                         E
                                                                                                                                                                                                      5
                1
    1/1.1
                      23
                            -XTB8
                           6                                             -AMB
                                                                                                                                               149
                                                                                                                                  149/2.2
                                             V/2.4
              -K13                                               -K11
               /1.6                                               /1.5
                                                                     33
                      24
                                                                              -XTB8
                           7                                              4
                      -XTB8
                               -XTBC2                                         -XTBC2
                                                                                                                                                         =1-XTBF
                                                                                                                                                  149
                                                                                                                                            GND                     GND
               -KP1                                               KP2                                                                                                             +EXT
                                                                                                                                                         +EXT
                2                                                                                                                                    2
   2/1.2                                                                                                                               2/2.8
LD27950b
                                                                                               DWG. 5
FIGURE 20 - PUMP WIRING (CONT’D)
JOHNSON CONTROLS                                                                                                                                                                                 81
                                                                                                      FORM 150.72-ICOM6
SECTION 5 – TECHNICAL DATA
                                                                                                   ISSUE DATE: 10/24/2019
=1-EEVC
                                                          INPUT CONFIGURATION
                                                                 0-10V
                                                                                     ON
                                           J15-3    S+
                       P15 TO MICROBOARD                                    STEP-1        OFF
                                           J15-7     S-
                                                                           STEP-2         OFF
                                                   OPN                     STEP-3         OFF
                                                                         POLARITY         BI
                                                   CLS
                                                                        DIRECTION         STD
                                                   REF             RESPONSE TIME          STD
                                                                PULSE PER SECOND          200pps
                                            BLK      B
                                                                 VALVE OPERATION          STD
                                           WHT       W
                        TO SYSTEM #1 EEV
                                           GRN       G
                                           RED       R
                              T3             42    24V+
                                             43    24V-
FROM TRANSFORMER -1T
=2-EEVC
                                                          INPUT CONFIGURATION
                                                                 0-10V
                                                                                     ON
                                           J15-4    S+
                       P15 TO MICROBOARD                                    STEP-1        OFF
                                           J15-8     S-
                                                                           STEP-2         OFF
                                                   OPN                     STEP-3         OFF
                                                                         POLARITY         BI
                                                   CLS
                                                                        DIRECTION         STD
                                                   REF             RESPONSE TIME          STD
                                                                PULSE PER SECOND          200pps
                                            BLK      B
                                                                 VALVE OPERATION          STD
                                           WHT       W
                        TO SYSTEM #2 EEV
                                           GRN       G
                                           RED       R
                              T3            42A    24V+
                                            43A    24V-
FROM TRANSFORMER -1T
LD27951
82                                                                                                  JOHNSON CONTROLS
FORM 150.72-ICOM6
                                                              SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/24/2019
JOHNSON CONTROLS                                                                     83
                                                                                                                                                                                                                                           FORM 150.72-ICOM6
SECTION 5 – TECHNICAL DATA
                                                                                                                                                                                                                                        ISSUE DATE: 10/24/2019
                                                                                                            COMPRESSOR WIRING
035-21589-106 REV N
                                                                                                                                                                                                            ;7%)
                                                                                                                                                                                                                                        (;7
: 8 9
                                                                              8           9    :
     ;7%                                                              (
                                                                                  :       8        9
                                                                                                                                                (;7
                                                                              8           9    :
                                                                                                                                 6)(:+7                   6)(%51
                                                                        (                                                                           
  -%                                                                                                                            6)(%/8                   6)(%/.
                                                                    *1'                    
     ;7%                                                                                                                                                                                                                                                  25
                                                                                  :       8        9
                        (;7                                                                                                                            (;7
                                                                                  8       9        :
                                                                        (
                                                                                                                                                             
                                                                    *1'                        
 -%                                             (;7
                                                                                  :       8        9
                                                                                  8       9        :
                                                                        (
                        -%
                                                                    *1'                        
                                                                                  (;7                                        (;7
                                                                                                                                      *1'
                                                                                                                                                                                       25
                                                                                           *1'
                                                                                                                                                             %'35('        
                                                                                                                                                                                                                                    (;7
                                                                                                                                                              %'3%/.                    $       %
                                                                                                                                                                                                                
                                                                                                     $6                                                    %'3:+7                         &                         
                                                                                                                                      
                                                                                                                                                                                                                        $
                             )6&
              7%                        7%                    7%
                                /   /     /        8         9         :
3( 3(
                                                          *1'
                                                                                                                                                                                                                    
                                                                    (;7
                                               $                $9                                                                                                                                            
                                                           
                                                                                                                                                                                                                    
3( 3(
                                                          *1'
                                                                    (;7
                                                                                                                   $                                                                                                     
                                               $                $:
                                                                                                                  $                                                             $                                        $
/'
84                                                                                                                                                                                                                                        JOHNSON CONTROLS
FORM 150.72-ICOM6
                                                                                                                                                                SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/24/2019
                                                                                                                                              *1'
                                                                                                                                                        (;7
                                                                                                                                 $                  $*
                                                                                                                                               
    *
                      (;7                                                                                                                    *1'
    *1'                                                                                                                                                 (;7
      $4                                                                                                                         $                 $+    9
                                                                                                                                               
                                                                                                                                  %635('             
                                                                                                                                   %63%/.            
                                                                                                                                  %63:+7             
                                                                                                                                     25
                                                                                                                                                                9
                                                                                                                                                    $       %
                                                                                                                                                        &
-%
                                                                                                                                  %635('             
                                                                                                                                   %63%/.            
                                                                                                                                  %63:+7             
25 25
                                                                                                                                                    $
                                                                                                                                                        &
                                                                                                                                                            %
                                                                                                                                                                                             5
                                                      25
                                                                                                                   (;7
                               %'35('    
                                                                  $       %                                                                                 9
                                %'3%/.                                                                    
                               %'3:+7                             &                                  
$
                                                                                                                                                                9
       $1                                                 $.                                               $-
                                                                                                             
/'
JOHNSON CONTROLS                                                                                                                                                                       85
                                                                                                                                          FORM 150.72-ICOM6
SECTION 5 – TECHNICAL DATA
                                                                                                                                       ISSUE DATE: 10/24/2019
035-21589-103 REV C
1 3 5
                                                                                                                                             -QSD
                                                            -QSD
2 4 6
PE
PE PE
                                                        B                              140C
                                                                                                   1           3           5
                                                                      -T3
                                                        R                              2 LA
                                                                     R            B
                                                                     R            B
                                                                                                   2           4           6
                                                                     R2           B2
LD13234C
86                                                                                                                                      JOHNSON CONTROLS
FORM 150.72-ICOM6
                                                                                                      SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/24/2019
                                                           1        3     5                       1        3     5
                                                 43                                     43
                         L1 B    L2 B    L3 B
33 33
1 3 5
                                                                                                                                               5
                                                 34                                     34
                          2       4       6
                                                 44                                     44
                                                           2       4      6                       2        4     6
                         2L1 A   2L2 A   2L3 A
                         2L1 B   2L2 B   2L3 B
                         2L1C    2L2C    2L3C
                                                      24                       2             33                       2
                                                                               2
A1 A2 A1 A2
1 3 5 21 1 3 5 21
-KP1 -KP2
                          1       3       5
                                                            2       4    6         22             2       4     6         22
2 4 6
LD13234D
JOHNSON CONTROLS                                                                                                                          87
                                                                                                                                                                                                                                                 FORM 150.72-ICOM6
SECTION 5 – TECHNICAL DATA
                                                                                                                                                                                                                                              ISSUE DATE: 10/24/2019
POWER PANEL
035-21589-101 REV H
                                          /            /
                                          /            /           /                                                                                                                                       25
                                                                                         /          /              /
            )
            *
$ $
                                          )                                          )
          &$.1                                                                                                                                                                                                                             &$.1
                         $                                                                                                                                                                                                                        $
                                                                                                                                                               .                    ;    ,                                    ;
                                  .                                                                                                                           -                            -                                    ,                               +
                                  /                                                                                                                                                                                                                                ;
/ /
) ;7%)
                                                                                 /$         / $        /$                      /%        / %       / %                          / &        / &        / &
                                                                
                                                 $                                                                                                                                                      
                                                                
$
                                                
                                                 $
                                                
                                                 $
                                            
                                                 $
                                  )+3
$ %
$
$
$
                                                 $           &                                                                                                                                           
                                                 (           
                                                   $$          -
                                                   $%          ,
                                                   $(          ,
                                                                +
                                                                +               %                                                %                                                   %
                                                                *
                                                  $-           2   -03
                                                               <
                                                 $5            <
                                                                1
                                                  $4           1               $                               $    2           $                              $   3                $                                $        4
                                                  $*           0                                                      3                                                 4 5                                                      5
                                                  $9           0
         (+5+(;7                                             /
                                                                                                                      -                                              .                                                          /
                                                                                                                        .                                                / 0                                                       0
         (+5+(;7                             *                                                                                                                                                      
                                                )                                                                  %                                             &                                                         '
                                                          63                                                            &                                               '
63
/'
88                                                                                                                                                                                                                                                 JOHNSON CONTROLS
FORM 150.72-ICOM6
                                                                                                                                                                                                    SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/24/2019
$
                                                                                                                                                                                                                                                    $
                                                             *                                ( )                                (
                                                             +                                    *                                 )                                                                                                                      '
                                                                                                                                                                                                                                                             (
                                                                                                                                                                                                                                                                      5
                                                                / $        / $        / $                     / %        / %         / %                              / &       / &       / &
                                                                                                                                                                                                                         ;7%)
                                                                                                                                                                                                                                            $
                                                                                                                                                                                                                               
$
                                                                                                                                                                                                                                                
                                                                                                                                                                                                                                                $
                                                                                                                                                                                                                                                
                                                                                                                                                                                                                                                $
                                                                                                                                                                                                                                                
                                                                                                                                                                                                                                                $
                                                                                                                                                                                                                               %             $
$
$
                                                                                                                                                                                                                                            $
                                                                                                                                                                                                    
                                                                                                                                                                                                                               &             $
                                                                                                                                                                                                                                            (
                                                                                                                                                                                                                                  3            $&
                                                                                                                                                                                                                                   2           $'
                                                                                                                                                                                                                                  2            $)
                                                                %                                                %                                                          %                                             1
                                                                                                                                                                                                                                  1
                                                                                                                                                                                                                                   0
                                                                                                                                                                                                                                  8             $:
                                                                                                                                                                                                                                   7
                                                                                                                                                                                  $                              $     :       7             $/
                                                                $                                $     8         $                                 $   9                                                                     6            $0
                                                                                                         9                                                  : $                                                     $
                                                                                                                                                                                                                                  6             $3
                                                                                                       3                                               4                                                         5        5            $+
                                                                                                      4                                              5                                                                          63
                                                                                                       %                                              &                                                        '
                                                                                                                                                                                                                                           63
                                                                                                         &                                                '
                                                                                                                                                                                                                                           63
/'
JOHNSON CONTROLS                                                                                                                                                                                                                                                 89
                                                                                                                                                                                                                                                                                       FORM 150.72-ICOM6
SECTION 5 – TECHNICAL DATA
                                                                                                                                                                                                                                                                                    ISSUE DATE: 10/24/2019
                                                                                                                                              ---> -AMB
                                                                    -XP2                                                                                                                                     -XTB7
     1 1D                     4 119A                               7 122A                 10 129A                     13 26A                                                                           1     118A
                                                                                                                                                                                                             118B
     2 2C                     5 120A                                8 127A                11 131A                     14 29A
                                                                                                                                                                                                       2     119A
     3 118A                   6 121A                               9 128A                 12 25A                      15 30A
                                                                                                                                                                                                       3     120A 127A
                                                                          -XP2                                                                                                                               121A
                                                                                                                                                                                                      4
  13 26B                      10 129B                              7 122B                  4    119B                  1   1E
                                                                                                                                                                                                       5     122A
  14 29B                      11 131B                               8 127B                 5    120B                  2   2D
                                                                                                                                                                                                                                     NB34
  15 30B                      12 25B                               9 128B                  6    121B                  3   118C                                                                         6     118B
     1 13I                        2 18B                                                                                                                                24
                                                                                                                                                                   7
     3 19B                        4
                                                                                                                                                                   8
         -XP4                                                                                                                                                      9
     3   19C                      4
     1   13K                      2   18C
                                                                                                                                                                                                                                                                                                                                   -AMB
                                                                                                                                                                                                             -XTB9                                   TB8
                                                                                                                                                                                                       1     1B
                                                                                                                                                                       -XTB10                                1C
                                                                                                                                                                       218A                            2     231A
         NB41                                                                                                         SC-EQ                                        1
                                                                                                                                                                       218B
                                                                                                                                                                                                                                                     TB9
                                                                                                                                                                   2   219A                            3
                                                                                                                                                                                                                                                             1
                                                                                                                                                   COM
                                                                   COM
COM
                                                                                                                                                   SHD
                                                       HOT
SHD
                                                                                                                                              +
                                                                                                      +
                                                                                                                                              -
                                                                                                      -
                                                                                                                                                                   3   220A 227A                      4
                                             J10
J12
J8
                                                                                                                                                                                                                                                                                           031-02550-
                                                                                                                                                                  4    221A
                                                                                                                                                                   5   222A
                             OR
                                                                                      R                                                                                                        NB34
                                                                                                                                                                   6   218B                                                                         TB10
                                                                                                                                                                                                                                                             1
                                                                                                                                                                   7   223A
8 227A
9 228A
-ELINK 10 229A
                                                                                                                                                                                                                     -J14
                                                                                                                                                                                                               1      40
                                                                                                                                                                                                                                                                                                                           1
                                                                                                                                                                                                               2      41                                                                                             J14
                                                                                                                                                                                                               3      GND B
                                                                                                       PORT2A RS485       PORT2B RS232   PORT3 RS485
                                                                                          COM
SHD
SHD
SHD
                                                                                                                                         SHD
                                             COM
REF
REF
                                                                                                                                         REF
                                             HOT
RX
                                                                                                                                                                                NB4
                                                                                                                          TX
                                                                                                                                                                  NB49
                                                                          PORT1
                                                                                                                                                                                                                                                                                           NB34                      NB39
                                                                                                                                         +
                                                                                                      -
                                                                                                                                         -
                                       TB5
J2
                                                                                                                                                                                                                                                                       1E
                                                                                                      ELINK/AMB:RED
                                                                                                      ELINK/AMB:BLK
                                                                                                                                                                       223A 123A        33     32A    31A     30A      29A    28A     27A    26A      25A        24    23     5A     L1                 2 LA   2           2A      2A
                                                                                                                                                                                                                                                                              5B                                           2B     GNDA
                                             WHT
                                             BLK
223I 123I 33I 32I 31I 30I 29I 28I 27I 26I 25I 24I 23I 5I LI 2I 2I 2I GNDI
                                                                                                                                                                                                                                                                               LK    LK
                                                                              R
                      TB1
                                                                                                                                                                                                                                                                                                                                  GND
                                                                                                                                                                       223      123     33     32     31      30       29     28      27     26       25         24    23      5     L                  2      2           2
               1 2 3 4                -AMB
                                                                                                                                                                         223E    123E   33E     32E    31E     30E      29E    28E     27E    26E      25E       24E   23E     5E     LE                2E      2E         2E      GNDE
             ELINK/AMB:RED
             ELINK/AMB:BLK
                                                                                                                                                                                                                                                                                                                                  GND
                                                                                                          WHT
                                                                                                                                                                                                                                                                             NB41
                                                                                                                                                       2          NB49          NB4           NB19                                                                                                           NB4           NB49
NB19
LD29090a
90                                                                                                                                                                                                                                                                                   JOHNSON CONTROLS
FORM 150.72-ICOM6
                                                                                                                                                                                                                                    SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/24/2019
                                                                                                                                                                                                                                                               035-21589-102
                                                                                                                                                                                                                                                                  REV. O
                     -J15
  7   S-         8   S-              9
                                                                                                               -XP5                                                                                                         -ADIS
  4   S+         5                   6
                                                                  NB46
                                                                                                          1    BRN-NEG             NB6
  1              2                   3   S+                                                               2    BRN-POS
12
                                                                                                                                                                                                                                          13J
                                                                             SHLD GND +   +5V   +5V GND RXD TXD CTS RTS
                                                     TB1                                                                            NB6
                                          PL1                                                                             TB4
                                                                             TB2                     TB3
           1         1         J15                         SHLD REF -   +
                                                                                                                          -       BRN-NEG                                                                              -SOA
           TB6
TB5
                                                                                                                          +       BRN-POS
                                                                                                                   J2 1
                                                                                                         J1
                                                                                                          1
NB32
                                                                                                                                                                            -J6                                                                     -J6
                                                                                                                                                                                                                                                                                       NB37
                                                                                                                                                 7   BLCT:BLK       8       BECT:BLK          9    BAMB:BLK                  7                  8   BDAT:BLK    9
                                                                                                                                                 9 =1-BSP:BLK
                                                                                                                                                                                        -J7                                                                                                        5
                                                                                                                                                                    10 =1-BSP:WHT             11 =1-BDP:WHT      12 1-TC:PNK 52
                                                                                                                                                                                                                                                               A-POS       A+
                                                                                                                          J6
                                                                                                                                                                            -J8
                                                                                                                                                                                                                                                                     51    51
                                                                                                                                                 7   BST:BLK        8                         9
                                                                                                                                                                                                                      NB42                                          13H    13   13J
                                                                                                                                                 4   BST:RED        5                         6                                                                      13I
                                                                                                                              1
                                                                                                                    7
                                                                                                                          4
                                                                                                                          J7                                                                                                                                         50    50
                                                                                                                                                 1   BST:SCR        2                         3
                                                                                                         J4                                                                                                                                                         13G    13
                                                                                                                                                                                                                                                                    13H
                                                                                                                                                                                                                                                                     21    21
                                                                                                                                                                                        -J9
                                                                                                                                                                                                                                                                    13F    13
                                                                                                                    9
                                                                                                                          5
                                                                                                                              1
J9 19A 19 19B
                                                                                                                                                                                                                                                                    13D    13
                                                                                                                                            NO
                                                                                                                                                                            -J10                                                                                    13E
                                                                                                                                                                                                                                                                    18A         18B         NB50
                                                                                                                                                                                                                                                                           18
                                                                                                                                                 7   BST:BLK        8                         9
                                                                                                                                                                                                                                                                    13C    13   13
                                                                                                                                                                                                                      NB42
                                                                                                                    9
                                                                                                                          5
                                                                                                                              1
                                                                                                                                                                                                                                                                                            -SFE
                                              J13                               9               11                        J11                                                                        -J11
                                                                                                                                                                                                                                                                    13A    13
                                                                                5               6                                                                                                                                                                   13B
                                                                               12                                                                11 A-POS           12 LK1                    13                 14 J11/QPA1:BLK 15 J11/QPA2:BLK
                                                 2                                                                                                                                                                                                                         40
                                                                                1               1                                                                                                                                                                   40A         SFE:BRN
                                                                                                                                                 6 A-NEG            7 LK1                     8                   9 J11/QPA1:RED 10 J11/QPA2:RED
                                                                                                                                                                                                                                                                    41A    41    SFE:BLU
                                                                                                                                                 1                  2                         3                  4    J11/QPA1:SCR 5    J11/QPA2:SCR
                                              5A               5B            L1
                                                                                           GNDA
                                                                                           GNDB
                                                                                                                                                                            NB37                                                 NB19
                                                                                                     NB46
-T1
                                                                                                    40        41
                                               1A              3A            1.5A                   40A       41A
                                               1E
                                               1                        NB19
                                                       NB39                               NB72
LD29090b
JOHNSON CONTROLS                                                                                                                                                                                                                                                                             91
                                                                                                                                                                                                                                            FORM 150.72-ICOM6
 SECTION 5 – TECHNICAL DATA
                                                                                                                                                                                                                                         ISSUE DATE: 10/24/2019
                                                                                                                                                        1678 [66.1]
                                                                                                                                                        1117 [44.0]
                                                                                                                                                                                                                                                                 035-24059-001 REV-E
                                                                                                                                                                                                                                                                   POWER ENTRY
                                                                                                 2077 [81.8]                                                                                                                                                       330.2 [13.00] WIDE X 177.8 [7.00] HIGH
                                                                                                                                                                                   1097 [43.2]
                                                                                                                                                                                                 1669 [65.7]
                                                                                                                                                                                                                            201 [0.8]
                                                                                                                                                                                                                                                                        1177 [46.4]
                                                                                                           82 [3.2]
                                                                             DISCONNECT SWITCH
                                                                             (OPTIONAL)
                                                                                                                              51 [2.0]
              OVERALL HEIGHT
                               FRAME HEIGHT
                                 2251 [88.6]
2398 [94.4]
                                                                                                                                                                                       3” VICTAULIC
                                                                                                                                                                                              INLET
                                               1595 [62.8]
1085 [42.7]
822 [32.4]
                                                                                                                                                                                                                                              269 [10.6]
                                                                                                                                                                                                                            254 [10.0]
 NOTE:
 		 Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
    operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow
    patterns and possible diminished performance. Johnson Control’s unit controls will optimize operation without nuisance high-pressure safety
    cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is
    no higher than on spring isolators. Recommended minimum clearances: Side to wall – 6 ft; rear to wall – 6 ft; control panel to end wall – 4 ft;
    top – no obstructions allowed; distance between adjacent units – 10 ft. No more than one adjacent wall may be higher than the unit.
 92                                                                                                                                                                                                                                         JOHNSON CONTROLS
                                              FORM 150.72-ICOM6
                                                                                                                                                                                                                                                                                                     SECTION 5 – TECHNICAL DATA
                                              ISSUE DATE: 10/24/2019
                                                                                                                                                                                                             1678 [66.1]
                                                                                                                                                                                                             1117 [44.0]
035-24059-002 REV-E
                                                                                                                                                                                                                                                                                                                               POWER ENTRY
                                                                                                                                                                                                                                                                                                                               330.2 [13.00] WIDE X 177.8 [7.00] HIGH
                                                                                                                                                                                                                                                                                                                              (190mm x 120mm EUROPEAN BUILD)
                                                                                                                                                                                                                             1097 [43.2]
                                                                                                                                                                                                                                           1669 [65.7]
                                                                                                                  2077 [81.8]
                                                                                    OPTIONAL
                                                                                                                                              82 [3.2]
                                                                                    DISCONNECT SWITCH
                                                                                    (STANDARD ON CE)
                                                                                                                                                             51.4 [2.02]
                                                                                                                                                                                                                                                                                                                                                                        5
                                                                                                                                                                                                                                    3” VICTAULIC
                                                                                                                                                                                                                                    OUTLET
                                                                                                        (OPTIONAL HEAT
OVERALL HEIGHT
                                                                                                        RECOVERY UNIT)
   2398 [94.4]
                                                                                                                                                                                                                                     3” VICTAULIC
                               FRAME HEIGHT
                                                                                                                                                                                                                                            INLET
                 2248 [88.5]
                                                                                                                                                                                                                                  3” VICTAULIC
                                              1595 [62.8] (60Hz)
                                              (1497mm (50Hz) )
1276 [50.2]
                                                                                                                                                                                                                                         INLET
                                                                                                                                1085 [42.7]
                                                                                                                                                                                                                                                                    822 [32.4]
                                                                                                                                                686 [27.0]
                                                                                                                                                                                                                                                                                                                                               36 [1.4]
                                                                                                                                                                                                                                                                                        254 [10.0]
                                                                                                                                                                                                                                                                                                          269 [10.6]
                                                                        141 [5.5] OR 226.9 [8.93]                                                                                                              16mm [5/8”]                                                                                WATER CONNECTIONS                    MOUNTING
                                                                                                                                                                                  741 [29.2]
                                                                       DIMENTION VARIES BASED ON                                                                                                              MOUNTING                                                                               36 [1.4]                                  HOLES TYP
                                                                                                                                                                               588 [23.2]
                                                                       CHILLER MODEL SELECTED                                                                                                                 HOLES TYP                                                                              MOUNTING
                                                                                                                                                                                               1735 [68.3]                                                                                           HOLES TYP
                                                                     2242 [88.3]                                                                                            495 [19.5]
                                                                   FRAME WIDTH                                                                                                                 1921 [75.6]
                                                                                                                                                                               2547 [100.3]
                                                                    2256 [88.8]                                                                                            WATER CONNECTIONS
                                                                                                                                                                                                       2911 [114.6]
                                                                   OVERALL WIDTH                                                                                                                      FRAME LENGTH
                                                                                                                                                                              2994 [117.9]                                                                                                                                                          LD23532
                                                                                                                                                                            OVERALL LENGTH
                                              NOTE:
                                              		 Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
                                                 operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow
                                                 patterns and possible diminished performance. Johnson Control’s unit controls will optimize operation without nuisance high-pressure safety
                                                 cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is
                                                 no higher than on spring isolators. Recommended minimum clearances: Side to wall – 6 ft; rear to wall – 6 ft; control panel to end wall – 4 ft;
                                                 top – no obstructions allowed; distance between adjacent units – 10 ft. No more than one adjacent wall may be higher than the unit.
                                              JOHNSON CONTROLS                                                                                                                                                                                                                                                                                                93
                                                                                                                                                                                                                                                                  FORM 150.72-ICOM6
SECTION 5 – TECHNICAL DATA
                                                                                                                                                                                                                                                               ISSUE DATE: 10/24/2019
2795 [110.0]
                                                                                                                                                                                 573 [22.5]
                                                                                                                                                               561 [22.1]
POWER ENTRY
                                                                                                                                                                                              1132 [44.6]
                                                                                                                                                                                                                                                                                                 330.2 [13.00] WIDE X 177.8 [7.00] HIGH
                                                                                                                                                                                                                                                                                                 (190mm x 120mm EUROPEAN BUILD)
                                                                                                                                                                                                            1669 [65.7]
                                                                                                 2077 [81.8]
                                                                                                                                                                                                                                           21 [0.8]
                                                                                                                                                                                                                                                                                                       1298mm EUROPEAN BUILD
                                                                                                                                                                                                 3” VICTAULIC
                                                                                                                                                                                                 OUTLET
      REFER TO NOTES 5 ADN 6 ABOVE
                                                                                                                                                                                    3” VICTAULIC INLET
             FRAME HEIGHT
                  2248 [88.5]
                                                                                                                                                                                                                          3” VICTAULIC
                                                                                                                                                                                                                          OUTLET
       1595 [62.8] (60Hz)
       (1497mm (50Hz))
1276 [50.2]
                                                                                                                                                                                                                                                      822 [32.4]
                                                                                                      686 [27.0]
                                                                                                                                                                                                                                                                   254 [10.0]
                                                                                                                                                                                                                                                                                    269 [10.6]
                                            289 [11.4] 288.0 [11.34]                                                                                                                                                                                                            35 [1.4]                                            35 [1.4]
                                           DIMENSION VARIES BASED                                                                                          16mm [5/8”]
                                           ON CHILLER MODEL SELECTED                             194 [7.6]                                                MOUNTING
                                                                                                                                                          HOLES TYP
                                                                                                 588 [21.1]
                                               2242 [88.3]
                                             FRAME WIDTH                                                              1753 [69.0]                           1222 [48.1]
                                              2256 [88.8]
                                                                                                                      1256 [49.5]
                                            OVERALL WIDTH
                                                                                                                                       3022 [119.0]
                                                                                                                                     FRAME LENGTH
                                                                                                                                       3245 [127.8]
                                                                                                                                    WATER CONNECTIONS
                                                                                                                                           3696 [145.5]                                                                                                                                                                    LD23533
                                                                                                                                         OVERALL LENGTH
NOTE:
		 Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
   operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow
   patterns and possible diminished performance. Johnson Control’s unit controls will optimize operation without nuisance high-pressure safety
   cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is
   no higher than on spring isolators. Recommended minimum clearances: Side to wall – 6 ft; rear to wall – 6 ft; control panel to end wall – 4 ft;
   top – no obstructions allowed; distance between adjacent units – 10 ft. No more than one adjacent wall may be higher than the unit.
94                                                                                                                                                                                                                                                                       JOHNSON CONTROLS
                                                           FORM 150.72-ICOM6
                                                                                                                                                                                                                                                                                                   SECTION 5 – TECHNICAL DATA
                                                           ISSUE DATE: 10/24/2019
                                                                                                                                                                                                                  2795 [110.0]
                                                                                                                                                                                                                    1678 [66.1]
                                                                                                                                                                                                                                                                                                                           POWER ENTRY
                                                                                                                                                                                                                                                                                                                           330.2 [13.00] WIDE X 177.8 [7.00] HIGH
                                                                                                                                                                                                                                                                                                                           (190mm x 120mm EUROPEAN BUILD)
                                                                                                                                                                                                                                                1669 [65.7]
                                                                                                                                                                                                                                   573 [22.5]
                                                                                                                                            2077 [81.8]
1177 [46.4]
                                                                                                                                                                                                                                                                           21 [0.8]
                                                                                                                                                             82 [3.2]
                                                                                                          OPTIONAL                                                      83 [3.3]
                                                                                                          DISCONNECT SWITCH
                                                                                                          (STANDARD ON CE)
                                                                                                                                                                                                                                                                                                                                                                    5
OVERALL HEIGHT DEPENDS ON BUILD LOCATION
     REFER TO NOTES 5 ADN 6 ABOVE
                                                                                                                          (OPTIONAL HEAT
                                                                                                                          RECOVERY UNIT)                                                                                          3” VICTAULIC
                                           FRAME HEIGHT
                                                                                                                                                                                                                                  INLET
                                             2248 [88.5]
                                                                                                                                                                                                                                             3” VICTAULIC
                                                                                                                                                                                                                                             INLET
                                                           1595 [62.8] (60Hz)
                                                            (1497mm (50Hz))
1276 [50.2]
686 [27.0]
                                                                                                                                                                                                                                                                                      822 [32.4]
                                                                                                                                                                                                                                                                                                                   269 [10.6]
                                                                                                                                                                                                                                                                                                   254 [10.0]
                                                                                                                                                                                                                                                                                                                   WATER CONNECTIONS
                                                                                  288 [11.3] OR 288.0 [11.34]                                                                                                   15.9 [0.63]                                                                                     35 [1.4]                        35 [1.4]
                                                                                  DIMENSION VARIES BASED                                                                                     1256 [49.5]        MOUNTING                                                                                        MOUNTING                        MOUNTING
                                                                                  ON CHILLER SELECTED                                                                                                           HOLES TYPE                                                                                      HOLES TYPE                      HOLES TYPE
                                                                                           2242 [88.3]                                      194 [7.6]                              1753 [69.0]                  1222 [48.1]
                                                                                         FRAME WIDTH
                                                           NOTE:
                                                           		 Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
                                                              operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow
                                                              patterns and possible diminished performance. Johnson Control’s unit controls will optimize operation without nuisance high-pressure safety
                                                              cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is
                                                              no higher than on spring isolators. Recommended minimum clearances: Side to wall – 6 ft; rear to wall – 6 ft; control panel to end wall – 4 ft;
                                                              top – no obstructions allowed; distance between adjacent units – 10 ft. No more than one adjacent wall may be higher than the unit.
                                                           JOHNSON CONTROLS                                                                                                                                                                                                                                                                                 95
                                                                                                                                                                                                                                            FORM 150.72-ICOM6
 SECTION 5 – TECHNICAL DATA
                                                                                                                                                                                                                                         ISSUE DATE: 10/24/2019
035-24059-010 REV-D
                                                                                                                                                                                                                                                               POWER ENTRY
                                                                                 2077.3 [81.78]                                                                                                                                                                330.2 [13.00] WIDE X 177.8 [7.00] HIGH
82.9 [3.26]
1177.0 [46.35]
                                                                                                                                                                                                                             20.7 [0.81]
                                                                                                                                                                                                                                                   CONTROL PANEL BOTTOM DETAIL
                                                                                                                                                                                                              4” VICTAULIC
                                                                                                                                                                                                              OUTLET
                 FRAME HEIGHT
2397.6 [94.39]
2248.0 [88.50]
1275.7 [50.22]
685.7 [27.00]
                                                                                                                                                                                     885.9 [34.88]
                                                                                                                                                            4731.4 [186.28] WATER CONNECTIONS
                                                                                                                                                           FRAME LENGTH
                                                                                                                                                            4768.9 [187.75]                                                                                                                  LD26941
                                                                                                                                                          OVERALL LENGTH
 NOTE:
 		 Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
    operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow
    patterns and possible diminished performance. Johnson Control’s unit controls will optimize operation without nuisance high-pressure safety
    cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is
    no higher than on spring isolators. Recommended minimum clearances: Side to wall – 6 ft; rear to wall – 6 ft; control panel to end wall – 4 ft;
    top – no obstructions allowed; distance between adjacent units – 10 ft. No more than one adjacent wall may be higher than the unit.
 96                                                                                                                                                                                                                                        JOHNSON CONTROLS
                                         FORM 150.72-ICOM6
                                                                                                                                                                                                                                                                         SECTION 5 – TECHNICAL DATA
                                         ISSUE DATE: 10/24/2019
035-24059-012 REV-B
                                                                                                                                                                                                                                                                                                      POWER ENTRY
                                                                                                                                                                                                                                                                                                      330.2 [13.00] WIDE X 177.8 [7.00] HIGH
                                                                                                                              2077.3 [81.78]
                                                                                                                                                                                                                                                               2169.2
                                                                                                                                                                                                                                                               [85.40]
                                                                                                                                                                                                                                                                                                         1177 [46.35]
                                                                                                                                                                                                                                                                         20.7 [0.81]
                                                                                                                                               82.4 [3.24]
                                                                                                                                                                                                                                                            [1.43]
                                                                                                                                                                                                                                                            36.4
                                                                                                                                                              194.6
                                                                                                                                                              [7.66]
                                                                                                                                                                                                                                                                                                                                               5
                                                                                                                                                                                                                                              4” VICTAULIC INLET
3” VICTAULIC OUTLET
                                                                              3” VICTAULIC INLET
                 FRAME HEIGHT
2397.6 [94.39]
2248.0 [88.50]
                                                                                                                                                                                                                                                                                        4” VICTAULIC
                                                                                                                                                                                                                                                                                               INLET
                                                                               1275.7 [50.22]
                                                                                                 [42.72]
                                                                                                1085.1
685.7 [27.00]
                                                                                                                                                                                                                                                                                           OUTLET
                                   [5.54”]-[11.34”] -DIMENTION VARIES BASED                                                                                  1256.1 [49.45]
                                   ON CHILLER MODEL SELECTED                                                                                                                                                                        2002.8                                             136.8 [5.38]
                                                                                                                                                                                                                                    [78.85]
                                                      2242.1 [88.27]                                                                                                     2061.5
                                                     FRAME WIDTH                                                                                                         [81.16]
                                                                                                                                                                                                      5848.3 [230.25]
                                                                                                                                                                                                     FRAME LENGTH
                                                                                                                                                                                                      5885.7 [231.72]
                                                                                                                                                                                                    OVERALL LENGTH
                                                                                                                                                                                                                                                                                                                           LD26942
                                         NOTE:
                                         		 Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
                                            operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow
                                            patterns and possible diminished performance. Johnson Control’s unit controls will optimize operation without nuisance high-pressure safety
                                            cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is
                                            no higher than on spring isolators. Recommended minimum clearances: Side to wall – 6 ft; rear to wall – 6 ft; control panel to end wall – 4 ft;
                                            top – no obstructions allowed; distance between adjacent units – 10 ft. No more than one adjacent wall may be higher than the unit.
                                         JOHNSON CONTROLS                                                                                                                                                                                                                                                                            97
                                                                                                                                                                                                                                                        FORM 150.72-ICOM6
 SECTION 5 – TECHNICAL DATA
                                                                                                                                                                                                                                                     ISSUE DATE: 10/24/2019
                                                                                                                                                                                                                                                                                 035-24059-017 REV-
                                                                                                                                                                  15.9mm [5/8”] DIA
                                                                                                                                                                  MOUNTING HOLES (TYP.)
POWER ENTRY
                                                                                                                                                                                                                                  20.7 [0.81]
                                                                                                                                                                                                                                                     330.2 [13.00] WIDE X 177.8 [7.00] HIGH
                                                                                                       2077.3
                                                                                                       [81.78]
                                                                                                                                                                                                                                                           1177 [46.35]
                                                                                                               [3.16]
                                                                                                               80.3
                                                                                                                                                                                                                             [1.43]
                                                                                                       ORIGIN
                                                                                                                                                                                                                             36.4
                                                                                                                                  194.6 [7.66]
                                                                  3” VICTAULIC OUTLET
                 FRAME HEIGHT
                                                                  3” VICTAULIC OUTLET
                  2251.4 [88.64]
2397.7 [94.40]
1275.7 [50.22]
                                                                                      1085.1 [42.72]
                                                                                                       732.9 [28.85]
                                                                                                       [27.00]
                                                                                                       685.7
                                                                                                                                                                                                                                       137.5
                                                                                                                        588.3                                                                                                          [5.43]       5” VICTAULIC
                                                                                                             [16.20]
                                                                                                                                                                                                                                                           OUTLET
                                        2253.344 [88.71]
                                        OVERALL WIDTH                                                                    1256.1 [49.45]
                                                                                                                             2061.5 [81.16]
                                                                                                                                   3154.3 [124.18]
4986.1 [196.30]
6459.3 [254.30]
LD26943
 NOTE:
 		 Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
    operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow
    patterns and possible diminished performance. Johnson Control’s unit controls will optimize operation without nuisance high-pressure safety
    cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is
    no higher than on spring isolators. Recommended minimum clearances: Side to wall – 6 ft; rear to wall – 6 ft; control panel to end wall – 4 ft;
    top – no obstructions allowed; distance between adjacent units – 10 ft. No more than one adjacent wall may be higher than the unit.
 98                                                                                                                                                                                                                                                    JOHNSON CONTROLS
FORM 150.72-ICOM6
                                                                                                      SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/24/2019
WEIGHT DISTRIBUTION AND ISOLATOR                                      Whenever the isolator option is ordered, the isolators
MOUNTING POSITIONS                                                    will be shipped loose with the chiller. Packed with
                                                                      the isolators and also in the control panel informa-
General                                                               tion packet is a drawing and table specifically for each
Weights of specific chiller models vary significantly as              chiller, based on the option selection. The drawing and
options are added. As a result, total weights, weights at             table will be similar to the two samples shown below
individual isolator positions, and actual isolator selec-             and on the following page. The drawing will show the
tion at each position cannot be published due to the                  isolator locations along with the weight in pounds and
vast number of possible combinations. This informa-                   kilograms at the specific location, isolator position,
tion will be available when the specific chiller/ option              and location measurements for each isolator.
selection is made from the local Johnson Controls sales
office. Be aware, weights will change with each op-                   Sample Isolator Location Drawings
tion along with possible isolator changes. Weights and                See Figure 33 below for sample printouts supplied in
isolators may need to be recalculated when the option                 the isolator package and in the chiller panel literature
selections are changed.                                               packets.
                                                                                    UNIT SHIPPING           KG         LB
                                                                                        WEIGHT
                                                                                  (Display on unit data
                                                                                                           2032       4480
                                                                                       nameplate)
                                                                                                                                   5
                                           L1                                                                 L2
                                 Control Panel
                    0
                                           R1                                                                 R2
                             0                   Y
                                                                       Top View
                                                       X
                          X DISTANCE                  Y DISTANCE
                                                                                                          OPERATING WEIGHT
   LOCATION              INCHES (MM)                 INCHES (MM)            VENDOR NUMBER
                                                                                                               LB (KG)
Figure 33 - SAMPLE PRINTOUT SUPPLIED IN THE ISOLATOR PACKAGE AND IN THE CHILLER PANEL
             LITERATURE PACKET
JOHNSON CONTROLS                                                                                                             99
                                                                           FORM 150.72-ICOM6
SECTION 5 – TECHNICAL DATA
                                                                        ISSUE DATE: 10/24/2019
CLEARANCES
See Figure 34 below for minimum clearances for all
YLAA units.
(2 m)
                  (1.3 m)                                           (2 m)
                                                            (2 m)
NOTES:
  1.	 No obstructions allowed above the unit.
  2.	 Only one adjacent wall may be higher than the unit.
  3.	 Adjacent units should be 10 ft (3 m) apart.
                                       ISOLATOR LOCATIONS
 FOUR FAN ISOLATOR LOCATIONS YLAA0041HE, YLAA0048HE, YLAA0058HE, YLAA0065HE,
                           YLAA0081HE, YLAA0082HE
LD18078
1.4
LD18079
LD18080
LD18081
                                                                                               5
                                                                                     LD18082
                                                        TOP
                                                        VIEW                        LD21040
                                ISOLATOR INFORMATION
                    One Inch Deflection Spring Isolator Cross-reference
CP
5/8"
Ø1/2"
H"
                                                                            C"
                             T"
                                                                            B"        L"
                                    D"
                             W"
                                                                                              LD13759A
       MODEL NUMBER               RATED CAPACITY (LB)                 DEFLECTION RATED (IN.)                  COLOR CODE
             CP1-1D-85                          85                                    1.360                     LT. PURPLE
            CP1-1D-120                         120                                    1.200                    DK. YELLOW
            CP1-1D-175                         175                                    1.170                     DK. BLUE
            CP1-1D-250                         250                                    1.400                      YELLOW
            CP1-1D-340                         340                                    1.130                        RED
            CP1-1D-510                         510                                    1.020                       BLACK
            CP1-1D-675                         675                                    1.320                    DK. PURPLE
            CP1-1D-900                         900                                    1.020                     DK. GREEN
            CP1-1D-1200                        1200                                   0.900                       GRAY
            CP1-1D-1360                        1360                                   0.770                       WHITE
        CP1-1D-1785N                           1785                                   0.880                     GRAY/RED
       MODEL NUMBER               RATED CAPACITY (LB)                 DEFLECTION RATED (IN.)                  COLOR CODE
            CP2-1D-1020                        1020                                   1.020                       BLACK
            CP2-1D-1350                        1350                                   1.320                    DK. PURPLE
            CP2-1D-1800                        1800                                   1.020                     DK. GREEN
            CP2-1D-2400                        2400                                   0.900                       GRAY
            CP2-1D-2720                        2720                                   0.770                       WHITE
        CP2-1D-3570N                           3570                                   0.880                     GRAY / RED
LD13790
                                                                             Y2RS
                                                   5"                   1-1/8"
                                                 5/8"   2-3/4"
                                                                                  2-3/4"
                                                                                               12"
                                      3/8" GAP
                                                                                                 5/8-11UNC
                                           Ø3/4"                                                 TYP. (4)
                                         TYP.(4)
                               3/4"
                               7/8"
                                                                                                         1/2" LIMIT
                                                                                                         STOP &
                                                                                                         NUT         8-3/8"
                                                                                                                     OPER.
                                                                                                                    HEIGHT
                                                                  12-1/4"
                                                            14"
                                                                                                     3-1/2"                       LD13761A
                                                                                                                    3/8"
5"
                               NOTES:
                               1. ALL DIMENSIONS ARE IN INCHES, INTERPRET PER ANSI Y14.
                               2. STANDARD FINISH: HOUSING-POWDER COATED (COLOR:BLACK), SPRING-POWDER COATED (COLOR: SEE T
                                   HARDWARE ZINC-ELECTROPLATE.
 1.	 All dimensions are in inches, interpret per ANSI                                      4.	 All springs are designed for 50% overload capac-
                               3. EQUIPMENT MUST BE BOLTED OR WELDED TO THE TOP PLATE TO MEET ALLOWABLE SEISMIC RATINGS.
                               4. ALL SPRINGS ARE DESIGNED FOR 50% OVERLOAD CAPACITY WITH EXCEPTION OF THE 2D-3280N & 2D-2870
                                          RATED                                                                                                ALLOWABLE
   SEISMIC        RATED LOAD                                                SPRING RATE              SOLID LOAD                 COLOR
                                        DEFLECTION                                                                                              G RATING
  MOUNT SIZE         (LB)                                                     (LB/IN.)                  (LB)                    CODE
                                           (IN.)                                                                                               HORIZONTAL
 Y2RSI-2D-150          150                         2.4                            62                          234                WHITE              34.7
 Y2RSI-2D-320          320                         2.3                           140                          490               YELLOW              16.3
 Y2RSI-2D-460          460                         2.3                           200                          688               GREEN               11.3
 Y2RSI-2D-710          710                         2.2                           330                          1072             DK BROWN              7.3
 Y2RSI-2D-870          870                         1.9                           460                          1312                RED                6.0
Y2RSI-2D-1200N        1200                         1.9                           638                          1818             RED/BLACK             4.3
 Y2RSI-2D-1450        1450                         1.8                           900                          2450                TAN                3.6
 Y2RSI-2D-1690        1690                         1.7                           1140                         2892                PINK               3.1
Y2RSI-2D-2000N        2000                         1.7                           1318                         3342            PINK/BLACK             2.6
Y2RSI-2D-2640N        2640                         1.5                           1854                         4283             PINK/GRAY             2.0
                                                                                                                               PINK/GRAY/
Y2RSI-2D-2870N        3080                         1.5                           2004                         4629                                   1.7
                                                                                                                                ORANGE
                                                                                                                              PINK/GRAY/DK
Y2RSI-2D-3280N        3740                         1.8                           2134                         4930                                   1.4
                                                                                                                                 BROWN
                                                                                 ("F")
                                                             WASHER                                        ("E")
                                                             ("F")
                                                                 ("C")
                                                                                ("C")
                                                                     ("B")
LD13763B
RD-Style DW
Isolators
CD
                                                                                                    MOLDED
                                                                                                    DURULENE
                                              HF                                                     ø AD THRU
                                                                                                     TYP 2 PLACES
BT
                                                                AL
                                                                                                      W
                                                            L
LD13760A
 1.	 All dimensions are inches, interpreted per ANSI                                     4.	 AL = Mounting hole center to center spacing.
     Y14.                    Notes:
                             1. All dimensions are inches, interpreted per ANSI Y14. 5.	 HF = Free height of mount, before loading. Oper-
                             2. Refer to Page 98 for installation instructions.
 2.	 See next page for installation      instructions.
                             3. Mount molded                                                  ating height
                                                 in weather resistant duralene compound as standard.                calculated
                                                                                                         Also available                 by the free height less the
                                                                                                                        in other materials
                             such as natural rubber, extreme high temperature silicone, high-damped silicone, nitrile and EDPM.
                             4. AL = Mounting hole center to center spacing.                  static deflection under load. All dimensions for
 3.	 Mount molded in weather 5. HFresistant
                                     = Free height duralene
                                                    of mount, prior com-
                                                                    to loading. Operating height calculated by the free height less the
                             static deflection under load. All dimensions for reference only. reference only.
     pound as standard. Also6.available          in other materi-
                                Hardware zinc-electroplated.
  1.	 Read instructions in their entirety before begin-        4.	 Bolt or anchor all isolators to supporting structure
      ning installation.                                           utilizing base thru holes (“B”).
  2.	 Isolators are shipped fully assembled and are to be      5.	 Remove top bolt and top washer. Place equip-
      positioned in accordance with the submittal draw-            ment on top of isolators so that mounting holes
      ings or as otherwise recommended.                            in equipment or base line up with threaded hole
                                                                   (“C”).
  3.	 Set isolators on floor, housekeeping pad, or sub-
      base, ensuring that all isolator centerlines match       6.	 Reinstall top bolt and washer and tighten down.
      the equipment mounting holes. The VMC group
                                                               7.	 Installation is complete.
      recommends that the isolator base (“A”) be in-
      stalled on a level surface. Shim or grout as re-
      quired, leveling all isolator bases to the same
      elevation (1/32 in. maximum difference can be
      tolerated).
                                                                                         TOP BOLT
                                                   ("B")
                                                                                         TOP WASHER                         5
        D                                           D
                                                            ("C")
                                                                                                  ("B")
                              CL                                           CL                          ("A")
                                                                      SECTION D-D
                                                                                                           LD13762B
SECTION 6 – COMMISSIONING
             Commissioning of this unit should only                      Charging after vacuuming - Charge 10%
             be carried out by Johnson Controls Au-                      of the specified amount of refrigerant into
             thorized personnel.                                         the evaporator. Otherwise, the compressor
                                                                         is in risk when it starts. Find the system
                                                                         charges on the unit nameplate.
      JUMP       INPUT
    LOCATION    SIGNAL
        1       0–10 V
LD23530
Verify the control panel display is illuminated. Assure    If mains power must be switched OFF for extended
the system switches under the SYSTEM SWITCHES              maintenance or an extended shutdown period, the com-
key are in the OFF position.                               pressor suction, discharge and economizer service stop
                                                           valves should be closed (clockwise). If there is a pos-
Supply Voltage                                             sibility of liquid freezing due to low ambient tempera-
                                                           tures, the coolers should be drained or power should be
Verify that the site voltage supply corresponds to the
                                                           applied to the chiller. This will allow the cooler heater
unit requirement and is within the limits given in SEC-
                                                           to protect the cooler from freezing down to –20°F. Be-
TION 5 – TECHNICAL DATA.
                                                           fore placing the unit back in service, valves should be
Water System                                               opened and power must be switched ON (if power is
                                                           removed for more than 8 hours) for at least 8 hours (24
Verify the chilled liquid system has been installed cor-   hours if ambient temperature is below 86°F [30°C])
rectly, and has been commissioned with the correct         before the unit is restarted.
direction of water flow through the cooler. The inlet
should be at the refrigerant piping connection end of
the cooler. Purge air from the top of the cooler using
the plugged air vent mounted on the extension pipe.
F/ Protection
Verify all sources of electrical supply to the unit are   Low Switch
taken from a single point of isolation. Check that the    Verify a chilled water flow switch is correctly fitted in
maximum recommended fuse sizes given in SECTION           the customer’s piping on the cooler outlet, and wired
5 – TECHNICAL DATA has not been exceeded.                 into the control panel correctly using shielded cable.
                                                          There should be a straight run of at least 5 pipe diam-
                                                          eters on either side of the flow switch. The flow switch
                                                          should be connected to terminals 13 and 14 of XTBC1
                                                          on the panel.
LD18421
LD18422
LD18419
                                       LD18420
                                                                                                         LD18424
0 1 2 3 4 5 6 7 8 9 LOW HIGH
                           SET POINT
                                                                              0       1       2       3   4       5       6 7          8       9
                                                                                                                                                       LD29415
YLAA
STARTUP CHECKLIST
 A. PRE-STARTUP
    Unit Checks (No Power)                                                                  a. High voltage........................................................
    The following basic checks should be made with the                                      b. Low voltage ........................................................
    customer power to the unit switched OFF.                                                c. Check tightness of power wiring inside the pow-
                                                                                               er panel on both sides of the motor contactors
   1. Inspect the unit for shipping or installation
                                                                                               and overloads. ....................................................
      damage ...................................................................            d. Check to ensure BAS control is wired correctly
   2. Assure that all piping has been completed. ............                                  and operational. ...................................................             6
   3. Visually check for refrigerant piping leaks ...............                        9. Check for proper size fuses in main and control
                                                                                            circuits, and verify overload setting corresponds
   4. If available, open suction line ball valve, discharge
                                                                                            with RLA and FLA values in electrical tables (see
      line ball valve, and liquid line valve for each
                                                                                            Table 8 and Table) ...................................................
      system.....................................................................
                                                                                        10. Assure 120VAC (110VAC for 50Hz units) Control
   5. At shutdown, the oil level should be between
                                                                                            Power to TB1 has 15 amp minimum capacity. .........
      the bottom and middle of the oil equalizing sight
      glass. .......................................................................    11. Are all water temp sensors inserted completely into
                                                                                            their respective wells and are coated with heat con-
   6. Are water pumps ON?
                                                                                            ductive compound? .................................................
      a. Check and adjust water pump flow rate and pres-
         sure drop across the cooler Refer to Operating                                 12. Are the evaporator TXV bulbs strapped onto the
         Limitations, SECTION 8 - TECHNICAL DATA                                            suction lines at 4 or 8 o'clock positions or suction
         (Form 150.72-ICOM6). .......................................                       temp. sensors if EEVs are installed? ......................
      b. Is the flow switch in place, wired properly, and
                                                                                        13. Do all sides of the unit have the recommended
         operational? ........................................................
                                                                                            amount of space for air ventilation? Refer to SEC-
       c. Are the chilled water pumps operational? ..........                               TION 4 - INSTALLATION (Form 150.72-ICOM6). ...
       d. Is the water system filled with water? .................                      14. Does the cabinet edge clear the insulation of cable
       e. Is ALL air purged from the water system? .......                                  at the power entry to avoid slicing the cable? .........
           NOTE: Any air found in the water system MUST
           be purged before the chiller can start up. Exces-                           B. COMPRESSOR HEATER
           sive flow may cause catastrophic damage to the                                 (Power On - 24 Hours Prior To Start)
           heat exchanger (evaporator)
                                                                                         Apply 120VAC and verify its value between terminals
   7. Is the control panel free of foreign material (wires,                              5 and 2 of XTBC2. The voltage should be 120VAC
      metal chips and so on)? ..........................................                 (110VAC for 50Hz units) plus or minus 10% .................
   8. Is ALL power wired to the chiller and meets the follow-                          NOTE: Power must be applied 24 hours prior to start-up.
      ing N.E.C. and local codes?                                                      Each heater should draw approximately 0.5 to 1A.
JOHNSON CONTROLS 1
 C. STARTUP
                                                                                               SETPOINTS ENTRY LIST
      Panel checks (Power On - Both unit switch Off)                                                                  UNIT OPTIONS
      1. Apply 3-phase power and verify its value. Voltage                                     Display Language
         imbalance should be no more than 2% of the aver-
                                                                                               Sys 1 Switch
         age voltage. ............................................................
                                                                                               Sys 2 Switch
      2. Apply 120VAC (110VAC for 50Hz units) and verify its
                                                                                               Chilled Liquid
         value on the terminal block in the Power Panel. Make the
         measurement between Terminals 5 and 2 of XTBC2.                                       Ambient Control*
         The voltage should be 120VAC plus or minus 10%                                        Local/Remote Mode
      3. Program/verify the Cooling Setpoints, Program                                         Control Mode
         Setpoints, and Unit Options. Record the values in                                     Display Units
         the Setpoints Entry List table. ...................................                   Lead/Lag Control*
      4. Place the unit into Service Mode and cycle each                                       Fan Control*
         condenser fan to ensure proper rotation. ..................
                                                                                               Manual Override
      5. Turn system 2 OFF and leave System 1 run-                                             Current Feedback
         ning. Refer to SECTION 6 – OPERATIONS (Form
                                                                                               Power Fail Restart
         150.72-ICOM6), UNIT KEYS, Option 2 for more in-
         formation on System Switches. ................................                        Soft Start**
                                                                                               Unit Type**
      6. Connect a manifold gauge to system 1 suction and
         discharge service valves. ..........................................                  Refrigerant Type**
      7. Place the Unit Switch in the control panel to the ON                                  Flash Card Update
         position. ......................................................................      Remote Temperature Reset
            NOTE: The chilled liquid setpoint may need to be                                   External Evaporator Pump
            temporarily lowered to ensure all compressors
                                                                                               YORK Hydro Kit Pump
            cycle ON.
                                                                                               Pump Selection
          As each compressor cycles ON, ensure that the dis-
          charge pressure rises and the suction pressure de-                                   Data Log to Flashcard Enabled
          creases. If this does not occur, the compressor being                                Expansion Valve Type**
          tested is operating in the reverse direction and must be
          corrected.                                                                                                COOLING SETPOINTS
      8. Verify proper compressor rotation and then turn the                                   Cooling Setpoint
         Unit Switch to “OFF.” ................................................                Range
           NOTE: This unit uses scroll compressors which                                       EMS-PWM Max. Setpoint
           can only operate in one direction. Failure to ob-
                                                                                                                PROGRAM SETPOINTS
           serve this will lead to compressor failure.
                                                                                               Discharge Pressure Cutout
      9. Turn system 1 OFF and system 2 ON (two system units
                                                                                               Suction Pressure Cutout
         only). Refer to SECTION 6 – OPERATIONS (Form
         150.72-ICOM6), UNIT KEYS for more information ...                                     Low Ambient Temp. Cutout
                                                                                               Leaving Liquid Temp. Cutout
  10. Place the Unit Switch in the control panel to the ON
      position. ......................................................................         Anti-Recycle Time
         NOTE: The chilled liquid setpoint may need to                                         Fan Control ON Pressure
         be temporarily lowered to ensure all compres-                                         Fan Differential OFF Pressure
         sors cycle ON.
                                                                                               Total # of Compressors
          As each compressor cycles ON, ensure that the dis-
          charge pressure rises and the suction pressure de-                                   Number of Fans/System*
          creases. If this does not occur, the compressor being                                Unit/Sys Voltage*
          tested is operating in the reverse direction and must be
                                                                                               Remote Unit ID
          corrected.
                                                                                               *Not on All Models    **Viewable Only
   11. Ensure the Data Logging feature has been enabled
       .....................................................................................
  12. Verify proper compressor rotation and then turn the
      Unit Switch to OFF. ....................................................
2 JOHNSON CONTROLS
 JOHNSON CONTROLS                                                                                                                                                          3
JOHNSON CONTROLS                                                                                                                                                            119
                                              FORM 150.72-ICOM6
                                           ISSUE DATE: 10/24/2019
LD13283
Remote cycling, demand limiting, and chilled liquid       Keypad commands are actuated upon by the micropro-
temperature reset can be accomplished by field sup-       cessor to change set points, cutouts, scheduling, oper-
plied contacts.                                           ating requirements, and to provide displays. The key-
                                                          pad and display are connected to the I/O board.
Compressor starting/stopping and loading/unload-
ing decisions are performed by the Microprocessor to      The on-board power supply converts 24 VAC from 75
maintain leaving or return chilled liquid temperature.    VA, 120/24 VAC 50/60 Hz UL listed class 2 power
These decisions are a function of temperature devia-      transformer to +12 V, +5 V and +3.3 V using switch-
tion from set point.                                      ing and linear voltage regulators located on the I/O and
                                                          IPU II boards. These voltages are used to operate in-
A Master ON/OFF switch activates or deactivates the       tegrated circuitry on the board. The 40 character dis-
unit.                                                     play and unit sensors (transducers and temp sensors)
When a key is pressed, such as the OPER DATA key,           PROGRAMMING # OF COMPRESSORS
system parameters will be displayed and will remain
                                                            The total number of compressors is programmable un-
on the display until another key is pressed. The system
                                                            der the PROGRAM key. Dual (2) system chillers can
parameters can be scrolled with the use of the ↑ (UP)
                                                            have 4, 5, or 6 compressors.
and ↓ (DOWN) arrow keys. The display will update all
information at a rate of about 1 a second.
Display Messages may show characters indicating
“greater than” (>) or “less than” (<). These characters
indicate the actual values are greater than or less than
the limit values which are being displayed.
STATUS KEY
00066VIP
Unit Status                                                  		 		 D	A	 I	 L	Y 		 S	C	H	E	D	U	L	E
Pressing the STATUS key will enable the operator to          							S	       H	U	 T	D	O	W	N
determine current chiller operating status. The messag-
es displayed will include running status, cooling de-      The DAILY SCHEDULE SHUTDOWN message in-
mand, fault status, external cycling device status. The    dicates that the daily/holiday schedule programmed is
display will be a single message relating to the highest   keeping the unit from running.
priority message as determined by the microprocessor.
Status messages fall into the categories of General Sta-                    REMOTE STOP
tus and Fault Status.                                                       NO RUN PERM
  		 S	Y	S		 1		 D	S	C	H		 L	 I	 M	 I	 T	 I	 N	G
  		 S	Y	S		 2		 D	S	C	H		 L	 I	 M	 I	 T	 I	 N	G            If MANUAL OVERRIDE mode is selected, the STA-
                                                            TUS display will display this message. This will indi-
                                                            cate that the Daily Schedule is being ignored and the
When this message appears, discharge pressure limit-
                                                            chiller will start-up when chilled liquid temperature
ing is in effect. The Discharge Pressure Limiting fea-
                                                            allows, Remote Contacts, UNIT switch and SYSTEM
ture is integral to the standard software control; howev-
                                                            switches permitting. This is a priority message and can-
er the discharge transducer is optional on some models.
                                                            not be overridden by anti-recycle messages, fault mes-
Therefore, it is important to keep in mind that this con-
                                                            sages, etc. when in the STATUS display mode. There-
trol will not function unless the discharge transducer is
                                                            fore, do not expect to see any other STATUS messages
installed in the system.
                                                            when in the MANUAL OVERRIDE mode. MANUAL
The internal motor protector opens at 185°F to 248°F       This safety will shut down a system if either suction
(85°C to 120°C) and auto resets. The mechanical HP         temperature or suction pressure sensors read out of
switch opens at 585 psig plus or minus 10 psig (27.92      range high or low. This condition must be present for 3
barg plus or minus 0.69 barg) and closes at 330 psig       seconds to cause a system shutdown. The safety locks
plus or minus 25 psig (22.75 barg plus or minus 1.72       out a system after the first fault and will not allow au-
barg).                                                     tomatic restarting.
The compressor is also equipped with a discharge           Unit Safeties
temperature sensor for the purpose of sensing inter-
                                                           Unit safeties are faults that cause all running compres-
nal scroll temperature. This sensor protects the scrolls
                                                           sors to be shut down. Unit faults are auto reset faults
from overheating due to inadequate cooling that may
                                                           in that the unit will be allowed to restart automatically
occur when refrigerant charge is low, or superheat is
                                                           after the fault condition is no longer present.
too high.
                                                             						U	N	I	T		F	A	U	L	T	:
When the sensor senses a high temperature, it opens
                                                             			 L	O	W		 A	M	B	I	E	N	T 		 T	E	M	P
the motor protector circuit in the compressor causing
the compressor to shut down.
                                                           The Low Ambient Temp Cutout is a safety shutdown
During the first two faults an MP/HP INHIBIT message       designed to protect the chiller from operating in a low
will be displayed and the system will not be locked out.   ambient condition. If the outdoor ambient temperature
Only after the third fault in 90 minutes will the MP/      falls below the programmable cutout, the chiller will
HPCO FAULT message be displayed.                           shut down. Restart can occur when temperature rises 2
Whenever the motor protector or discharge sensor           °F above the cutoff.
shuts down a compressor and the system, the inter-           		 			U	N	I	T		F	A	U	L	T	:
nal compressor contacts will open for a period of 30         			 L	O	W		 L	 I	 Q	U	 I	 D		 T	 E	M	P
minutes to assure that the motor or scroll temperatures
have time to dissipate the heat and cool down. The MP/
HP INHIBIT message will be displayed while these           The Low Leaving Chilled Liquid Temp Cutout protects
contacts are open or when the HPCO is open.                the chiller form an evaporator freeze-up should the
While this message is displayed, the compressors           chilled liquid temperature drop below the freeze point.
will not be permitted to start.                            This situation could occur under low flow conditions or
                                                           if the micro panel set point values are improperly pro-
After 30 minutes, the contacts will close and the sys-     grammed. Anytime the leaving chilled liquid tempera-
tem will be permitted to restart. The microprocessor       ture (water or glycol) drops below the cutout point, the
will not try to restart the compressors in a system that   chiller will shutdown. Restart can occur when chilled
shuts down on this safety for a period of 30 minutes to    liquid temperature rises 2 °F above the cutout.
allow the internal compressor to time out.
                                                             						U	        N	I	T		F	 A	U	L	T	:
During the 30 minute timeout, the MP/HPCO INHIB              	1	 1	 5	 V	A	C		 U	N	D	E	R		 V	O	L	 T	A	G	E
message will be displayed. The MP/HPCO fault will
only be displayed after 3 shutdowns in 90 minutes,         The Under Voltage Safety assures that the system is
indicating the system is locked out and will not           not operated at voltages where malfunction of the mi-
restart.                                                   croprocessor could result in system damage. When the
  		 S	 Y	 S		 1		H I G H     M T R		 C	 U	 R	 R	          115VAC to the micro panel drops below a certain level,
  		 S	 Y	 S		 2	 	H I G H    M T R		 C	 U	 R	 R           a unit fault is initiated to safely shut down the unit. Re-
                                                           start is allowed after the unit is fully powered again and
                                                           the anti-recycle timers have finished counting down.
When the System Current Feedback option is installed
and selected (Option 11 under OPTIONS key Current
Feedback), this safety will operate as follows. If the
actual feedback voltage of the system proportional to
currents exceeds the programmed trip voltage for 5
seconds, the system will shutdown.
After the first 3 minutes, if the suction pressure falls     of the system exceeds the programmed voltage for 5
below the programmed cutout setting, a transient pro-        seconds, the system will shut down. This fault will not
tection routine is activated. This sets the cutout at 10%    be cleared until the condition is no longer present. Fol-
of the programmed value and ramps up the cutout              lowing are the messages for both systems.
over the next 30 seconds. If at any time during the 30
                                                               		 S	 Y	 S		 1		H I G H      M T R		 C	 U	 R	 R	
seconds the suction pressure falls below the ramped
                                                               		 S	 Y	 S		 2	 H
                                                                               	 I G H      M T R		 C	 U	 R	 R
cutout, the system will stop. This transient protection
scheme only works if the suction pressure transducer
is installed.                                                Low Superheat Cutout (EEV Mode Only)
Motor Protector/High Pressure Cutout Fault                   The Low Superheat Cutout protects the compressors
                                                             from liquid flowing back due to low suction superheat.
The Motor Protector/High Pressure Cutout protects the        This safety is only active when EEV is selected as the
motor from overheating or the system from experienc-         expansion valve type. This safety is ignored for the
ing dangerously high discharge pressure. This fault          first 15 seconds of system run time.
condition is present when CR1 (SYS 1) or CR2 (SYS
2) opens causing 0 VDC to be read on the input. The          Two events can trigger this safety. The first event is
fault condition is cleared and will allow to restart the     when the suction superheat is lower than 2.0°F for 3
system when a 30 VDC signal is restored to the input         seconds. The second event is when the LLSV is closed
by closing CR1 or CR2. This fault will shut down the         10 times in 2 minutes due to low superheat. See the
system 0.5 seconds after the relay opens. This fault will    LLSV control section for further details. Following are
only occur when a system is running. Following are the       the messages for all systems.
messages for both systems.
                                                                  		 S	 Y	 S		 1			L O W		S U P E R H E A T	
  		 S	Y	S		 1		 M	P	 /	 H	P	C	O		 F	A	U	L	T                      		 S	 Y	 S		 2			L O W		S U P E R H E A T	
  		 S	Y	S		 2		 M	P	 /	 H	P	C	O		 F	A	U	L	T
Table 14 - LEGEND
      TYPE                                                         DEFINITION
          3X       Automatically restarts on the first and second fault with a lockout on the third fault in 90 minutes
                                                                                                                                 7
          1X       Locks out on the first fault
      AUTO         Allows restart once meeting the required conditions
             Rem Stop
         No Run Permissive             System X MP/HPCO Inhibit                       115VAC Undervoltage
             Flow Switch
                Open
                                                                                            Low Battery
                                        System X MP/HPCO Fault
                                                                                       Check Prog/Step/Optn
        System X Switch Off                                                           (Unit Warning Message)
         System X AR Timer
                                                                                        High Motor Current
System X AC Timer
DISPLAY/PRINT KEYS
00067VIP
The Display/Print keys allow the user to retrieve sys-      With the “UNIT TYPE” set as a liquid chiller (no
tem and unit information that is useful for monitoring      jumper from J11-7 to J11-12 on the I/O Board), the
chiller operation, diagnosing potential problems, trou-     following list of operating data screens are viewable
bleshooting, and commissioning the chiller.                 under the OPER DATA key in the order that they are
                                                            displayed. The ↓ (DOWN) arrow key scrolls through
System and unit information, unit options, set points,      the displays in the order they appear below:               7
and scheduling can also be printed out with the use of
a printer. Both real-time and history information are                   The chiller MUST be set to be a liquid
available.                                                              chiller (no jumper from J11-7 to J11-12
                                                                        on the I/O Board). DO NOT operate the
Oper Data Key                                                           chiller if not properly set up.
The OPER DATA key gives the user access to unit and
system operating parameters. When the OPER DATA
key is pressed, system parameters will be displayed and        L	C	H	L	T		 =		 4	6	.	2	°	F
remain on the display until another key is pressed. After     	R	C	H	L	 T		 =		 5	 7	 .	 4	 °	 F	 °
pressing the OPER DATA key, the various operating
data screens can be scrolled through by using the ↑ (UP)    This display shows chilled leaving and return liquid
and ↓ (DOWN) arrow keys or the ENTER/ADV key                temperatures. The minimum limit on the display for
located under the “ENTRY” section.                          these parameters are 2.2 °F (-19 °C). The maximum
             System 2 information will only be dis-         limit on the display is 140 °F (60 °C).
             played for 2 system units.                       		 	 A	M	B	I	E	N	T		 A	I	R		 T	E	M	P
                                                              						=		8	      7	.	5	°	F
  S	Y	S		X		S	P		=		7	2	.	1		P	S	I	G                           		 		 C	O	O	L	 I	 N	G		 D	E	M	A	N	D
  							D	   P		=	2	2	7	.	0		P	
                               S	I	G                           					2		O	F		8		S	T	E	P	S
These displays show suction and discharge pressures          The display of COOLING DEMAND indicates the
for each system. The discharge pressure transducer is        current “step” in the capacity control scheme when in
optional on some models.                                     Return Water Control Mode. The number of available
                                                             steps are determined by how many compressors are in
If the optional discharge transducer is not installed, the   the unit. In the above display, the “2” does not mean
discharge pressure would display 0 PSIG (0 barg).            that two compressor are running but only indicates that
The minimum limits for the display are:                      the capacity control scheme is on step 2 of 8. Capacity
                                                             Control is covered in more detail in this publication
  •	 Suction Pressure: 0 psig (0 barg)                       which provides specific information on compressor
  •	 Discharge Pressure: 0 psig (0 barg)                     staging (for Return Water Control only).
  	    L	 O	 A	 D		 T	 I	 M	 E	 R		 5	 8		 S	 E	 C             E	 V	A	P	O	R	A	T	O	R		 H	E	A	T	E	R					
  	U	N	L	O	A	D		 T	 I	 M	E	R				 0		 S	E	C                     S	T	 A	T	U	S		I	S							=	       X	X	
                                                                                                   X		
This display of the load and unload timers indicate          This display indicates the status of the evaporator
the time in seconds until the unit can load or unload.       heater. The evaporator heater is controlled by ambient
Whether the systems loads or unloads is determined by        air temperature. When the ambient temperature drops
how far the actual liquid temperature is from set point.     below 40°F the heater is turned ON. When the tem-
A detailed description of unit loading and unloading is      perature rises above 45°F the heater is turned OFF. An
covered under the topic of Capacity Control.                 under voltage condition will keep the heater OFF until
                                                             full voltage is restored to the system.
  E	V	
     A	P	
        O	R	
           A	T	
              O	R		W	A	T	
                        E	R						                             		S	Y	S		X		C	O	M	P		S	T	A	T	U	S
  P	U	
     M	P				S	T	A	T	
                   U	S				=	 X	
                              X	X	
                                 X                            		 1	=	X	X	X		 2	=	X	X	X		 3	=	X	X	X
     *See Remote BAS/EMS Temperature Reset Using            The fifth message displays current as sensed by the op-
     a Voltage or Current Signal on page 181.               tional current feedback circuitry. The display reads out
                                                            in amps along with the DC feedback voltage from the
If the microprocessor is programmed for CURRENT             module. Current is calculated by:
FEEDBACK ONE PER UNIT under the OPTIONS
                                                                             225 A x Actual Volts
key, the display will show up as the first display before
the SYS 1 displays. Total chiller current is displayed as                            5 Volts
shown below:
                                                            Individual displays will be present for each system, if
  		 	 U	 N	 I	 T			 A M P S = 5 4 . 0
                                                            CURRENT FEEDBACK ONE PER SYSTEM is pro-
  									V O L T S =           1 . 2
                                                            grammed under the OPTIONS key. Combined com-
                                                            pressor current for each system is displayed.
If the microprocessor is programmed for CURRENT
FEEDBACK NONE, no current display will appear.
History Displays                                               		 			 C	O	N	T	R	O	L	 	M	O	D	E
The HISTORY key gives the user access to many unit             				 L	E	A	V	I	N	G 		 L	I	Q	U	I	D
and system operating parameters at the time of a unit
or system safety shutdown. When the HISTORY key is           Displays the type of chilled liquid control; Leaving or
pressed the following message is displayed.                  Return.
  	D	 I	 S	P	L	A	Y		 S	A	F	E	T	Y		 S	H	U	T-                    		 	 L	 E	A	D	 /	 L	 A	G		 C	O	N	T	R	O	L
  		 D	 O	W	N		 N	 O	 .	 	 1		 (	 1	 T	O	 9	 )                 							 X	X	X	X	X	X	X	X
While this message is displayed, the ↑ (UP) arrow key        Displays the type of lead/lag control; Manual System
can be used to select any of the six history buffers. Buf-   1, Manual System 2 or Automatic. This is only select-
fer number 1 is the most recent, and buffer number 6 is      able on 2-system chillers.
the oldest safety shutdown that was saved.
                                                               		 			 F	 A	N		 C	O	N	T	R	O	L
After selecting the shutdown number, pressing the EN-          		 D	 I	 S	C	H	A	R	G	E		 P	R	E	S	S	U	R	E
TER key displays the following message which shows
when the shutdown occurred.
                                                             Displays the type of fan control; Discharge Pressure or
  		 S	H	U	T	D	O	W	N		 O	C	C	U	R	R	E	D                       Ambient and Discharge Pressure.
  		0	3	:	5	6	 	P	M		2	9		J	A	N		0	2
                                                               	M	A	N	U	A	L		 O	V	E	R	R	 I	 D	E		 M	O	D	E
                                                               							 X	X	X	X	X	X	X	X	X
The ↑ (UP) and ↓ (DOWN) arrow keys are used to
scroll forward and backward through the history buffer
                                                             Displays whether Manual Override was Enabled or
to display the shutdown conditions stored at the instant
                                                             Disabled.
the fault occurred. The ↓ (DOWN) arrow key scrolls
through the displays in the order they appear below:           		   C U R R E N T    F E E D B A C K
                                                               		    X X X X X X X X X X X X X X X X
  						U	N	I	T		F	A	U	L	T	:
  			 L	O	W			 L	 I	 Q	U	 I	 D		 T	 E	M	P
                                                             Displays type of Current Feedback utilized.
Displays the type of fault that occurred.                      		            S O F T S T A R T
                                                               		              X X X X X X X
  		 				U	  N	I	T		T	  Y	P	E
  				 L	I	Q	U	I	D 		 C	H	I	L	L	E	R
                                                             Displays whether the optional European Soft Start was
                                                             installed and selected.
Displays the type of chiller; Liquid, Condensing Unit
or Heat Pump.                                                  		 D	 I	 S	C	H	A	R	G	E		 P	R	E	S	S	U	R	E
                                                               		 C	U	T	O	U	T		 =		 X	X	X	X		 P	S	 I	 G
  		 		 C	H	I	L	L	E	D		 L	I	Q	U	I	D
  								X	      X	X	X	X	
                                                             Displays the programmed Discharge Pressure Cutout.
Displays the chilled liquid type; Water or Glycol.             		 S	U	C	T	 I	 O	N		 P	R	E	S	S	U	R	E
                                                               		 C	U	T	O	U	T		 =		 X	X	X	X		 P	S	 I	 G
  				 A	M	B	 I	 E	N	T		 C	O	N	T	R	O	L
  						 X	X	X	X	X	X	X	X	X	X
                                                             Displays the programmed Suction Pressure Cutout.
Displays the type of Ambient Control; Standard or              		 	 L	O	W		 A	M	B	I	E	N	T		 T	E	M	P
Low Ambient.                                                   			 C	U	T	O	U	T		 =		 X	X	X	 .	 X		 °	 F
  		 L	 O	 C	 A	 L	 /	 R	E	 M	 O	 T	 E		 M	O	 D	 E
  							 X	X	X	X	X	X	X	X	X                                  Displays the programmed Low Ambient Cutout.
  		 L	 E	A	V	 I	 N	G		 L	 I	 Q	U	 I	 D		 T	E	M	P             				 L	E	A	D		 S	Y	S	T	E	M		 I	 S
  			 C	U	T	O	U	T		 =		 X	X	X	 .	 X		 °	 F                    				 S	 Y	 S	 T	 E	M		 N	U	M	B	E	R		 X
Displays the Leaving Liquid Temp. Cutout pro-               Displays which system is in the lead at the time of the
grammed.                                                    fault.
  			 	 F	 A	N 		 C	O	N	T	R	O	L 		 O	N                        E	 V	A	P	O	R	A	T	O	R		 H	E	A	T	E	R
  		 P	R	E	S	S	U	R	E 	= 	X	X	X 		 P	S	 I	 G                   S	T	 A	T	U	S		I	S									X	       X	
                                                                                                  X
Displays the programmed Fan On Pressure.                    Displays status of the Evaporator Heater at the time of
                                                            the fault.
  		 F	 A	 N 		 D	 I	 F	 F	 E	 R	 E	 N	 T	 I	 A	 L		O F F
  				 P	R	E	S	S	U	R	E 	=	 P	S	 I	 G                          E	 V	A	P	O	R	A	 T	O	R		 W	A	 T	 E	R
                                                              P	U	 M	P		S	 T	 A	T	U	S						X	     X	
                                                                                                   X	X
Displays the programmed Fan Off Differential.
                                                            Displays status of Evaporator Water Pump at the time
 			      S Y S 1  T R I P           V O L T S
                                                            of fault. Status may read ON, OFF or trip.
 			      		      = X . X             V O L T S
                                                              E	V	A	P		P	U	M	P		T	O	T	A	L		R	U	N
Displays the programmed High Current Trip Voltage.            H	O	U	R	S											=	       X	X	X	X
			      S Y S 2 T R I P V O L T S
                                                            Evap Pump total run hours at the time of fault.
			      		      = X . X  V O L T S
                                                              		 A	C	T	 I	 V	E		 R	E	M	O	T	E		 C	T	R	L
Displays the programmed High Current Trip Voltage.            									X	          X	X	X	
  					Y	 O	R	
             K			H	Y	
                    D	R	
                       O					
                                                            Displays whether Remote Chiller Control was active
  K	I	T		P	
          U	M	
             P	S										=	 X
                                                            when the fault occurred.
  			 A	M	B	I	E	N	T		 A	I	R		 T	E	M	P
                                                            Displays the system Suction and Discharge Pressure of
  							=		X	      X	X	.	X		°	 F	
                                                            the time of the fault.
Displays whether the System Liquid Line Solenoid or        Further explanation of the above displays is covered
Hot Gas Solenoid was energized at the time of the fault.   under the STATUS, OPER DATA, COOLING SET
                                                           POINTS, PROGRAM, and OPTIONS keys.
  	
  S	Y	S		X		F	A	N		S	T	A	G	E		X	X	X	
                                                           Software Version
                                                           The software version may be viewed by first pressing
Displays the number of Fan Stages in the system active     the HISTORY key and then repeatedly pressing the ↓
at the time of the fault.                                  (DOWN) arrow key until you scroll past the first his-
                                                           tory buffer choice.
  S	Y	S		X		 A	
              C	T	U	A	L		A	M	P	S
  					=	  X	
            X	X	.	X		A	 M	
                         P	S                                 D	 I	 S	P	L	A	Y		 S	A	F	E	T	Y		 S	H	U	T	 -
                                                             D	O	W	N		N	O	.	1		 (	1	T	O	6	)
Displays the system Amperage (calculated approxi-
mately) at the time of the fault.                          After the ↓ (DOWN) arrow key is pressed again, the
                                                           software version will appear.
For this message to appear, CURRENT FEEDBACK
ONE PER SYSTEM must be programmed under the                  C	 O	N	T	R	O	L						 C.	M	X	X.	Z	Z.	Y	 Y
OPTIONS key. If the microprocessor is programmed             	I	/	O										C.	     M	X	X.	1	8.	Y	 Y
as one CURRENT FEEDBACK ONE PER UNIT un-
ENTRY KEYS
00068VIP
The Entry Keys allows the user to view, change pro-          Enter/Adv Key
grammed values. The ENTRY keys consist of an ↑ (UP)          The ENTER/ADV key must be pushed after any change
arrow key, ↓ (DOWN) arrow key, and an ENTER/ADV              is made to the cooling set points, daily schedule, safety
key.                                                         set points, chiller options, and the clock. Pressing this
                                                             key “enters” the new values into memory. If the EN-
Up and Down Arrow Keys
                                                             TER/ADV key is not pressed after a value is changed,
Used in conjunction with the OPER DATA, HISTORY,             the changes will not be “entered” and the original val-
COOLING SET POINTS, SCHEDULE/ADVANCE                         ues will be used to control the chiller.
DAY, OPTIONS, and CLOCK keys, the ↑ (UP) and
↓(DOWN) arrow keys allow the user to scroll through          Programming and a description on the use of the ↑ (UP)
the various data screens. See Display/Print Keys on          arrow key, and ↓ (DOWN) arrow, and ENTER/ADV
page 131 for specific information on the displayed           keys are covered in detail under the SET POINTS, and
information and specific use of the ↑ (UP) and ↓             UNIT keys.
(DOWN) arrow keys.
The ↑ (UP) arrow key, and ↓ (DOWN) arrow key are
also used for programming the control panel such as
changing numerical or text values when programming
cooling set points, setting the daily schedule, changing
safety set points, chiller options, and setting the clock.
00069VIP
Programming of the cooling set points, daily schedule,      Leaving Chilled Liquid Control
and safeties is accomplished by using the keys located        		S	E	T	P	O	I	N	T		=		4	5	.	0	°	F
under the SET POINTS section.                                 			 R	A	N	G	E		 =		 +/-		 2	 .	 0	 °	 F	
The three keys involved are labeled COOLING SET
POINTS, SCHEDULE/ADVANCE DAY, and PRO-                      The above message shows the current chilled water
GRAM.                                                       temperature SET POINT at 45.0°F (notice the cursor
                                                            positioned under the number 0). Pressing either the ↑
Following are instructions for programming the respec-      (UP) or ↓ (DOWN) arrow will change the set point in
tive set points. The same instruction should be used to     0.5°F increments. After using the ↑ (UP) or ↓ (DOWN)
view the set points with the exception that the set point   arrow keys to adjust to the desired set point, the EN-
will not be changed.                                        TER/ADV key must be pressed to enter this number
                                                            into memory and advance to the RANGE SET POINT.
Cooling Set Points
The Cooling Set Point and Range can be programmed           Entry of the set point will be indicated by the cursor
by pressing the COOLING SET POINTS key. The                 moving under the current RANGE set point. The ↑ (UP)
cooling mode (leaving chilled liquid or return chilled      and ↓ (DOWN) arrow keys are used to set the RANGE,
liquid) will be displayed for a few seconds, and the set    in 0.5°F increments, to the desired RANGE set point.
point display entry screen will appear.                     After adjusting the set point, the ENTER/ADV key
                                                            must be pressed to enter the data into memory.
                                                            Notice that the RANGE was programmed for
                                                            +/- X.X°F. This indicates the SET POINT to be in the
center of the control range. If the control mode has        The following messages illustrate both leaving chilled
been programmed for RETURN LIQUID control, the              liquid control and return chilled liquid control respec-
message below would be displayed in place of the pre-       tively.
vious message.
                                                              		R	E	M		S	E	T	P		 =		 4	4	.	0	°	F
When in leaving chilled liquid temperature control, the       			R	A	N	G	E		=		+	/	-	2	.	0	°	F
microprocessor will attempt to control the leaving wa-
ter temperature within the temperature range of the set                 (leaving chilled liquid control)
point + or – the range. In the above example, control
will be in the range of 43°F to 47°F.                         		 R	E	M		S	E	T	P		 =		 4	4	.	0	°	F	
                                                              					R	   A	N	G	E		=		 + 1	
                                                                                        0	.	0	°	F
Return Chilled Liquid Control
  	
  S	E	T	P	O	I	N	T		=		4	5	.	0		 °	F                                      (return chilled liquid control)
  				 R	 A	 N	 G	 E		 =		 +	 1 0	 .	 0	 °	 F	
                                                            The low limit, high limit, and default values for the
                                                            keys under “SET POINTS” are listed in Table 23 on
In return chilled liquid control, the range no longer has   page 173.
a +/- X.X°F, but only a + X.X°F RANGE set point.
This indicates that the set point is not centered within    Pressing the COOLING SET POINTS a third time will
the RANGE but could be described as the bottom of           bring up the display that allows the Maximum EMS-
the control range. A listing of the limits and the pro-     PWM Temperature Reset to be programmed. This
grammable values for the COOLING SET POINTS                 message is shown below.
are shown in Table 23 on page 173.
                                                              		 M	 A	 X		 E	 M	 S 	 -	 P	 W	M		 R 	E	 M	 O	 T	 E
The SET POINT and RANGE displays just described               		 T	 E	 M	 P		 R	 E	 S	 E	 T		 =		 +	 2 0	 °	 F
were based on LOCAL control. If the unit was pro-
grammed for REMOTE control (under the OPTIONS               The Temp Reset value is the maximum allowable re-
key), the above programmed set points would have no         mote reset of the temperature set point. The set point
effect.                                                     can be reset upwards by the use of an Energy Man-
When in return chilled liquid temperature control, the      agement System or from the Temperature Reset Op-
                                                            tion Board. See Remote BAS/EMS Temperature Reset
microprocessor will turn all compressors OFF at set
                                                            Using a Voltage or Current Signal on page 181 for a
                                                                                                                          7
point and will turn compressors ON as return chilled
liquid temperature rises. All compressors will be on at     detailed explanation of this feature.
set point plus the range. If the range equals the tem-      As with the other set points, the ↑ (Up) arrow and ↓
perature drop across the evaporator when fully loaded,      (Down) arrow keys are used to change the Temp Reset
the leaving chilled liquid temperature will remain near     value. After using the ↑ (UP) and ↓ (DOWN) arrows to
the set point plus or minus a few degrees as the chiller    adjust to the desired set point, the ENTER/ADV key
loads and unloads according to return chilled liquid        must be pressed to enter this number into memory.
temperature.
                                                            SCHEDULE/ADVANCE DAY KEY
Both LEAVING and RETURN control are described in
detail under Capacity Control on page 171.                  The SCHEDULE is a seven day daily schedule that
                                                            allows one start/stop time per day. The schedule can
Remote Set Point Control                                    be programmed Monday through Sunday with an al-
Pressing the COOLING SET POINTS key a second                ternate holiday schedule available. If no start/stop
time will display the remote set point and cooling          times are programmed, the unit will run on demand,
range. This display automatically updates about every       providing the chiller is not shut off on a unit or system
2 seconds. Notice that these set points are not “locally”   shutdown. The daily schedule is considered “not pro-
programmable, but are controlled by a remote device         grammed” when the times in the schedule are all zeros
such as an ISN control, remote reset option board, or       (00:00 AM).
remote PWM signal. These set points would only be           To set the schedule, press the SCHEDULE/ADVANCE
valid if the unit was operating in the REMOTE mode.         DAY key. The display will immediately show the fol-
                                                            lowing display.
* Refer to the Engineering Guide for operation below 30°F (-1.1°C). Alternate thermal expansion valves must be used below 30°F (-1.1°C).
*When using glycol, Leaving Chilled Liquid Set Point should not be set below 20°F (-6.7°C).
**Do not exceed 55°F (12.8°C) set point before contacting the nearest Johnson Controls Office for application guidelines.
   	M	
     O	N		S	T	A	R	T		=		0	0	 :	 0	0		 A	M                                After SUN (Sunday) schedule appears on the display
   						S	   T	O	P		=		0	0	:	0	  0		A	 M                                a subsequent press of the SCHEDULE/ADVANCE
                                                                         DAY key will display the Holiday schedule. This is a
                                                                         two part display. The first reads:
The line under the 0 is the cursor. If the value is wrong,
it may be changed by using the ↑ (UP) and ↓ (DOWN)                           	H	O	L		 S	T	A	R	T		 =		 0	0	 :	 0	0		 A	M
arrow keys until correct. Pressing the ENTER/ADV                             						S	     T	O	P		=		0	  0	:	0	  0		A	 M
key will enter the times and then move the cursor to
the minute box. The operation is then repeated if nec-                   The times may be set using the same procedure as de-
essary. This process may be followed until the hour,                     scribed above for the days of the week. After chang-
minutes, and meridian (AM or PM) of both the START                       ing the meridian of the stop time, pressing the ENTER/
and STOP points are set. After changing the meridian                     ADV key will advance the schedule to the following
of the stop time, pressing the ENTER/ADV key will                        display:
advance the schedule to the next day.
                                                                             				S __ 	
                                                                                      M		T		W		T		F		S
                Whenever the daily schedule is changed                       			H	O	L	I	D	A	Y		N	O	T	E	D		B	Y		 *
                for Monday, all the other days will change
                to the new Monday schedule. This means
                if the Monday times are not applicable                   The line below the empty space next to the S is the
                for the whole week then the exceptional                  cursor and will move to the next empty space when
                days would need to be reprogrammed to                    the ENTER/ADV key is pressed. To set the Holiday,
                the desired schedule.                                    the cursor is moved to the space following the day of
                                                                         the week of the holiday and the ↑ (UP) arrow key is
To page to a specific day, press the SCHEDULE/AD-                        pressed. An * will appear in the space signifying that
VANCE DAY key until the desired day appears. The                         day as a holiday. The * can be removed by pressing the
start and stop time of each day may be programmed                        ↓ (DOWN) arrow key.
differently using the ↑ (UP) and ↓ (DOWN) arrow, and
ENTER/ADV keys.                                                          The Holiday schedule must be programmed weekly –
                                                                         once the Holiday schedule runs, it will revert to the
                                                                         normal daily schedule.
PROGRAM KEY                                                The LOW AMBIENT TEMP CUTOUT allows the user
                                                           to select the chiller outside ambient temperature cutout
There are several operating parameters under the PRO-
                                                           point. If the ambient falls below this point, the chiller
GRAM key that are programmable. These set points
                                                           will shut down. Restart can occur when temperature
can be changed by pressing the PROGRAM key, and
                                                           rises 2°F (1.11°C) above the cutout set point.
then the ENTER/ADV key to enter Program Mode.
Continuing to press the ENTER/ADV key will display           	L	 E	A	V	 I	 N	G		 L	 I	 Q	U	 I	 D		 T	 E	M	P
each operating parameter. While a particular parameter       			 C	U	T	O	U	T		 =		 3	 6	 .	 0	 °	 F	
is being displayed, the ↑ (UP) and ↓ (DOWN) arrow
keys can be used to change the value. After the value is
                                                           The LEAVING LIQUID TEMP CUTOUT protects
changed, the ENTER/ADV key must be pressed to en-
                                                           the chiller from an evaporator freeze-up. Anytime the
ter the data into memory. Table 16 on page 145 shows
                                                           leaving chilled liquid temperature drops to the cutout
the programmable limits and default values for each
                                                           point, the chiller shuts down. Restart will be permitted
operating parameter.
                                                           when the leaving chilled liquid temperature rises 2°F
Following are the displays for the programmable val-       (1.11°C) above the cutout set point.
ues in the order they appear:
                                                           When water cooling mode is programmed (OPTIONS
  d	 D	 I	 S	C	H	A	R	G	E			 P	R	E	S	S	U	R	E                key), the value is fixed at 36.0°F (2.22°C) and cannot
  			 C	U	T	O	U	T		 =		 3	 9	 5		 P	S	 I	 G                be changed. Glycol cooling mode can be programmed
                                                           to values listed in Table 16 on page 145.
DISCHARGE PRESSURE CUTOUT is the discharge                   	A	N	T	 I		 R	E	C	Y	C	L	E		 T	 I	 M	E	R	
pressure at which the system will shutdown as moni-          					=		6	      0	0		S	 E	C	
tored by the optional discharge transducer. This is a
software shutdown that acts as a backup for the me-
                                                           The programmable anti-recycle timer assures that sys-
chanical high pressure switch located in the refrigerant
                                                           tems do not short cycle, and the compressor motors
circuit. The system can restart when the discharge pres-
                                                           have sufficient time to dissipate heat after a start. This
sure drops 40 psig (2.76 barg) below the cutout point.
                                                           timer is programmable under the PROGRAM key be-
If the optional discharge pressure transducer is not in-   tween 300 seconds and 600 seconds. Whenever pos-
stalled, this programmable safety would not apply. It      sible, to reduce cycling and motor heating, the anti-re-
should be noted that every system has a mechanical         cycle timer should be adjusted as high as possible. The      7
high pressure cutout that protects against excessive       programmable anti-recycle timer starts the timer when
high discharge pressure regardless of whether or not       the first compressor in a system starts. The timer be-
the optional discharge pressure is installed.              gins to count down. If all the compressors in the circuit
                                                           cycle OFF, a compressor within the circuit will not be
  		 	 S	U	C	T	 I	 O	N		 P	R	E	S	S	U	R	E                   permitted to start until the anti-recycle timer has timed
  		 C	U	T	O	U	T		 =		 80	.	 0		 P	S	 I	 G                 out. If the lead system has run for less than 5 minutes,
                                                           3 times in a row, the anti-recycle timer will be extended
The SUCTION PRESSURE CUTOUT protects the                   to 10 minutes, if currently programmed for less than 10
chiller from an evaporator freeze-up. If the suction       minutes.
pressure drops below the cutout point, the system will
                                                             				 F	 A	N		 C	O	N	T	R	O	L		 O	N
shut down. Typically, the cutout should be set to 80
                                                             		 P	 R	 E	 S	 S	 U	 R	 E	 =	 X	 X	 X	 P	 S	 I	 G
psig (5.52 bar) form water cooling.
             There are some exceptions when the suc-
                                                           The Fan Control On Pressure is the programmed pres-
             tion pressure is permitted to temporarily
                                                           sure value that is used to stage the condenser fans on, in
             drop below the cutout point. Details are
                                                           relation to discharge pressure. See Standard Condens-
             explained under the topic of SYSTEM
                                                           er Fan Control on page 176 in SECTION 7 – UNIT
             SAFETIES.
                                                           CONTROLS and Table 26 on page 178 and Table 27
                                                           on page 179.
  			 L	O	W		 A	M	B	I	E	N	T		 T	E	M	P	
  				 C	U	T	O	U	T		 =		 2	 5	 .	 0	 °	 F	
* T
   he minimum discharge pressure allowed is 235 psig. The Fan Differential Off Pressure High Limit will be lowered (reduced) to prevent go-
  ing below 235 psig based on where the fan control On Pressure is programmed.
JOHNSON CONTROLS                                                                                                                          145
                                                                                                               FORM 150.72-ICOM6
SECTION 7 – UNIT CONTROLS
                                                                                                            ISSUE DATE: 10/24/2019
                                                                                               Leaving Liquid
                         EMS - PWM                                                              Temperature
                        Remote Temp                                                               Cutout
                        Reset Setpoint
                                                                                                Anti-Recycle
      Table 12 provides a quick reference of the set points list for the Set Points Keys.          Timer
                                                                                               Fan Control
                                                                                               On-Pressure
                                                                                              Fan Differential
                                                                                               Off-Pressure
                                                                                              Total Numbers
                                                                                                    of
                                                                                               Compressors
                                                                                                Number of
                                                                                             Fans Per System
                                                                                                 SYS / Unit
                                                                                             Trip Volts Option
Remote Unit ID
LD07404c
Service Mode
Use the Service Mode to view all the inputs and enable       normal control. The user can disable the Service Mode
or disable all the outputs on the unit, except the com-      by turning on the unit switch or by powering off and on
pressors. Some of the internal timers and counters are       the 115 VAC.
viewable and modifiable in the Service Mode. To enter                     The Imperial units are exact values. The
the Service Mode, turn off the unit switch and press                      Metric units are approximates.
PROGRAM, ↑, ↑, ↓, ↓, and ENTER in sequence. The
Service Mode times out after 30 minutes and returns to
* If the chilled liquid cooling type is modified, the suction pressure cutout is set to the default value.
                                   or
   						L O W T E M P E R A T U R E					
   								G	    L	Y	C	 O	L
UNIT KEYS
OPTIONS
CLOCK
00070VIP
English, Spanish, French, German, Italian, Portuguese,                 This turns systems 1 and 2 OFF.
Hungarian, Polish, and Swedish can be programmed.
                                                                           Turning a system OFF with its system
                                                                           switch allows a pumpdown to be per-
                                                                           formed before shutdown.
The low ambient cutout is adjustable from 25°F to 60°F    Unit control is based on return chilled liquid temp.
(-3.9°C to 15.6°C).                                       Return Chilled Liquid Control can only be selected on
                                                          units that have 4 to 6 compressors (dual system units).
                          or
                                                                                    or
  			 A	M	B	 I	 E	N	T		 C	O	N	T	R	O	L
  					L	   O	  W		A	 M	B	I	E	N	T                           		 			 C	O	N	T	R	O	L		 M	O	D	E
                                                            				 L	E	A	V	I	N	G		 L	I	Q	U	I	D
The low ambient cutout is programmable down to
-10°F (-23.3°C). A low ambient kit and variable           Option 6 – Display Units
speed fans MUST be installed for this option to be
                                                            		 		 D	 I	 S	P	L	A	Y		 U	N	 I	 T	S
chosen. If the kit is NOT installed, and low ambi-
                                                            						I	      M	P	E	R	I	A	L
ent is selected, low pressure faults and compressor
damage may occur.
                                                          This mode displays system operating values in Impe-
Option 4 – Local/Remote Control Type                      rial units of °F or PSIG.
  	L	O	C	A	 L		 /		 R	E	M	O	T	 E		 M	O	D	E	 L                                       or
  									L	         O	C	A	L
                                                            				D	 I	 S	P	L	A	Y		 U	N	 I	 T	S
                                                            										S	I
When programmed for LOCAL, an ISN or RCC con-
trol can be used to monitor only. The micro panel will
operate on locally programmed values and ignore all       This mode displays system operating values in Scien-
commands from remote devices, or through the RS-          tific International Units of °C or barg.
485 inputs. The chiller will communicate and send data
to the remote monitoring devices.
                          or
  		 L	O	C	A	 L	 /	 R	E	M	O	T	 E		 M	O	D	E
  								R	          E	M	O	T	 E
Option 7 – Lead/Lag Type (two system units                 Option 9 – Manual Override Mode
only)                                                        	M	A	N	U	A	L		 O	V	E	R	R	 I	 D	E		 M	O	D	E
  			 L	 E	A	D	 /	 L	 A	G		 C	O	N	T	R	O	L                    							D	I	S	      A	B	L	E	  D
  			 M	A	N	U	A	L		 S	Y	S		 1		 L	E	A	D
                                                           This option allows overriding of the daily schedule
SYS 1 selected as lead compressor. SYS 1 lead option       that is programmed. MANUAL OVERRIDE MODE –
MUST be chosen if Hot Gas Bypass is installed.             DISABLED indicates that override mode has no effect.
                          or                                                         or
  			 L	 E	A	D	 /	 L	 A	G		 C	O	N	T	R	O	L                    	M	A	N	U	A	L		 O	V	E	R	R	 I	 D	E		 M	O	D	E
  			 M	A	N	U	A	L		 S	Y	S		 2		 L	E	A	D                      								E	       N	A	B	L	E	  D
SYS 2 selected as lead compressor.                         Manual Override Mode is enabled. This is a service
                                                           function and when enabled, will allow the unit to start
                          or                               when shut down on the daily schedule. It will auto-
  			 L	 E	A	D	 /	 L	 A	G		 C	O	N	T	R	O	L                  matically be disabled after 30 minutes.
  						A	     U	  T	 O	M	A	T	I	C
                                                           Option 10 – Current Feedback Options
                                                           Installed
Lead/lag between systems may be selected to help
equalize average run hours between systems on chillers          C U R R E N T F E E D B A C K
                                                             				
                                                             										    N O N E
with 2 refrigerant systems. Auto lead/lag allows auto-
matic lead/lag of the two systems based on an average
run hours of the compressors in each system. A new         This mode should be selected when the panel is not
lead/lag assignment is made whenever all compressors       equipped with current sensing capability.
shut down. The microprocessor will then assign the
                                                                                     or
“lead” to the system with the shortest average run time.
                                                                C U R R E N T F E E D B A C K
                                                             				
Option 8 – Condenser Fan Control Mode                        						O N E P E R U N I T
  					 F	 A	N	 	 C	O	N	T	R	O	L
                                                                                                                     7
  		 D	 I	 S	C	H	A	R	G	E		 P	R	E	S	S	U	R	E                 This mode should be selected when an optional 2ACE
                                                           Module is installed to allow combined current moni-
Condenser fans are controlled by discharge pressure        toring of all systems by sensing current on the incom-
only. This mode must be chosen.                            ing line.
                          or                                                         or
  		 			 F	 A	N 		 C	O	N	T	R	O	L                               C U R R E N T F E E D B A C K
                                                             			
  	A	M	B	 I	 E	N	T	 	& 		 D	S	C	H 		 P	R	E	S	S               				O N E P E R S Y S T E M
Do not select this option on R-410A chillers.              This mode should be selected when an optional 2ACE
                                                           module is installed to allow individual current moni-
                                                           toring of each system. SYS 1 input is to J7 of the I/O.
                                                           SYS 2 input is to J8 of the I/O.
Chiller auto restarts after a power failure.            Refrigerant type R-410A must be selected under Ser-
                                                        vice Mode. Refrigerant type is displayed under the
  P	 O	W	E	R		 F	A	 I	 L		 R	E	S	T	A	R	T
                                                        OPTIONS key, but is only programmable in Service
  							M	      A	N	  U	A	L
                                                        Mode.
                                                                     Incorrect programming may cause dam-
After a power failure, the UNIT switch must be tog-
                                                                     age to compressors.
gled before restart at the unit is allowed. NORMALLY
MANUAL RESTART should NOT BE SELECTED.
If the operating software is to be updated, insert the                  The options display message for Remote
Flash Card into the Flash Card input port. Turn off the                 Temp Reset Input only appears if the
unit switch and set the FLASH CARD UPDATE TO                            Temp Reset Option is enabled under Ser-
“ENABLED” using the ↑ and ↓ keys.                                       vice Mode. The option must be enabled
                                                                        under the Service Mode for the Remote
  F	L	A	S	H		C	A	R	D		U	P	D	A	T	E 					                                 Temperature Reset to operate.
  						E	   N	A	B	L	E	
                      D
Remote Temp Reset input selection is programmable          EXTERNAL EVAP PUMP should be selected if an ex-
according to the type of input utilized. The following     ternal pump is being controlled with the chiller pump
options are available:                                     contacts. The operation will be the same as YORK
                                                           HDRO KIT PUMPS = 1
  •	 DISABLED (default)
                                                           The following option should not be selected.
  •	 0.0 – 10.0 (DC)
                                                             					Y	 O	R	
                                                                        K		H	
                                                                            Y	D	
                                                                               R	O							
  •	 2.0 – 10.0 V (DC)
                                                             K	I	T		P	
                                                                     U	M	
                                                                        P	S										=	 2
  •	 0.0 – 20.0 mA
  •	 4.0 – 20.0 mA
Option 23 – Variable Water Outlet Mode                      To change the day, time, and date press the CLOCK
When the following option is selected, the variable wa-     key. The display will show something similar to the
                                                            following:
ter outlet mode is enabled.
                                                              	T	 O	 D	 A	 Y		 I	 S		 F	R	I		 0	8	 :	 5	1	A	M
   V A R I A B L E O U T L E T
  		                                      M O D E
                                                              						2	5		J	A	N		0	2
  						 E    	 N A B L E D
                                              Options Key
                                                                            Expansion Valve Type
                                          (press Options Key
                                                to adv.)                  (Thermoplastic or Electric)
                                                                          (Programmed under Service
                                          Display Language                    Mode, Viewable Only)
                                                                             Must be programmed
                                           System Switches                     for Thermostatic
                                                on/off
                                                                            Flash Card Update
                                          Chilled Liquid Type
                                           (water or glycol)
                                                                           Remote Temp Reset
                                            Ambient Control
                                                                              Pump Control
                                           (standard or low)
                                                                             Pump Selection
                                         Local/Remote Mode
                                           Display Units
                                         (English or Metric)
                                               Unit Type
                                      (”Chiller” MUST be Selected
                                        Via No Jumper Installed
                                             (Viewable Only)
                                            Refrigerant Type
                                            R-410A
                                   (Programmed under Service Mode)
                                           Viewable Only)
                                                                                                LD07405d
Figure 438 provides a quick reference list for the Unit key set points.
BACNET, MODBUS, N2, AND YORKTALK 2                               •	 RS-485: connect to TB2 - Network (-1) to TB2
COMMUNICATIONS                                                      (-1); Network (+1) to TB2 (+1)
Data can be read and in some cases modified using a              •	 RS-232: connect to TB3 - Network (RX) to TB3
serial communication BACnet, Modbus, or YorkTalk 2                  (TXD); Network (TX) to TB3 (RXD); Network
network connection. This information allows commu-                  (GND) to TB3 (GND)
nications of chiller operating parameters and external
                                                              See Figure 44 on page 158 for TB1, TB2 and TB3
control changes to set point, load limiting, and start/
                                                              locations.
stop commands.
                                                              In most cases, communication parameters will need to
BACnet and YorkTalk 2 RS485 networks are wired to
                                                              be modified. Table 30 on page 159 lists setup parame-
the + and - terminals of TB1 for port 1 communica-
                                                              ters for the available protocols. Modification is accom-
tions. Modbus network connection has the option of
                                                              plished by pressing the PROGRAM, DOWN ARROW,
RS232 or RS485 connection for port 2 communica-
                                                              DOWN ARROW, DOWN ARROW, DOWN ARROW,
tions. Modbus network is wired to either TB2 or TB3
                                                              and ENTER keys in sequence. The list below shows
as follows:
                                                              the displays for the values that may be modified:
                                                       P2 PROTOCOL
                    DE MODIFIER ADDRESS
                                                                     XXXXXXXXXX
                                      XXXXX
                                                       P2 MANUAL MAC
                    DE MODIFIER OFFSET
                                                          ADDRESS                XXX
                                          XX
                                                       P2 BAUD RATE
                    P1 PROTOCOL
                                                                             XXXXX
                                     XXXXXX
                                                       P2 PARITY
                    P1 MANUAL MAC
                                                                             XXXXX                                          7
                    ADDRESS              XXX
                                                       P2 STOP BITS
                    P1 BAUD RATE
                                                                                    X
                                      XXXXX
                                                       P2 HW SELECT BIT
                    P1 PARITY
                                                                             XXXXX
                                      XXXXX
                                            X          RESET 1 = YES, 0 = NO 0
                                                      Note: See Table 20 on page 160 for error descriptions
LD14318
1. As required by network. 2. Or other as required by network. 3. Number is multiplied by 100, set as required by network.
4. Number is added to de modifier address, set as required by network.
5. Unit operating software version C.Mmc.13.03 or later required for Modbus Protocol.
6. Unit operating software version 04 (C.MMC.13.04, C.MMC.14.04, or C.MMC.16.04) or higher required for N2 protocol functionality.
                                                                                                                                               7
BACnet and Modbus Communications                                        Analog Read Only Points
Chiller data that can be read and modified using spe-                   This data can be read using a BACnet or Modbus net-
cific BACnet or Modbus Register Addresses; and the                      work connection and can NOT be modified using this
data associated with the addresses, is outlined in the                  connection. The Modbus Register Address for these
following description:                                                  points is 513 + AI #.
JOHNSON CONTROLS
                                                                                                                                                                                                                                                                                                 ISSUE DATE: 10/24/2019
                      9
                      10
                     25 S2_SUCT_TEMP          AI15       528           03,04            x10           ADF 22            °F            °C        Sys 2 Suction Temperature (EEV)                    S
                     26 S2_RUN_TIME           AI16       529           03,04            x10           ADF 23           None          None       Sys 2 Run Time in seconds                          S
                     27 S2_SUCT_PR            AI17       530           03,04            x10           ADF 24            PSI          BAR        Sys 2 Suction Pressure                             S
                     28 S2_DSCH_PR            AI18       531           03,04            x10           ADF 25            PSI          BAR        Sys 2 Discharge Pressure                           S
                     29 S2_CIR_TEMP           AI19       532           03,04            x10           ADF 26            °F            °C        Sys 2 Cooler Inlet Refrigerant Temp (R-407c)       O
                     30 S2_DEF_TEMP           AI20       533           03,04            x10           ADF 27            °F            °C        Sys 2 Defrost Temperature (HP)                     O
                     31 S2_SUCT_SH            AI21       534           03,04            x10           ADF 28          °F (diff)     °C (diff)   Sys 2 Suction Superheat                            S
                     32 S2_AR_TIMER           AI22       535           03,04            x10           ADF 29           None          None       Sys 2 Anti-Recycle Timer                           S
                     33 S2_EEV_OUT            AI23       536           03,04            x10           ADF 30             %            %         Sys 2 EEV Output % (EEV)                           O
                     34 NUM_COMPS             AI24       537           03,04             x1           ADF 31           None          None       Number of Compressors                              S
161
                                                                                                                                                                                                                                                                                                      SECTION 7 – UNIT CONTROLS
                                                                                                    7
                    Item                     BACnet                                  Modbus
                                                       Modbus    Modbus Data Type                                     Engineering Units        Point List Code: S = Standard O = Optional N = Not Available
162
                     Ref    BACnet Name      Object                                 Scaling (See   N2 Metasys
                                                       Address      Supported
                    Num                     Instance                                   Note 5)                       Imperial        SI                        Point List Description             1 2 3 4 5 6 7 8 9 10
                      35   S1_OP_CODE         AI25       538          03,04              x1         ADF 32             None         None       Sys 1 Operational Code                             S
                      36   S1_FLT_CODE        AI26       539          03,04              x1         ADF 33             None         None       Sys 1 Fault Code                                   S
                      37   S2_OP_CODE         AI27       540          03,04              x1         ADF 34             None         None       Sys 2 Operational Code                             S
                      38   S2_FLT_CODE        AI28       541          03,04              x1         ADF 35             None         None       Sys 2 Fault Code                                   S
                      39   S1_DBG_CODE        AI29       542          03,04              x1         ADF 36             None         None       Sys 1 Debug Code                                   N
                      40   S1_FAN_STAGE       AI30       543          03,04              x1         ADF 37             None         None       Sys 1 Condenser Fan Stage                          S
                      41   S2_DBG_CODE        AI31       544          03,04              x1         ADF 38             None         None       Sys 2 Debug Code                                   N
                      42   S2_FAN_STAGE       AI32       545          03,04              x1         ADF 39             None         None       Sys 2 Condenser Fan Stage                          S
                                                                                                                                               Unit Control Mode [1=LW, 2=RW, 3=DA, 4=SP, 5=HC,
                     43    CONTROL_MODE       AI33       546          03,04              x1         ADF 40            None          None                                                          S
                                                                                                                                               6=HP]
                     44 AR_TIME               AI34       547          03,04              x1         ADF 41            None          None       Anti-Recycle Time Programmed                       S
                                                                                                                                                                                                                                                                                                             SECTION 7 – UNIT CONTROLS
                     45 LCHLT_CUT             AI35       548          03,04             x10         ADF 42             °F            °C        Leaving Chilled Liquid Temp Cutout                 S
                     46 LOW_AMB_CUT           AI36       549          03,04             x10         ADF 43             °F            °C        Low Ambient Temperature Cutout                     S
                     47 SUCT_P_CO_HT          AI37       550          03,04             x10         ADF 44             PSI          BAR        Low Suction Pressure Cutout Heating (HP)           O
                     48 L_SUCT_P_CO           AI38       551          03,04             x10         ADF 45             PSI          BAR        Low Suction Pressure Cutout Cooling                S
                     49 H_DSCH_P_CO           AI39       552          03,04             x10         ADF 46             PSI          BAR        High Discharge Pressure Cutout                     S
                     50 COOL_SETP             AI40       553          03,04             x10         ADF 47             °F            °C        Cooling Setpoint                                   S
                     51 SP_SETP_S1            AI41       554          03,04             x10         ADF 48             PSI          BAR        Sys 1 Cooling Setpoint (SP Unit)                   O
                     52 CONTROL_RG            AI42       555          03,04             x10         ADF 49             °F            °C        Cooling Range                                      S
                     53 SP_CTL_RG_S1          AI43       556          03,04             x10         ADF 50             PSI          BAR        Sys 1 Cooling Range (SP Unit)                      O
                     54 SP_SETP_S2            AI44       557          03,04             x10         ADF 51             PSI          BAR        Sys 2 Cooling Setpoint (SP Unit)                   O
                     55 HEAT_SETP             AI45       558          03,04             x10         ADF 52             °F            °C        Heating Setpoint (HP)                              O
                     56 SP_CTL_RG_S2          AI46       559          03,04             x10         ADF 53             PSI          BAR        Sys 2 Cooling Range (SP Unit)                      O
                     57 HEAT_RANGE            AI47       560          03,04             x10         ADF 54             °F            °C        Heating Range (HP)                                 O
                     58 S1_DSCH_TEMP          AI48       561          03,04             x10         ADF 55             °F            °C        Sys 1 Discharge Temperature (EEV)                  O
                     59 S1_DSCH_SH            AI49       562          03,04             x10         ADF 56           °F (diff)     °C (diff)   Sys 1 Discharge Superheat (EEV)                    O
                     60 S2_DSCH_TEMP          AI50       563          03,04             x10         ADF 57             °F            °C        Sys 2 Discharge Temperature (EEV)                  O
                     61 S2_DSCH_SH            AI51       564          03,04             x10         ADF 58           °F (diff)     °C (diff)   Sys 2 Discharge Superheat (EEV)                    O
                     62 LEAVING_HOT           AI52       565          03,04             x10         ADF 59             °F            °C        Leaving Liquid Hot Temp (R-410a)                   O
                     63 RETURN_HOT            AI53       566          03,04             x10         ADF 60             °F            °C        Return Liquid Hot Temp (R-410a)                    O
                     64 R_COOL_SETP           AI54       567          03,04             x10         ADF 61             °F            °C        Remote Setpoint                                    S
                     65 R_SP_SETP_S1          AI55       568          03,04             x10         ADF 62             PSI          BAR        Remote Setpoint 1 (SP Unit)                        O
                     66 R_SP_SETP_S2          AI56       569          03,04             x10         ADF 63             PSI          BAR        Remote Setpoint 2 (SP Unit)                        O
                     67 R_HEAT_SETP           AI57       570          03,04             x10         ADF 64             °F            °C        Remote Heating Setpoint (HP)                       O
                   BINARY READ ONLY POINTS
                     68 S1_ALARM              BI1       1282         01,02,03           N/A          BD4               0/1           0/1       Sys 1 Alarm [0=No Alarm, 1=Alarm]                  S
                     69 S2_ALARM              BI2       1283         01,02,03           N/A          BD5               0/1           0/1       Sys 2 Alarm [0=No Alarm, 1=Alarm]                  S
                     70 EVAP_HTR              BI3       1284         01,02,03           N/A          BD6               0/1           0/1       Evaporator Heater Status                           S
                     71 EVAP_PUMP             BI4       1285         01,02,03           N/A          BD7               0/1           0/1       Evaporator Pump                                    S
                     72 S1_C1_RUN             BI5       1286         01,02,03           N/A          BD8               0/1           0/1       Sys 1 Comp 1 Run                                   S
                     73 S2_C1_RUN             BI6       1287         01,02,03           N/A          BD9               0/1           0/1       Sys 2 Comp 1 Run                                   S
                     74 S1_LLSV               BI7       1288         01,02,03           N/A          BD10              0/1           0/1       Sys 1 Liquid Line Solenoid Valve                   S
                     75 S1_MODE_SV            BI8       1289         01,02,03           N/A          BD11              0/1           0/1       Sys 1 Mode Solenoid Valve (HP)                     O
                     76 S1_HGBV               BI9       1290         01,02,03           N/A          BD12              0/1           0/1       Sys 1 Hot Gas Bypass Valve                         O
                                                                                                                                               Bivalent Heat Source (YLAE HP)
                     77    S1_BHS             BI10      1291         01,02,03           N/A          BD13              0/1           0/1                                                          O
                                                                                                                                               Tray Heater (YLPA)
                     78    S1_C2_RUN          BI11      1292         01,02,03           N/A          BD14              0/1           0/1       Sys 1 Comp 2 Run                                   S
                     79    S2_C2_RUN          BI12      1293         01,02,03           N/A          BD15              0/1           0/1       Sys 2 Comp 2 Run                                   S
                     80    S2_LLSV            BI13      1294         01,02,03           N/A          BD16              0/1           0/1       Sys 2 Liquid Line Solenoid Valve                   S
                                                                                                                                                                                                                             TABLE 21 - NATIVE BACNET, MODBUS AND N2 COMMUNICATIONS DATA MAP (CONT’D)
                     81    S2_MODE_SV         BI14      1295         01,02,03           N/A          BD17              0/1           0/1       Sys 2 Mode Solenoid Valve (HP)                     O
                     82    LEAD_SYS           BI15      1296         01,02,03           N/A          BD18              0/1           0/1       Lead System [0=Sys 1, 1=Sys 2]                     S
                     83    S1_C3_RUN          BI16      1297         01,02,03           N/A          BD19              0/1           0/1       Sys 1 Comp 3 Run                                   S
JOHNSON CONTROLS
                                                                                                                                                                                                                                                                                                        ISSUE DATE: 10/24/2019
                                                                                                                                                                                                                                                                                                           FORM 150.72-ICOM6
                     Item                         BACnet                                                Modbus
                                                               Modbus         Modbus Data Type                                                Engineering Units        Point List Code: S = Standard O = Optional N = Not Available
                      Ref     BACnet Name         Object                                              Scaling (See       N2 Metasys
                                                               Address            Supported
                     Num                         Instance                                                Note 5)                            Imperial            SI                      Point List Description            1 2 3 4 5 6 7 8 9 10
                       84 S2_C3_RUN                 BI17         1298               01,02,03               N/A              BD20               0/1             0/1     Sys 2 Comp 3 Run                                   S
                       85 CH_LIQ_TYPE               BI18         1299               01,02,03               N/A              BD21               0/1             0/1     Chilled Liquid Type [0=Water, 1=Glycol]            S
                       86    Code Value
                          AMB_MODE                  BI19                            Code
                                                                 1300Operational 01,02,03                  N/A         Code   Value
                                                                                                                            BD22               0/1             0/1         Fault/Inhibit
                                                                                                                                                                       Ambient   Control Mode
                                                                                                                                                                                         Code[0=Std Amb, 1=Low Amb]       S
                       87         0
                          CNTL_MODE           No  Abnormal
                                                    BI20    Condition
                                                                 1301               01,02,03               N/A               0
                                                                                                                            BD23         No  Fault
                                                                                                                                               0/1 Code        0/1     Local Remote Control Mode [0=Manual, 1=Auto]       S
                       88         1
                          DATA_UNIT           Unit Switch
                                                    BI21  OFF    1302               01,02,03               N/A               1
                                                                                                                            BD24         115  VAC
                                                                                                                                               0/1  Under   Voltage
                                                                                                                                                               0/1     Display Units [0=Imperial, 1=SI]                   S
                       89 AUTO_LL 2           System   Switch
                                                    BI22      OFF1303               01,02,03               N/A               2
                                                                                                                            BD25         Low  Ambient
                                                                                                                                               0/1      Temperature
                                                                                                                                                               0/1     Lead Lag Control Mode [0=Manual, 1=Auto]           S
                                                                                                                                                                                                                                                                                                                                FORM 150.72-ICOM6
                       90 S2_HGBV 3           Lockout
                                                    BI23         1304               01,02,03               N/A               3
                                                                                                                            BD26               0/1             0/1     Sys 2 Hot Gas Bypass Valve                         O
JOHNSON CONTROLS
                                  4           Unit Fault                                                                     4           Low Leaving Chilled Liquid Temperature
                                                                                                                                                                                                                                                                                                                                ISSUE DATE: 10/24/2019
                         24       47                                                                               24       47 Sensor Fault
                         25       48                                                                               25       48 Discharge Inhibit
                         26       49                                                                               26       49 MP/HPCO Inhibit
                         27       50                                                                               27       50 Pump Trip
                         28                                                                                        28          Pump Fail Make Flow
                         29                                                                                        29     Property
                                                                                                                               HighofAmbient    Controls, Inc.
                                                                                                                                       JohnsonTemperature
                    SCROLL
                         30Native Comms 16 AUG 2017                                                                30      Subject
                                                                                                                               Anti-Vacuum    without
                                                                                                                                   to change Low    Pressure
                                                                                                                                                       notice.Cutout                                                                        3 of 4
                         31                                                                                        31
                         32                                                                                        32
                                                                                                                         Property of Johnson Controls, Inc.
                         33                                                                                        33
                   SCROLL Native Comms 16 AUG 2017                                                                        Subject to change without notice.                                                                                4 of 4
                         34                                                                                        34
163
                                                                                                                                                                                                                                                                                                                                     SECTION 7 – UNIT CONTROLS
                         35                                                                                        35
                         36                                                                                        36
                         37                                                                                        37
                         38                                                                                        38
                                                                                                                 7
                         39                                                                                        39
                                                                                                 FORM 150.72-ICOM6
SECTION 7 – UNIT CONTROLS
                                                                                              ISSUE DATE: 10/24/2019
JOHNSON CONTROLS
                                                                                                                                                                                                                                                                         ISSUE DATE: 10/24/2019
                      6
                      7
                      8
                      9
                      10
SECTION 1
165
                                                                                                                                                                                                                1 of 6
                                                                                                                                                                                                                                                                              SECTION 7 – UNIT CONTROLS
166
                    Eng BACnet                                                                                           Engineering
                                 BACnet Object        LON Profile                         N2          Modbus                             Point List Code: S = Standard O = Optional N = Not Available
                    Page Object                                     LON SNVT Type                                           Units
                                     Name               Name                            Metasys
                     Ref Typ/Ins                                                                  Address    Scale    Imperial     SI                    Point List Description            1   2   3   4 5 6 7 8 9 10
                     P27  AV21 YT2_ S01_ P27         nvoYTS01p027   SNVT_count_f (51)   ADF 21     0025        x1       None     None      Sys 2 Run Time in seconds                       S   S   S   S
                     P28  AV22 YT2_ S01_ P28         nvoYTS01p028   SNVT_count_f (51)   ADF 22     0026       x10        PSI     BAR       Sys 2 Suction Pressure                          S   S   S   S
                     P29  AV23 YT2_ S01_ P29         nvoYTS01p029   SNVT_count_f (51)   ADF 23     0027       x10        PSI     BAR       Sys 2 Discharge Pressure                        S   S   S   S
                                 YT2_ S01_ P30                                                                                             Sys 2 Suction Temperature (Cond Unit)
                     P30  AV24                       nvoYTS01p030   SNVT_count_f (51)                                    °F        °C                                                      O O O O
                                                                                        ADF 24     0028       x10                          Sys 2 Cooler Inlet Refrigerant Temp (R-407c)
                    P31     AV25     YT2_ S01_ P31   nvoYTS01p031   SNVT_count_f (51)   ADF 25     0029       x10        °F        °C      Sys 2 Defrost Temperature (HP)                  O   O   O   O
                    P32     AV26     YT2_ S01_ P32   nvoYTS01p032   SNVT_count_f (51)   ADF 26     0030       x10      °F (diff) °C (diff) Sys 2 Suction Superheat (EEV)                   O   O   O   O
                    P33     AV27     YT2_ S01_ P33   nvoYTS01p033   SNVT_count_f (51)   ADF 27     0031        x1       None      None Sys 2 Anti-Recycle Timer in seconds                 S   S   S   S
                                                                                                                                                                                                                                                                                        SECTION 7 – UNIT CONTROLS
                    P34     AV28     YT2_ S01_ P34   nvoYTS01p034   SNVT_count_f (51)   ADF 28     0032       x10         %         %      Sys 2 EEV Output % (EEV)                        O   O   O   O
                    P35     AV29     YT2_ S01_ P35   nvoYTS01p035   SNVT_count_f (51)   ADF 29     0033        x1       None      None Number of Compressors                               S   S   S   S
                    P36     BV5      YT2_ S01_ P36   nvoYTS01p036   SNVT_switch (95)     BD 5      0065       N/A        0/1       0/1     Sys 1 Alarm [0=No Alarm, 1=Alarm]               S   S   S   S
                    P37     BV6      YT2_ S01_ P37   nvoYTS01p037   SNVT_switch (95)     BD 6      0066       N/A        0/1       0/1     Sys 2 Alarm [0=No Alarm, 1=Alarm]               S   S   S   S
                    P38     BV7      YT2_ S01_ P38   nvoYTS01p038   SNVT_switch (95)     BD 7      0067       N/A        0/1       0/1     Evaporator Heater Status                        S   S   S   S
                    P39     BV8      YT2_ S01_ P39   nvoYTS01p039   SNVT_switch (95)     BD 8      0068       N/A        0/1       0/1     Evaporator Pump Status                          S   S   S   S
                    P40     BV9      YT2_ S01_ P40   nvoYTS01p040   SNVT_switch (95)     BD 9      0069       N/A        0/1       0/1     Sys 1 Comp 1 Run                                S   S   S   S
                    P41     BV10     YT2_ S01_ P41   nvoYTS01p041   SNVT_switch (95)    BD 10      0070       N/A        0/1       0/1     Sys 2 Comp 1 Run                                S   S   S   S
                                     YT2_ S01_ P42                                                                                         Sys 1 Liquid Line Solenoid Valve
                    P42     BV11                     nvoYTS01p042   SNVT_switch (95)                                     0/1       0/1                                                     S S S S
                                                                                         BD 11     0071       N/A                          Sys 1 Mode Solenoid Valve (HP)
                                     YT2_ S01_ P43                                                                                         Sys 1 Hot Gas Bypass Valve
                    P43     BV12                     nvoYTS01p043   SNVT_switch (95)                                     0/1       0/1     Bivalent Heat Source (YLAE HP)                  S S S S
                                                                                         BD 12     0072       N/A                          Tray Heater (YLPA HP)
                    P44     BV13     YT2_ S01_ P44   nvoYTS01p044   SNVT_switch (95)     BD 13     0073       N/A        0/1       0/1     Sys 1 Comp 2 Run                                S S S S
                    P45     BV14     YT2_ S01_ P45   nvoYTS01p045   SNVT_switch (95)     BD 14     0074       N/A        0/1       0/1     Sys 2 Comp 2 Run                                S S S S
                                     YT2_ S01_ P46                                                                                         Sys 2 Liquid Line Solenoid Valve
                    P46     BV15                     nvoYTS01p046   SNVT_switch (95)                                     0/1       0/1                                                     S S S S
                                                                                         BD 15     0075       N/A                          Sys 2 Mode Solenoid Valve (HP)
                    P47     BV16     YT2_ S01_ P47   nvoYTS01p047   SNVT_switch (95)     BD 16     0076       N/A        0/1       0/1     Lead System [0=Sys1, 1=Sys2]                    S   S   S   S
                    P48     BV17     YT2_ S01_ P48   nvoYTS01p048   SNVT_switch (95)     BD 17     0077       N/A        0/1       0/1     Sys 1 Comp 3 Run                                S   S   S   S
                    P49     BV18     YT2_ S01_ P49   nvoYTS01p049   SNVT_switch (95)     BD 18     0078       N/A        0/1       0/1     Sys 2 Comp 3 Run                                S   S   S   S
                    P50     BV19     YT2_ S01_ P50   nvoYTS01p050   SNVT_switch (95)     BD 19     0079       N/A        0/1       0/1     Chilled Liquid Type [0=Water, 1=Glycol]         S   S   S   S
                    P51     BV20     YT2_ S01_ P51   nvoYTS01p051   SNVT_switch (95)     BD 20     0080       N/A        0/1       0/1     Ambient Control Mode [0=Std Amb, 1=Low Amb]     S   S   S   S
                    P52     BV21     YT2_ S01_ P52   nvoYTS01p052   SNVT_switch (95)     BD 21     0081       N/A        0/1       0/1     Local/Remote Control Mode [0=Local, 1=Remote]   S   S   S   S
                                                                                                                                                                                                                          TABLE 22 - YORKTALK 2 COMMUNICATIONS DATA MAP (CONT’D)
                    P53     BV22     YT2_ S01_ P53   nvoYTS01p053   SNVT_switch (95)     BD 22     0082       N/A        0/1       0/1     Units [0=Imperial, 1=SI]                        S   S   S   S
                    P54     BV23     YT2_ S01_ P54   nvoYTS01p054   SNVT_switch (95)     BD 23     0083       N/A        0/1       0/1     Lead/Lag Control Mode [0=Manual, 1=Auto]        S   S   S   S
                    P55     BV24     YT2_ S01_ P55   nvoYTS01p055   SNVT_switch (95)     BD 24     0084       N/A        0/1       0/1     Sys 2 Hot Gas Bypass Valve                      O   O   O   O
                    P56     MV1      YT2_ S01_ P56   nvoYTS01p056   SNVT_count_f (51)    ADI 1     0030       x1        None      None Sys 1 Operational Code                              S   S   S   S
                    P57     MV2      YT2_ S01_ P57   nvoYTS01p057   SNVT_count_f (51)    ADI 2     0031       x1        None      None Sys 1 Fault Code                                    S   S   S   S
                    P58     MV3      YT2_ S01_ P58   nvoYTS01p058   SNVT_count_f (51)    ADI 3     0032       x1        None      None Sys 2 Operational Code                              S   S   S   S
                    P59     MV4      YT2_ S01_ P59   nvoYTS01p059   SNVT_count_f (51)    ADI 4     0033       x1        None      None Sys 2 Fault Code                                    S   S   S   S
                    P60     MV5      YT2_ S01_ P60   nvoYTS01p060   SNVT_count_f (51)    ADI 5     0034       x1        None      None Sys 1 Debug Code                                    N   N   N   N
                    P61     MV6      YT2_ S01_ P61   nvoYTS01p061   SNVT_count_f (51)    ADI 6     0035       x1        None      None Sys 1 Condenser Fan Stage                           S   S   S   S
                    P62     MV7      YT2_ S01_ P62   nvoYTS01p062   SNVT_count_f (51)    ADI 7     0036       x1        None      None Sys 2 Debug Code                                    N   N   N   N
                    P63     MV8      YT2_ S01_ P63   nvoYTS01p063   SNVT_count_f (51)    ADI 8     0037       x1        None      None Sys 2 Condenser Fan Stage                           S   S   S   S
                    P64     MV9      YT2_ S01_ P64   nvoYTS01p064   SNVT_count_f (51)    ADI 9     0038                                                                                    N   N   N   N
                                     YT2_ S01_ P65                                                                                       Unit Control Mode [0=LW, 1=RW, 2=DA, 3=SP,
                    P65     MV10                     nvoYTS01p065   SNVT_count_f (51)                                   None     None                                                      S S S S
                                                                                        ADI 10     0039        x1                        4=CL, 5=HT]
                    P66     AV30     YT2_ S01_ P66   nvoYTS01p066   SNVT_count_f (51)   ADF 30     0040        x1       None     None    Anti-Recycle Time Programmed                      S   S   S   S
                    P67     AV31     YT2_ S01_ P67   nvoYTS01p067   SNVT_count_f (51)   ADF 31     0041       x10        °F       °C     Leaving Chilled Liquid Temp Cutout                S   S   S   S
                    P68     AV32     YT2_ S01_ P68   nvoYTS01p068   SNVT_count_f (51)   ADF 32     0042       x10        °F       °C     Low Ambient Temp Cutout                           S   S   S   S
                    P69     AV33     YT2_ S01_ P69   nvoYTS01p069   SNVT_count_f (51)   ADF 33     0043       x10        PSI     BAR     Low Suction Pressure Cutout Heating (HP)          S   S   S   S
JOHNSON CONTROLS
                                                                                                                                                                                                                                                                                   ISSUE DATE: 10/24/2019
                                                                                                                                                                                                                                                                                      FORM 150.72-ICOM6
                                                                                                                                                                                                            04/17/2018
                    Eng BACnet                                                                                           Engineering
                                 BACnet Object        LON Profile                         N2          Modbus                                 Point List Code: S = Standard O = Optional N = Not Available
                    Page Object                                     LON SNVT Type                                           Units
                                     Name               Name                            Metasys
                     Ref Typ/Ins                                                                  Address    Scale    Imperial      SI                   Point List Description            1   2   3   4 5 6 7 8 9 10
                     P70  AV34 YT2_ S01_ P70         nvoYTS01p070   SNVT_count_f (51)   ADF 34     0044       x10        PSI      BAR        Low Suction Pressure Cutout Cooling           S   S   S   S
                     P71  AV35 YT2_ S01_ P71         nvoYTS01p071   SNVT_count_f (51)   ADF 35     0045       x10        PSI      BAR        High Discharge Pressure Cutout                S   S   S   S
                     P72  AV36 YT2_ S01_ P72         nvoYTS01p072   SNVT_count_f (51)   ADF 36     0046       x10        °F        °C        Remote Setpoint                               S   S   S   S
                                                                                                                                                                                                                                                                                      FORM 150.72-ICOM6
P73 AV37 YT2_ S01_ P73 nvoYTS01p073 SNVT_count_f (51) ADF 37 0047 x10 °F °C Cooling Range S S S S
JOHNSON CONTROLS
                                 YT2_ S01_ P74                                                                           PSI      BAR        Remote Setpoint 2 (SP)
                                                                                                                                                                                                                                                                                      ISSUE DATE: 10/24/2019
167
                                                                                                                                                                                                                                                                                           SECTION 7 – UNIT CONTROLS
168
                                                                                                         SECTION 2
                     P31 AV129 YT2_ S02_ P31     nvoYTS02p031   SNVT_count_f (51)   ADF 68     0125                                                                               N   N   N   N
                     P32 AV130 YT2_ S02_ P32     nvoYTS02p032   SNVT_count_f (51)   ADF 69     0126                                                                               N   N   N   N
                     P33 AV131 YT2_ S02_ P33     nvoYTS02p033   SNVT_count_f (51)   ADF 70     0127                                                                               N   N   N   N
                     P34 AV132 YT2_ S02_ P34     nvoYTS02p034   SNVT_count_f (51)   ADF 71     0128                                                                               N   N   N   N
                     P35 AV133 YT2_ S02_ P35     nvoYTS02p035   SNVT_count_f (51)   ADF 72     0129                                                                               N   N   N   N
                     P36 BV105 YT2_ S02_ P36     nvoYTS02p036   SNVT_switch (95)    BD 34      0165       N/A        0/1      0/1    Option Indicator [0=Disabled, 1=Enabled]     N   S   S   S
                     P37 BV106 YT2_ S02_ P37     nvoYTS02p037   SNVT_switch (95)    BD 35      0166                                                                               N   N   N   N
                     P38 BV107 YT2_ S02_ P38     nvoYTS02p038   SNVT_switch (95)    BD 36      0167                                                                               N   N   N   N
                     P39 BV108 YT2_ S02_ P39     nvoYTS02p039   SNVT_switch (95)    BD 37      0168                                                                               N   N   N   N
                     P40 BV109 YT2_ S02_ P40     nvoYTS02p040   SNVT_switch (95)    BD 38      0169                                                                               N   N   N   N
                     P41 BV110 YT2_ S02_ P41     nvoYTS02p041   SNVT_switch (95)    BD 39      0170                                                                               N   N   N   N
                     P42 BV111 YT2_ S02_ P42     nvoYTS02p042   SNVT_switch (95)    BD 40      0171                                                                               N   N   N   N
                     P43 BV112 YT2_ S02_ P43     nvoYTS02p043   SNVT_switch (95)    BD 41      0172                                                                               N   N   N   N
                     P44 BV113 YT2_ S02_ P44     nvoYTS02p044   SNVT_switch (95)    BD 42      0173                                                                               N   N   N   N
                     P45 BV114 YT2_ S02_ P45     nvoYTS02p045   SNVT_switch (95)    BD 43      0174                                                                               N   N   N   N
                     P46 BV115 YT2_ S02_ P46     nvoYTS02p046   SNVT_switch (95)    BD 44      0175                                                                               N   N   N   N
                     P47 BV116 YT2_ S02_ P47     nvoYTS02p047   SNVT_switch (95)    BD 45      0176       N/A        0/1      0/1    Expansion Valve Type [0=TXV, 1=EEV]          N   S   S   S
JOHNSON CONTROLS
                                                                                                                                                                                                                                                                             ISSUE DATE: 10/24/2019
                                                                                                                                                                                                                                                                                FORM 150.72-ICOM6
P51 BV120 YT2_ S02_ P51 nvoYTS02p051 SNVT_switch (95) BD 49 0180 N/A 0/1 0/1 SCC Auto Detect Digit 2 N S S S
JOHNSON CONTROLS
                     P52 BV121 YT2_ S02_ P52            nvoYTS02p052      SNVT_switch (95)      BD 50       0181        N/A       0/1       0/1    SCC Auto Detect Digit 3                            N   S   S   S
                                                                                                                                                                                                                                                                                                    ISSUE DATE: 10/24/2019
                     P53 BV122 YT2_ S02_ P53            nvoYTS02p053      SNVT_switch (95)      BD 51       0182        N/A       0/1       0/1    SCC Auto Detect Digit 4                            N   S   S   S
                     P54 BV123 YT2_ S02_ P54            nvoYTS02p054      SNVT_switch (95)      BD 52       0183        N/A       0/1       0/1    SCC Auto Detect Digit 5                            N   S   S   S
                     P55 BV124 YT2_ S02_ P55            nvoYTS02p055      SNVT_switch (95)      BD 53       0184        N/A       0/1       0/1    SCC Auto Detect Digit 6                            N   S   S   S
                     P56 MV101 YT2_ S02_ P56            nvoYTS02p056      SNVT_count_f (51)     ADI 25      0130        x1       None      None    Refrigerant [0=R-22, 1=R-407c, 2=R-410a]           N   S   S   S
                     P57 MV102 YT2_ S02_ P57            nvoYTS02p057      SNVT_count_f (51)     ADI 26      0131                                                                                      N   N   N   N
                     P58 MV103 YT2_ S02_ P58            nvoYTS02p058      SNVT_count_f (51)     ADI 27      0132                                                                                      N   N   N   N
                     P59 MV104 YT2_ S02_ P59            nvoYTS02p059      SNVT_count_f (51)     ADI 28      0133                                                                                      N   N   N   N
                     P60 MV105 YT2_ S02_ P60            nvoYTS02p060      SNVT_count_f (51)     ADI 29      0134                                                                                      N   N   N   N
                     P61 MV106 YT2_ S02_ P61            nvoYTS02p061      SNVT_count_f (51)     ADI 30      0135                                                                                      N   N   N   N
                     P62 MV107 YT2_ S02_ P62            nvoYTS02p062      SNVT_count_f (51)     ADI 31      0136                                                                                      N   N   N   N
                     P63 MV108 YT2_ S02_ P63            nvoYTS02p063      SNVT_count_f (51)     ADI 32      0137                                                                                      N   N   N   N
                     P64 MV109 YT2_ S02_ P64            nvoYTS02p064      SNVT_count_f (51)     ADI 33      0138                                                                                      N   N   N   N
                     P65 MV110 YT2_ S02_ P65            nvoYTS02p065      SNVT_count_f (51)     ADI 34      0139                                                                                      N   N   N   N
                     P66 AV130 YT2_ S02_ P66            nvoYTS02p066      SNVT_count_f (51)     ADF 73      0140                                                                                      N   N   N   N
                     P67 AV131 YT2_ S02_ P67            nvoYTS02p067      SNVT_count_f (51)     ADF 74      0141                                                                                      N   N   N   N
                     P68 AV132 YT2_ S02_ P68            nvoYTS02p068      SNVT_count_f (51)     ADF 75      0142                                                                                      N   N   N   N
                     P69 AV133 YT2_ S02_ P69            nvoYTS02p069      SNVT_count_f (51)     ADF 76      0143                                                                                      N   N   N   N
                     P70 AV134 YT2_ S02_ P70            nvoYTS02p070      SNVT_count_f (51)     ADF 77      0144                                                                                      N   N   N   N
                     P71 AV135 YT2_ S02_ P71            nvoYTS02p071      SNVT_count_f (51)     ADF 78      0145                                                                                      N   N   N   N
                     P72 AV136 YT2_ S02_ P72            nvoYTS02p072      SNVT_count_f (51)     ADF 79      0146                                                                                      N   N   N   N
                     P73 AV137 YT2_ S02_ P73            nvoYTS02p073      SNVT_count_f (51)     ADF 80      0147                                                                                      N   N   N   N
                     P74 AV138 YT2_ S02_ P74            nvoYTS02p074      SNVT_count_f (51)     ADF 81      0148                                                                                      N   N   N   N
                     P75 AV139 YT2_ S02_ P75            nvoYTS02p075      SNVT_count_f (51)     ADF 82      0149                                                                                      N   N   N   N
                     P76 AV140 YT2_ S02_ P76            nvoYTS02p076      SNVT_count_f (51)     ADF 83      0150                                                                                      N   N   N   N
                     P77 AV141 YT2_ S02_ P77            nvoYTS02p077      SNVT_count_f (51)     ADF 84      0151                                                                                      N   N   N   N
                     P78 AV142 YT2_ S02_ P78            nvoYTS02p078      SNVT_count_f (51)     ADF 85      0152                                                                                      N   N   N   N
                                                                                                                                                                                                                                           TABLE 22 - YORKTALK 2 COMMUNICATIONS DATA MAP (CONT’D)
                     P79 AV143 YT2_ S02_ P79            nvoYTS02p079      SNVT_count_f (51)     ADF 86      0153                                                                                      N   N   N   N
                     P80 BV125 YT2_ S02_ P80            nvoYTS02p080      SNVT_switch (95)      BD 54       0185                                                                                      N   N   N   N
                     P81 BV126 YT2_ S02_ P81            nvoYTS02p081      SNVT_switch (95)      BD 55       0186                                                                                      N   N   N   N
                     P82 BV127 YT2_ S02_ P82            nvoYTS02p082      SNVT_switch (95)      BD 56       0187                                                                                      N   N   N   N
                     P83 BV128 YT2_ S02_ P83            nvoYTS02p083      SNVT_switch (95)      BD 57       0188                                                                                      N   N   N   N
                     P84 BV129 YT2_ S02_ P84            nvoYTS02p084      SNVT_switch (95)      BD 58       0189        N/A       0/1       0/1    Units [0=Imperial, 1=Metric]                       N   S   S   S
                   NOTES
                     1   LON SNVTs used: SNVT_count_f (51) and SNVT_switch (95). Must use LON eLink.
                         Modbus scaling factors indicated in bold with an asterisk (*) are user configurable by a field technician, if necessary. All Modbus values are of the type SIGNED with the exception of the user configurable
                     2
                         values that are all UNSIGNED. Modbus function types supported: ENG P03-P06 = Types 03, 06, 16; ENG P07-P10 = 01, 03, 05, 06, 15, 16; ENG P36-P55 & P80-84 = 01, 02, 03
                     3   BACnet engineering units shown with an Asterisk (*) will be assigned a BACnet engineering unit type of 95 - No Units.
                         Status codes: Special display characters such as ( ) [ ] { } / \ % < > are not compatible with eLink N2 formats. Substitute text strings "-", PCT, GTN will be used. String lengths are limited to 60 total
                     4
                         characters, including spaces.
                     5
                     6
                     7
                     8
                     9
                     10
169
                                                                                                                     Subject to change without notice.
                                                                                                                                                                                                                                                                                                         SECTION 7 – UNIT CONTROLS
                                                                                                             7
170
                                                                                                                                            04/17/2018
                            Code                                                 Code
                                                              Operational Code                                         Fault/Inhibit Code
                            Value                                                Value
                              0      No Abnormal Condition                         0     No Fault Code
                              1      Unit Switch Off                               1
                              2      System Switch Off                             2     Low Ambient Temperature
                              3      Lockout                                       3
                              4      Unit Fault                                    4     Low Leaving Chilled Liquid Temp
                              5      System Fault                                  5     High Discharge Pressure
                              6      Remote Shutdown                               6
                              7      Daily Schedule Shutdown                       7     Low Suction Pressure
                                                                                                                                                                                                                         SECTION 7 – UNIT CONTROLS
                              8      No Run Permissive                             8
                              9      No Cool Load                                  9
                             10      Anti-Coincidence Timer Active                10
                             11      Anti-Recycle Timer Active                    11
                             12      Manual Override                              12
                             13      Suction Limiting                             13
                             14      Discharge Limiting                           14
                             15                                                   15
                             16      Load Limiting                                16
                             17      Compressor(s) Running                        17
                             18      Heatpump Load Limiting                       18     MP/HPCO Fault
                             19                                                   19     Low Evaporator Temperature
                             20                                                   20
                             21                                                   21
                             22                                                   22     Unit Motor Current
                             23                                                   23     Low Superheat
                             24                                                   24     Sensor Fault
                             25                                                   25     Discharge Inhibit
                             26                                                   26     MP/HPCO Inhibit
                             27                                                   27     Pump Trip
                             28                                                   28     Pump Fail Make Flow
                             29                                                   29     High Ambient Temperature
                             30                                                   30     Anti-Vacuum Low Pressure Cutout
                             31                                                   31
                                                                                                                                                           TABLE 22 - YORKTALK 2 COMMUNICATIONS DATA MAP (CONT’D)
                             32                                                   32
                             33                                                   33
                             34                                                   34
                             35                                                   35
                             36                                                   36
                             37                                                   37
                             38                                                   38
                             39                                                   39
                             40                                                   40
                             41                                                   41
                             42                                                   42
                             43                                                   43
                             44                                                   44
                             45                                                   45
                             46                                                   46
                             47                                                   47
                             48                                                   48
                             49                                                   49
                             50                                                   50
JOHNSON CONTROLS
                                                                                                                                                                                                                    ISSUE DATE: 10/24/2019
                                                                                                                                                                                                                       FORM 150.72-ICOM6
FORM 150.72-ICOM6
ISSUE DATE: 10/24/2019
SUCTION PRESSURE LIMIT CONTROLS                                    If after 60 seconds of run-time the leaving chilled liq-
                                                                   uid temperature is still above the Set Point High Limit,
The anticipatory controls are intended to prevent the
                                                                   the next compressor in sequence will be energized.
unit from ever actually reaching a low-pressure cut-
                                                                   Additional compressors will be energized at a rate of
out. Loading is prevented, if the suction pressure drops
                                                                   once every 60 seconds if the chilled liquid temperature
below 1.15 x suction pressure cutout (15% below the
                                                                   remains above the Set Point High Limit and the chilled
cutout). Loading may reoccur after suction pressure
                                                                   liquid temperature is dropping less than 3 °F/min. The
rises above the unload point and a period of one min-
                                                                   lag system will not be allowed to start a compressor
ute elapses. This control is only operable if the optional
                                                                   until the lead system has run for 5 minutes.
suction pressure transducers are installed.
                                                                   If the chilled liquid temperature falls below the Set
DISCHARGE PRESSURE LIMIT CONTROLS                                  Point High Limit but is greater than the Set Point Low
                                                                   Limit, loading and unloading do not occur. This area of
The discharge pressure limit controls unload a system
                                                                   control is called the control range.
before it reaches a safety limit due to high load or dirty
condenser coils. The microprocessor monitors dis-                  If the chilled liquid temperature drops to between Set
charge pressure and unloads a system, if fully loaded,             Point Low Limit and 0.5°F (0.28°C) below the Set
by one compressor when discharge pressure exceeds                  Point Low Limit, unloading (a compressor turns OFF)
the programmed cutout minus 10 psig (0.69 barg). Re-               occurs at a rate of 1 every 30 seconds. If the chilled
loading will occur when the discharge pressure on the              liquid temperature falls to a value greater than 0.5°F
affected system drops to 85% of the unload pressure                (0.28°C) below the Set Point Low Limit but not greater
and 10 minutes have elapsed.                                       than 1.5°F (0.83°C) below the Set Point Low Limit,
This control is only applicable if optional discharge              unloading occurs at a rate of 20 seconds. If the chilled
pressure transducers are installed.                                liquid temperature falls to a value greater than 1.5°F
                                                                   (0.83°C) below the Set Point Low Limit, unloading oc-
LEAVING CHILLED LIQUID CONTROL                                     curs at a rate of 10 seconds. If the chilled liquid tem-
                                                                   perature falls below 1°F above the low chilled liquid
The set point, when programmed for Leaving Chilled                 temperature cutout, unloading occurs at a rate of 10
Liquid Control, is the temperature the unit will control           seconds if it is greater than 10 seconds.
to within plus or minus the (control) cooling range. The
Set Point High Limit is the Set Point plus the Cooling             In water cooling mode on R-410A chillers, the mini-
Range. The Set Point Low Limit is the Set Point minus              mum low limit of the control range will be 40.0ºF. For
the Cooling Range. Figure 30 below should be used to               leaving chilled liquid temperature set point and control
aid in understanding the following description of Leav-            range combinations that result in the low limit of the
ing Chilled Liquid Control.                                        control range being below 40.0ºF, the low limit will be
                                                                   reset to 40.0ºF and the difference will be added to the
        30 sec.          Contol Range            60 sec.           high limit. This will result in a control range the same
      unloading     (no compressor staging)      loading           size as programmed but not allow the unit to run below
                                                                   40.0ºF. This control will not affect glycol chillers.
 LWT                                                               Hot gas, if present, will be the final step of capacity. Hot
             44.0 ºF        46.0 ºF          48.0 ºF
             (6.7 ºC)       (7.8 ºC)         (8.9 ºC)
                                                                   gas is energized when only a single compressor is run-
            Low Limit       Setpoint        High Limit             ning and LWT is less than SP. Hot gas is turned OFF
                                                                   as temperature rises when LWT is more than SP plus
      Leaving Water Temp. Control - Compressor Staging
      Setpoint = 46.0 ºF (7.8 ºC) Range = +/-2 ºF (1.1 ºC)         CR/2. If temperature remains below the set point low
                                                         LD14404   limit on the lowest step of capacity, the microprocessor
Figure 45 - LEAVING WATER TEMPERATURE                             will close the liquid line solenoid, after turning off hot
             CONTROL EXAMPLE                                       gas, and pump the system down before turning off the
                                                                   last compressor in a system.
If the leaving chilled liquid temperature is above the             The leaving chilled liquid set point is programmable
Set Point High Limit, the lead compressor on the lead              from 40°F to 70°F (4.4°C to 21.1°C) in water chilling
system will be energized along with the liquid line so-            mode and from 10°F to 70°F (-12.2°C to 21.1°C) in
lenoid. Upon energizing any compressor, the 60 sec-                glycol chilling mode. In both modes, the cooling range
ond Anti-Coincidence timer will be initiated to prevent            can be from plus or minus1.5°F to plus or minus 2.5°F
multiple compressors from turning ON.                              (plus or minus 0.83°C to 1.39°C).leaving chilled liquid
                                                                   control.
172                                                                                                      JOHNSON CONTROLS
FORM 150.72-ICOM6
                                                                                                                             SECTION 8 – UNIT OPERATION
ISSUE DATE: 10/24/2019
*Unloading only
NOTES:
1. Step 1 is Hot Gas Bypass and is skipped when loading occurs. Hot Gas Bypass operation is inhibited during Pumpdown.
2. Step 3 is skipped when loading occurs.
3. Step 4 is skipped when unloading occurs.
* STEP can be viewed using the OPER DATA key and scrolling to COOLING DEMAND.
As an example of compressor staging (See Table 24           sor run time for the purpose of lubrication. It will also
on page 173), a chiller with six compressors using a        prevent the same compressor from starting 2 times in
Cooling Set Point programmed for 45°F (7.20°C) and a        a row. The microprocessor will not attempt to equalize
Range Set Point of 10°F (5.56°C). Using the formulas        run time on individual compressors within a system.
in Table 24 on page 173, the control range will be          Each compressor in a system will be assigned an ar-
split up into six (seven including hot gas) segments,       bitrary number 1, or 2. The non-running compressor
with the Control Range determining the separation be-       within a system with the lowest priority number will
tween segments. Note also that the Cooling Set Point is     always be the next compressor to start. The running
the point at which all compressors are OFF, and Cool-       compressor with priority number 1 will always be the
ing Set Point plus Range is the point all compressors       next compressor to shut OFF. Whenever a compressor
are ON. Specifically, if the return water temperature is    is shut OFF, the priority numbers of all compressors
55°F (12.8°C), then all compressors will be ON, pro-        in each system will be decreased by 1 with the wrap
viding full capacity. At nominal gpm, this would pro-       around. This control scheme assures the same com-
vide approximately 45°F (7.2°C) leaving water tem-          pressor does not repeatedly cycle ON and OFF.
perature out of the evaporator.
                                                            ANTI-RECYCLE TIMER
If the return water temperature drops to 53.4°F (11.9°C),
one compressor would cycle OFF leaving five com-            The programmable anti-recycle timer assures that sys-
pressors running. The compressors would continue to         tems do not cycle. This timer is programmable under
cycle OFF approximately every 1.7°F (0.94°C), with          the PROGRAM key between 300 and 600 seconds.
the exception of hot gas bypass. Notice that the hot gas    Whenever possible, to reduce cycling and motor heat-
bypass would cycle ON when the return water tem-            ing, the anti-recycle timer should be adjusted to 600
perature dropped to 46.25°F (7.9°C). At this point one      seconds. The programmable anti-recycle timer starts
compressor would be running with hot gas.                   the timer when the first compressor in a system starts.
                                                            The timer begins to count down. If all of the compres-
Should the return water temperature rise from this point
                                                            sors in a circuit cycle OFF, a compressor within the cir-
to 46.7°F (8.2°C), the hot gas bypass would shut OFF,
                                                            cuit will not be permitted to start until the anti-recycle
still leaving one compressor running. As the load in-
                                                            timer has timed out. If the lead system has run for less
creased, the compressors would stage ON every 1.7°F
                                                            than 5 minutes, 3 times in a row, the anti-recycle timer
(0.94°C).
                                                            will be extended to 10 minutes.
Also note that Table 24 on page 173 not only pro-
vides the formulas for the loading (ON POINT) and           ANTI-COINCIDENCE TIMER
unloading (OFF POINT) of the system, the “STEP” is          This timer is not present on single-system units. Two
also shown in the table. The “STEP” is the increment        timing controls are present in software to assure com-
in the sequence of the capacity control scheme that can     pressors within a circuit or between systems, do not         8
be viewed under the OPER DATA key. See Display/             start simultaneously. The anti-coincidence timer as-
Print Keys on page 131 for specific information on          sures there is at least a one minute delay between sys-
the OPER DATA key.                                          tem starts on 2-circuit systems. This timer is NOT pro-
                                                            grammable. The load timers further assure that there
RETURN CHILLED LIQUID SYSTEM LEAD/                          is a minimum time between compressor starts within
LAG AND COMPRESSOR SEQUENCING                               a system.
A Lead/Lag option may be selected to help equalize
                                                            EVAPORATOR PUMP CONTROL AND YORK
average run hours between systems with 2 refriger-
                                                            HYDRO KIT PUMP CONTROL
ant systems. This may be programmed under the OP-
TIONS key. Auto Lead/Lag of the 2 systems based on          The evaporator pump dry contacts (XTBC2 – Termi-
average run hours of the compressors in each system.        nals 23 and 24) are energized when any of the follow-
Manual Lead/Lag selects specifically the sequence           ing conditions are true:
which the microprocessor starts the systems.
                                                              1.	 Low Leaving Chilled Liquid Fault
The microprocessor will sequence compressors load
                                                              2.	 Any compressor is running
and unload systems according to Table 25 on page
174. The microprocessor will lead/lag compressors             3.	 Daily Schedule is ON, Unit Switch is ON and Re-
within each circuit to maximize individual compres-               mote Stop is closed
The pump will not run if the microprocessor panel         for the next stage is decreased 20 psig and ramped back
has been powered up for less than 30 seconds or if the    to the programmed off pressure minus the differential
pump has run in the last 30 seconds to prevent pump       over the next 20 seconds.
motor overheating.                                        Condenser fan locations are shown in Figure 47 on
Whenever the option “YORK HYDRO KIT PUMPS =               page 177. Detailed Standard Fan Control operation
1” is selected under the OPTIONS key, the pump con-       is shown in Table 26 on page 178 and Table 27 on
trol will be as described above. DO NOT SELECT the        page 179.
option “YORK HYDRO KIT PUMPS = 2” under the
OPTIONS key. If a dual pump option is installed, the      VSD FAN
active pump is selected by the selector switch.           VSD fans are equipped and controlled to extend the
                                                          minimum starting ambient temperature to -10°F
EVAPORATOR HEATER CONTROL
                                                          (-23.3°C).
The evaporator heater is controlled by ambient air tem-
perature. When the ambient temperature drops below        The number of compressors running in the system, the
40°F (4.4°C) the heater is turned ON. When the tem-       programmed fan speed references, and the fan ramp
perature rises above 45°F (7.2°C) the heater is turned    speed determine the speed of the VSD.
OFF. An under voltage condition will keep the heater      For the YLAA fan speed control, there are the follow-
OFF until full voltage is restored to the system.         ing options:
PUMPDOWN CONTROL                                            •	 SINGLE SPEED or STANDARD fans
Each system has a pump-down feature upon shut-off.          •	 YLAA TWO SPEED FANS
Manual pumpdown from the keypad is not possible.
On a non-safety, non-unit switch shutdown, all com-         •	 YLAA VSD FANS
pressors but one in the system will be shut OFF. The      To enable fan inverter control, set the fan speed control
LLSV will also be turned OFF. The final compressor        in SERVICE MODE to YLAA VSD FANS.
will be allowed to run until the suction pressure falls
below the cutout, or for 180 seconds, whichever comes     CHANGING THE SWITCH POINT OF THE
first.                                                    THERMAL DISPERSION FLOW SWITCH
                                                          To change the factory-set LED 7, complete the follow-
STANDARD CONDENSER FAN CONTROL
                                                          ing steps:
Condenser fan operation must be programmed with
the OPTIONS key under “Fan Control.” Condenser              1.	 Press the ◄ or ► push button. The switch point
fan must be selected for Discharge Pressure only. Fan           LED flashes.
control by discharge pressure will work according to        2.	 Press the ◄ or ► push button as many times as re-
the tables on the following pages (see Table 26 on page         quired in less than 2 seconds between each press.
178 and Table 27 on page 179). The fan control on               Each press of the push button shifts the LED by
pressure and fan differential off-pressure are program-         one position in the indicated direction.
mable under the PROGRAM key. Standard fan control
operates down to a temperature of 25°F.                     3.	 Stop pressing the button when the switch posi-
                                                                tion LED changes to the required position. The
The delay between turning ON and OFF fan stages is              flow switch automatically returns to the operating
always fixed at 5 seconds.                                      mode with the new setting in 2 seconds.
When a fan stage is turned ON by pressure, the on
                                                            4.	 To prevent unintentional settings, press both push
pressure for the next stage is increased 20 psig and
                                                                buttons simutaneously for at least 10 seconds in
ramped back to the programmed on pressure over the
                                                                operating mode to lock the switch electronically.
next 20 seconds. Typically, standard ambient control
                                                                To unlock the flow switch, perform the same oper-
on pressure should be programmed at 385 psig with a
                                                                ation again. The setting remains the same in case
differential of 125 psig.
                                                                of power failure.
When a fan stage is turned OFF (programmed on pres-
sure minus programmed differential), the off pressure
 YLAA0041HE, YLAA0048HE,
 YLAA0058HE, YLAA0065HE,
 YLAA0070SE, YLAA0080SE,
 YLAA0081HE, YLAA0082HE,                                                                                             YLAA0092HE, YLAA0115SE,
       YLAA0089SE                          YLAA0100SE                              YLAA0101HE                             YLAA0120SE,
=2-MF1 =1-MF2 =2-MF1 =1-MF2 =2-MF1 =2-MF2 =1-MF2 =2-MF1 =1-MF2 =1-MF3
=2-MF2
=2-MF2 =1-MF1 =2-MF3 =1-MF1 =2-MF3 =2-MF4 =1-MF1 =2-MF3 =2-MF2 =1-MF1
=2-MF1 =2-MF2 =1-MF5 =1-MF4 =1-MF3 =2-MF1 =2-MF2 =1-MF6 =1-MF5 =1-MF4
=2-MF3 =2-MF4 =2-MF5 =1-MF2 =1-MF1 =2-MF3 =2-MF4 =1-MF3 =1-MF2 =1-MF1
                                                                                                                                                          8
                                                                                                       YLAA0200HE, YLAA0230HE
LD27281a
Table 26 - YLAA STANDARD CONDENSER FAN CONTROL USING DISCHARGE PRESSURE ONLY (2, 3,
            OR 4 FANS PER SYSTEM)
                                                                                                   FAN
  FAN                                                                IPUII I/O OUTPUT                                        FAN #
                      ON*                        OFF**                                          CONTACTOR
 STAGE
                                                                     SYS 1        SYS 2       SYS 1       SYS 2       SYS 1        SYS 2
                                        DP < PROGRAMMED
                                         FAN CONTROL ON
            DP > PROGRAMMED
                                         PRESSURE MINUS
      1      FAN CONTROL ON                                           7B7-8      TB10-8       1-KF1       2-KF1       1-MF1        2-MF2
                                        PROGRAMMED DIF-
                PRESSURE
                                         FERENTIAL PRES-
                                               SURE
                                        DP < PROGRAMMED
                                         FAN CONTROL ON
            DP > PROGRAMMED
                                         PRESSURE MINUS
             FAN CONTROL ON                                           TB7-8      TB10-8       1-KF1       2-KF1       1-MF1        2-MF1
                                        PROGRAMMED DIF-
      2     PRESSURE AND FAN                                           and        and          and         and         and          and
                                         FERENTIAL PRES-
             STAGE 1 IS ENER-                                         TB7-9      TB10-9       1-KF2       2-KF2       1-MF2        2-MF2
                                          SURE AND FAN
                  GIZED
                                         STAGE 1 IS ENER-
                                              GIZED
                                                                                                                      3 FAN:       3 FAN:
                                                                                                                      1-MF1        2-MF1
                                                                                                                       and          and
                                        DP < PROGRAMMED                                                               1-MF2        2-MF2
                                         FAN CONTROL ON                                                                and          and
            DP > PROGRAMMED                                          TB7-8        TB10-       1-KF1       2-KF1
                                         PRESSURE MINUS                                                               1-MF3        2-MF3
             FAN CONTROL ON                                           and         8 and        and         and
                                        PROGRAMMED DIF-                                                               4 FAN:       4 FAN:
      3     PRESSURE AND FAN                                         TB7-9       TB10-9       1-KF2       2-KF2
                                         FERENTIAL PRES-                                                              1-MF1        2-MF1
            STAGES 1 AND 2 ARE                                        and          and         and         and
                                           SURE AND FAN                                                                and          and
                ENERGIZED                                            TB7-10      TB10-10      1-KF3       2-KF3
                                          STAGES 1 AND 2                                                              1-MF2        2-MF2
                                          ARE ENERGIZED                                                                and          and
                                                                                                                      1-MF3        2-MF3
                                                                                                                       and          and
                                                                                                                      1-MF4        2-MF4
* When a fan stage is turned on, the pressure for the next stage is increased 20 PSIG and ramped back to the programmed on pressure over
  the next 20 seconds.
** W
    hen a fan stage is turned off (Programmed ON pressure minus the differential), the OFF pressure for the next stage is decreased 20 psig
   and ramped back to the programmed OFF pressure minus the differential.
Table 27 - YLAA STANDARD CONDENSER FAN CONTROL USING DISCHARGE PRESSURE ONLY (5 OR 6
            FANS PER SYSTEM)
  FAN                                                      IPUII I/O OUTPUT            FAN CONTACTOR                       FAN #
                    ON*                  OFF**
 STAGE                                                     SYS 1         SYS 2          SYS 1         SYS 2         SYS 1         SYS 2
                                     DP < PRO-
                                     GRAMMED
               DP > PRO-           FAN CONTROL
             GRAMMED FAN           ON PRESSURE
    1                                                      TB7-8         TB10-8         1-KF1         2-KF1         1-MF1         2-MF1
              CONTROL ON            MINUS PRO-
               PRESSURE              GRAMMED
                                   DIFFERENTIAL
                                    PRESSURE
                                     DP < PRO-
                                     GRAMMED
                                   FAN CONTROL
               DP > PRO-
                                   ON PRESSURE                                                                      1-MF1         2-MF1
            GRAMMED FAN
                                    MINUS PRO-             TB7-8         TB10-8         1-KF1         2-KF1          and           and
             CONTROL ON
    2                                GRAMMED                and           and            and           and          1-MF2         2-MF2
            PRESSURE AND
                                   DIFFERENTIAL            TB7-9         TB10-9         1-KF2         2-KF2          and           and
            FAN STAGE 1 IS
                                    PRESSURE                                                                        1-MF3         2-MF3
              ENERGIZED
                                      AND FAN
                                    STAGE 1 IS
                                    ENERGIZED
                                                                                                                    5 FAN:        5 FAN:
                                                                                                                    1-MF1         1-MF1
                                                                                                                     and           and
                                                                                                                    1-MF2         1-MF2
                                                                                                                     and           and
                                     DP < PRO-                                                                      1-MF3         1-MF3
                                     GRAMMED                                                                         and           and
                                   FAN CONTROL                                                                      1-MF4         1-MF4
               DP > PRO-
                                   ON PRESSURE                                                                       and           and
            GRAMMED FAN                                   TB7-8         TB10-8          1-KF1         2-KF1
                                    MINUS PRO-                                                                      1-MF5         1-MF5
             CONTROL ON                                    and            and            and           and
                                     GRAMMED                                                                        6 FAN:        6 FAN:
    3       PRESSURE AND                                  TB7-9         TB10-9          1-KF2         2-KF2
                                   DIFFERENTIAL                                                                     1-MF1         1-MF1
             FAN STAGES 1                                  and            and            and           and
                                     PRESSURE                                                                        and           and
            AND 2 ARE EN-
                                      AND FAN
                                                          TB7-10        TB10-10         1-KF3         2-KF3
                                                                                                                    1-MF2         1-MF2        8
               ERGIZED
                                   STAGES 1 AND                                                                      and           and
                                    2 ARE ENER-                                                                     1-MF3         1-MF3
                                       GIZED                                                                         and           and
                                                                                                                    1-MF4         1-MF4
                                                                                                                     and           and
                                                                                                                    1-MF5         1-MF5
                                                                                                                     and           and
                                                                                                                    1-MF6         1-MF6
* When a fan stage is turned on, the pressure for the next stage is increased 20 psig and ramped back to the programmed on pressure over
  the next 20 seconds.
** When a fan stage is turned off (Programmed ON pressure minus the differential), the OFF pressure for the next stage is decreased 20 psig
    and ramped back to the programmed OFF pressure minus the differential.
The history buffers may be cleared by pressing the          After pressing the key sequence as described, the con-
HISTORY key and then repeatedly pressing the UP             trol will enter Service Mode permitting the outputs
arrow key until you scroll past the last history buffer     (except compressors), operating hours, refrigerant
choice. The following message will be displayed:            type, expansion valve type, and start/hour counters to
                                                            be viewed/modified. The ENTER/ADV key is used to
  I	 I	 N	 I	 T	 I	 A	L	 I	 Z	E			 H	 I	 S	T	O	R	Y          advance through the outputs. Using the ↑ and ↓ (UP/
  					E	       N	  T	E	R		=		Y	   E	S                      DOWN ) arrow keys will turn the respective digital out-
                                                            put ON/OFF or modify the value.
Pressing the ENTER/ADV key at this display will             Following is the order of outputs that will appear as the
cause the history buffers to be cleared. Pressing any       ENTER/ADV key is pressed:
other key will cancel the operation.
             DO NOT CLEAR BUFFERS. Important                       SYS 1 COMP 1 STATUS TB7-2 IS:
             information may be lost. Contact factory                SYS 1 LLSV STATUS TB7-3 IS:
             service.                                              SYS 1 COMP 2 STATUS TB7-4 IS:
                                                                   SYS 1 COMP 3 STATUS TB7-5 IS:
                                                                     SYS 1 HGBP STATUS TB7-7 IS:
                                                                   SYS 2 COMP 1 STATUS TB10-2 IS:
                                                                    SYS 2 LLSV STATUS TB10-3 IS:
RESETTING SYSTEM LOCKOUT FAULTS                                    SYS 2 COMP 2 STATUS TB10-4 IS:
If 3 faults on the same system occur within 90 minutes,            SYS 2 COMP 3 STATUS TB10-5 IS:
that system will be locked out on the last fault. This              SYS 1 FAN OUTPUT 1 TB7-8 IS:
condition requires a manual reset. The system switch                SYS 1 FAN OUTPUT 2 TB7-9 IS:
(under OPTIONS key) must be turned off and then                    SYS 1 FAN OUTPUT 3 TB7-10 IS:
back on to clear the lockout fault. Fault messages will            SYS 2 FAN OUTPUT 1 TB10-8 IS:
be displayed whenever a system is locked out.                      SYS 2 FAN OUTPUT 2 TB10-9 IS:
                                                                   SYS 2 FAN OUTPUT 3 TB10-10 IS:
SERVICE MODE                                                       EVAP HEATER STATUS TB8-2 IS:
                                                                   SYS 1 ALARM STATUS TB8-3 IS:
Service Mode is a mode that allows the user to enable              SYS 2 ALARM STATUS TB9-2 IS:
or disable all of the outputs (except compressors) on               EVAP PUMP STATUS TB8-6,7 IS:
the unit, change chiller configuration setup parameters             SYS 2 HGBV STATUS TB10-7 IS:
and view all the inputs to the microboard.                               SPARE DO TB8-4 IS:
To enter Service Mode, turn the Unit Switch OFF and                      SPARE DO TB8-5 IS:
press the following keys in the sequence shown:                         SPARE DO TB8-8, 9 IS:
  •	   PROGRAM
                                                                         SPARE DO TB9-4 IS:                             9
                                                                 SYS 1 EEV OUTPUT TB5-1, 2 = XXX%
  •	   UP ARROW                                                  SYS 2 EEV OUTPUT TB6-1, 2 = XXX%
  •	   UP ARROW                                                SYS 1 COND FAN SPEED J15-1,5 = XXX%
                                                               SYS 2 COND FAN SPEED J15-2,6 = XXX%
  •	   DOWN ARROW                                                     SPARE AO J15-3,7 = XXX%
  •	   DOWN ARROW                                                     SPARE AO J15-4,8 = XXX%
  •	   ENTER                                                    DATA LOGGING MODE 1 = ON, 0 = OFF
                                                                    DATA LOGGING TIMER X SECS
Service Mode will time out after 30 minutes and return
                                                                        SOFT START (disabled)
to normal control mode, if the panel is accidentally left
                                                                  REFRIGERANT TYPE (R-410A only)
in this mode. Otherwise, turning the unit switch ON
                                                              EXPANSION VALVE TYPE (Thermostatic Only)
will take the panel out of Service Mode.
The analog inputs will display the input connection,        Table 30 - I/O DIGITAL OUTPUTS
the temperature or pressure, and corresponding input          TB7-2      SYS 1 Compressor 1
voltage such as:                                              TB7-3      SYS 1 Liquid Line Solenoid Valve
This example indicates that the system 1 suction pres-       TB10-2      SYS 2 Compressor 1
sure input is connected to plug 7 – pin 10 (J7-10) on the    TB10-3      SYS 2 Liquid Line Solenoid Valve
I/O board. It indicates that the voltage is 2.1 VDC which    TB10-4      SYS 2 Compressor 2
corresponds to 81 psig (5.6 bar) suction pressure.           TB10-5      SYS 2 Compressor 3
                                                              TB7-8      SYS 1 Condenser Fan Output 1
The digital inputs will display the input connection and
                                                              TB7-9      SYS 1 Condenser Fan Output 2
ON/OFF status such as:
                                                             TB7-10      SYS 1 Condenser Fan Output 3
  		 F	L	O	
          W		S	W	/	R	E	M		S	T	A	R	T                          TB10-8      SYS 2 Condenser Fan Output 1
  						J	   13	
               -	5		I	S		O	 N                                TB10-9      SYS 2 Condenser Fan Output 2
                                                             TB10-10     SYS 2 Condenser Fan Output 3
This indicates that the flow switch/remote start input is     TB8-2      Evaporator Heater
connected to plug 13- pin 5 (J13-5) on the microboard,        TB8-3      SYS 1 Alarm
and is ON (ON = +30 VDC unregulated input, OFF =              TB9-2      SYS 2 Alarm
0VDC input on digital inputs).
                                                            TB8-6 & 7 Evaporator Pump Starter
CONTROL INPUTS/OUTPUTS                                       TB10-7      SYS 2 Hot Gas Bypass Valve
Table 29 through Table 32 on page 185 are a quick           Table 31 - I/O ANALOG INPUTS
reference list providing the connection points and a
                                                                      SYS 1 Suction Transducer
description of the inputs and outputs respectively. All      J7-10    -or-
input and output connections pertain to the connections               SYS 1 Low Pressure Switch
at the microboard.                                                 Unit Type: Chiller = NO Jumper J11-12 to +24
                                                                   VDC
Table 29 - I/O DIGITAL INPUTS                               J11-12
                                                                   YCUL Condensing Unit = Jumper J11-12 to +24
 J13-2    Unit ON/OFF Switch                                       VDC (Do NOT Use)
 J13-3    Load Limit Stage 2 on 3, 5 & 6 Comp. Units         J7-11    SYS 1 Discharge Pressure Transducer (Optional)
 J13-4    Load Limit Stage 1                                 J6-9     Ambient Air Temp. Sensor
 J13-5    Flow Switch and Remote Start/Stop                  J6-7     Leaving Chilled Liquid Temp. Sensor
 J13-6    Spare                                              J6-8     Return Chilled Liquid Temp. Sensor
          Single System Select                                        SYS 2 Suction Pressure Transducer
 J13-7
          (Jumper = Single Sys, No Jumper = Two Sys)         J9-10    -or-
 J13-8
          CR1                                                         SYS 2 Low Pressure Switch
                                                                                                                       9
          (Sys 1 Motor Protector/High Pressure Cutout)                SYS 2 Discharge Pressure Transducer
                                                             J9-11
          CR2                                                         (Optional)
 J13-10
          (Sys 2 Motor Protector/High Pressure Cutout)       J7-12    Unit/SYS 1 Voltage
                                                             J9-12    SYS 2 Voltage
                                                            J11-11 Remote Temperature Reset
TB1
TB7
J3
TB8
J5
                                                                            IPU
                                                                            BOARD
 TB9
                                                                              J6
J7
                                                                              J8
TB10
J9
J10
                           J14                                        JP1
                                          J13               J11
                                                      J12
                                                                                    LD12721
Table 34 - ENTERING/LEAVING CHILLED LIQUID     Liquid and Refrigerant Sensor Test Points
            TEMP. SENSOR, TEMPERATURE/
                                                (See Table 34 on page 188)
            VOLTAGE CORRELATION
                     VOLTAGE                    Entering Chilled Liquid Sensor
      TEMP °F     (SIGNAL INPUT      TEMP °C
                   TO RETURN)
                                                J6-5 = +5 VDC regulated supply to sensor.
        10             1.33               -12   J6-8 = VDC input signal to the I/O board. See Table
        12             1.39               -11           34 on page 188for voltage readings that cor-
        14             1.46               -10           respond to specific liquid temperatures.
        16             1.51               -9
                                                J6-2 = drain (shield connection = 0 VDC) Return
        18             1.58               -8
        20             1.65               -7    Leaving Chilled Liquid Temperature Sensor
        22             1.71               -6    J6-4 = +5 VDC regulated supply to sensor.
        24             1.78               -4
        26             1.85               -3    J6-7 = VDC input signal to the microboard. See Table
        28             1.91               -2
                                                        34 on page 188for voltage readings that cor-
                                                        respond to specific liquid temperatures.
        30             1.98               -1
        32             2.05               0     J6-1 = drain (shield connection = 0 VDC) return
        34             2.12               1
        36             2.19               2     Analog Inputs – Pressure
        38             2.26               3     See the unit wiring diagram. Pressure inputs are con-
        40             2.33               4     nected to the microboard on plugs J7 and J9. These an-
        42             2.40               6     alog inputs represent varying DC signals correspond-
        44             2.47               7
                                                ing to varying pressures. All voltages are in reference
                                                to the unit case (ground).
        46             2.53               8
        48             2.60               9     System 1 discharge and suction pressures will be con-
        50             2.65               10    nected to J7 of the microboard. System 2 discharge and
        52             2.73               11    suction pressure transducers will be connected to J9 of
        54             2.80               12    the microboard.
        56             2.86               13    The discharge transducers are optional on all units. If
        58             2.92               14    the discharge transducers are not installed, no connec-
        60             2.98               16    tions are made to the microboard and the discharge
        62             3.05               17    pressure readout on the display would be zero.
        64             3.11               18
                                                The suction pressure transducers are standard on all
        66             3.17               19
                                                YLAA. The suction pressure transducers have a range
        68             3.23               20    of 0 psig to 400 psig. The output will be linear from
        70             3.29               21    0.5 VDC to 4.5 VDC over the 400 psig (27.5 barg)
        72             3.34               22    range.
        74             3.39               23
                                                The discharge transducers have a range from 0 psig to
        76             3.45               24
                                                650 psig. The output will be linear from 0.5 VDC to
        78             3.5                26
                                                4.5 VDC over the 600 psig (41.25 barg) range. Follow-
        80             3.54               27    ing is the formula that can be used to verify the volt-
                                                age output of the transducer. All voltage reading are in
                                                reference to ground (unit case).
J7-11 = V
         DC input signal to the microboard. See the                                    J7-11 = drain (shield connection = 0VDC).
        formula above for voltage readings that cor-                                                                                               9
        respond to specific discharge pressures.                                        Digital Outputs
                                                                                        See the unit wiring diagram and Figure 49 on page
J7-7 = +5 VDC return                                                                    190. The digital outputs are located on TB7, TB8,
J7-2 = drain (shield connection = 0VDC)                                                 and TB9 and TB-10 of the microboard. All outputs are
                                                                                        120VAC with the exception of TB8-6 to TB8-7 which
System 2 Discharge Transducer                                                           are the contacts that can be used for a remote evapora-
                                                                                        tor pump start signal. The voltage applied to either of
J9-6 = +5 VDC regulated supply to transducer.
                                                                                        these terminals would be determined by field wiring.
J9-11 = VDC input signal to the microboard. See the
formula above for voltage readings that correspond to
specific discharge pressures.
                                              SYS 2
                                       TB10-7 HGSV
                                       TB10-8
TB10
                                       TB10-9 SYS 2
                                               FAN 2
                                               SYS 2
                                       TB10-10 FAN 4
                                       TB8-6    EVAP
                                       TB8-7    PUMP
 TB8
                                                HEAT EXCH
                                       TB8-2    HEATER
LD12722
TB3-3 TXD 2 RD
TB3-5 GND 7 SG
LD12723
                                    TROUBLESHOOTING
Table 37 - TROUBLESHOOTING
             PROBLEM                          CAUSE                                      SOLUTION
                               1. No 115 VAC to 24 VAC                1a. Check wiring and fuse 1FU.
                                  Transformer.
                                                                      1b. C
                                                                           heck wiring emergency stop contacts 5 to
                                                                          L of XTBC2 Terminal Block.
                                                                      1c. Replace Control Transformer.
                               2. No 24 VAC to Microboard.            2. Check wiring Control Transformer to
                                                                         Microboard.
                               3. Control Transformer defective,      3. Replace Control Transformer.
                                  no 24 VAC output.
   NO DISPLAY ON PANEL. UNIT   4. Short in wire to temp. sensors or   4. Unplug connections at IPU II & I/O Board to
        WILL NOT OPERATE          pressure transducers.                  isolate.
                               5. Defective IPU II & I/O Board or     5. Replace IPU II & I/O Board or the Display
                                  the Display Board.                     Board.
                                                                                     Contact Johnson Controls
                                                                                     Service before replacing cir-
                                                                                     cuit Boards!
      LOW LIQUID TEMP FAULT                                               3. Increase chilled liquid flow. See Operational
                                 3. Chilled liquid flow too low.
                                                                             Limitations on page 47).
                                 4. Defective LWT or RWT sensor           4. Compare sensor against a known good
                                    (assure the sensor is properly           Temperature sensing device. See Table 34
                                    installed in the bottom of the well      on page 188.
                                    with a generous amount of heat)
                                    conductive compound).
                                 1. Compressor internal motor             1. Verify refrigerant charge is not low. Verify
                                    protector (MP) open.                     superheat setting of 10°F to 15°F (5.6°C to
                                                                             8.3°C). Verify correct compressor rotation.
                                                                             Verify compressor is not overloaded.
         MP / HPCO FAULT         2. External overload tripped.            2. Determine cause and reset.
                                 3. HPCO switch open.                     3. See High Press. Disch. Fault.
                                 4. Defective HPCO switch.                4. Replace HPCO switch.
                                 5. Defective CR relay.                   5. Replace relay.
                                 1. Demand not great enough.              1. No problem. Consult Installation Manual to
                                                                             aid in understanding compressor operation
                                                                             and capacity control.
                                 2. Defective water temperature           2. Compare the display with a thermometer.
 COMPRESSOR(S) WON’T START          sensor.                                  Should be within plus or minus 2 degrees.
                                                                             See Table 34 on page 188for RWT/LWT
                                                                             temp./voltage table.
                                 3. Contactor/Overload failure.           3. Replace defective part.
                                 4. Compressor failure.                   4. Diagnose cause of failure and replace.
                                 1. Fouled evaporator surface.            1. Contact the local Johnson Controls service
                                    Low suction pressure will be             representative.
                                    observed.
                                 2. Improper flow through the             2. Reduce flow to within chiller design specs.
   LACK OF COOLING EFFECT
                                    evaporator.                              See Operational Limitations on page 47).
                                 3. Low refrigerant charge. Low           3. Check subcooling and add charge as
                                    suction pressure will be                 needed.
                                    observed.
SECTION 10 – MAINTENANCE
COMPRESSORS
                                                            CONDENSER MCHX CLEANING
Oil Level check                                             The cleaning procedure for the condenser MCHX is
The oil level can only be tested when the compressor is     significantly different than tube and fin type MCHX.
running in stabilized conditions, to ensure that there is   Care must be taken to understand the differences to
no liquid refrigerant in the lower shell of the compres-    avoid damage to the MCHX. These differences require
sor. When the compressor is running at stabilized con-      a number of DO NOT’s that must be observed:
ditions, the oil level must be between 1/4 and 3/4 in the
                                                              •	 DO NOT use coil cleaners or any chemical on
oil sight glass. At shutdown, it is acceptable if the oil
                                                                 a MCHX. This can cause severe damage to the
level falls to the bottom limit of the oil sight glass.
                                                                 coils.
             Use YORK “V” oil 011-00949-000, when
             adding oil to Copeland compressor. The           •	 DO NOT use a pressure washer to clean the
             Bitzer compressor uses 011-00982-000 oil.           MCHX. While it is possible to clean a the MCHX
                                                                 with a pressure washer, it’s also possible to de-
                                                                 stroy it.
                                                              •	 DO NOT contact the MCHX with a hard surface
Oil Analysis                                                     such as a hose nozzle or metal vacuum nozzle or
                                                                 any other tool.
The oil used in these compressors is pale yellow in
color (POE oil). If the oil color darkens or exhibits a     Follow the three steps below for cleaning the MCHX:
change in color, this may be an indication of contami-
                                                             1.	 Remove surface debris such as dirt, leaves, insects,
nants in the refrigerant system. If this occurs, an oil
                                                                 fibers, etc. with a vacuum cleaner having a soft at-
sample should be taken and analyzed. If contaminants
                                                                 tachment rather than a metal tube. Compressed air
are present, the system must be cleaned to prevent
                                                                 blown from the inside out can also be used. When
compressor failure.
                                                                 brushing debris off the face of the MCHX a soft
             Never use the scroll compressor to pump             bristle (not wire) brush can be used. Do not scrape    10
             the refrigerant system down into a vacu-            the MCHX with the vacuum nozzle, air nozzle, or
             um. Doing so will cause internal arcing             any other tool.
             of the compressor motor which will result
             in failure of compressor.
  2.	 Rinse the MCHX with tap water. Do not use              THERMAL DISPERSION FLOW SWITCH
      MCHX cleaners. Rinse the coil from the inside
                                                             Check the sensor tip for buildup regularly, because it
      out, running water through every passage in the
                                                             can affect the sensitivity of the sensor.
      heat exchanger surface until it is clean. Use a gen-
      tle spray from a spray nozzle with a plastic end or    In case of any buildup at the sensor tip, use a soft cloth
      put your finger on the end of the spray nozzle to      to remove it. Use vinegar as the cleaning agent to re-
      reduce impact and provide a gentle spray.              move any stubborn buildup if necessary.
  3.	 Because of the fin geometry, the condenser
                                                             BRAZED PLATE HEAT EXCHANGER
      MCHX retain water more than tube and fin style.
                                                             (EVAPORATOR) HEATER
      It is generally recommended to blow or vacuum
      out the rinse water from the MCHX to speed dry-                     The internal power supply to the Evapo-
      ing and prevent water pooling.                                      rator Heater is 120 VAC. Disconnecting
                                                                          120 VAC power from the unit, at or below
OPERATING PARAMETERS                                                      freezing temperatures, can result in dam-
Regular checks of the system should be preformed                          age to the evaporator and unit as a result
to ensure that operating temperatures and pressures                       of the chilled liquid freezing.
are within limitations, and that the operating controls
                                                             OVERALL UNIT INSPECTION
are set within proper limits. See SECTION 8 – UNIT
OPERATION, SECTION 6 – COMMISSIONING, and                    In addition to the checks listed on this page, periodic
SECTION 4 – INSTALLATION of this manual.                     overall inspections of the unit should be accomplished
                                                             to ensure proper equipment operation. Items such as
ON-BOARD BATTERY BACK-UP                                     loose hardware, component operation, refrigerant
The Real Time Clock chip (U5) located on the 031-            leaks, unusual noises, etc. should be investigated and
02630 IPU II board that maintains the date/time and          corrected immediately.
stores customer programmed set points.
             Do not confuse JP1 on the IPU II (031-
             02630) board with JP1 on the I/O (031-
             02550) board.
                                  TEMPERATURE
                                  TEMPERATURE CONVERSION
                                              CONVERSION CHART
                                                         CHART
             Temperature Conversion Chart -                    Temperature Conversion Chart -
                 Actual Temperatures                              Differential Temperatures
        °F       =         °C         °C    =     °F     °F      =     °C            °C       =    °F
         0               -17.8       -18         -0.4     0               0           0              0
         4               -15.6       -16           3.2    4             2.2           2            3.6
         8               -13.3       -14           6.8    8             4.4           4            7.2
        12                -11.1      -12         10.4    12             6.7           6           10.8
        16                 -8.9      -10            14   16             8.9           8           14.4
        20                 -6.7        -8        17.6    20            11.1          10             18
        24                 -4.4        -6        21.2    24            13.3          12           21.6
        28                 -2.2        -4        24.8    28            15.6          14           25.2
        32                  0.0        -2        28.4    32            17.8          16           28.8
        36                  2.2         0          32    36              20          18           32.4
        40                  4.4         2        35.6    40            22.2          20             36
        44                  6.7         4        39.2    44            24.4          22           39.6
        48                  8.9         6        42.8    48            26.7          24           43.2
        52                 11.1         8        46.4    52            28.9          26           46.8
        56                 13.3       10           50    56            31.1          28           50.4
        60                 15.6       12         53.6    60            33.3          30             54
        64                 17.8       14         57.2
        68                 20.0       16         60.8
        72                 22.2       18         64.4           Pressure Conversion Chart -
        76                 24.4       20           68               Gauge or Differential
        80                 26.7       22         71.6
        84                 28.9       24         75.2    PSI      =    BAR           BAR      =   PSI
        88                 31.1       26         78.8     20            1.38          1.5          21.8
        92                 33.3       28         82.4     30            2.07           2            29
        96                 35.6       30           86     40            2.76          2.5          36.3
       100                 37.8       32         89.6     50            3.45           3           43.5
       104                 40.0       34         93.2     60            4.14          3.5          50.8
       108                 42.2       36         96.8     70            4.83           4            58
       112                 44.4       38        100.4     80            5.52          4.5          65.3
       116                 46.7       40          104     90            6.21           5           72.5
       120                 48.9       42        107.6    100             6.9          5.5          79.8
       124                 51.1       44        111.2    110            7.59           6            87
       128                 53.3       46        114.8    120            8.28          6.5          94.3
       132                 55.6       48        118.4    130            8.97           7          101.5
       136                 57.8       50          122    140            9.66          7.5         108.8
       140                 60.0       52        125.6    150           10.34           8           116
       144                 62.2       54        129.2    160           11.03          8.5         123.3
       148                 64.4       56        132.8    170           11.72           9          130.5
       152                 66.7       58        136.4    180           12.41          9.5         137.8
       156                 68.9       60          140    190           13.1           10           145
       160                 71.1       62        143.6    200           13.79         10.5         152.3
       164                 73.3       64        147.2    210           14.48          11          159.5
       168                 75.6       66        150.8    220           15.17         11.5         166.8
       172                 77.8       68        154.4    230           15.86          12           174
       176                 80.0       70          158    240           16.55         12.5         181.3
       180                 82.2       72        161.6    250           17.24          13          188.5
       184                 84.4       74        165.2    260           17.93         13.5         195.8
       188                 86.7       76        168.8    270           18.62          14           203
       192                 88.9       78        172.4    280           19.31         14.5         210.3
       196
       200
                           91.1
                           93.3
                                      80
                                      82
                                                  176
                                                179.6
                                                         290
                                                         300
                                                                         20
                                                                       20.69
                                                                                      15
                                                                                     15.5
                                                                                                  217.5
                                                                                                  224.8
                                                                                                          10
       204                 95.6       84        183.2    310           21.38          16           232
       208                 97.8       86        186.8    320           22.07         16.5         239.3
       212               100.0        88        190.4    330           22.76          17          246.5
       216               102.2        90          194    340           23.45         17.5         253.8
       220               104.4        92        197.6    350           24.14          18           261
       224               106.7        94        201.2    360           24.83         18.5         268.3
       228               108.9        96        204.8    370           25.52          19          275.5
       232               111.1        98        208.4    380           26.21         19.5         282.8
       236               113.3       100          212    390            26.9          20           290
       240               115.6       102        215.6    400           27.59         20.5         297.3
       244               117.8       104        219.2
TEMPERATURE
To convert degrees Fahrenheit (°F) to degrees Celsius
(°C), subtract 32° and multiply by 5/9 or 0.5556.
Example: (45.0°F - 32°) x 0.5556 = 7.22°C
To convert a temperature range (i.e., a range of 10°F)
from Fahrenheit to Celsius, multiply by 5/9 or 0.5556.
Example: 10.0°F range x 0.5556 = 5.6 °C range