Manual Compresores
Manual Compresores
30HXA,HXC076-271
                                Data           Condenserless and Water-Cooled
                                                           Liquid Chillers with
                                                    COMFORTLINK™ Controls
                                                                      50/60 Hz
                                                                                               75 to 265 Nominal Tons
                                                                                                       (264 to 931 kW)
                                                                                          ®
                                     evergrn
                                                                                         Features/Benefits
                                                                                         Quality design and
                                                     Co m f o r t Li n k
                                                          N AV I G ATO R ™
                                                                                         construction make the
                                                                                         30HXC (water-cooled) and
                                                               12.58
                                                   TIME        54.6 F
                                                   EWT         44.1 F
                                                   LWT         44.0 F
                                                   SETP
                                                      M ORun E
                                                          D Status        Alarm Status
                                                          Service Test
                                                          Temperatures
                                                          Pressures
                                                          Setpoints
                                                          Inputs
                                                          Outputs
                                                          Configuration
                                                          Time Clock
                                                          Operating Modes    ESC
                                                          Alarms
                                         Co m f o r t Li n k
                                              N AV I G ATO R ™
                                                   12.58
                                       TIME        54.6 F
                                       EWT         44.1 F
                                       LWT         44.0 F
                                       SETP
                                          M ORun
                                              D Status
                                                 E            Alarm Status
                                              Service Test
                                              Temperatures
                                              Pressures
                                              Setpoints
                                              Inputs
                                              Outputs
                                              Configuration
                                              Time Clock
                                              Operating Modes    ESC
                                              Alarms
ENTER
                                                                                                           MO
                                                                                                                    DE
                                                                                                            Run               Ala rm
                                                                                                                   Status              Sta tus
                                                                                                           Service
                                                                                                                     Test
                                                                                                          Tem
                                                                                                               peratu
                                                                                                                      res
                                                                                                         Pressu
                                                                                                                 res
                                                                                                        Setpoi
                                                                                                               nts
                                                                                                       Inputs
                                                                                                      Outpu
                                                                                                           ts
                                                                                                     Configu
                                                                                                              ration
                                                                                                    Time
                                                                                                          Clock
                                                                                                   Opera                    ESC
                                                                                                         ting
                                                                                                               Modes
                                                                                                  Alarms
                                                                                                     EN TE
                                                                                                                R
2
Table of contents
Features/Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1,2
Model Number Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
AHRI Capacity Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4,5
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-9
Options and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10,11
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12-21
Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22-29
Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31,32
Typical Piping and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33,34
Typical Control Wiring Schematic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36-47
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49-51
         LEGEND
FIOPS — Factory-Installed Options
                                                                                                 a30-4646
Quality Assurance
Certified to ISO 9001:2000
                                                                                                                3
AHRI* capacity ratings
                                 30HXC WATER-COOLED CHILLER ARI RATINGS (60 Hz ONLY)
                                                                 COOLER         CONDENSER             CONDENSER
  UNIT        CAPACITY           INPUT      COOLER FLOW         PRESSURE                               PRESSURE        FULL-LOAD
                                                                   DROP           FLOW                    DROP                            IPLV†
  SIZE                          POWER                                                                                  EFFICIENCY
                                                                                                                                        (kW/Ton)
 30HXC               Output       (kW)                          Ft of                                 Ft of             (kW/Ton)
            Tons                             GPM        L/s            kPa       GPM       L/S                 kPa
                      kW                                        Water                                 Water
    076     75.4     265.2        53.7       181.0      11.4    14.5  43.2      226.2      14.3         8.9   26.6         0.712          0.512
    086     83.1     292.3        60.4       199.4      12.6    17.2  51.4      249.3      15.7        10.7   31.8         0.727          0.523
    096     94.0     330.5        67.0       225.5      14.2    17.0  50.7      282.0      17.8        11.0   32.7         0.713          0.513
    106    104.3     366.8        75.3       250.3      15.4    15.4  46.0      312.9      19.7        13.3   39.6         0.722          0.521
    116    113.5     399.3        83.2       272.5      17.2    13.3  39.8      340.6      21.5        17.0   50.6         0.733          0.509
    126    122.9     432.1        92.2       295.2      18.6    15.4  45.9      369.0      23.3        19.6   58.5         0.751          0.530
    136    136.5     479.9        97.0       327.5      20.7    14.6  43.7      409.4      25.8        18.5   55.1         0.711          0.541
    146    145.9     513.2       105.1       350.2      22.1    16.5  49.3      437.8      27.6        20.9   62.4         0.720          0.533
    161    156.5     550.6       111.7       375.5      23.7    13.7  40.9      469.6      29.6        21.3   63.6         0.714          0.520
    171    165.9     585.3       118.2       398.1      25.1    15.2  45.4      497.6      31.4        17.2   51.4         0.712          0.538
    186    177.2     623.1       126.7       426.2      26.8    13.9  41.5      531.6      33.5        19.5   58.1         0.715          0.562
    206    211.5     744.0       146.4       507.7      32.0    14.7  43.9      634.7      40.0        20.9   62.4         0.692          0.510
    246    248.6     874.1       172.4       596.5      37.6    16.2  48.3      745.7      47.0        21.9   65.2         0.693          0.522
    261    257.2     904.6       180.5       617.3      38.9    17.2  51.4      771.6      48.7        23.3   69.5         0.702          0.523
    271    267.4     940.3       189.5       641.7      40.5    18.5  55.1      802.1      50.6        25.1   74.7         0.709          0.525
         LEGEND                                                              3. IPLV is a single number part-load efficiency value calculated using
IPLV — Integrated Part-Load Value                                               the efficiency values at 100%, 75%, 50%, and 25% of load when
                                                                                the chiller is operating at ARI conditions.
*Air Conditioning, Heating, and Refrigeration Institute (U.S.A.).            4. All data in this table is rated (60 Hz only) in accordance with AHRI
†IPLV shown is the lower of Sequence A or Sequence B unloading.                 Standard 550/590 as represented in the Chiller Selection Program
                                                                                (E-Cat) version 2.93.
NOTES:                                                                       5. Contact Carrier for custom ratings.
 1. Rated (60 Hz only) in accordance with AHRI Standard 550/590 at
    standard rating conditions.
 2. Standard rating conditions are as follows:
    Cooler Conditions:
      Leaving Water Temperature: 44 F (6.7 C)
      Flow:                         2.4 gpm per ton (0.043 L/s per kW)
    Condenser Conditions:
      Entering Water temperature: 85 F (29.4 C)
      Flow:                         3.0 gpm per ton (0.054 L/s per kW)
    Fouling Factor (Cooler):                                                             60 Hz only
      0.00010 hr x sq ft x F per Btuh (0.000018 m2 x K per W)
    Fouling Factor (Condenser):
      0.00025 hr x sq ft x F per Btuh (0.000044 m2 x K per W)
4
                                    30HXA CONDENSERLESS CHILLER RATINGS (60 Hz ONLY)
                                                                                                     COOLER
     UNIT                   CAPACITY                INPUT                COOLER FLOW                PRESSURE                   FULL-LOAD
     SIZE                                          POWER                                               DROP                    EFFICIENCY
    30HXA                         Output             (kW)                                         Ft of                         (kW/Ton)
                    Tons                                             GPM             L/s                    kPa
                                    kW                                                            Water
     076             67.7          237.9            76.2             162.4          10.2          11.9      35.6                   1.127
     086             76.0          267.2            84.5             182.3          11.5          14.7      43.8                   1.112
     096             85.8         301.9             95.1             206.0          13.0          14.4      43.1                   1.108
     106             96.9         340.9            106.9             232.7          14.7          13.5      40.3                   1.103
     116            104.9         368.9            115.0             251.8          15.9          11.6      34.6                   1.097
     126            113.9         400.6            125.4             273.4          17.2          13.4      40.1                   1.101
     136            127.0         446.5            138.5             304.7          19.2          12.9      38.4                   1.091
     146            137.2         482.5            150.0             329.3          20.8          14.8      44.1                   1.094
     161            147.3         518.1            159.9             353.6          22.3          12.3      36.7                   1.086
     171            159.0          559.3           173.8             381.7          24.1          14.1      42.1                   1.093
     186            174.3         612.8            192.7             418.2          26.4          13.5      40.3                   1.106
     206            198.5          698.2           216.4             476.5          30.1          13.1      39.2                   1.090
     246            231.9          815.4           252.4             556.5          35.1          14.3      42.7                   1.089
     261            244.1         858.6            267.5             585.9          37.0          15.7      46.8                   1.096
     271            257.9          907.0           283.9             619.0          39.1          17.3      51.6                   1.101
NOTES:                                                                           Fouling Factor (Cooler):
 1. Rated (60 Hz only) in accordance with AHRI Standard 550/590 at                 0.00010 hr x sq ft x F per Btuh (0.000018 m2 x K per W)
    standard rating conditions.                                               3. All data in this table is rated (60 Hz only) in accordance with AHRI
 2. Standard rating conditions are as follows:                                   Standard 550/590 as represented in the Chiller Selection Program
    Cooler Conditions:                                                           (E-Cat) version 2.93.
      Leaving Water Temperature:            44 F (6.7 C)                      4. Contact Carrier for custom ratings.
      Flow:                                 2.4 gpm per ton (0.043 L/s
                                            per kW)
    Saturated Discharge Temperature:        125 F (52 C)
                                                                                                                                                   5
Physical data
                                                                      ENGLISH
UNIT SIZE 30HX                                      076         086         096         106         116         126         136         146
UNIT OPERATING WEIGHT (lb)
  Water-Cooled (HXC)                               5700        5723        5855      6177        6415      6465            6688        6718
  Condenserless (HXA)                              4717        4744        4835      5151        5163      5205            5309        5333
COMPRESSORS                                                                      Semi-Hermetic, Twin Screw
  Quantity                                           2           2           2         2           2         2               2           2
  Nominal Capacity per Compressor (tons)           39/39       46/39       56/39    66/39        66/46     66/56           80/56       80/66
  Economizer                                        No          No          No        No          No        No              No          No
  No. Capacity Steps
    30HXC Unit                                       6           6           6           6           6           6           6           6
    30HXA Unit (maximum on 30HXC unit
    with factory-installed option)                   8           8           8           8           8           8           8           8
  Minimum Step Capacity (%)
    30HXC Unit                                       20          20          20          20          20          20          20          20
    30HXA Unit (30HXC unit with factory-
    installed option)                                10          10          10          10         10         10            10          10
REFRIGERANT                                                                                 R-134a
  Charge* (lb) Circuit A/Circuit B                 75/75       76/75       94/70      110/70      112/89    112/89        124/89      119/100
COOLER                                                                    Shell and Tube with Enhanced Copper Tubes
  Part No. 10HX400-                                 401         401         402         408        406        406          405          405
  Net Fluid Volume (gal)                            17.0        17.0       19.0        22.6        21.4       21.4         24.0         24.0
  Maximum Refrigerant Pressure (psig)               220         220         220         220        220        220          220          220
  Maximum Water-Side Pressure (psig)                300         300         300         300        300        300          300          300
  Water Connections
    Inlet and Outlet (in.) (Standard Pass)           4           4           4           5           5           5           5           5
    Drain (in. NPT) (Standard Pass)                  3/8         3 /8        3 /8        3 /8        3 /8        3 /8        3 /8        3 /8
  Relief Valve
    Connection (in. NPTF)                            3/          3/          3/         3/           3/          3/         3/           3/
                                                        4           4           4          4            4           4          4            4
    Flow Capacity (lb air/min)                      31.7        31.7        31.7       31.7         31.7        31.7       31.7         31.7
  Relief Setting (psig)                             220         220         220        220          220         220        220          220
  Standard Number of Passes                           3           3           3          3            2           2          2            2
30HXA OIL SEPARATOR
  Part No. 09RX400-                                 217         217         216         216         215         215         215         215
  Maximum Refrigerant Pressure (psig)               320         320         320         320         320         320         320         320
  Refrigerant Connections (in.)
    Discharge Circuit A/B                         21/8/21/8   21/8/21/8   21/8/21/8   21/8/21/8   21/8/21/8   21/8/21/8   21/8/21/8   21/8/21/8
    Liquid Circuit A/B                            11/8/11/8   11/8/11/8   11/8/11/8   11/8/11/8   11/8/11/8   11/8/11/8   11/8/11/8   11/8/11/8
  Relief Valve
    Connection (in. SAE Flare)                       5/          5/         5/           5/          5/        5/           5/           5/
                                                        8           8          8            8           8         8            8            8
    Flow Capacity (lb air/min)                      21.6        21.6       21.6         21.6        21.6      21.6         21.6         21.6
  Relief Setting (psig)                             320         320        320          320         320       320          320          320
CONDENSER (HXC)                                                           Shell and Tube with Enhanced Copper Tubes
  Part No. 09RX400-                                 257         257        258          258         259       259          260          260
  Net Fluid Volume (gal)                            16.8        16.8       18.3         18.3        23.9      23.9         27.5         27.5
  Maximum Refrigerant Pressure (psig)               220         220        220          220         220       220          220          220
  Maximum Water-Side Pressure (psig)                300         300        300          300         300       300          300          300
  Water Connections (in.)                                                          Victaulic Type Connection
    Inlet and Outlet (Standard Pass)                 5           5           5            5           5         5            5           5
    Drain (NPT) (Standard Pass)                      3/          3/         3/           3/          3/        3/            3/          3/
                                                          8           8        8            8           8         8               8           8
  Relief Valve
    Connection (in. NPTF)                            3/          3/          3/          3/          3/          3/          3/          3/
                                                          4           4           4           4           4           4           4           4
    Flow Capacity (lb air/min)                      31.7        31.7        31.7       31.7         31.7        31.7       31.7         31.7
  Relief Setting (psig)                             220         220         220        220          220         220        220          220
  Standard Number of Passes                          2           2           2          2            2           2          2            2
DISCHARGE LINE†
  Relief Valve
    Connection (in. SAE Flare)                       3/          3/          3/          3/          3/          3/          3/          3/
                                                        8           8           8           8           8           8           8           8
    Flow Capacity (lb air/min)                      6.3         6.3         6.3         6.3         6.3         6.3         6.3         6.3
    Setting (psig)                                  350         350         350         350         350         350         350         350
            LEGEND
NPTF — National Pipe Thread Female
SAE — Society of Automotive Engineers
*Charges listed are for 30HXC units. The 30HXA units are shipped with
 a nitrogen holding charge only. To determine the refrigerant charge
 requirements for 30HXA units see the System Refrigerant Charge for
 Start-Up table in the Application Data on page 29.
†Only on units with factory-installed suction service valves.
6
                                                               ENGLISH (cont)
UNIT SIZE 30HX                                       161           171            186          206           246            261         271
UNIT OPERATING WEIGHT (lb)
  Water-Cooled (HXC)                                7452          7660           7854        10,581        10,969         10,992      11,029
  Condenserless (HXA)                               5752          5777           5946         7,485         7,621          7,621       7,621
COMPRESSORS                                                                         Semi-Hermetic, Twin Screw
  Quantity                                            2             2              2            3             3              3            3
  Nominal Capacity per Compressor (tons)            80/56         66/80          80/80      66/39/80      80/56/80        80/66/80    80/80/80
  Economizer                                         Yes           Yes            Yes         Yes           Yes             Yes         Yes
  No. Capacity Steps
    30HXC Unit                                        6             6              6            8             8              8           8
    30HXA Unit (maximum on 30HXC unit
    with factory-installed option)                    8             8              8            11            11             11          11
  Minimum Step Capacity (%)
    30HXC Unit                                        20           20              20           13            13             13          13
    30HXA Unit (30HXC unit with factory-
    installed option)                                 10           10              10        7           7           7                   7
REFRIGERANT                                                                               R-134a
  Charge* (lb) Circuit A/Circuit B                 157/110      119/140    135/135        220/135     220/135     220/135             220/135
COOLER TYPE                                                             Shell and Tube with Enhanced Copper Tubes
  Part No. 10HX400-                                  601          611          621          631         632         632                632
  Net Fluid Volume (gal)                             28.5        28.5         33.4          43.1        47.2       47.2                47.2
  Maximum Refrigerant Pressure (psig)                220          220          220          220         220         220                220
  Maximum Water-Side Pressure (psig)                 300          300          300          300         300         300                300
  Water Connections
    Inlet and Outlet (in.) (Standard Pass)            5             5              5            6             6              6           6
    Drain (in. NPT) (Standard Pass)                   3/           3/              3/           3/            3/             3/          3/
                                                           8            8               8            8             8              8           8
  Relief Valve
    Connection (in. NPTF)                             3 /4         3 /4            3 /4         3 /4          3 /4          3/4         3 /4
    Flow Capacity (lb air/min)                       31.7         31.7            31.7         31.7          31.7          31.7        31.7
  Relief Setting (psig)                              220          220             220          220           220           220         220
  Standard Number of Passes                            2            2               2            2             2             2           2
30HXA OIL SEPARATOR
  Part No. 09RX400-                                  215          214             214          213           213            213         213
  Maximum Refrigerant Pressure (psig)                320          320             320          320           320            320         320
  Refrigerant Connections (in.)
    Discharge Circuit A/B                          21/8/21/8    21/8/21/8       21/8/21/8    21/8/21/8     21/8/21/8      21/8/21/8   21/8/21/8
    Liquid Circuit A/B                             13/8/13/8    13/8/13/8       13/8/13/8    15/8/13/8     15/8/13/8      15/8/13/8   15/8/13/8
  Relief Valve
    Connection (in. SAE Flare)                        5/           5/               5/                5/           5/       5/          5/
                                                         8            8                8                 8            8        8           8
    Flow Capacity (lb air/min)                       21.6         21.6            21.6               21.6        21.6      21.6        21.6
  Relief Setting (psig)                              320          320              320               320          320      320         320
CONDENSER (HXC)                                                             Shell and Tube with Enhanced Copper Tubes
  Part No. 09RX400-                                  261          262              262               263          264      264         264
  Net Fluid Volume (gal)                             30.6         37.6            37.6               47.6        55.1      55.1        55.1
  Maximum Refrigerant Pressure (psig)                220          220              220               220          220      220         220
  Maximum Water-Side Pressure (psig)                 300          300              300               300          300      300         300
  Water Connections (in.)                                                                Victaulic Type Connection
    Inlet and Outlet (Standard Pass)                  6             6                6                 8            8        8           8
    Drain (NPT) (Standard Pass)                       3 /8         3 /8             3 /8              3 /8         3 /8      3/8         3 /8
  Relief Valve
    Connection (in. NPTF)                             3/           3/              3/           3/            3/            3/          3/
                                                         4            4               4            4             4             4           4
    Flow Capacity (lb air/min)                       31.7         31.7            31.7         31.7          31.7          31.7        31.7
  Relief Setting (psig)                              220          220             220          220           220           220         220
  Standard Number of Passes                            2            2               2            2             2             2           2
DISCHARGE LINE†
  Relief Valve
    Connection (in. SAE Flare)                        3/           3/              3/           3/            3/             3/          3/
                                                         8            8               8            8             8              8           8
    Flow Capacity (lb air/min)                       6.3          6.3             6.3          6.3           6.3            6.3         6.3
    Setting (psig)                                   350          350             350          350           350            350         350
            LEGEND
NPTF — National Pipe Thread Female
SAE — Society of Automotive Engineers
*Charges listed are for 30HXC units. The 30HXA units are shipped with
 a nitrogen holding charge only. To determine the refrigerant charge
 requirements for 30HXA units see the System Refrigerant Charge for
 Start-Up table in the Application Data on page 29.
†Only on units with factory-installed suction service valves.
                                                                                                                                                  7
Physical data (cont)
                                                                          SI
UNIT SIZE 30HX                                      076         086              096         106         116         126         136         146
UNIT OPERATING WEIGHT (kg)
  Water-Cooled (HXC)                               2586         2597            2657       2803        2911       2933           3034        3048
  Condenserless (HXA)                              2140         2152            2194       2337        2342       2362           2408        2420
COMPRESSORS                                                                            Semi-Hermetic, Twin Screw
  Quantity                                           2           2                2          2           2          2             2           2
  Nominal Capacity per Compressor (kW)            137/137     162/137          197/137   232/137      232/137    232/197       281/197     281/232
  Economizer                                        No          No               No         No          No         No            No          No
  No. Capacity Steps
    30HXC Unit                                       6           6                6           6           6           6           6           6
    30HXA Unit (maximum on 30HXC unit
    with factory-installed option)                   8           8                8           8           8           8           8           8
  Minimum Step Capacity (%)
    30HXC Unit                                       20          20               20          20          20          20          20          20
    30HXA Unit (30HXC unit with factory-
    installed option)                                10          10               10          10          10         10           10          10
REFRIGERANT                                                                                       R-134a
  Charge* (kg) Circuit A/Circuit B               34.1/34.1    34.5/34.1        42.7/31.8 49.9/31.8 50.8/40.4 50.8/40.4         56.3/40.4   54.0/45.4
COOLER                                                                          Shell and Tube with Enhanced Copper Tubes
  Part No. 10HX400-                                401          401               402         408        406        406          405          405
  Net Fluid Volume (L)                             64.3         64.3             71.9        85.5        81.0       81.0         90.8        90.8
  Maximum Refrigerant Pressure (kPa)               1517         1517             1517        1517        1517      1517          1517        1517
  Maximum Water-Side Pressure (kPa)                2068         2068             2068        2068        2068      2068          2068        2068
  Water Connections
    Inlet and Outlet (in.) (Standard Pass)           4           4                4           5           5           5           5           5
    Drain (in. NPT) (Standard Pass)                  3/8         3 /8             3 /8        3 /8        3 /8        3 /8        3 /8        3 /8
  Relief Valve
    Connection (in. NPTF)                           3/          3/               3/          3/          3/          3/          3/          3/
                                                       4           4                4           4           4           4           4           4
    Flow Capacity (kg air/min)                     14.38       14.38            14.38       14.38       14.38       14.38       14.38       14.38
  Relief Setting (kPa)                             1517        1517             1517        1517        1517        1517        1517        1517
  Standard Number of Passes                          3           3                3           3           2           2           2           2
30HXA OIL SEPARATOR
  Part No. 09RX400-                                 217          217             216         216         215         215          215         215
  Maximum Refrigerant Pressure (kPa)               2205         2205            2205        2205        2205        2205         2205        2205
  Refrigerant Connections (in.)
    Discharge A/B                                 21/8/21/8   21/8/21/8        21/8/21/8   21/8/21/8   21/8/21/8   21/8/21/8   21/8/21/8   21/8/21/8
    Liquid A/B                                    11/8/21/8   11/8/11/8        11/8/11/8   11/8/11/8   11/8/11/8   11/8/11/8   11/8/11/8   11/8/11/8
  Relief Valve
    Connection (in. SAE Flare)                      5/           5/               5/          5/          5/        5/            5/          5/
                                                       8            8                8           8           8         8             8           8
    Flow Capacity (kg air/min)                     9.80         9.80            9.80         9.80        9.80      9.80          9.80        9.80
  Relief Setting (kPa)                             2206         2206            2206        2206        2206      2206           2206        2206
CONDENSER (HXC)                                                                Shell and Tube with Enhanced Copper Tubes
  Part No. 09RX400-                                257           257             258         258         259       259           260         260
  Net Fluid Volume (L)                             63.6         63.6            69.3         69.3        90.5      90.5         104.1       104.1
  Maximum Refrigerant Pressure (kPa)               1517         1517            1517        1517        1517      1517          1517        1517
  Maximum Water-Side Pressure (kPa)                2068         2068            2068        2068        2068      2068          2068        2068
  Water Connections (in.)                                                               Victaulic Type Connection
    Inlet and Outlet (Standard Pass)                 5           5                 5           5           5         5            5           5
    Drain (NPT) (Standard Pass)                      3/          3/               3/          3/          3/        3/            3/          3/
                                                          8           8              8           8           8         8               8           8
  Relief Valve
    Connection (in. NPTF)                            3/          3/               3/          3/          3/          3/          3/          3/
                                                          4           4                4           4           4           4           4           4
    Flow Capacity (kg air/min)                     14.38       14.38            14.38       14.38       14.38       14.38       14.38       14.38
  Relief Setting (kPa)                             1517        1517             1517        1517        1517        1517        1517        1517
  Standard Number of Passes                          2           2                2           2           2           2           2           2
DISCHARGE LINE†
  Relief Valve
    Connection (in. SAE Flare)                      3/           3/              3/          3/          3/          3/           3/          3/
                                                       8            8               8           8           8           8            8           8
    Flow Capacity (kg air/min)                      2.9          2.9             2.9         2.9         2.9         2.9          2.9         2.9
    Relief Pressure (kPa)                          2413         2413            2413        2413        2413        2413         2413        2413
            LEGEND
NPTF — National Pipe Thread Female
SAE — Society of Automotive Engineers
*Charges listed are for 30HXC units. The 30HXA units are shipped with
 a nitrogen holding charge only. To determine the refrigerant charge
 requirements for 30HXA units see the System Refrigerant Charge for
 Start-Up table in the Application Data on page 29.
†Only on units with factory-installed suction service valves.
8
                                                                      SI (cont)
UNIT SIZE 30HX                                    161           171               186         206         246            261           271
UNIT OPERATING WEIGHT (kg)
  Water-Cooled (HXC)                              3381         3475           3564         4799           4976          4986          5003
  Condenserless (HXA)                             2610         2621           2698         3395           3457          3457          3457
COMPRESSORS                                                                        Semi-Hermetic, Twin Screw
  Quantity                                         2             2              2            3              3            3              3
  Nominal Capacity per Compressor (kW)          281/197       232/281        281/281    232/137/281 281/197/281     281/232/281    281/281/281
  Economizer                                      Yes           Yes            Yes          Yes            Yes          Yes            Yes
  No. Capacity Steps
    30HXC Unit                                     6             6                 6           8           8              8             8
    30HXA Unit (maximum on 30HXC unit
    with factory-installed option)                 8             8                 8           11          11             11            11
  Minimum Step Capacity (%)
    30HXC Unit                                     20            20                20          13          13             13            13
    30HXA Unit (30HXC unit with factory-
    installed option)                              10            10                10          7            7            7              7
REFRIGERANT                                                                                 R-134a
  Charge* (kg) Circuit A/Circuit B              71.3/49.9    54.0/63.6       61.3/61.3     90.8/61.3    99.9/61.3    99.9/61.3      99.9/61.3
COOLER                                                                     Shell and Tube with Enhanced Copper Tubes
  Part No. 10HX400-                               601           611             621           631          632          632            632
  Net Fluid Volume (L)                           107.9         107.9          126.4          163.2        178.7        178.8          178.7
  Maximum Refrigerant Pressure (kPa)             1517          1517            1517          1517         1517         1517           1517
  Maximum Water-Side Pressure (kPa)              2068          2068            2068          2068         2068         2068           2068
  Water Connections
    Inlet and Outlet (in.) (Standard Pass)         5             5                 5           6           6              6             6
    Drain (in. NPT) (Standard Pass)                3/            3/                3/          3/          3/             3/            3/
                                                        8             8                 8           8           8              8             8
  Relief Valve
    Connection (in. NPTF)                         3 /4          3/4             3 /4          3 /4        3 /4           3 /4          3 /4
    Flow Capacity (kg air/min)                   14.28         14.38           14.38         14.38       14.38          14.38         14.38
  Relief Setting (kPa)                           1517          1517            1517          1517        1517           1517          1517
  Standard Number of Passes                        2             2               2             2           2              2             2
30HXA OIL SEPARATOR
  Part No. 09RX400-                                215          214                214        213         213            213           213
  Maximum Refrigerant Pressure (kPa)              2205         2205               2205       2205        2205           2205          2205
  Refrigerant Connections (in.)
    Discharge A/B                               21/8/21/8     21/8/21/8       21/8/21/8     21/8/21/8   21/8/21/8      21/8/21/8     21/8/21/8
    Liquid A/B                                  13/8/13/8     13/8/13/8       13/8/13/8     15/8/13/8   15/8/13/8      15/8/13/8     15/8/13/8
  Relief Valve
    Connection (in. SAE Flare)                     5/           5/               5/               5/           5/        5/            5/
                                                      8            8                8                8            8         8             8
    Flow Capacity (kg air/min)                    9.80         9.80            9.80              9.80         9.80      9.80          9.80
  Relief Setting (kPa)                            2206         2206            2206             2206          2206      2206          2206
CONDENSER (HXC)                                                            Shell and Tube with Enhanced Copper Tubes
  Part No. 09RX400-                               261           262             262              263          264        264           264
  Net Fluid Volume (L)                           115.8         142.3          142.3             177.9        208.6      208.6         208.6
  Maximum Refrigerant Pressure (kPa)             1517          1517            1517             1517          1517      1517          1517
  Maximum Water-Side Pressure (kPa)              2068          2068            2068             2068          2068      2068          2068
  Water Connections (in.)                                                             Victaulic Type Connection
    Inlet and Outlet (Standard Pass)               6             6                6                8            8         8             8
    Drain (NPT) (Standard Pass)                    3 /8          3/8             3 /8             3 /8         3 /8       3 /8          3 /8
  Relief Valve
    Connection (in. NPTF)                         3/            3/              3/            3/          3/             3/            3/
                                                     4             4               4             4           4              4             4
    Flow Capacity (kg air/min)                   14.38         14.38           14.38         14.38       14.38          14.38         14.38
  Relief Setting (kPa)                           1517          1517            1517          1517        1517           1517          1517
  Standard Number of Passes                        2             2               2             2           2              2             2
DISCHARGE LINE†
  Relief Valve
    Connection (in. SAE Flare)                     3/           3/                 3/         3/          3/             3/            3/
                                                      8            8                  8          8           8              8             8
    Flow Capacity (kg air/min)                     2.9          2.9                2.9        2.9         2.9            2.9           2.9
    Relief Pressure (kPa)                         2413         2413               2413       2413        2413           2413          2413
            LEGEND
NPTF — National Pipe Thread Female
SAE — Society of Automotive Engineers
*Charges listed are for 30HXC units. The 30HXA units are shipped with
 a nitrogen holding charge only. To determine the refrigerant charge
 requirements for 30HXA units see the System Refrigerant Charge for
 Start-Up table in the Application Data on page 29.
†Only on units with factory-installed suction service valves.
                                                                                                                                                 9
Options and accessories
                                                                                FACTORY-                         FIELD-
                                  ITEM                                         INSTALLED                       INSTALLED
                                                                                 OPTION                       ACCESSORY
Wye-Delta Start                                                                    X
Brine                                                                              X
Minus-One-Pass Cooler Head                                                         X
Plus-One-Pass Cooler Head                                                          X
Control Power Transformer                                                                                          X
Minimum Load Control                                                                X                              X
Sound Reduction Enclosure                                                                                          X
Vibration Isolation                                                                                                X
Temperature Reset Sensor                                                                                           X
Chillervisor System Manager III                                                                                    X
Cooler Head Insulation                                                                                             X
Suction Service Valves                                                              X
Energy Management Module                                                            X                              X
Nitrogen Holding Charge (30HXC)                                                     X
BACnet Communications                                                               X
Factory-installed options                                          temperature reset. These types of reset are available with
Wye-delta start — Generally, Wye-delta start is not                the main board. However, an accessory thermistor is
required when using multiple compressors since the start-          required for outdoor air and/or space temperature reset.)
ing current is generally less than with one larger compres-        Demand limiting allows the unit capacity to be limited dur-
sor using Wye-delta start. Wye-delta start is standard on          ing periods of peak energy usage. Demand limit requires
208/230 v, 60 Hz, 230 v, 60 Hz, and 230 v, 50 Hz units.            an external 4 to 20 mA signal or a 2-step remote pair of
It is available as a factory-installed option for all other unit   dry contacts. Both the 4 to 20 mA and 2-step demand
voltages.                                                          limit percentage values are adjustable. EMM is also avail-
                                                                   able as a field-installed accessory.
Brine — The brine option permits supply liquid tempera-
tures to be set below 40 F (4.4 C). Refrigeration circuit          Nitrogen holding charge — The 30HXC units can be
components, such as the expansion device, are modified at          shipped with either the standard HFC-134a refrigerant
the factory to correct for the lower refrigeration flow rates.     charge or an optional nitrogen charge. The 30HXA units
Special installation requirements apply to brine units. See        are always shipped with a nitrogen holding charge.
Cooler and Water-Cooled Condenser Freeze Protection                BACnet communication option — Provides factory
section, page 24.                                                  installed communication capability with a BACnet MS/TP
Minus-one-pass cooler — This factory-installed option              network. Allows integration with i-Vu® Open control sys-
reduces pressure drop for high flow applications and/or            tem or a BACnet building automation system.
provides same end inlet and outlet for 076-106 sizes, or           Field-installed accessories
opposite end inlet and outlet on 116-271 sizes.
                                                                   Control power transformer — The transformer is sized
Plus-one-pass cooler — This factory-installed option               to supply the needs of the control circuit, sourcing power
improves low temperature brine performance. See the                from the main unit power connection.
30HX electronic catalog for performance data.
                                                                   Minimum load control — This accessory allows addi-
Minimum load control — This option allows additional               tional capacity reduction for unit operation below the mini-
capacity reduction for unit operation below the minimum            mum step of unloading (down to 10% of full load capacity).
step of unloading (down to 10% of full load capacity).             Minimum load control is also available as a factory-installed
Minimum load control is also available as a field-installed        option.
accessory.
                                                                   Sound reduction enclosure — This kit contains a
Suction service valves — Standard refrigerant dis-                 sound enclosure that covers the entire unit to reduce sound
charge isolation and liquid valves enable service personnel        levels.
to store the refrigerant charge in the cooler or condenser
                                                                   Vibration isolation — Neoprene isolators are field
during servicing. This factory-installed option allows further
isolation of the compressor from the cooler vessel.                installed to reduce vibration transmission from the com-
                                                                   pressor through the floor and into the conditioned space.
Energy management module (EMM) — The EMM is
                                                                   Temperature reset sensor — This accessory sensor
used for 4 to 20 mA leaving fluid temperature reset, cool-
ing point reset, 4 to 20 mA demand limit and two-step              provides temperature reset capability from either the occu-
demand limit. Temperature reset lets the unit reset the            pied space or outdoor-air temperature.
leaving fluid temperature to a higher temperature during           NOTE: Temperature reset capability using return tempera-
low load conditions. Temperature reset can also be accom-          ture is standard.
plished based on return fluid, outdoor air or space temper-
ature. (The EMM option is not required when using                  *Sponsored by ASHRAE (American Society of Heating, Refrigerating,
entering-water, outdoor-air, or space temperature for              and Air Conditioning Engineers).
10
Chillervisor System Manager III — This control can be        temperature. (The EMM option is not required when using
used to regulate up to eight 30HXA or 30HXC chillers.        entering-water, outdoor-air, or space temperature for tem-
Cooler head insulation — This accessory is designed          perature reset. These types of reset are available with the
with flexible, 3/4 in. (19 mm) PVC foam (closed-cell) to     main board. However, an accessory thermistor is required
insulate the cooler heads to minimize heat loss and head     for outdoor air and/or space temperature reset.) Demand
sweating.                                                    limiting allows the unit capacity to be limited during periods
                                                             of peak energy usage. Demand limit requires an external 4
Energy management module (EMM) — The EMM is                  to 20 mA signal or a 2-step remote pair of dry contacts.
used for 4 to 20 mA leaving fluid temperature reset, cool-
                                                             Both the 4 to 20 mA and 2-step demand limit percentage
ing point reset, 4 to 20 mA demand limit and two-step        values are adjustable. EMM is also available as a factory-
demand limit. Temperature reset lets the unit reset the      installed option.
leaving fluid temperature to a higher temperature during
low load conditions. Temperature reset can also be accom-    Consult factory for other available options not
plished based on return fluid, outdoor air or space          listed here.
                                                                                                                        11
12
                                                                                              30HXC076-106
                                                                                                             NOTES:
                                                                           WGT DISTRIBUTION AT EACH           1. Operating weight includes weight of water and refrigerant.
                 OPERATING                                                     MTG PLATE - lb (kg)
       UNIT                          B        C       E        L
                WEIGHT - lb (kg)                                                                              2.        Denotes center of gravity.
                                                                        1     2     3     4       5   6
                      5700          45.87    45.87   32.50    65.22    738   943   595 1110 1418 896          3. Dimensions are in inches (mm).
     30HXC076                                                                                                 4. Recommended service clearance around machine is 36 in. (914.4 mm).
                     (2586)        (1165)   (1165)   (826)   (1657)   (335) (428) (270) (503) (643) (406)
                                                                                                              5. Victaulic nozzles are standard on all models. Flow switch factory
     30HXC086         5723          45.87    45.87   32.50    65.22    738   947   597 1112 1427 902             installed in cooler inlet victaulic nozzle.
                     (2597)        (1165)   (1165)   (826)   (1657)   (335) (430) (271) (504) (647) (409)
     30HXC096         5855          54.12    37.63   32.50    65.22    686   968   693 1027 1447 1034
                     (2657)        (1375)    (956)   (826)   (1657)   (311) (439) (314) (466) (656) (469)
                                                                                                                                                                                      Dimensions
                      6177          54.12    37.63   33.50    67.22    730 1028 744 1073 1510 1092
     30HXC106
                     (2803)        (1375)    (956)   (851)   (1707)   (331) (466) (337) (487) (685) (495)
                                                                               a30-4647.eps
                                                                               30HXC116-146
                                                                         NOTES:
                                        WGT DISTRIBUTION AT EACH          1. Operating weight includes weight of water and refrigerant.
                 OPERATING                  MTG PLATE - lb (kg)
       UNIT
                WEIGHT - lb (kg)                                          2.        Denotes center of gravity.
                                     1     2     3     4       5   6
                      6415          728 1114 777 1053 1615 1127           3. Dimensions are in inches (mm).
     30HXC116                                                             4. Recommended service clearance around machine is 36 in.
                     (2911)        (330) (505) (352) (478) (733) (511)
                                                                             (914.4 mm).
                      6465          738 1127 780 1061 1628 1131           5. Victaulic nozzles are standard on all models. Flow switch fac-
     30HXC126
                     (2933)        (335) (511) (354) (481) (738) (513)       tory installed in cooler inlet victaulic nozzle.
                      6688          758 1176 811 1083 1689 1171
     30HXC136
                     (3034)        (344) (533) (368) (491) (766) (531)
     30HXC146         6718          763 1182 815 1085 1697 1172
                     (3048)        (346) (536) (370) (492) (770) (532)
                                                                                                                                              a30-4648
13
14
                                                                                     30HXC161-186
                                                                                    NOTES:
                OPERATING                          WGT DISTRIBUTION AT EACH          1. Operating weight includes weight
       UNIT      WEIGHT -     B        C               MTG PLATE - lb (kg)              of water and refrigerant.
                  lb (kg)                       1     2     3     4       5   6      2.       Denotes center of gravity.
                   7452      72.12    50.63    817 1272 908 1219 1890 1346
     30HXC161                                                                        3. Dimensions are in inches (mm).
                  (3381)    (1832)   (1286)   (371) (577) (412) (553) (857) (610)
                                                                                     4. Recommended service clearance
                   7660      61.37    61.37    936 1318 840 1379 1946 1241              around machine is 36 in.
     30HXC171     (3475)    (1559)   (1559)   (425) (598) (381) (626) (883) (563)       (914.4 mm).
                   7854      61.37    61.37    962 1361 860 1410 1996 1265           5. Victaulic nozzles are standard on
     30HXC186     (3564)    (1559)   (1559)   (436) (617) (390) (640) (905) (574)       all models. Flow switch factory
                                                                                        installed in cooler inlet victaulic
                                                                                        nozzle.
                                                                                                                                         Dimensions (cont)
                                                                                                                              a30-4649
                                                                                         30HXC206-271
                                                                                              NOTES:
                                                   WGT DISTRIBUTION AT EACH                    1. Operating weight includes weight of water and refrigerant.
                 OPERATING                               MTG PLATE - lb (kg)
       UNIT                         A
                WEIGHT - lb (kg)                                                               2.        Denotes center of gravity.
                                             1         2      3     4        5     6
                     10581         33.88    948      2406 1243 1201 3133         1650          3. Dimensions are in inches (mm).
     30HXC206                                                                                  4. Recommended service clearance around machine is 36 in. (914.4 mm).
                     (4799)        (860)   (430)    (1091) (564) (545) (1421)    (748)
                                                                                               5. Victaulic nozzles are standard on all models. Flow switch factory installed
     30HXC246        10969         34.38    985      2515 1306 1154 3276         1733             in cooler inlet victaulic nozzle.
                     (4976)        (873)   (447)    (1141) (592) (523) (1486)    (786)
                     10992         34.38    985      2520 1311 1154 3283         1739
     30HXC261
                     (4986)        (873)   (447)    (1143) (595) (523) (1489)    (789)
                     11029         34.38    985      2529 1318 1154 3294         1749
     30HXC271        (5003)        (873)   (447)    (1147) (598) (523) (1494)    (793)
15
16
                                                                                                    30HXA076-106
     NOTES:
      1. Operating weight includes weight of water and
         refrigerant.
      2.          Denotes center of gravity.
      3. Dimensions are in inches (mm).
      4. Recommended service clearance around
         machine is 36 in. (914.4 mm).
      5. Victaulic nozzles are standard on all models.
         Flow switch factory installed in cooler inlet vic-
         taulic nozzle.
                                                                       30HXA116-146
     NOTES:
      1. Operating weight includes weight of water and
         refrigerant.
      2.        Denotes center of gravity.
      3. Dimensions are in inches (mm).
      4. Recommended        service    clearance    around
         machine is 36 in. (914.4 mm).
      5. Victaulic nozzles are standard on all models. Flow
         switch factory installed in cooler inlet victaulic
         nozzle.
17
18
                                                                                          30HXA161-186
     NOTES:
      1. Operating weight includes weight of water and refrigerant.
      2.          Denotes center of gravity.
      3. Dimensions are in inches (mm).
      4. Recommended service clearance around machine is 36 in.
         (914.4 mm).
      5. Victaulic nozzles are standard on all models. Flow switch
         factory installed in cooler inlet victaulic nozzle.
                                                                                       30HXA206-271
     NOTES:
      1. Operating weight includes weight of water and refrigerant.
      2.        Denotes center of gravity.
      3. Dimensions are in inches (mm).
      4. Recommended service clearance around machine is 36 in. (914.4 mm).
      5. Victaulic nozzles are standard on all models. Flow switch factory installed
         in cooler inlet victaulic nozzle.
19
20
                                                                           ACCESSORY SOUND ENCLOSURE
                                                                                                                                                         Dimensions (cont)
     NOTES:                                                                  6. Recommended control wiring entry area. Notch to suit and cover/
     1. Dimensions are in inches (millimeters).                                 insulate remaining open area for acoustic purposes.
     2. Recommended service clearance around machine is 36 in. (914.4).      7. Recommended cooler relief valve vent line and 30HXC condenser relief
     3. Unused portion of piping openings must be closed and insulated          vent line entry area. The 30HXA discharge and liquid line entry areas
        for acoustic purposes. Use filler panel in accessory package.           are on opposite side. Notch enclosure to suit particular installation.
     4. Field-fabricated holes must be closed and insulated for acoustic     8. Model in drawing is typical and represents 30HX116-146 sizes in the
        purposes.                                                               30HX-900---001 accessory sound enclosure.
     5. Recommended electrical power supply area. Notch to suit and          9. Sound enclosure accessory should be aligned to the center lines of the
        cover/insulate remaining open area for acoustic purposes.               control panel access and piping openings.
                                   WEIGHT DISTRIBUTION AT MOUNTING PLATES
                                                                                        5.00
                                                                                     (127.00)
                                                                          0.88
                                                                        (22.35)         3.25
                                                                                      (82.55)
                                                                                                        1.42
                                                                                                      (36.07)
                                                                                                   2.17
                                                                   0.50 DIA                      (53.34)
                                                                   (4) HOLES
WEIGHT DISTRIBUTION AT EACH MOUNTING PLATE                                                               3.58
                                                                                                       (90.93)
                                                                                                                        21
Application data
Unit storage                                                        Temperature can also be reset using a 4 to 20 mA signal
Provide machine protection — Store machine and                   from the control system. This type of reset requires the
starter indoors, protected from construction dirt and            energy management module accessory.
moisture. Inspect under shipping tarps, bags, or crates to       Condenser fluid temperature
be sure water has not collected during transit. Keep protec-
                                                                  1. Maximum leaving condenser fluid temperature is
tive shipping covers in place until machine is ready for
installation.                                                        110 F (43 C) on all 30HXC units.
                                                                  2. Standard 30HXC units will start at entering con-
Unit location                                                        denser fluid temperatures above 55 F (12.8 C). In
Unit should be level (particularly in its major lengthwise           general, however, continuous machine operation with
dimension) to assure proper oil return.                              entering condenser fluid temperatures below 70 F
  The unit should be located indoors in an area of temper-           (21.1 C) is not recommended. When the entering
ature between 50 to 104 F (10 to 40 C).                              condenser fluid temperature is expected to drop
                                                                     below 70 F (21.1 C), it is recommended that some
  Good acoustic design practice should be followed, i.e.,            form of condenser flow control be used to optimize
unit should not be located adjacent to sound-sensitive areas
                                                                     performance. Tower pump, bypass valves, or flow
unless appropriate consideration has been made.                      regulating valves may be controlled by a 4 to 20 mA
Cooler fluid temperature                                             output from the 30HXC control (60-second open to
 1. Maximum leaving water (fluid) temperature (LWT) is               close time recommended for actuator).
    60 F (21 C). Unit can start and pull down with up to         Cooler and water-cooled condenser
    95 F (35 C) entering water (fluid) temperature due to        temperature rise
    MOP (maximum operating pressure) feature of the
                                                                 Ratings and performance data in this publication are for a
    expansion valve. For sustained operation, it is recom-
                                                                 cooling temperature rise of 10° F (5.6° C). Units may be
    mended that entering fluid temperature not exceed
                                                                 operated at a different temperature rise, provided flow lim-
    70 F (21.1 C).
                                                                 its are not exceeded and corrections to capacity, etc., are
 2. Minimum LWT is 40 F (4.4 C) for standard units.              made. For minimum flow rates, see the Minimum Flow
    The brine option is required for operation with              Rates table. High flow rate is limited by pressure drop that
    leaving fluid temperatures in the range of 39 to 14 F        can be tolerated.
    (4 to –9 C). For ratings below 40 F (4.4 C) LWT,
                                                                 Minimum cooler flow — Flow (maximum cooler tem-
    contact your local Carrier representative.
                                                                 perature rise) is shown in the Minimum Flow Rates table.
 3. Minimum entering water (fluid) temperature (EWT) is          Minimum flow rate must be maintained to prevent fouling.
    45 F (7.2 C). Maximum EWT is 70 F (21.1 C).                  When gpm (L/s) required is lower (or rise is higher), follow
Leaving-fluid temperature reset                                  recommendations below:
The accessory reset sensor can be applied to the chiller to        1. Multiple smaller chillers can be applied in series, each
provide reset of in LWT constant fluid flow systems. Reset             providing a portion of the design temperature rise.
reduces compressor power usage at part load when design            2. Chilled fluid can be recirculated to raise flow rate.
LWT is not necessary. Humidity control should be consid-               However, mixed temperature entering cooler must be
ered, since higher coil temperatures resulting from reset              maintained at a minimum of at least 5° F (2.8° C)
will reduce latent heat capacity. Three reset applications             above the leaving chilled fluid temperature.
are offered:                                                       3. Special plus one-pass cooler can be used. Contact
From return-fluid temperature — Increases LWT set                      your Carrier representative for further information.
point as return (or entering) fluid temperature decreases        Maximum cooler flow (> 5 gpm/ton or < 5° F rise
(indicating load decrease). Reset from return fluid may be       [> 0.09 L/s · kW or < 2.7° C rise]) — Maximum flow
used in any application where return fluid provides accu-        results in practical maximum pressure drop through cooler.
rate load indication. Limitation of return-fluid reset is that   Special minus-one-pass cooler can be used to reduce pres-
the LWT may only be reset to value of design return-fluid        sure drop. Contact your Carrier representative.
temperature. No additional hardware is required.                    Return fluid can bypass the cooler to keep pressure drop
From outdoor-air temperature — Increases LWT as                  through cooler within acceptable limits. This permits a
outdoor ambient temperature decreases (indicating load           higher T with lower fluid flow through cooler and mixing
decrease). This reset should be applied only where outdoor       after the cooler. Contact your Carrier representative if
ambient temperature is an accurate indication of load. A         pressure drop appears excessive.
field-supplied thermistor is required.                           Variable cooler flow rates — These variable rates may
From occupied space temperature — Increases LWT                  be applied to standard 30HX series chillers. However, the
as space temperature decreases (indicating load decrease).       unit will attempt to maintain a constant leaving chilled-fluid
This reset should be applied only where space temperature        temperature. In such cases, minimum fluid loop volume
is an accurate indication of load. A field-supplied thermis-     must be in excess of 3 gal per ton (3.2 L per kW) and flow
tor is required.                                                 rate must change in steps of less than 10% per minute.
                                                                 Apply 6 gal per ton (6.5 L per kW) fluid loop volume mini-
                                                                 mum if flow rate changes more rapidly.
22
Minimum water-cooled condenser flow — This value
(maximum rise) is shown in Minimum Flow Rates table.                                                    RECIRCULATION FLOW
Ensure leaving-fluid temperature does not exceed 105 F
(40.5 C).
                       MINIMUM FLOW RATES
                                  COOLER           MIN. FLOW      COOLER TEMP
                   UNIT                              RATE*         DIFFERENCE
    DEVICE         SIZE
                   30HX      No. of
                             Passes      Type      GPM      L/s     F        C
                               2       Minus 1     136.0    8.6     13       7.4
                    076        3       Standard     90.0    5.7     20      11.1
                               4        Plus 1      68.0    4.3     27      14.8
                               2       Minus 1     149.0    9.4     13       7.4
                    086        3       Standard    100.0    6.3     20      11.1      Oversizing chillers
                               4        Plus 1      75.0    4.7     27      14.8
                               2       Minus 1     169.0   10.7     13       7.4      Oversizing chillers by more than 15% at design conditions
                    096        3       Standard    113.0    7.1     20      11.1      must be avoided as the system operating efficiency will be
                               4        Plus 1      85.0    5.3     27      14.8      adversely affected (resulting in greater and/or excessive
                               2       Minus 1     188.0   11.8     13       7.4      electrical demand and cycling of compressors). When
                    106        3       Standard    125.0    7.9     20      11.1
                                                                                      future expansion of equipment is anticipated, install a sin-
                               4        Plus 1      94.0    5.9     27      14.8
                               1       Minus 1     272.0   17.2     10       5.6
                                                                                      gle chiller to meet present load requirements, and install a
                    116        2       Standard    136.0    8.6     20      11.1      second chiller to meet the additional load demand.
                               3        Plus 1      91.0    5.7     30      16.7         It is also recommended that the installation of 2 smaller
                               1       Minus 1     295.0   18.6     10       5.6
                                                                                      chillers be considered where operation at minimum load is
                    126        2       Standard    147.0    9.3     20      11.1
                               3        Plus 1      98.0    6.2     30      16.7
                                                                                      critical. The operation of 2 small chillers at higher loading
                               1       Minus 1     327.0   20.7     10       5.6      is preferred to operating a single chiller at or near its mini-
                    136        2       Standard    164.0   10.3     20      11.1      mum recommended value.
                               3        Plus 1     109.0    6.9     30      16.7
                                                                                         The minimum load control accessory should not be used
                               1       Minus 1     350.0   22.1     10       5.6
   COOLER           146        2       Standard    175.0   11.0     20      11.1
                                                                                      as a means to allow oversizing chillers. Minimum load con-
                               3        Plus 1     117.0    7.4     30      16.7      trol should be given consideration where substantial oper-
                               1       Minus 1     376.0   23.7     10       5.6      ating time is anticipated below the minimum unloading
                    161        2       Standard    188.0   11.9     20      11.1      step.
                               3        Plus 1     125.0    7.9     30      16.7
                               1       Minus 1     399.0   25.2     10       5.6      Parallel chillers
                    171        2       Standard    199.0   12.6     20      11.1
                                                                                      Where chiller capacities greater than can be supplied by a
                               3        Plus 1     133.0    8.4     30      16.7
                               1       Minus 1     426.0   26.9     10       5.6
                                                                                      single 30HX chiller are required, or where stand-by capa-
                    186        2       Standard    213.0   13.4     20      11.1      bility is desired, chillers may be installed in parallel. Units
                               3        Plus 1     142.0    9.0     30      16.7      may be of the same or different sizes. However, cooler and
                               1       Minus 1     508.0   32.1     10       5.6      condenser flow rates must be balanced to ensure proper
                    206        2       Standard    254.0   16.0     20      11.1      flow to each chiller. The standard 30HX ComfortLink™
                               3        Plus 1     169.0   10.7     30      16.7
                                                                                      controls can be configured to provide lead/lag control
                               1       Minus 1     597.0   37.7     10       5.6
                    246        2       Standard    309.0   18.8     20      11.1
                                                                                      for two chillers. The accessory Chillervisor System Man-
                               3        Plus 1     199.0   12.6     30      16.7      ager III control may be used for proper leaving chilled fluid
                               1       Minus 1     618.0   39.0     10       5.6      temperature control and to ensure proper staging
                    261        2       Standard    309.0   19.5     20      11.1      sequence of up to 8 chillers. Refer to the accessory
                               3        Plus 1     206.0   13.0     30      16.7      Chillervisor System Manager III installation instructions for
                               1       Minus 1     642.0   40.5     10       5.6
                                                                                      further details.
                    271        2       Standard    321.0   20.3     20      11.1
                               3        Plus 1     214.0   13.5     30      16.7      Series chillers
                  076,086      2          —         105     6.6     —        —
                  096,106      2          —         135     8.5     —        —        Chillers in series may be used for capacities greater than
                  116,126      2          —         170    10.7     —        —        those supplied by a single 30HX chiller. Using the minus-
                  136,146      2          —         195    12.3     —        —        one-pass cooler head option, fluid pressure drop across the
 CONDENSER
                    161        2          —         235    14.8     —        —        cooler can be held to reasonable levels. The leaving fluid
                  171,186      2          —         255    16.1     —        —
                                                                                      temperature sensors need not be relocated. However, the
                    206        2          —         273    17.2     —        —
                    246        2          —         333    21.0     —        —
                                                                                      cooler minimum entering fluid temperature limitations
                    261        2          —         333    21.0     —        —        should be considered for the chillers located downstream of
                    271        2          —         333    21.0     —        —        other chillers. The standard 30HX control can control two
*Based on 20 F (11.1 C) temperature difference at AHRI conditions.                    30HX chillers in series. Condensers should be piped in
NOTES:                                                                                parallel to maximize capacity and efficiency. This should
 1. The 30HX units will start with loop temperatures up to 95 F (35 C).
 2. Minimum flow rate shown is based on AHRI Ratings and is for reference only.       also minimize condenser pressure drop and saturated con-
    20 F (11.1 C) is the maximum cooler temperature differential that will            densing temperatures. However, if condensers are piped in
    determine actual minimum flow rate.
 3. To obtain proper temperature control, loop fluid volume must be at least 3 gal/   series, ensure that the leaving fluid temperature does not
    ton (3.23 L/kW) of chiller nominal capacity for air conditioning and at least
    6 gal/ton (6.5 L/kW) for process applications.
                                                                                      exceed 105 F (40.5 C) on standard machines.
                                                                                                                                                 23
Application data (cont)
Energy management
Demand limiting and load shedding are popular techniques                              TANK INSTALLATION
used to reduce peak electric demands typically experienced
during hot summer days when air conditioning loads are
highest. When utility electricity demands exceed a certain
level, electrical loads are turned off to keep the peak
demands below a prescribed maximum limit. Compressor
unloading reduces electrical demand while allowing the
chiller to operate under part-load capacity and to maintain
partial chilled fluid cooling.
   Electrical demand can be limited through demand limit
input to chiller control which unloads the chiller to a prede-
termined percentage of the load. One stage of unloading
can be initiated by a remote signal to significantly reduce
the chiller power consumption. This power reduction                Fouling factor
applies to the full load power at nominal conditions. The          The factor used to calculate tabulated ratings for the cooler
demand limit control should not be cycled less than                is 0.00010 ft2 · hr · F/Btu (0.000018 m2 · K/W), and for
10 minutes on and 5 minutes off.                                   the condenser is 0.00025 ft2 · hr · F/Btu (0.00044 m2 ·
                                                                   K/W). As fouling factor is increased, unit capacity
Duty cycling                                                       decreases and compressor power increases. To determine
Duty cycling will cycle an electrical load at regular intervals,   selections at other fouling factors, use the chiller program
regardless of electrical demand. This reduces the electrical       in the electronic catalog.
demand by “fooling” demand measuring devices. Duty
cycling of the entire compressor is NOT recommended                Cooler and water-cooled condenser freeze
since motor windings and bearings will be damaged by               protection
constant cycling.                                                  If chiller refrigerant or fluid lines are in an area where ambi-
                                                                   ent conditions fall below 32 F (0° C), it is recommended
Wye-delta start                                                    that an antifreeze solution be added to protect the unit and
Wye-delta start is standard on 30HX 208/230-v, 60-Hz               fluid piping to a temperature 12° F (6.7° C) below the
units and 230-v, 50-Hz units and optional on all other             lowest anticipated temperature. For corrections to perfor-
30HX units. This feature is not always required on 30HX            mance, refer to the chiller program in the electronic
units due to the use of multiple compressors that allow small      catalog.
electrical load increments, but is available if required. Maxi-       Use only antifreeze solutions approved for heat
mum instantaneous current flow (see ICF in Electrical Data         exchanger duty. Use of automotive antifreezes is not rec-
tables on pages 36-39) should be used in determining need.         ommended because of the fouling that can occur once
Vibration isolation                                                their relatively short-lived inhibitors break down.
External vibration isolators are available as field-installed         If the system will not be used during freezing weather
accessories.                                                       conditions and the chiller and fluid piping are not protected
                                                                   with an antifreeze solution, it is recommended that the
Strainers                                                          chiller and outdoor piping be drained.
A strainer with a minimum screen size of 20 mesh must be              Refer to Cooler Fluid Temperature section, page 22, for
installed in both the cooler and condenser fluid lines, within     leaving fluid temperature for brine units. When leaving
10 ft (3 m) of the inlets to both the cooler and condenser.        chilled fluid temperatures will be lower than 40 F (4.4 C),
For 30HXA units, this requirement applies only to the              an appropriate antifreeze solution must be used in the
cooler.                                                            cooler. In addition, the following special installation instruc-
Chilled fluid loop volume                                          tions will apply:
The chilled fluid loop volume in circulation must equal or           1. In addition to the factory-mounted chilled water flow
exceed 3 gal per nominal ton of cooling (3.2 L per kW) for               switch, a field-supplied condenser water flow switch
temperature stability and accuracy in normal air condition-              must be installed.
ing applications. For example, a 30HXC096 with a nomi-               2. The chiller must control both the chilled water pump
nal capacity of 94.0 tons would require 282 gal (1067.4 L)               and the condenser pump. The cooler pump must
in circulation in the system loop.                                       operate for a minimum of 10 minutes after the chiller
   For process jobs where accuracy is vital, or for operation            has shut down and the condenser pump must operate
at ambient temperatures below 32 F (0° C) with low unit                  for a minimum of 30 minutes after the chiller has shut
loading conditions, there should be from 6 to 10 gal per                 down. In the event of a loss of condenser water flow,
ton (6.5 to 10.8 L per kW). To achieve this volume, it is                the flow of chilled fluid to the evaporator must be
often necessary to install a tank in the loop. Tank should be            stopped or the isolation valve must be closed. This is
baffled to ensure there is no stratification, and that water             necessary to reduce the possibility of condenser
(or brine) entering the tank is adequately mixed with liquid             freeze-up.
in the tank. See Tank Installation drawing.
24
 3. Condenser head pressure control valves must not                air back into a condenser can increase condensing
    reduce condenser flow below 0.75 gallons per ton               temperatures and may significantly reduce capacity
    (0.4 L/s per kW) or the lowest detectable flow level of        and efficiency. Unit shut down may occur if condens-
    the condenser water flow switch. For further informa-          ing temperatures exceed the maximum set point.
    tion, refer to the 30HX Installation Instructions or           Airflow patterns are complex and beyond the scope
    contact your Carrier representative.                           of equipment manufacturer prediction. Consultation
                                                                   with a specialist may be required in some
30HXA remote condenser requirements                                applications.
 1. Do not manifold independent refrigerant circuits into
                                                              14. Units with vertical fan discharge should be located no
    a single condenser circuit.                                    closer than the width of the unit to an obstruction
 2. Ensure each refrigerant circuit has its own head pres-         such as a wall or another unit. Minimum clearances
    sure control.                                                  for airflow and service are indicated on the equipment
 3. Condensing pressure control must be provided on                drawings and should be increased as necessary to pre-
    condensers used with 30HXA to maintain a minimum               vent air recirculation when obstructions exist or multi-
    75 F (24 C) saturated discharge temperature at light           ple units are applied.
    loads.                                                    Refrigerant pipe sizing for 30HXA with 09D con-
 4. Condenser must provide 15° F (8.3° C) subcooling, a       denser combinations — For refrigerant pipe sizing of
    maximum of 40° F (22.2° C) difference between satu-       the 30HXA follow these directions:
    rated condensing temperature and outdoor ambient          Discharge line:
    temperature (to prevent overload at high ambient            1. For applications at conditions of 40 F (4.4 C) or
    temperatures), and a minimum of 20° F (11.1° C)
                                                                   higher, use the Refrigerant Line Sizes for 30HXA
    difference (to assure subcooling).                             Chiller/Remote Condenser Combinations tables on
 5. Minimum saturated discharge temperature (SDT) is               pages 26 and 27.
    90 F (32.2 C). Maximum SDT is 145 F (62.8 C) at
                                                                   For applications using brine, other condensers, or
    full load.                                                     LWT below 40 F (4.4 C), size lines using the
 6. Condenser should not be located more than 15 ft                ASHRAE Refrigeration Handbook, or other suitable
    (4.6 m) below chiller to maintain subcooling.                  design guide.
 7. Design discharge and liquid piping according to the         2. Install horizontal lines level or pitched slightly toward
    System Design Manual and Refrigerant Piping Design             the base of discharge riser and the condenser (in the
    Program. Piping must be sized for HFC-134a refrig-             direction of flow).
    erant. Refer to the ASHRAE Refrigeration Handbook           3. If chiller is below the condenser, loop the discharge
    for R-134a refrigerant sizing tables. Also see 30HX
                                                                   line to at least one inch (25.4 mm) above the top of
    Installation Instructions and the Typical 30HXA                condenser.
    Refrigerant Piping to Remote Condenser diagrams
    on page 33.                                                 4. A double discharge riser (as shown in Refrigerant
                                                                   Line Sizes for 30HXA Chiller/Remote Condenser
 8. For proper electronic expansion valve (EXV) opera-             Combinations, Double Discharge Riser Pipe Sizes
    tion, discharge line losses should not exceed 4° F             table on page 27) is required if any of the following
    ( – 15.6° C) at full load. A calculation of line loss
                                                                   conditions exist:
    should be performed prior to installation.
                                                                   a. Unit is equipped with minimum load control.
 9. Maximum interconnecting refrigerant line length is
    200 ft (61 m) actual.                                          b. Chiller is located below condenser.
10. Liquid line solenoid valves are required.                   5. Minimize line length and restrictions to minimize pres-
                                                                   sure drop and refrigerant charge.
11. If accessory sound enclosure is installed, run lines
    along the floor so the sound enclosure can be notched       6. If accessory sound enclosure is applied, run lines
    to clear lines.                                                along the floor so sound enclosure may be notched to
                                                                   clear lines.
12. Locate equipment on a level surface in an area having
    unobstructed air circulation. Proper flow of fresh air      7. Lines should not be buried underground.
    to the condenser is essential for unit operation and        8. Snow and ice on hot discharge gas piping can serve
    performance. Care should be taken to keep the area             as a heat sink. Refrigerant piping exposed to the out-
    around the condensers free of airborne dirt, debris,           doors should be protected from snow and ice to pre-
    and materials that can restrict airflow or be drawn            vent excessive condensation at start-up.
    into the equipment, causing damage, clogging, or          Liquid line:
    blocking of the coil area.
                                                                1. For applications at conditions of 40 F (4.4 C) or
13. For multiple units, assure discharge air from one unit         higher LWT, use the Refrigerant Line Sizes for
    does not become intake air for another. Obstructions           30HXA Chiller/Remote Condenser Combinations
    such as screens, walls, roofs, overhangs, landscaping,         tables on pages 26 and 27.
    etc., located at a site may restrict airflow or cause
                                                                   For applications using brine, other condensers, or
    warm air circulation. Recirculation of warm discharge
                                                                   LWT below 40 F (4.4 C), size lines using the
                                                                                                                         25
Application data (cont)
      ASHRAE Refrigeration Handbook, or other suitable
                                                                                                 LIQUID LINE                                  TO
      design guide.                                                              FROM
                                                                                 CONDENSER                                                    CHILLER
 2.   If chiller is above condenser, maximum vertical sepa-
                                                                                                                STORAGE
      ration is 15 ft (4.6 m).                                                                                  RECEIVER
 3.   Minimize line length and restrictions to minimize pres-
      sure drop and refrigerant charge.                                         7. Filter driers (field supplied) are required indoors near
                                                                                   chiller.
 4.   Field-supplied liquid line solenoid valves are required.
      The solenoid valves must be located close to the                         Relief valve vent lines
      chiller.                                                                  1. Vent per local code requirements.
 5.   If sound enclosure is applied, run lines along floor so                   2. Each chiller has a minimum of 4 refrigerant relief
      sound enclosure may be notched to clear lines.                               valves: 2 on the cooler and 2 on the condenser
 6.   In-line receivers are NOT recommended due to their                           (30HXC) or oil separator (30HXA). Units with
      negative effect on system subcooling. Where the use                          factory-installed suction service valves also have one
      of a receiver is desired for service purposes, the                           relief valve on each compressor discharge line. See
      receiver should be piped in parallel with the main liq-                      Dimensions section on pages 12-19 for specific
      uid line and equipped with shut-off valves to isolate it                     locations.
      during unit operation. See the following storage                          3. If sound enclosure is applied, run lines along floor so
      receiver figure.                                                             sound enclosure may be notched to clear lines.
26
             REFRIGERANT LINE SIZES FOR 30HXA CHILLER/REMOTE CONDENSER COMBINATIONS (cont)
                                                DOUBLE DISCHARGE RISER PIPE SIZES (in. OD)
                                                                                              RED.
                                                                                              TEE
                                                                                    FROM
                                                                                    CHILLER
                                                                                              45 DEGREE              90 DEGREE
                                                                                              STR ELLS               STR ELLS
                                                                                          LEGEND
                                                                                   RED. TEE — Reducing Tee
                                                                                   STR ELLS — Street Elbows
                                                                                                                                                   27
Application data (cont)
For chillers using brine or those matched with other con-        Example Calculation of Circuit Capacities:
densers, the lines must be sized manually using design           Select (Standard) 30HXA086 Chiller
guides such as ASHRAE, or curves in the 30HXA installa-
                                                                 From Electronic catalog (E-cat) selection or balance
tion instructions. In many 30HXA sizes, the individual
                                                                 diagram:
refrigerant circuits have unequal capacities. The Circuit
Cooling Capacity table below lists the percentage capacity       Total Unit Capacity = 74 tons (from unit selection at design
of each circuit for line sizing purposes. The Circuit Unload-    conditions)
ing Capacity table below indicates the minimum unloading         Using the Circuit Cooling Capacity table:
capacities per circuit as well as a sample calculation of the    Ckt “A” design capacity = 74 x 0.55 = 40.7 tons
minimum circuit tonnage for riser design. The example
below lists circuit capacity calculations based on the Circuit   Using the Circuit Unloading Capacity table:
Cooling and Circuit Unloading Capacity tables.                   Ckt “A” minimum capacity = 40.7 x 0.40 = 16.3 tons
                                                                 Ckt “B” design capacity       = 74 x 0.45       = 33.3 tons
                CIRCUIT COOLING CAPACITY
                                                                 Ckt “B” minimum capacity = 33.3 x 0.40 = 13.3 tons
                        PERCENT OF TOTAL UNIT CAPACITY
  30HXA UNIT SIZE                                                System refrigerant charge — The 30HXA units are
                         Circuit A %       Circuit B %
                                                                 shipped from the factory with a small holding charge of
         076                 50                50
                                                                 nitrogen. The approximate refrigerant charge required for
         086                 55                45
                                                                 starting the 30HXA system is listed in the table on next
         096                 59                41
                                                                 page. This initial charge will allow starting of the unit.
         106                 64                36
                                                                 Additional refrigerant may be required to accommodate liq-
         116                 60                40
                                                                 uid line storage. See the liquid line refrigerant storage
         126                 55                45
                                                                 capacity table below for liquid line storage information.
         136                 59                41
         146                 55                45
                                                                   LIQUID LINE REFRIGERANT STORAGE CAPACITY
         161                 59                41
         171                 47                53                                      REFRIGERANT (lb)   REFRIGERANT (kg)
         186                 50                50                  PIPING SIZE (in.)   PER FT OF TUBING   PER M OF TUBING
                                                                                           LENGTH             LENGTH
         206                 54                46
                                                                         1 1 /8               0.41              0.61
         246                 61                39
                                                                         1 3 /8               0.63              0.94
         261                 63                37
                                                                         1 5 /8               0.89              1.33
         271                 64                36
                                                                         2 1 /8               1.52              2.26
                                                                         2 5 /8               2.32              3.45
               CIRCUIT UNLOADING CAPACITY
                         MINIMUM CIRCUIT CAPACITY —
                            PERCENT OF FULL LOAD
 30HXA UNIT                                 With Minimum
    SIZE             Standard Unit
                                            Load Control
                 Circuit A    Circuit B Circuit A    Circuit B
     076-186       40%          40%       20%          20%
     206-271       20%          40%       10%          20%
28
                                                   SYSTEM REFRIGERANT CHARGE FOR START-UP
                                                                                                                   RECOMMENDED                  TOTAL
                    AIR-COOLED                                            COOLER           CONDENSER                               PIPING
                                                                                                                                            REFRIGERANT
                                                  REFRIGERANT             CHARGE            CHARGE                  REFRIGERANT   CHARGE
  30HXA           CONDENSER TYPE,                                                                                                              CHARGE
                                                    CIRCUIT                                                          PIPE SIZES
                     SIZE (Qty)*
                                                                          Lb      Kg        Lb         Kg             (in. OD)†   Lb   Kg    Lb       Kg
                                                          A                48     22         62         28             11/8       10    5    120       55
    076               09DK 084 (1)
                                                          B                48      22        62         28             11/8       10    5   120        55
                                                          A                61      28        62         28             11/8       10    5   133        61
    086               09DK 084 (1)
                                                          B                52      24        62         28             11/8       10    5   124        57
                                                          A                75      34        68         31             11/8       10    5   153        70
    096               09DK 094 (1)
                                                          B                56      25        68         31             11/8       10    5   134        61
                    09DK 074 (1) and                      A                88      40        82         37             13/8       16    7   186        84
                      09DK 044 (1)                        B                56      25        62         28             13/8       16    7   134        60
    106
                                                          A                88      40        24         11             13/8       16    7   128        58
                    09AZ 102FE (1)
                                                          B                56      25        18          8             13/8       16    7    90        40
                    09DK 074 (1) and                      A                84      38        82         37             13/8       16    7   182        82
                      09DK 054 (1)                        B                61      28        56         25             13/8       16    7   133        60
    116
                                                          A                84      38        42         19             13/8       16    7   142        64
                    09AZ 112FE (1)
                                                          B                61      28        42         19             13/8       16    7   119        54
                                                          A                90      41        82         37             13/8       16    7   188        85
                      09DK 074 (2)
                                                          B                71      32        82         37             13/8       16    7   169        76
    126
                                                          A                90      41        24         11             13/8       16    7   130        59
                    09AZ 122FE (1)
                                                          B                71      32        24         11             13/8       16    7   112        50
                                                          A                99      45        82         37             13/8       16    7   197        89
                      09DK 074 (2)
                                                          B                71      32        82         37             13/8       16    7   169        76
    136
                                                          A                99      45        57         26             13/8       16    7   172        78
                    09AZ 132FE (1)
                                                          B                71      32        42         19             13/8       16    7   130        58
                                                          A                95      43      124          56             13/8       16    7   235       106
                      09DK 084 (2)
                                                          B                80      36      124          56             13/8       16    7   220        99
    146
                                                          A                95      43        57         26             13/8       16    7   168        76
                    09AZ 142FE (1)
                                                          B                80      36        57         26             13/8       16    7   153        69
                                                          A               120      54      124          56             13/8       16    7   260       117
                      09DK 084 (2)
                                                          B                88      40      124          56             13/8       16    7   228       103
    161
                                                          A               120      54        68         31             13/8       16    7   204        92
                    09AZ 162FE (1)
                                                          B                88      40        68         31             13/8       16    7   172        78
                                                          A                95      43      124          56             13/8       16    7   235       106
                      09DK 084 (2)
                                                          B               112      51      124          56             13/8       16    7   252       114
    171
                                                          A                95      43        68         31             13/8       16    7   179        81
                    09AZ 172FE (1)
                                                          B               112      51        68         31             13/8       16    7   196        89
                                                          A               108      49      124          56             13/8       16    7   248       112
                      09DK 084 (2)
                                                          B               108      49      124          56             13/8       16    7   248       112
    186
                                                          A               108      49        68         31             13/8       16    7   192        87
                    09AZ 182FE (1)
                                                          B               108      49        68         31             13/8       16    7   192        87
                    09DK 084 (2) and                      A               160      73      272         123             15/8       22   10   454       206
                      09DK 094 (1)                        B               108      49      124          56             13/8       16    7   248       112
    206
                  09AZ 101FA (1) and                      A               160      73        49         22             15/8       22   10   231       105
                    09AZ 91FA (1)                         B               108      49        37         17             13/8       16    7   161        73
                                                          A               176      80      272         123             21/8       38   17   486       220
                      09DK 094 (3)
                                                          B               108      49      136          62             13/8       16    7   260       118
    246
                  09AZ 151FA (1) and                      A               176      80      113          51             21/8       38   17   327       148
                    09AZ 91FA (1)                         B               108      49        37         17             13/8       16    7   161        73
                                                          A               176      80      272         123             21/8       38   17   486       220
                      09DK 094 (3)
                                                          B               108      49      136          62             13/8       16    7   260       118
    261
                  09AZ 171FA (1) and                      A               176      80      136          62             21/8       38   17   350       159
                    09AZ 91FA (1)                         B               108      49        37         17             13/8       16    7   161        73
                                                          A               176      80      272         123             21/8       38   17   486       220
                      09DK 094 (3)
                                                          B               108      49      136          62             13/8       16    7   260       118
    271
                  09AZ 181FA (1) and                      A               176      80      136          62             21/8       38   17   350       159
                    09AZ 91FA (1)                         B               108      49        37         17             13/8       16    7   161        73
*Refer to the electronic catalog for 09AZ/30HX rating data.
†Based on 25 ft (7.6 m) liquid line.
NOTE: Multiply the liquid line length (in feet) by the factor shown on page 28 for the refrigerant/ft of the tubing.
Add base unit charge to liquid line charge to determine approximate refrigerant charge.
                                                                                                                                                        29
Selection procedure
The electronic catalog chiller selection program provides     30HXC chillers and 30HXA condenserless chillers with
quick, easy selection of chillers. The program considers      air-cooled condensers or 30HXA chillers to be matched
specific temperature and flow requirements and other          with other condensers. To select a 30HXC or 30HXA
factors, such as fouling and altitude correction. The elec-   chiller, use the electronic catalog or contact your Carrier
tronic catalog can be used to select both water-cooled        representative.
30
Performance data
                                         30HXA,HXC STANDARD PASS COOLER PRESSURE DROP
                                                                                   ENGLISH
                             70.0
60.0 246,271
                                                                                                                                   206
                             50.0
                                                     076,086 096
                                                                   106                                   161,171
                                                                                    136,146
     PRESSURE DROP (ft wg)
                                                                         116,126
                             40.0                                                                          186
30.0
20.0
10.0
                              0.0
                                 100           300                       500                       700                900                 1100
                                                                               COOLER FLOW RATE (gpm)
            NOTES:
             1. Ft of water = 2.31 x change in psig.
             2. See page 23 for minimum flow rates and the electronic catalog for maximum flow rates.
                                                                                         SI
                             200.0
                             180.0
                                                                                                                                                 246,271
                             160.0
                                                                                                                                 206
                                                          076,086 096
                             140.0                                                                        161,171
                                                                           106            136,146
      PRESSURE DROP (kPa)
                                                                               116,126
                             120.0                                                                           186
100.0
80.0
60.0
40.0
20.0
                               0.0
                                     0    10              20                30                40                 50         60           70           80
                                                                                 COOLER FLOW RATE (L/s)
NOTE: See page 23 for minimum flow rates and the electronic catalog for maximum flow rates.
                                                                                                                                                            31
Performance data (cont)
                                                                                        136,146
                              50.0                                         116,126
                              40.0                                  096,106
      PRESSURE DROP (ft wg)
076,086
30.0
20.0
10.0
                               0.0
                                  100          300              500                      700                  900                   1100                1300
                                                                         CONDENSER FLOW RATE (gpm)
            NOTES:
             1. Ft of water = 2.31 x change in psig.
             2. See page 23 for minimum flow rates and the electronic catalog for maximum flow rates.
                                                                                        SI
                              200.0
                              180.0
                                                                                                    161         171,186       206           246,271
                              160.0
                                                                                         136,146
                                                                              116,126
                              140.0
        PRESSURE DROP (kPa)
120.0 096,106
100.0 076,086
80.0
60.0
40.0
20.0
                                0.0
                                      0   10         20             30             40              50          60             70            80            90
                                                                           CONDENSER FLOW RATE (L/s)
NOTE: See page 23 for minimum flow rates and the electronic catalog for maximum flow rates.
32
Typical piping and wiring
             TYPICAL 30HXA REFRIGERANT PIPING TO REMOTE CONDENSER (076-096 SIZES SHOWN)
 NOTES:
  1. Piping shown is for general point-of-connection only and is not intended to show details for a specific installation. Certified field wiring
     and dimensional drawings are available upon request. The 30HXA units should be installed using certified drawings.
  2. Refer to the System Design Manual for details regarding piping techniques.
  3. Refrigerant piping including liquid line solenoid valves, liquid line filter driers, and relief valves are field supplied.
  4. Relief valve vent piping per local codes.
  5. If unit is equipped with accessory sound enclosure, run lines down to floor and notch bottom of enclosure to clear lines.
  6. When the remote condenser is equipped with Motormaster® head pressure control, the 30HXA chiller may be started with outdoor-air
     temperature as low as 35 F and may operate at loads equal to or greater than its second stage of capacity with outdoor-air tempera-
     tures as low as 0° F.
a30-4644
a30-4645
                                                                                                                                                    33
34
                                         TYPICAL PIPING AND WIRING FOR 30HXA,HXC COOLER AND 30HXC CONDENSER
                   a30-4652
                                                                                                                                                                                             Typical piping and wiring (cont)
                                                                 NOTES:
                                                                 1. Chiller must be installed levelly to maintain proper compressor oil return.
                              LEGEND                             2. Wiring and piping shown are general points-of-connection guides only and are not intended for a specific installation.
                                                                    Wiring and piping shown are for a quick overview of system and are not in accordance with recognized standards.
            Airflow Through Air-Handling Unit                    3. All wiring must comply with applicable local and national codes.
                                                                 4. All piping must follow standard piping techniques. Refer to the System Design Manual or appropriate ASHRAE (Ameri-
            Power Wiring                                            can Society of Heating, Refrigeration, and Air Conditioning Engineers) handbook for details.
                                                                 5. See Application Data section on page 24 for minimum cooler loop volume. This system may require the addition of a
          Chilled Fluid Piping                                      holding tank to ensure adequate volume.
     ST — Starter
     FD — Field-Supplied Disconnect
                                                                                           POWER AND CONTROL WIRING
                                                                   SEE
                                                                   NOTE 12
                                                                                           SEE
                                                                                           NOTE 12
                                                                     LEGEND
     A         —   Alarm                             CWPI      —     Chilled Water Pump Interlock      OAT     — Outdoor Air Temperature
     CFR       —   Condenser Fan Relay               EMM       —     Energy Management Module          SPT     — Space Temperature
     CNFS      —   Condenser Flow Switch             EWT       —     Entering Water Temperature        TB      — Terminal Block
     CNPI      —   Condenser Pump Interlock          FIOP      —     Factory-Installed Option                    Factory Installed Wiring
                                                                                                                                                                 Typical control wiring schematic
     CNPR      —   Condenser Water Pump              LLSV      —     Liquid Line Solenoid Valve                  Field Control Wiring
     CWFS      —   Chilled Water Flow Switch         LWT       —     Leaving Water Temperature                   Field Power Wiring
     CWP       —   Chilled Water Pump                NEC       —     National Electrical Code
     NOTES:
      1. Factory wiring is in accordance with National Electrical Code (NEC). Field modifications or additions must be in compliance with all
         applicable codes.
      2. Wiring for main field supply must be rated 75 C minimum. Use copper for all units. Maximum incoming wire size for each terminal
         block is 500 kcmil.
      3. Power for control circuit should be supplied from a separate source (except 380/415v units) through a field-supplied disconnect with
         15A maximum protection for 115v control circuits and 15A maximum protection for 230v control circuit. Connect control circuit power
         to terminals 1 and 2 of TB4. Control circuit conductors for all units must be copper only. Control circuit power is factory wired for 380/
         415v units.
      4. Terminals 13 and 14 TB5 are for field external connection for remote on-off. The contacts must be rated for dry circuit application
         capable of handling a 24vac load up to 50mA.
      5. Terminals 1 and 2 of TB5 are for chilled water pump interlock (CWPI) functions. If added, chilled water pump interlock contacts must
         be wired in series with flow contacts. The contacts must be rated for dry circuit application capable of handling a 24vac load up to
         50mA. Chilled water flow switch (CWFS) is factory installed.
      6. Terminals 10 and 12 of TB5 are for control of the chilled water pump starter. The maximum load allowed for the chilled water pump
                                                                                                                                                      a30-4650
         relay is 75va sealed, 360va inrush at 115v or 230v. Separate field power supply is not required.
      7. Terminals 11 and 12 of TB5 are for alarm relay. The maximum load allowed for the alarm relay is 75va sealed, 360va inrush at 115v
         or 230v. Separate field power supply is not required.
      8. Terminals 7 and 9 of TB2 are for condenser water pump (HXC) or circuit A condenser fan contactor (HXA only). Terminals 8 and 9
         of TB2 are for circuit B contactor (HXA only) or liquid line solenoid valves (factory-wired 30HXC brine). The maximum load allowed
         is 75va sealed, 360va inrush at 115v or 230v. Separate field power supply is not required. Liquid line solenoid valves (30HXA only)
         must be connected in parallel fan contactors as shown.
      9. Terminals 5 and 6 of TB2 are for condenser flow switch (CNFS) and/or condenser pump interlock (CNPI). The contacts must be
         rated for dry circuit application capable of handling a 24vac load up to 50mA.
     10. Make appropriate connections to TB6 as shown for energy management board options. The contacts for demand limit and ice done
         options must be rated for dry circuit application capable of handling a 24vac load up to 50mA.
     11. TB1B supplied on 30HXA186 208/230v Y-Delta, 30HXA206-271 208/230, 230v Y-Delta and by special order.
     12. 500 kcmil if minimum circuit amps (MCA)  200A, 300 kcmil if MCA  200A.
35
Electrical data
                                              ELECTRICAL DATA, 30HXC UNITS
            UNIT VOLTAGE                                                  UNIT VOLTAGE                       CONTROL CIRCUIT
 UNIT                             POWER        NO. POWER
                    Supplied      SUPPLY        SUPPLY                         ICF     Rec Fuse Size    V-Hz    Supplied MCA and
30HXC      V-Hz                                            MCA     MOCP                                (Single
          (3 Ph)    Min Max      QTY. REQD.   CONDUCTORS                   XL     WD      XL    WD             Min Max    MOCP
                                                                                                         Ph)
          230-60     207   253       1            3        198.7   250     —      297.3    —    225    115-60   104   127   15
        208/230-60   187   253       1            3        220.7   300     —      307.1    —    250    115-60   104   127   15
          460-60     414   506       1            3         99.7   125    374.3   148.3   125   125    115-60   104   127   15
 076      575-60     518   633       1            3         79.7   110    299.4   118.4    90    90    115-60   104   127   15
          380-60     342   418       1            3        120.8   150    418.7   168.7   150   150    230-60   207   254   15
        380/415-50   342   440       1            3        125.6   175    399.8   164.8   150   150    230-50   198   254   15
          230-50     207   253       1            3        207.2   250     —      266.1    —    250    230-50   207   254   15
          230-60     207   253       1            3        221.7   300     —      297.3    —    250    115-60   104   127   15
        208/230-60   187   253       1            3        246.4   350     —      307.1    —    300    115-60   104   127   15
          460-60     414   506       1            3        111.3   150    374.3   148.3   125   125    115-60   104   127   15
 086      575-60     518   633       1            3         88.9   125    299.4   118.4   100   100    115-60   104   127   15
          380-60     342   418       1            3        134.8   175    418.7   168.7   175   175    230-60   207   254   15
        380/415-50   342   440       1            3        140.4   200    478.8   189.8   175   175    230-50   198   254   15
          230-50     207   253       1            3        231.9   300     —      305.1    —    300    230-50   207   254   15
          230-60     207   253       1            3        251.3   350     —      344.3    —    300    115-60   104   127   15
        208/230-60   187   253       1            3        279.2   400     —      354.1    —    350    115-60   104   127   15
          460-60     414   506       1            3        126.2   175    449.3   172.3   150   150    115-60   104   127   15
 096      575-60     518   633       1            3        100.8   150    359.4   137.4   125   125    115-60   104   127   15
          380-60     342   418       1            3        152.7   225    501.7   194.7   175   175    230-60   207   254   15
        380/415-50   342   440       1            3        157.9   225    561.8   215.8   200   200    230-50   198   254   15
          230-50     207   253       1            3        260.7   350     —      347.1    —    300    230-50   207   254   15
          230-60     207   253       1            3        285.6   400     —      395.3    —    350    115-60   104   127   15
        208/230-60   187   253       1            3        317.4   450     —      405.1    —    400    115-60   104   127   15
          460-60     414   506       1            3        143.3   200    529.3   197.3   175   175    115-60   104   127   15
 106      575-60     518   633       1            3        114.5   175    423.4   158.4   150   150    115-60   104   127   15
          380-60     342   418       1            3        173.6   250    589.7   222.7   200   200    230-60   207   254   15
        380/415-50   342   440       1            3        178.1   250    660.8   246.8   225   225    230-50   198   254   15
          230-50     207   253       1            3        294.2   450     —      397.1    —    350    230-50   207   254   15
          230-60     207   253       1            3        304.1   450     —      413.7    —    350    115-60   104   127   15
        208/230-60   187   253       1            3        337.9   500     —      425.6    —    400    115-60   104   127   15
          460-60     414   506       1            3        152.6   225    538.6   206.6   175   175    115-60   104   127   15
 116      575-60     518   633       1            3        121.9   175    430.8   165.8   150   150    115-60   104   127   15
          380-60     342   418       1            3        184.8   250    600.9   233.9   225   225    230-60   207   254   15
        380/415-50   342   440       1            3        190.0   250    672.7   258.7   225   225    230-50   198   254   15
          230-50     207   253       1            3        313.9   450     —      416.8    —    400    230-50   207   254   15
          230-60     207   253       1            3        327.7   450     —      437.4    —    400    115-60   104   127   15
        208/230-60   187   253       1            3        364.2   500     —      451.9    —    450    115-60   104   127   15
          460-60     414   506       1            3        164.5   225    550.5   218.5   200   200    115-60   104   127   15
 126      575-60     518   633       1            3        131.4   175    440.3   175.3   150   150    115-60   104   127   15
          380-60     342   418       1            3        199.1   250    615.2   248.2   225   225    230-60   207   254   15
        380/415-50   342   440       1            3        204.0   300    686.7   272.7   250   250    230-50   198   254   15
          230-50     207   253       1            3        337.0   450     —      439.9    —    400    230-50   207   254   15
          230-60     207   253       1            3        366.7   500     —      497.4    —    450    115-60   104   127   15
        208/230-60   187   253       1            6        407.4   600     —      511.9    —    500    115-60   104   127   15
          460-60     414   506       1            3        183.8   250    645.5   248.5   225   225    115-60   104   127   15
 136      575-60     518   633       1            3        147.1   200    536.3   199.3   175   175    115-60   104   127   15
          380-60     342   418       1            3        222.8   300    720.2   282.2   300   300    230-60   207   254   15
        380/415-50   342   440       1            3        230.2   300    796.7   307.7   300   300    230-50   198   254   15
          230-50     207   253       1            6        380.3   500     —      495.9    —    450    230-50   207   254   15
          230-60     207   253       1            6        394.1   500     —      524.9    —    450    115-60   104   127   15
        208/230-60   187   253       1            6        437.9   600     —      542.4    —    500    115-60   104   127   15
          460-60     414   506       1            3        197.5   250    659.2   262.2   225   225    115-60   104   127   15
 146      575-60     518   633       1            3        158.1   225    547.3   210.3   200   200    115-60   104   127   15
          380-60     342   418       1            3        239.5   350    736.9   298.9   300   300    230-60   207   254   15
        380/415-50   342   440       1            3        246.3   350    812.8   323.8   300   300    230-50   198   254   15
          230-50     207   253       1            6        407.1   600     —      522.7    —    500    230-50   207   254   15
          230-60     207   253       1            6        398.7   600     —      574.8    —    500    115-60   104   127   15
        208/230-60   187   253       1            6        443.0   600     —      590.6    —    600    115-60   104   127   15
          460-60     414   506       1            3        200.1   300    756.2   287.2   250   250    115-60   104   127   15
 161      575-60     518   633       1            3        159.9   225    604.9   229.9   200   200    115-60   104   127   15
          380-60     342   418       1            3        242.2   350    843.2   325.2   300   300    230-60   207   254   15
        380/415-50   342   440       1            3        249.0   350    944.2   358.2   300   300    230-50   198   254   15
          230-50     207   253       1            6        411.3   600     —      577.7    —    500    230-50   207   254   15
36
                                                    ELECTRICAL DATA, 30HXC UNITS (cont)
               UNIT VOLTAGE                                                                UNIT VOLTAGE                            CONTROL CIRCUIT
  UNIT                                 POWER           NO. POWER
                       Supplied        SUPPLY           SUPPLY                                 ICF      Rec Fuse Size         V-Hz    Supplied MCA and
 30HXC         V-Hz                                                       MCA     MOCP                                       (Single
              (3 Ph)   Min Max        QTY. REQD.      CONDUCTORS                            XL      WD       XL       WD             Min Max    MOCP
                                                                                                                               Ph)
             230-60      207   253          1                 6           428.4   600       —      604.5     —        500    115-60    104   127      15
           208/230-60    187   253          1                 6           476.0   700       —      623.6     —        600    115-60    104   127      15
             460-60      414   506          1                 3           215.0   300      771.1   302.1    250       250    115-60    104   127      15
   171       575-60      518   633          1                 3           171.8   250      616.8   241.8    200       200    115-60    104   127      15
             380-60      342   418          1                 3           260.2   350      861.2   343.2    300       300    230-60    207   254      15
           380/415-50    342   440          1                 3           266.6   350      961.8   375.8    300       300    230-50    198   254      15
             230-50      207   253          1                 6           440.4   600       —      606.8     —        500    230-50    207   254      15
             230-60      207   253          1                 6           462.3   600       —      638.5     —        600    115-60    104   127      15
           208/230-60    187   253          1                 6           513.7   700       —      661.3     —        600    115-60    104   127      15
             460-60      414   506          1                 3           232.0   300      788.1   319.1    300       300    115-60    104   127      15
   186       575-60      518   633          1                 3           185.4   250      630.4   255.4    225       225    115-60    104   127      15
             380-60      342   418          1                 3           280.8   400      881.8   363.8    350       350    230-60    207   254      15
           380/415-50    342   440          1                 3           289.4   400      984.6   398.6    350       350    230-50    198   254      15
             230-50      207   253          1                 6           478.1   600       —      644.5     —        600    230-50    207   254      15
             230-60      207   253          1                 6           524.5   700       —      700.7     —        600    115-60    104   127      15
           208/230-60    187   253          1                 6           582.8   800       —      730.4     —        700    115-60    104   127      15
             460-60      414   506          1                 3           263.2   350      819.3   350.3    300       300    115-60    104   127      15
   206       575-60      518   633          1                 3           210.4   250      655.4   280.4    250       250    115-60    104   127      15
             380-60      342   418          1                 3           318.6   400      919.6   401.6    350       350    230-60    207   254      15
           380/415-50    342   440          1                 3           326.8   450     1022.0   436.0    400       400    230-50    198   254      15
             230-50      207   253          1                 6           539.8   700       —      706.2     —        600    230-50    207   254      15
             230-60      207   253          1                 6           604.1   800       —      780.3     —        700    115-60    104   127      15
           208/230-60    187   253          1                 6           671.3   800       —      818.9     —        800    115-60    104   127      15
             460-60      414   506          1                 3           303.2   400      859.3   390.3    350       350    115-60    104   127      15
   246       575-60      518   633          1                 3           242.3   300      687.3   312.3    300       300    115-60    104   127      15
             380-60      342   418          1                 3           367.0   450      968.0   450.0    400       400    230-60    207   254      15
           380/415-50    342   440          1                 3           377.6   500     1072.8   486.8    450       450    230-50    198   254      15
             230-50      207   253          1                 6           623.8   800       —      790.2     —        700    230-50    207   254      15
             230-60      207   253          1                 6           633.8   800       —      810.0     —        700    115-60    104   127      15
           208/230-60    187   253          1                 6           704.3   800       —      851.9     —        800    115-60    104   127      15
             460-60      414   506          1                 3           318.1   400      874.2   405.2    350       350    115-60    104   127      15
   261       575-60      518   633          1                 3           254.2   300      699.2   324.2    300       300    115-60    104   127      15
             380-60      342   418          1                 6           385.0   500      986.0   468.0    450       450    230-60    207   254      15
           380/415-50    342   440          1                 6           395.2   500     1090.4   504.4    450       450    230-50    198   254      15
             230-50      207   253          1                 6           652.9   800       —      819.3     —        800    230-50    207   254      15
             230-60      207   253          1                 6           667.8   800       —      843.9     —        800    115-60    104   127      15
           208/230-60    187   253          1                 6           742.0   800       —      889.6     —        800    115-60    104   127      15
             460-60      414   506          1                 3           335.1   400      891.2   422.2    400       400    115-60    104   127      15
   271       575-60      518   633          1                 3           267.8   350      712.8   337.8    300       300    115-60    104   127      15
             380-60      342   418          1                 6           405.6   500     1006.6   488.6    450       450    230-60    207   254      15
           380/415-50    342   440          1                 6           418.0   500     1113.2   527.2    500       500    230-50    198   254      15
             230-50      207   253          1                 6           690.6   800       —      857.0     —        800    230-50    207   254      15
                            LEGEND                                                 3.   Maximum incoming wire size for each terminal block is 500 kcmil.
ICF  — Maximum Instantaneous Current Flow during start-up (the                     4.   Maximum allowable phase imbalance is: voltage, 2%; amps, 5%.
       point in the starting sequence where the sum of the LRA for                 5.   Use copper conductors only.
       the start-up compressor, plus the total RLA for all running                 6.   The MOCP is calculated as follows:
       compressors is at a maximum)                                                     MOCP = (2.25) (largest RLA) + the sum of the other RLAs. Size the fuse
LRA  — Locked Rotor Amps                                                                one size down from the result. The RLAs are listed on the nameplate.
MCA — Minimum Circuit Ampacity (for wire sizing)
MOCP — Maximum Overcurrent Protection                                                   The recommended fuse size in amps (RFA) is calculated as follows:
RLA  — Rated Load Amps                                                                  RFA = (1.50) (largest RLA) + the sum of the other RLAs. Size the fuse
WD   — Wye-Delta Start                                                                  one size up from the result. The RLAs are listed on the nameplate.
XL   — Across-the-Line Start
                                                                                        MCA = (1.5) (largest RLA) + the sum of the other RLAs. Size the wires
NOTES:                                                                                  one size up from the result.
1. Each main power source must be supplied from a field-supplied fused
   electrical service with a (factory-installed or field-installed) disconnect
   located in sight from the unit.
2. Control circuit power must be supplied from a separate source through a
   field-supplied disconnect (except for 380/415-50 units). An accessory
   control transformer may be used to provide control circuit power from the
   main unit power supply.
ETL_listed_C_US-tif
                                                                                                                                                           37
Electrical data (cont)
                                               ELECTRICAL DATA, 30HXA UNITS
ETL_listed_C_US-tif
38
                                                    ELECTRICAL DATA, 30HXA UNITS (cont)
                                                                                                                                                            39
Electrical data (cont)
                                              COMPRESSOR ELECTRICAL DATA, 30HXC UNITS
40
                                          COMPRESSOR ELECTRICAL DATA, 30HXC UNITS (cont)
                                                                                                                                 41
Electrical data (cont)
                                          COMPRESSOR ELECTRICAL DATA, 30HXC UNITS (cont)
                                       NAMEPLATE                                               COMPRESSOR NUMBERS
     UNIT SIZE 30HXC                        V-Hz                                         A1                            B1
                                         (3 Phase)                         RLA                  LRA            RLA          LRA
                                        208/230-60                           *                   *               *           *
                                           230-60                            *                   *               *           *
                                           460-60                          103.1                685             71.2        525
          161-XL                           575-60                           82.4                548             56.9        420
                                           380-60                          124.8                757             86.2        580
                                           230-50                            *                   *               *           *
                                        380/415-50                         128.6                856             88.2        600
                                        208/230-60                         228.8                433            157.6        350
                                           230-60                          205.5                433            141.8        350
                                           460-60                          103.1                216             71.2        175
          161-WD                           575-60                           82.4                173             56.9        140
                                           380-60                          124.8                239             86.2        193
                                           230-50                          212.5                432            145.7        348
                                        380/415-50                         128.6                270             88.2        200
                                        208/230-60                           *                   *               *           *
                                           230-60                            *                   *               *           *
                                           460-60                           86.1                580            103.1        685
          171-XL                           575-60                           68.8                484             82.4        548
                                           380-60                          104.2                641            124.8        757
                                           230-50                            *                   *               *           *
                                        380/415-50                         105.8                715            128.6        856
                                        208/230-60                         190.6                367            228.8        433
                                           230-60                          171.5                367            205.5        433
                                           460-60                           86.1                183            103.1        216
          171-WD                           575-60                           68.8                147             82.4        173
                                           380-60                          104.2                203            124.8        239
                                           230-50                          174.8                361            212.5        432
                                        380/415-50                         105.8                233            128.6        270
                                        208/230-60                           *                   *               *           *
                                           230-60                            *                   *               *           *
                                           460-60                          103.1                685            103.1        685
          186-XL                           575-60                           82.4                548             82.4        548
                                           380-60                          124.8                757            124.8        757
                                           230-50                            *                   *               *           *
                                        380/415-50                         128.6                856            128.6        856
                                        208/230-60                         228.8                433            228.8        433
                                           230-60                          205.5                433            205.5        433
                                           460-60                          103.1                216            103.1        216
          186-WD                           575-60                           82.4                173             82.4        173
                                           380-60                          124.8                239            124.8        239
                                           230-50                          212.5                432            212.5        432
                                        380/415-50                         128.6                270            128.6        270
        LEGEND
LRA    — Locked Rotor Amps
RLA    — Rated Load Amps
WD     — Wye-Delta Start
XL     — Across-the-Line Start
*Units are shipped with wye-delta start as standard. Across-the-line start is not available.
42
                                          COMPRESSOR ELECTRICAL DATA, 30HXC UNITS (cont)
                                                                                                                                 43
Electrical data (cont)
                                              COMPRESSOR ELECTRICAL DATA, 30HXA UNITS
44
                                          COMPRESSOR ELECTRICAL DATA, 30HXA UNITS (cont)
                                       NAMEPLATE                                               COMPRESSOR NUMBERS
    UNIT SIZE 30HXA                         V-Hz                                         A1                            B1
                                         (3 Phase)                         RLA                  LRA             RLA         LRA
                                        208/230-60                          *                     *              *            *
                                           230-60                           *                     *              *            *
                                           460-60                          115.4                 820            77.6         580
          116-XL                           575-60                           92.2                 656            62.1         484
                                           380-60                          139.7                 906            94.0         641
                                           230-50                           *                     *              *            *
                                        380/415-50                         145.4                 960            99.2         715
                                        208/230-60                         255.5                 518           171.9         367
                                           230-60                          230.0                 518           154.7         367
                                           460-60                          115.4                 259            77.6         183
          116-WD                           575-60                           92.2                 207            62.1         147
                                           380-60                          139.7                 286            94.0         203
                                           230-50                          240.2                 485           163.9         361
                                        380/415-50                         145.4                 303            99.2         226
                                        208/230-60                          *                     *              *            *
                                           230-60                           *                     *              *            *
                                           460-60                          115.4                 820            94.8         685
          126-XL                           575-60                           92.2                 656            75.7         548
                                           380-60                          139.7                 906           114.7         757
                                           230-50                           *                     *              *            *
                                        380/415-50                         145.4                 960           119.9         856
                                        208/230-60                         255.5                 518           209.8         433
                                           230-60                          230.0                 518           188.8         433
                                           460-60                          115.4                 259            94.8         216
          126-WD                           575-60                           92.2                 207            75.7         173
                                           380-60                          139.7                 286           114.7         239
                                           230-50                          240.2                 485           198.2         432
                                        380/415-50                         145.4                 303           119.9         270
                                        208/230-60                          *                     *              *            *
                                           230-60                           *                     *              *            *
                                           460-60                          140.7                 920            94.8         685
          136-XL                           575-60                          112.4                 736            75.7         548
                                           380-60                          170.2                1017           114.7         757
                                           230-50                           *                     *              *            *
                                        380/415-50                         178.8                1226           119.9         856
                                        208/230-60                         311.4                 581           209.8         433
                                           230-60                          280.3                 581           188.8         433
                                           460-60                          140.7                 291            94.8         216
          136-WD                           575-60                          112.4                 233            75.7         173
                                           380-60                          170.2                 321           114.7         239
                                           230-50                          295.3                 619           198.2         432
                                        380/415-50                         178.8                 387           119.9         270
                                        208/230-60                          *                     *              *            *
                                           230-60                           *                     *              *            *
                                           460-60                          140.7                 920           115.4         820
          146-XL                           575-60                          112.4                 736            92.2         656
                                           380-60                          170.2                1017           139.7         906
                                           230-50                           *                     *              *            *
                                        380/415-50                         178.8                1226           145.4         960
                                        208/230-60                         311.4                 581           255.5         518
                                           230-60                          280.3                 581           230.0         518
                                           460-60                          140.7                 291           115.4         259
          146-WD                           575-60                          112.4                 233            92.2         207
                                           380-60                          170.2                 321           139.7         286
                                           230-50                          295.3                 619           240.2         485
                                        380/415-50                         178.8                 387           145.4         303
        LEGEND
LRA    — Locked Rotor Amps
RLA    — Rated Load Amps
WD     — Wye-Delta Start
XL     — Across-the-Line Start
*Units are shipped with wye-delta start as standard. Across-the-line start is not available.
                                                                                                                                   45
Electrical data (cont)
                                          COMPRESSOR ELECTRICAL DATA, 30HXA UNITS (cont)
                                       NAMEPLATE                                               COMPRESSOR NUMBERS
     UNIT SIZE 30HXA                        V-Hz                                         A1                            B1
                                         (3 Phase)                        RLA                  LRA             RLA          LRA
                                        208/230-60                          *                   *                *            *
                                           230-60                           *                   *                *            *
                                           460-60                         157.9                1175            106.6         790
          161-XL                           575-60                         126.2                 940             85.1         630
                                           380-60                         191.2                1299            129.0         870
                                           230-50                           *                   *                *            *
                                        380/415-50                        201.2                1265            133.4        1045
                                        208/230-60                        349.6                 743            235.9         527
                                           230-60                         314.6                 743            212.3         527
                                           460-60                         157.9                 371            106.6         263
          161-WD                           575-60                         126.2                 297             85.1         211
                                           380-60                         191.2                 410            129.0         290
                                           230-50                         332.3                 638            220.3         607
                                        380/415-50                        201.2                 400            133.4         348
                                        208/230-60                          *                   *                *            *
                                           230-60                           *                   *                *            *
                                           460-60                         129.6                 920            157.9        1175
          171-XL                           575-60                         103.6                 736            126.2         940
                                           380-60                         156.9                1017            191.2        1299
                                           230-50                           *                   *                *            *
                                        380/415-50                        161.7                1226            201.2        1265
                                        208/230-60                        286.9                 581            349.6         743
                                           230-60                         258.2                 581            314.6         743
                                           460-60                         129.6                 291            157.9         371
          171-WD                           575-60                         103.6                 233            126.2         297
                                           380-60                         156.9                 321            191.2         410
                                           230-50                         267.2                 619            332.3         638
                                        380/415-50                        161.7                 387            201.2         400
                                        208/230-60                          *                   *                *            *
                                           230-60                           *                   *                *            *
                                           460-60                         157.9                1175            157.9        1175
          186-XL                           575-60                         126.2                 940            126.2         940
                                           380-60                         191.2                1299            191.2        1299
                                           230-50                           *                   *                *            *
                                        380/415-50                        201.2                1265            201.2        1265
                                        208/230-60                        349.6                 743            349.6         743
                                           230-60                         314.6                 743            314.6         743
                                           460-60                         157.9                 371            157.9         371
          186-WD                           575-60                         126.2                 297            126.2         297
                                           380-60                         191.2                 410            191.2         410
                                           230-50                         332.3                 638            332.3         638
                                        380/415-50                        201.2                 400            201.2         400
        LEGEND
LRA    — Locked Rotor Amps
RLA    — Rated Load Amps
WD     — Wye-Delta Start
XL     — Across-the-Line Start
*Units are shipped with wye-delta start as standard. Across-the-line start is not available.
46
                                          COMPRESSOR ELECTRICAL DATA, 30HXA UNITS (cont)
                                                                                                                                 47
Controls
The standard microprocessor-based control in the 30HX                                          Normal operation — The entering fluid temperature
units provides the following functions:                                                        sensor monitors changes in entering fluid temperature to
• leaving evaporator fluid control in COOL mode (using                                         anticipate changes in the cooling load. Based on leaving
   both entering and leaving fluid sensors)                                                    fluid temperature, the control adds or subtracts capacity to
• leaving condenser fluid control in HEAT mode (using                                          maintain a constant leaving fluid temperature.
   field-installed accessory entering and leaving fluid                                        Dual chiller control — The dual chiller routine is avail-
   sensors)                                                                                    able for the control of two units supplying chilled fluid on a
• 7-day time sequence of both pump and chiller                                                 common loop.
• temperature reset from return fluid (standard) or from                                          In parallel flow applications, an additional leaving fluid
   outdoor ambient (accessory), occupied space tempera-                                        temperature thermistor must be installed and connected to
   ture (accessory), 4 to 20 mA signal (accessory), or via                                     the lead chiller.
   the optional Carrier Comfort Network® (CCN) system
                                                                                               Transition to off — The chiller unloads once the “time-
• automatic compressor lead-lag switching based on com-
                                                                                               to-stop” signal has been given. This signal can be either
   pressor accumulated run times and number of cycles
                                                                                               internal or external.
• automatic temperature range across the cooler
   adjustment                                                                                  Safeties — The 30HX control as shipped from the fac-
• fully automatic control of the chiller components                                            tory automatically deenergizes any active compressor that
                                                                                               experiences any of the following:
A 4-line, 20-character per line display is used to accom-
plish the following (see figure below):                                                        • electrical overload
                                                                                               • thermal overload protection
• set schedules and set points
                                                                                               • high pressure
• identify operating mode
                                                                                               • low oil pressure
• display current temperatures and pressures being used
                                                                                               • loss of refrigerant charge
   by the control for internal calculations
                                                                                               • loss of phase protection
• identify abnormal (alarm or alert) conditions
                                                                                               • reverse rotation (control prevents compressor start)
Sequence of operation                                                                          • current imbalance
The control has a 44 F (6.2 C) leaving fluid temperature                                       • ground current
(LWT) set point as shipped from the factory. If temperature                                    • low chilled fluid temperature
reset or demand limiting is in effect, this set point may                                      Additional information
change.
                                                                                               Detailed information on controls and operation is available
Start-up — The chiller will start when the circulating                                         in the Controls, Start-Up, Operation and Troubleshooting
pump is energized. (If the flow switch is applied, the chiller                                 guide included with each unit. Packaged Service Training
starts after the flow has been proven.) The compressor                                         programs are also available. Contact your Carrier repre-
starts unloaded.                                                                               sentative for more information.
NOTE: Which compressor starts first is determined by the
automatic lead/lag feature.
   If the entering fluid temperature is 85 F (29 C) or higher,
the maximum operating pressure (MOP) feature limits the
suction pressure to keep the chiller on line.
                                                             Co m
                                                                         fort
                                                               NA
                                                                       VIG
                                                                                      Li n k
                                                                              ATO
                                                                                       R
                                               T IM E
                                               EWT              12.
                                              LW T             54. 58
                                              SETP             44. 6 F
                                                              4 4 . 01 F
                                                                      F
                                             MO
                                                    DE
                                              Run              Al ar
                                                                       m St
                                                    Statu                   atu   s
                                                         s
                                            Servi
                                                  ce Te
                                                        st
                                           Temp
                                                 eratur
                                                        es
                                          Pres
                                               sures
                                         Setpo
                                               ints
                                        Inputs
                                       Outpu
                                            ts
                                     Confi
                                           gurat
                                                 ion
                                    Time
                                          Cloc
                                              k              ESC
                                   Opera
                                         ting
                                              Mode
                                  Alarm              s
                                       s
                                      ENT
                                              ER
48
Guide specifications
Water-Cooled and Condenserless                                           working-side pressure of 220 psig (1408 kPa).
HVAC Guide Specifications                                                Water-side pressure rating shall be 300 psig
                                                                         (2068 kPa). In Canada, maximum water-side
Size Range: 75 to 265 Nominal Tons                                       pressure shall be 250 psig (1725 kPa), per the
             (264 to 931 kW)                                             Canadian National Registry.
Carrier Model Number: 30HXA — Condenserless                           2. Shall be mechanically cleanable shell-and-tube
                           30HXC — Water-Cooled                          type with removable heads.
Part 1 — General                                                      3. Tubes shall be internally enhanced, seamless-
1.01 SYSTEM DESCRIPTION                                                  copper type, and shall be rolled into
      Microprocessor controlled water-cooled (30HXC) or                  tube sheets. Tube wall thickness shall be
      condenserless (30HXA) liquid chiller utilizing screw               0.025 inches.
      compressors and electronic expansion valves.                    4. Shall be equipped with Victaulic fluid
1.02 QUALITY ASSURANCE                                                   connections.
   A. Unit shall be rated in accordance with AHRI Stan-               5. Shell shall be insulated with 3/4-in. (19-mm)
      dard 550/590, latest edition (U.S.A.). The 60 Hz                   closed-cell, polyvinyl chloride foam with a maxi-
      30HXC units shall be AHRI certified for perfor-                    mum K factor of 0.28. Heads may require field
      mance.                                                             insulation.
   B. Unit construction shall comply with ASHRAE 15                   6. Shall have a cooler drain and vent.
      Safety Code, NEC, and ASME applicable codes                     7. Design shall incorporate 2 independent refrig-
      (U.S.A. codes), latest version.                                    erant circuits.
   C. Unit shall be manufactured at an ISO 9001:2000                  8. Shall include isolation valves to allow isolation
      registered facility.                                               of the refrigerant charge in either the evapora-
   D. 208/230 v, 230 v, 460 v, 575 v, 60 Hz units shall                  tor or the condenser.
      be constructed in accordance with UL or UL Canada               9. Shall be equipped with factory-installed thermal
      standards and shall be tested and listed by ETL or                 dispersion chilled fluid flow switch.
      ETL, Canada, as conforming to those standards.             D. Condenser (30HXC units):
      Units shall carry the ETL and ETL, Canada, labels.
                                                                      1. Shall be tested and stamped in accordance with
1.03 DELIVERY, STORAGE, AND HANDLING                                     ASME code (U.S.A.) for a refrigerant working-
   A. Unit controls shall be capable of withstanding                     side pressure of 220 psig (1408 kPa).
      150 F (66 C) storage temperatures in the control                   Water-side pressure rating shall be 300 psig
      compartment.                                                       (2068 kPa). In Canada, maximum water-side
   B. When delivered, machine and starter should be                      pressure shall be 250 psig (1725 kPa), per the
      stored indoors, protected from construction dirt and               Canadian National Registry.
      moisture. Inspect under shipping tarps, bags, or                2. Shall be mechanically cleanable shell-and-tube
      crates to be sure water has not collected during tran-             type with removable heads.
      sit. Protective shipping covers should be kept in               3. Tubes shall be internally enhanced, seamless-
      place until machine is ready for installation.                     copper type, and shall be rolled into
Part 2 — Products                                                        tube sheets. Tube wall thickness shall be
2.01 EQUIPMENT                                                           0.025 inches.
   A. General:                                                        4. Shall be equipped with Victaulic water
                                                                         connections.
      Factory assembled, single-piece, water-cooled
      (30HXC) or condenserless (30HXA) liquid chiller                 5. Design shall incorporate 2 independent refrig-
      with dual (2) independent refrigerant circuits. Con-               erant circuits.
      tained within the unit cabinet shall be all factory wir-   E. Oil Separator (30HXA Units):
      ing, piping, controls, refrigerant charge (HFC-134a)            1. Shall be tested and stamped in accordance with
      (30HXA units shipped with holding charge only),                    ASME Code (U.S.A.) for a refrigerant working-
      and special features required prior to field start-up.             side pressure of 320 psig (2206 kPa).
      Unit must fit through a standard door.
                                                                      2. Design shall incorporate 2 independent refrig-
   B. Compressors:                                                       erant circuits.
        1. Semi-hermetic twin-screw compressors with             F. Refrigeration Components:
           internal muffler and check valve.
                                                                    Refrigerant circuit components shall include oil sep-
        2. Each compressor shall be equipped with a dis-            arator, high and low side pressure relief devices, dis-
           charge shutoff valve.                                    charge and liquid line shutoff valves, filter drier (on
   C. Cooler (Evaporator):                                          30HXC unit only) strainer (30HXA unit only), mois-
        1. Shall be tested and stamped in accordance with           ture indicating sight glass, expansion valve, refriger-
           ASME Code (U.S.A.) for a refrigerant                     ant economizer (unit sizes 161-271), and complete
                                                                                                                        49
Guide specifications (cont)
    charge of compressor oil. The 30HXC units shall               configuration points and alarm diagnostics.
    have a complete operating charge of refrigerant               Reference to factory codes shall not be
    HFC-134a; 30HXA units shall have a holding                    accepted. An industrial grade coiled exten-
    charge of nitrogen.                                           sion cord shall allow the display module to
 G. Controls, Safeties, and Diagnostics:                          be moved around the chiller. Magnets shall
                                                                  hold the display module to any sheet metal
     1. Controls:                                                 panel to allow hands-free operation. Display
        a. Unit controls shall include the following min-         module shall have NEMA 4x housing suit-
           imum components:                                       able for use in outdoor environments. Dis-
             1) Microprocessor with non-volatile mem-             play shall have back light and contrast
                ory. Battery backup system shall not be           adjustment for easy viewing in bright sun-
                accepted.                                         light or night conditions. The display module
             2) Power and control circuit terminal                shall have raised surface buttons with posi-
                blocks.                                           tive tactile response.
             3) ON/OFF control switch.                         d. The chiller controller shall include multiple
             4) Replaceable solid-state relay panels.             connection ports for communicating with
             5) Thermistor installed to measure satu-             the local equipment network, the Carrier
                rated condensing temperature, cooler              Comfort Network® (CCN) system and the
                saturation temperature, compressor                ability to access all chiller control functions
                return gas temperature, and cooler                from any point on the chiller.
                entering and leaving fluid temperatures.
                                                               e. The control system shall allow software
             6) Chilled fluid thermal dispersion flow
                                                                  upgrade without the need for new hardware
                switch.
                                                                  modules.
        b. Unit controls shall include the following
                                                            2. Safeties:
           functions as standard:
                                                               Unit shall be equipped with thermistors and all
             1) Automatic circuit lead/lag.
                                                               necessary components in conjunction with the
             2) Capacity control based on leaving
                                                               control system to provide the unit with the fol-
                chilled fluid temperature and compen-
                                                               lowing protections:
                sated by rate of change of return-fluid
                temperature with temperature set point         a. Loss of refrigerant charge.
                accuracy to 0.1 ° F (0.06° C).                 b. Reverse rotation.
             3) Limiting the chilled fluid temperature         c. Low chilled fluid temperature.
                pull-down rate at start-up to an adjust-
                                                               d. Low oil pressure (each compressor circuit).
                able range of 0.2° F to 2° F (0.11° C to
                1.1° C) per minute to prevent excessive        e. Ground current fault.
                demand spikes at start-up.                     f. Thermal overload.
             4) Seven-day time schedule.                       g. High pressure.
             5) Leaving chilled fluid temperature reset
                from return fluid, outdoor-air tempera-        h. Electrical overload.
                ture, space temperature, or 4 to 20 mA         i. Loss of phase.
                input.                                         j. Current imbalance.
             6) Demand limit control with 2-stage con-
                                                               k. Loss of flow.
                trol (0 to 100% each) or through 4 to
                20 mA input (0 to 100%).                    3. Diagnostics:
             7) Chilled and condenser water pump               a. The display module shall be capable of indi-
                start/stop control.                               cating the safety lockout condition by dis-
             8) Dual chiller control for series chiller           playing the information in clear language at
                applications without addition of hard-            the display. Information included for display
                ware modules or additional thermistors.           shall be:
             9) Dual chiller control for parallel flow              1) Compressor lockout.
                applications use one additional sensor.             2) Loss of charge.
           10) Amperage readout per compressor                      3) Low fluid flow.
                with %MTA (must trip amps) per                      4) Low oil pressure.
                compressor.                                         5) Cooler freeze protection.
        c. NEMA 1 control panel shall include, as stan-             6) High or low suction superheat.
           dard, a portable hand held display module                7) Thermistor malfunction.
           with a minimum of 4 lines and 20 characters              8) Entering and leaving-fluid temperature.
           per line, of clear English, Spanish, Portu-              9) Evaporator and condenser pressure.
           guese or French language. Display menus                10) Electronic expansion valve positions.
           shall provide clear language descriptions of           11) All set points.
           all    menu      items,   operating    modes,          12) Time of day.
50
         b. Display module, in conjunction with the               5. Temperature Reset Sensor:
             microprocessor, must also be capable of dis-            Unit shall reset leaving chilled fluid temperature
             playing the output results of a service test.           based on outdoor ambient temperature or
             Service test shall verify operation of every            space temperature when this sensor is installed.
             switch, thermistor, and compressor before
                                                                * 6. Brine Option:
             chiller is started. User shall be able to force
             each output device.                                     Unit shall be factory modified to start and oper-
                                                                     ate at leaving chilled fluid temperatures of
         c. Diagnostics shall include the ability to review
                                                                     between 15 F (–9 C) and 40 F (4.4 C).
             a list of the 20 most recent alarms with clear
             language descriptions of the alarm event.          * 7. Minimum Load Control:
             Display of alarm codes without the ability              Unit shall be equipped with factory (or field)
             for clear language descriptions shall be                installed, microprocessor-controlled, minimum
             prohibited.                                             load control that shall permit unit operation
         d. An alarm history buffer shall allow the user             down to 10% of full capacity.
             to store no less than 20 alarm events with           8. Chillerviser System Manager:
             clear language descriptions, time and date              Control shall enable management of multiple
             stamp event entry.                                      parallel chillers (up to 8) or two (2) chillers in
H. Operating Characteristics:                                        series in a single system.
    Unit shall be capable of starting up with 95 F (35 C)         9. Minus-One-Pass Cooler:
    entering fluid temperature to the cooler.                        Factory-installed option shall reduce pressure
 I. Electrical Requirements:                                         drop for high flow applications. Shall also
      1. Unit primary electrical power supply shall enter            provide same end inlet and outlet for
         the unit at a single location (some units have              076-106 sizes and opposite end inlet for 116-
         multiple power poles).                                      271 sizes.
      2. Unit shall operate on 3-phase power at the volt-        10. Plus-One-Pass Cooler:
         age shown in the equipment schedule.                        Factory-installed option shall enhance low tem-
      3. Control voltage shall be 115-v (60 Hz) or 230-v             perature brine performance.
         (50 Hz), single-phase, separate power supply.           11. Suction Service Valves:
      4. Unit shall be shipped with factory control and              Unit shall be supplied with factory-installed suc-
         power wiring installed.                                     tion service valves to isolate compressor from
J. Special Features:                                                 evaporator and condenser.
    Certain standard features are not applicable when            12. Cooler Head Insulation:
    the features designated by * are specified. For assis-           Unit shall be supplied with field-installed cooler
    tance in amending the specifications, contact your               insulation that shall cover the cooler heads.
    local Carrier Sales office.                                  13. Energy Management Module:
   * 1. Wye-Delta Starter:                                           A factory or field installed module shall provide
         Unit shall have a factory-installed, Wye-Delta              the following energy management capabilities:
         starter to minimize electrical inrush current.              4 to 20 mA signals for leaving fluid temperature
      2. Sound Reduction Enclosure:                                  reset, cooling set point reset or demand limit
                                                                     control; 2-point demand limit control (from 0 to
         Unit shall have field-installed sound reduction
                                                                     100%) activated by a remote contact closure;
         enclosure which covers the entire unit to muffle
                                                                     and discrete input for “Ice Done” indication for
         compressor noise.
                                                                     ice storage system interface.
      3. Vibration Isolation:
                                                                 14. BACnet Communication Option:
         Chiller manufacturer shall furnish neoprene iso-
                                                                     Shall provide factory installed communication
         lator pads for mounting equipment on a level,
                                                                     capability with a BACnet MS/TP network.
         concrete surface.
                                                                     Allows integration with i-Vu® Open control sys-
      4. Control Power Transformer:                                  tem or a BACnet building automation system.
         Unit shall be supplied with a field-installed trans-
         former that will supply control circuit power
         from the main unit power supply.
                                                                                                                    51
                 Carrier Corporation • Syracuse, New York 13221                  5-10
         Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Section 9                       Pg 52                      Catalog No. 04-52300025-01                    Printed in U.S.A.                         Form 30HX-10PD
Tab     9a                                                                                                                                      Replaces: 30HX-9PD