TORKEL 820
Battery Load Unit
TORKEL 820
Battery Load Unit
                                                                       ▪▪Lightweight
                                                                       ▪▪Expandable    system
                                                                       ▪▪Rugged   and reliable for field use
                                                                       ▪▪Test
                                                                            without disconnecting the battery
                                                                        from the equipment it serves
Description
During a power outage, crucial telecommunication and radio
equipment must be kept operating by batteries. However, the
capacity of such batteries can drop significantly for a number of
reasons before their calculated life expectancy is reached. Battery
capacity should thus be checked to prevent expensive downtime in
the event of a power failure.
The most reliable way to determine battery capacity is to conduct
a discharge test. The TORKEL™820 features a unique design that
combines efficiency with portability. Using TORKEL 820 you can
discharge 24 and 48 V batteries at a current of 270 A, and 12 V
batteries at 135 A. Moreover, two or more TORKEL 820 units
and/or extra load units, TXL, can be linked together if you need
higher current. Discharging proceeds at constant current, constant
power or constant resistance, or in accordance with a pre-selected
load profile.
The TORKEL 820 issues a warning and/or shuts down the test
automatically when a) the voltage has dropped to a certain level,
b) discharging has continued through a certain time interval or c) a
certain amount of capacity has been dissipated.
                                                                                                                   TORKEL 820
                                                                                                               Battery Load Unit
Features and benefits                                              Application example
1.	 Display                                                        Testing can be carried out without disconnecting the battery
2.	 External measurement input used to measure current in an       from the equipment it serves. Via a DC clamp-on ammeter,
    external path by means of a clamp-on ammeter or a current      TORKEL 820 measures total battery current while regulating it at
    shunt.                                                         a constant level.
3.	 Keys for operation and settings.                               The TORKEL 820 is connected to battery, the current and
4.	 Alarm output equipped with a relay contact for triggering an   the voltage alarm level are set. After starting the discharge
    external alarm device.                                         TORKEL 820 keeps the current constant at the preset level.
5.	 Start/Stop input used for starting and stopping discharging    When the voltage drops to a level slightly above the final voltage,
    from an external device. Galvanically isolated.                TORKEL 820 issues an alarm. If the voltage drops so low that
6.	 Indicating lamps. Operating, Stop/Limit                        there is a risk for deep discharging the battery, TORKEL shuts
7.	 TXL output used for control of TXL Extra Loads. Galvani-       down the test. The total voltage curve and the readings taken at
    cally isolated.                                                the end of the test are stored in TORKEL 820. Later, using the
8.	 Serial port used for connection to a PC or other controlling   TORKEL Win program, you can transfer these readings to your
    equipment.                                                     computer for storage, printout or export. If your PC is connected
                                                                   to TORKEL 820 during the test, TORKEL Win builds up a
9.	 Voltage controlled circuit breaker that connects / discon-
                                                                   voltage curve on the screen in real time and displays the current,
    nects the loading circuits in TORKEL from the battery.         voltage and capacity readings. You can also control the test using
10.	Positive current connection for battery being tested.          TORKEL Win.
11.	Input for sensing voltage at the battery terminals.
12.	Negative current connection for battery being tested.
13.	Mains connector, equipped with ON/OFF switch.
        1       2        3    4        5     6    7         8
            9       10             11             12        13
 2
                                                                                                                                TORKEL 820
                                                                                                                            Battery Load Unit
Specifications TORKEL 820                                            Load section
Specifications are valid at nominal input voltage and an ambient     Battery voltage                  10 – 60 V DC
temperature of +25°C, (77°F). Specifications are subject to change   Max. current                     270 A
without notice.
                                                                     Max. power                       15 kW
Environment                                                          Load patterns                    Constant current, constant power, con-
Application field       The instrument is intended for use in                                         stant resistance, current or power profile
                        high-voltage substations and industrial      Current setting                  0-270.0 A (2999.9 A) 1)
                        environments.
                                                                     Power setting         0-15.00 kW (299.99 kW) 1)
Temperature
                                                                     Resistance setting    0.1-2999.8 Ω
 Operating           0°C to +40°C (32°F to +104°F)
                                                                     Battery voltage range 2 ranges, selected automatically at start
 Storage & transport -40°C to +70°C (-40°F to +158°F)
                                                                                           of test
Humidity                5% – 95% RH, non-condensing                  Stabilization (For    ±(0.5% of reading + 0.5 A)
                                                                     internal current
CE-marking                                                           measurement)
LVD                     2006/95/EC                                               Battery   Highest permissible        Resistor ele-
EMC                     2004/108/EC                                              voltage   current                    ment (Nomi-
                                                                                                                      nal values)
General
Mains voltage           100 – 240 V AC, 50 / 60 Hz                   Range 1 10 – 27.6     270 A                      0.069 Ω
                                                                                 V
Power consumption       150 W (max)
                                                                     Range 2 10 – 55.2 270 A                          0.138 Ω
Protection              Thermal cut-outs, automatic overload
                                                                                 V
                        protection
                                                                     1) Maximum value for a system with more than one load unit
Dimensions
 Instrument             210 x 353 x 700 mm                           Inputs, maximal values
                        (8.3” x 13.9” x 27.6”)                       EXTERNAL                         1 V DC, 300 V DC to ground. Current
                                                                     CURRENT                          shunt should be connected to the negative
 Transport case         265 x 460 x 750 mm
                                                                     MEASUREMENT                      side of the battery
                        (10.4” x 18.1” x 29.5”)                      EXTERNAL
Weight                  22.3 kg (49.2 lbs)                           CURRENT
                        40.4 kg (89.1 lbs) with accessories and      START / STOP                     Closing / opening contact
                        transport case                                                                Closing and then opening the contact will
Display                 LCD                                                                           start / stop Torkel. It is not possible to keep
Available languages     English, French, German, Spanish, Swedish                                     the contacts in closed position.
Measurement section                                                  Delay until start                200 – 300 ms
Current measurement                                                  Stop delay                       100 – 200 ms
Display range     0.0 – 2999 A                                       Battery                          60 V DC, 500 V DC to ground
Basic inaccuracy  ±(0.5% of reading +0.2 A)                          VOLTAGE SENSE                    60 V DC, 500 V DC to ground
Resolution        0.1 A                                              SERIAL                           < 15 V
                                                                     ALARM                            250 V DC 0.28 A
Internal current measurement
                                                                                                      28 V DC 8 A
Range                0 – 270 A                                                                        250 V AC 8 A
Input for clamp-on ammeter
                                                                     Outputs, maximal values
Range               0–1V                                             START / STOP                     5 V, 6 mA
mV/A-ratio          Software settable, 0.3 to 19.9 mV/A              TXL                              Relay contact
Input impedance     >1 MΩ                                            SERIAL                           < 15 V
Voltage measurement                                                  ALARM                            Relay contact
Display range 0.0 – 60 V
                                                                     Discharging capacity, examples
 Basic inaccuracy      ±(0.5% of reading +0.1 V)
                                                                     12 V battery (6 cells) 2)
 Resolution            0.1 V
                                                                     Final voltage           Constant current                     Constant power
Time measurement                                                     1.80 V / cell (10.8 V)           0 – 121 A                   0 – 1.31 kW
Basic inaccuracy        ±0.1% of reading ±1 digit                    1.75 V / cell (10.5 V)           0 – 117 A                   0 – 1.23 kW
                                                                     1.67 V / cell (10.0 V)           0 – 110 A                   0 – 1.10 kW
                                                                     24 V battery (12 cells) 2)
                                                                     1.80 V / cell (21.6 V) 0 – 270 A                             0 – 5.8 kW
                                                                     1.75 V / cell (21.0 V) 0 – 266 A                             0 – 5.59 kW
                                                                     1.60 V / cell (19.2 V) 0 – 241 A                             0 – 4.63 kW
                                                                     48 V battery (24 cells) 2)
                                                                     1.80 V / cell (43.2 V) 0 – 270 A                             0 – 11.6 kW
                                                                     1.75 V / cell (42.0 V) 0 – 270 A                             0 – 11.3 kW
                                                                     1.60 V / cell (38.4 V) 0 – 259 A                             0 – 9,9 kW
                                                                     2)	 2.15 V per cell when test starts
                                                                                                                                                   3
                                                                                                                     TORKEL 820
                                                                                                                 Battery Load Unit
Optional accessories                                               Application examples with TORKEL/TXL sys-
                                                                   tems
TXL                                                                TORKEL and TXL can be combined into systems to match up
These resistive extra loads do not perform any regulating func-    for different battery capacities. Here is an example.
tions. They are designed for use together with TORKEL Battery
Load Units. Their purpose is to provide higher load currents
for use in constant current or constant power tests. Together,
TORKEL and the TXL Extra Loads form a system that can
discharge batteries with currents of up to several kA. TXL Extra
Loads are connected directly to the battery, and TORKEL mea-
sures the total current using a clamp-on ammeter.
TXL Extra Loads are shut down automatically when TORKEL is
stopped.
                                                                   TORKEL and the extra load TXL
                                                                   TORKEL / TXL - systems examples
                                                                   Max. constant current     Number of              Number of
                                                                   (A)                       TORKEL-units           TXL-units
                                                                   TORKEL 820 + TXL830, 12 V battery (6 cells)1)
                                                                   234                       1                      1
TXL850                                                             571                       1                      4
                                                                   918                       2                      6
TORKEL Win PC software                                             TORKEL 820 + TXL830, 24 V battery (12 cells)1)
Shows    the complete voltage curve                              495                       1                      1
Last
                                                                   1170                      1                      4
         recorded time, voltage, current and discharged
                                                                   1890                      2                      6
     capacity
                                                                   TORKEL 820 + TXL850, 48 V battery (24 cells)1)
Scroll-window    for all recorded values
                                                                   499                       1                      1
Remote     control of TORKEL                                     1189                      1                      4
Report    functions                                              1918                      2                      6
                                                                   1)	 Discharge from 2.15 V to 1.8 V per cell
TORKEL Win showing the total voltage graph
 4
                                                                                                                             TORKEL 820
                                                                                                                         Battery Load Unit
Specifications TXL830 / 850
Specifications are valid at nominal input voltage and an ambient
temperature of +25°C, (77°F). Specifications are subject to change
without notice.
Environment
Application field                 The instrument is intended for use
                                  in high-voltage substations and
                                  industrial environments.
Temperature
 Operating                        0°C to +40°C (32°F to +104°F)
 Storage & transport              -40°C to +70°C (-40°F to +158°F)
Humidity                          5% – 95% RH, non-condensing
CE-marking
LVD                               2006/95/EC
EMC                               2004/108/EC
General                                                                    Cable set, GA-00554
Mains voltage                     100 – 240 V AC, 50 / 60 Hz
Power consumption                 75 W (max)
Protection                        Thermal cut-outs, automatic over-
                                  load protection
Dimensions
Instrument                        210 x 353 x 600 mm
                                  (8.3” x 13.9” x 23.6”)
Transport case                    265 x 460 x 750 mm
                                  (10.4” x 18.1” x 29.5”)
Weight                            13 kg (28.7 lbs)
                                  21.4 kg (47.2 lbs) with transport case
Cable sets
for TXL830 / 850                  2 x 3 m (9.8 ft), 70 mm2, 270 A, with
                                  cable lug. Max. 100 V. 5 kg (11 lbs)
                                                                           Ordering information
Load section                                                                 Item                                                       Art. No.
                         TXL830                   TXL850                    TORKEL 820
Max. voltage (DC) 28 V                            56 V                      Complete with:
Max. current             300 A                    300 A                     Cable set GA-00554
Max. power               8.3 kW                   16.4 kW                   Transport case GD-00054                                     BS-49092
Internal resistance, 3-position selector                                    Optional
Position 1           TXL830                       TXL850                    TORKEL Win PC software                                      BS-8208X
 Current                 0.275 Ω                  0.55 Ω                    Extra loads
 100 A                   at 27.6 V (12 x 2.3 V)   at 55.2 V (24 x 2.3 V)    TXL830                                                      BS-59093
 78.5 A                  at 21.6 V (12 x 1.8 V)   at 43.2 V (24 x 1.8 V)
                                                                            TXL850                                                      BS-59095
 50.1 A                  –                        –
 39.2 A                  –                        –                         Cable sets
Position 2               TXL830                   TXL850                    Cable set for TXL830 and TXL850
 Current                 0.138 Ω                  0.275 Ω                   2 x 3 m, 70 mm2, with cable lug. Max 100 V 270 A.
 200 A                   at 27.6 V                at 55.2 V (24 x 2.3 V)    Weight: 5.0 kg (11 lbs)                                     GA-00554
 156 A                   at 21.6 V                43.2 V (24 x 1.8 V)–      Sensing lead set
Position 3               TXL830                   TXL850                    Cable set for measuring voltage at battery terminals.
  Current                0.092 Ω                  0.184 Ω                   2 x 5 m (16.4 ft)                                     GA-00210
  300 A                  at 27.6 V                at 55.2 V (24 x 2.3 V)    Clamp-on ammeters
  235 A                  at 21.6 V                43.2 A (24 x 1.8 V)       DC clamp-on ammeter, 200 A
  100 A                  –                        –                         To measure current in circuit outside TORKEL                XA-12792
  78.4 A                 –                        –
                                                                            DC clamp-on ammeter, 1000 A
                                                                            To measure current in circuit outside TORKEL                XA-12790
SWEDEN                                 UK                                  Other Technical Sales Offices      Registered to ISO 9001 and 14001
                                                                                                              Subject to change without notice.
Megger Sweden AB                       Archcliffe Road Dover               Dallas USA, Norristown USA,
                                                                                                              Art.No. ZI-BS01E • Doc. BS2642CE • 2010
Eldarvägen 4, Box 2970                 CT17 9EN England                    Toronto CANADA, Trappes FRANCE,
SE-187 29 TÄBY                         T +44 (0) 1304 502101               Oberursel GERMANY, Johannesburg    TORKEL-820_DS_en_V02
T	 +46 8 510 195 00                    F +44 (0) 1304 207342               SOUTH AFRICA, Kingdom of BAHRAIN   www.megger.com
F	 +46 8 510 195 95                                                        Mumbai INDIA, Chonburi THAILAND    Megger is a registered trademark
E	 seinfo@megger.com                                                       Sydney AUSTRALIA