Input Data 14 Bus
Data of Lines
 From Bus       To Bus       R in p.u.    X in p.u.   Qc/2 in p.u.
     1            2          0.01938     0.05917       0.02640
     1            2          0.09498      0.0219      0.025581
     1            5          0.05403     0.22304       0.02460
     2            3          0.04699     0.19797       0.02190
     2            4          0.05811     0.17632       0.01870
     2            5          0.05695     0.17388       0.01700
     3            4          0.06701     0.17103       0.01730
     4            5          0.01335     0.04211       0.00640
     6            11         0.09498     0.19890       0.00000
     6            12         0.12291     0.25581       0.00000
     6            13         0.06615     0.13027       0.00000
     9            10         0.03181     0.08450       0.00000
     9            14         0.12711     0.27038       0.00000
    10            11         0.08205     0.192017      0.00000
    12            13         0.22092     0.19988       0.00000
    13            14         0.17093     0.34802       0.00000
Data of Line in Simulation Model
 Line Number    From Bus       To Bus       R in Ω       X in Ω       B in μS
       1            1            2        6.75354      20.61956      151.5152
       2            1            2        6.75354      20.61956      151.5152
       3            1            5        9.41418      38.86249      282.3691
       4            2            3        8.18753      34.49428      251.3774
       5            2            4        10.12509     30.72200      214.6465
       6            2            5        9.92296      30.296850     195.1331
       7            3            4        11.67582     29.80027      198.5767
       8            4            5        2.32610       7.33724      73.4619
       9            6            11       1.034332      2.16602      0.00000
      10            6            12       1.33849       2.78577      0.00000
      11            6            13       0.72037       1.41864      0.00000
      12            9            10       0.34641       0.92020      0.00000
      13            9            14       1.38422       2.94443      0.00000
      14           10            11       0.89352       2.09164      0.00000
      15           12            13       2.40581       2.17669      0.00000
      16           13            14       1.86142       3.78993      0.00000
CASE 1 : The power system of 14 bus IEEE was carried out by load flow Newton-Raphson with the
normal load at all the load busses. The load scaling factor for this case is equal to 100% as the base
case for standard operating condition.
                                                             Voltage in p.u.
            Bus Number                                                          With STATCOM
                                             Without STATCOM
                  1                                  1.05                             1.05
                  2                                  1.05                             1.05
                  3                                  0.98                             0.98
                  4                                  0.99                             1.00
                  5                                  1.00                             1.00
                  6                                  1.02                             1.04
                  7                                  1.02                             1.03
                  8                                  1.04                             1.04
                  9                                  1.02                             1.03
                 10                                  1.01                             1.02
                 11                                  1.01                             1.03
                 12                                  1.00                             1.03
                 13                                  0.99                             1.03
                 14                                  0.96                             1.05
                                       Reactive Power (MVAR)                Active Power (MW)
 Generator 1                                   -39.57                             233.76
 Generator 2                                   115.92                              40.00
 Generator 3                                     0.00                               0.00
 Generator 6                                     0.00                               0.00
 Generator 8                                     8.01                               0.00
Summary of Load Flow Case 1
                                       Reactive Power (MVAR)                Active Power (MW)
 Generation                                     85.61                             273.77
 Grid Losses                                    31.94                              14.76
 Load                                           73.50                             259.00
Case 2: Case 1 with 20% increase in load without STATCOM
Bus Voltage After Run Load Flow in The Simulation Model
    Bus                   Voltage in p.u.                              Angle (˚)
  Number       Without STATCOM       With STATCOM          Without STATCOM With STATCOM
     1               1.05                 1.05
     2               1.05                 1.05
     3               0.98                 0.98
     4               0.99                 0.99
     5               0.99                 0.99
     6               1.02                 1.02
     7               1.02                 1.02
     8               1.04                 1.04
     9               1.01                 1.01
    10               1.00                 1.00
    11               1.00                 1.01
    12               0.99                 1.00
    13               0.98                 1.00
    14               0.94                 1.01
                          Reactive Power ( Mvar )                  Active Power ( MW )
                                                                 Without
                   Without STATCOM       With STATCOM                         With STATCOM
                                                                STATCOM
 Generator 1            -46.95               -47.24              292.82            292.84
 Generator 2            137.15               136.24               40.00            40.00
 Generator 3            15.46                 14.92               0.00              0.00
 Generator 6            11.64                 -5.14               0.00              0.00
 Generator 8            11.66                  9.85               0.00              0.00
Grid Summary of Load Flow
                       Reactive Power ( Mvar )                     Active Power ( MW )
                 Without STATCOM     With STATCOM          Without STATCOM With STATCOM
 Generation           128.98             108.63                 332.83             332.85
 Grid Losses          60.24               40.13                 22.03               22.05
 Load                 88.20               88.20                 310.80             310.80
Case 3: Case 1 with 40% increase in load without STATCOM
Voltages at Bus
    Bus                   Voltage in p.u.                              Angle (˚)
  Number       Without STATCOM       With STATCOM          Without STATCOM With STATCOM
     1               1.05                 1.05
     2               1.05                 1.05
     3               0.98                 0.98
     4               0.98                 0.98
     5               0.94                 0.95
     6               1.02                 1.02
     7               1.01                 1.01
     8               1.04                 1.04
     9               1.00                 1.00
    10               0.99                 0.99
    11               0.99                 1.00
    12               0.99                 1.00
    13               0.98                 0.99
    14               0.93                 1.00
Power at Generator
                          Reactive Power ( Mvar )                  Active Power ( MW )
                                                                 Without
                   Without STATCOM       With STATCOM                         With STATCOM
                                                                STATCOM
 Generator 1             -52.57              -52.85              353.72            353.56
 Generator 2             161.44              160.43               40.00            40.00
 Generator 3             31.57                30.99               0.00              0.00
 Generator 6             23.34                6.22                0.00              0.00
 Generator 8             15.62                13.76               0.00              0.00
Grid Summary of Load Flow
                        Reactive Power ( Mvar )                    Active Power ( MW )
                  Without STATCOM     With STATCOM         Without STATCOM With STATCOM
 Generation            179.42             158.56                393.72             353.56
 Grid Losses           95.59               74.97                31.12               30.96
 Load                  102.90             102.90                362.60             362.60
Case 4: Case 1 with 60% increase in load without STATCOM
Voltages at Bus
    Bus                   Voltage in p.u.                              Angle (˚)
  Number       Without STATCOM       With STATCOM          Without STATCOM With STATCOM
     1               1.05                 1.05
     2               1.05                 1.05
     3               0.98                 0.98
     4               0.97                 0.97
     5               0.98                 0.98
     6               1.02                 1.02
     7               1.00                 1.00
     8               1.04                 1.04
     9               0.99                 0.99
    10               0.98                 0.98
    11               0.99                 0.99
    12               0.98                 0.99
    13               0.97                 0.99
    14               0.91                 0.99
Power at Generator
                          Reactive Power ( Mvar )                  Active Power ( MW )
                                                                 Without
                   Without STATCOM       With STATCOM                         With STATCOM
                                                                STATCOM
 Generator 1             -56.25              -56.55              416.61            416.24
 Generator 2             189.07              187.94               40.00            40.00
 Generator 3             48.75                48.13               0.00              0.00
 Generator 6             36.06                18.55               0.00              0.00
 Generator 8             19.92                18.01               0.00              0.00
Grid Summary of Load Flow
                        Reactive Power ( Mvar )                    Active Power ( MW )
                  Without STATCOM     With STATCOM         Without STATCOM With STATCOM
 Generation            237.58             216.08                456.62             456.25
 Grid Losses           138.64             117.39                42.22               41.85
 Load                  117.60             117.60                414.40             414.40
Case 5: Case 1 with 80% increase in load without STATCOM
Voltages at Bus
    Bus                   Voltage in p.u.                              Angle (˚)
  Number       Without STATCOM       With STATCOM          Without STATCOM With STATCOM
     1               1.05                 1.05
     2               1.05                 1.05
     3               0.98                 0.98
     4               0.97                 0.97
     5               0.97                 0.97
     6               1.02                 1.02
     7               0.99                 1.00
     8               1.04                 1.04
     9               0.97                 0.98
    10               0.97                 0.97
    11               0.98                 0.99
    12               0.98                 0.99
    13               0.96                 0.98
    14               0.90                 0.97
Power at Generator
                          Reactive Power ( Mvar )                  Active Power ( MW )
                                                                 Without
                   Without STATCOM       With STATCOM                         With STATCOM
                                                                STATCOM
 Generator 1             -57.81              -58.15              481.72            481.09
 Generator 2             220.42              219.10               40.00            40.00
 Generator 3             67.11                66.43               0.00              0.00
 Generator 6             49.94                31.96               0.00              0.00
 Generator 8             24.90                22.61               0.00              0.00
Grid Summary of Load Flow
                        Reactive Power ( Mvar )                    Active Power ( MW )
                  Without STATCOM     With STATCOM         Without STATCOM With STATCOM
 Generation            304.27             281.97                521.73             521.10
 Grid Losses           190.20             168.15                55.53               54.90
 Load                  132.30             132.30                466.20             466.20
                                             Implementation STATCOM
    Case                        PLoss(MW)                             PLoss(MVAR)
                      Before                 After           Before                 After
      1                14.76                 14.76            31.94                 10.69
      2                22.03                 22.05            60.24                 40.13
      3                31.12                 30.96            95.59                 74.97
      4                42.22                 41.85           138.64                 117.39
      5                55.53                 54.90           190.20                 168.15
                      𝑃𝑙𝑜𝑠𝑠𝑒𝑠       𝑝𝑙
                 𝑅=     𝐼2
                                =   𝐴
                                         .
Where;
R : Resistance of conductor (Ω)
P : Resistivity of conductor (Ω)
l : Length of conductor (m)
A : Cross section area of conductor (m2)
                          𝜆
                     𝐿=   𝐼
                              .
Where;
L : Inductance (H)
I : Current (A)
𝜆 : Instantaneous flux linkage (Wb)
                          𝑞
                     𝐶=   𝑣
                                  .
Where;
C : Capacitance (C)
q : Charge on conductor (C)
v : Potential difference between conductor (V)
                                                                  2           𝛾𝐿
                     𝑍𝑒𝑥 = 𝑧𝑠 sinh 𝛾𝐿.              and   𝑌𝑒𝑥 =   𝑍𝑠
                                                                       tanh   2
                                                                                 .
Where;
Z : Series impedance
Y : Shunt admittance
L : length of line
                                                          𝑍
                     𝛾 = √𝑍𝑌.               And     𝑍𝑠 = √𝑌.
Where;
𝛾 : Propagation constant
Zs : Surge impedance
                     𝐴 = cosh 𝛾𝐿.
                     𝐵 = −𝑍𝑠 sinh 𝛾𝐿.
                                  1
                     𝐶 = − 𝑍 sinh 𝛾𝐿.
                                      𝑠
                     𝐷 = cosh 𝛾𝐿.
                      𝑣       𝐴           𝐵      𝑣
                     [ 𝑟 ]= [               ] = [ 𝑠 ].
                       𝑖𝑟     𝐶           𝐷      𝑣𝑟
                v              v                           v
P = P0 ( aP (      ) ea1 + bP ( ) ea1 + ( 1 − aP − bP ) ∗ ( )ea1
                v0             v0                          v0
                v              v                           v
Q = Q0 ( aQ (      ) ea2 + bQ ( ) ea2 + ( 1 − aP − bP ) ∗ ( )ec2
                v0             v0                          v0