Re 120gr

Ravel Electronics Pvt. Ltd. manufactures fire alarm panels including the RE-120GR model. The RE-120GR features a rugged powder-coated steel enclosure, LCD display, battery backup, programmable relays, zone isolation, compatible conventional detectors, and outputs for notification appliances, solenoids and remote devices. It operates on 220V AC power and has a dimension of 400 x 300 x 100 mm.

Uploaded by

Ravi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
1K views1 page

Re 120gr

Ravel Electronics Pvt. Ltd. manufactures fire alarm panels including the RE-120GR model. The RE-120GR features a rugged powder-coated steel enclosure, LCD display, battery backup, programmable relays, zone isolation, compatible conventional detectors, and outputs for notification appliances, solenoids and remote devices. It operates on 220V AC power and has a dimension of 400 x 300 x 100 mm.

Uploaded by

Ravi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

RAVEL ELECTRONICS PVT. LTD.

,
150-A, ELECTRONICS INDUSTRIAL ESTATE,
PERUNGUDI, CHENNAI - 600 096. INDIA.
Ph.: +91-44-2496 1004 / 0825. Fax: +91-44-4204 9599.
E-Mail: marketing@ravelfirepanels.com
URL: www.ravelfirepanels.com
FEATURES:
Ø
Ø
Rugged CRCA sheet with powder coated finish.
Operates on 220V, A.C supply
RE - 120GR
Ø Battery backup with built in charging.
Ø 16 X 2 LCD Dot Matrix Display.
Ø Evacuate and Key pad Enable, Disable Facility.
Ø Low battery visual warning with audible tone.
Ø 2 Form C Relay output for fire.
Ø One Programmable relay for fire/fault/solenoid on /timer
on.
Ø Remote fire indication with Audible Tone.
Ø Compatible to all types of conventional detectors.
Ø Zone Disable (Isolation) facility with loop voltage cut off.
Ø Resettable 24v DC output for 4 wire detectors .
Ø Three 24V Hooter Output (Fire, after Cross zone, after gas
release) .
Ø Two mode operation facility (Auto / Manual).
Ø Programmable FAP input selection Facility.
Ø Programmable Solenoid Output with On and OFF Timer.
Ø Main / Standby Cylinder output Facility .
Ø Gas Inhibition and Instant release facility.
Ø Manual Gas Release with or without timer.
Ø Actuator pressure low sensing facility.

Power Remote Outputs


220 VAC ± 10%,, 50 Hz. Fire Contact (C, NO, NC) : 220v AC/30v DC@ 1A
Wire size: 1.5 Sq. mm with 600V insulation Fault Contact (C, NO, NC ): 220v AC/30v DC@ 1A
Timer Contact (C, NO, NC): 220v AC/30v DC@ 1A
Battery (Lead Acid only)
Charging Voltage : 27.9 VDC. 24 VDC Power For remote devices
Charging Capacity : 7 Amp Hour Battery Max. Operating Voltage: 24VDC, 500mA Max.
System Quiescent Current: 80mA + (2.4mA for Detector s) RS 24 VDC Power For Four Wire devices
TECHNICAL DATA

Initiating Device Circuits (Zone Circuit) Operating Voltage: 24VDC, 500mA Max.
All zones are Class B wiring
Normal Operating Voltage : Nominal 24 VDC Dimension of the panel :
Alarm Current : 15 - 35mA threshold 400 x 300 x 100 mm ( length x height x width )
Short Circuit Current : 40mA Maximum
Loop resistance : 50 ohms Maximum
End-Of-Line Resistor : 4.7K, 1/4watt
Standby Current : 6.8mA (2.4mA for Detectors)
Notification Appliance Circuits (Sounder/Hooter Circuit)
Operating Nominal Voltage: 24 VDC
Hooter (NACs) output : 0.5A (Each)
End-Of-Line Resistor : 4.7K, 1/4watt

Solenoid Relay Output Circuits


Operating Nominal Voltage : 24 VDC
Solenoid output : 0.75A (Each)
2No’s of Hooter (NACs) output : 0.3A (Each)
End-Of-Line Resistor: 4.7K, 1/4watt (for Solenoid Output)