POWER FORMULA FOR 3-PHASE SYSTEM
KV I PF POWER IN MVA
132000 109.37 1 25.00460688
AMPS FORMULA
POWER KV PF HV AMPS
25000000 132000 1 228624 109.349849535
SHORT CIRCUIT MVA
MVA X% SHORT CIRCUIT MVA
25 9.02 277.1618625277
SHORT CIRCUIT CURRENT
Sc MVA KV ROOT KV*ROOT Sc A
400000 132 1.732 228.624 1749.59759255
TRANSFORMER
IMPEDENCE VOLTAGE FORMULA
% IMP BASE KV IMP V
9.02 132000 11906.4
IMPEDENCE RATIO
IMP V APP V RATIO
11906 415 28.689156627
I1 RATIO
HV-A IMP-RATIO I1-RATIO
82.668 45.06 1.834620506
I2 RATIO
I1 I2 RATIO
82.668 2598.15 57.659786951
VOLTAGE RATIO FOR CVT
Sec.V Appiled.V Base KV ratio
110 2000 400000 0.55
STABILIZING RESISTOR SELECTION CALCULATION
INPUTS
Base MVA of Transformer
Impedence
Amps
CT-primary-A
Rct*
Loop RL*
HV/LV-V
RELAY COIL VA
Id MIN
RELAY OPERATING CURRENT*
SHORT CIRCUIT MVA
MVA X%
25000000 0.1043
SHORT CIRCUIT CURR
Sc MVA KV
23969319271.3327 132000
Calculation of required operating voltage UR for through fa
UR = Ifmax/CT P-A (Rct +2 Rl)
Ifmax Rct
6.989443882 2.22
Relay operating Voltage
VA/I = burden/current
RELAY COIL VA SETTING A
0.04 0.0726666667
Voltage across stabilizing resistor:
UR RELAY OPERATING V
18.8714984815 0.5504587156
Voltage across resistor
Stabilizing resistance = Current through resistor
VOLTAGE ACROSS RESISTOR CURRENT THROUGH RESISTOR
18.3210397659 0.0726666667
select stabilizing resistor 252.1244004485
Rct= is a winding resistance of aCT secondary core
RI= loop resistance of connecting cables
standerd = 8.0ohm/km * 2run
G
Before enter please see the note
CALCULATION
ENTER YOUR INPUTS HERE
VA 25000000
%IMP/100 0.1043
RESISTOR VALUE
HV/LV 109
PRIMARY-A 150
WINDING RESISTANCE-OHM 2.22 1
150
WIRE RESISTANCE 0.48 0.0066666667
10.9
VOLTAGE 132000
0.04
VA
10% OF HV/LV -A 10.9
0.0726666667
T CIRCUIT MVA
SHORT CIRCUIT MVA
23969319271.3327
SHORT CIRCUIT CURRENT
ROOT KV*ROOT Ifmax
1.732 228624 1048 6.989443882
UR for through fault stability.
2RI UR
0.48 18.8714984815
RELAYOPERATING- V
0.5504587156
VOLTAGE ACROSS RESISTOR
18.3210397659
STEBILIZING RESISTANCE
252.1244004485
ohms
econdary core
NOTE:
1.CT RATIO IS EXAMPLE 500/1 1/500=.002
2.WIRE REISTANCE
252.1244 OHMS 8.8OHMS/KM YOU COLLECT HOW MUCH DISTANCE FROM YAR
FOR EXAMPLE 300M 8.8/300
RI= 2*2.8=5.6
3. MVA VALUE CONVERT TO VA
4. KV VALUE CONVERT TO V
5.ENTER ANY ONE OF HV OR LV VOLTAGE WHICH SIDE THE H
6.ENTER ANY ONE OF HV OR LV AMPS
7.* MARKING OF INPUT Automatly GENERATED
8. it is suitable for 2Winding and 3Winding transfomer
auto transformer ref stabilizing resistor calculation
relay coil VA for REx670 = 0.25VA
1/500=.002
HOW MUCH DISTANCE FROM YARD TO PANEL
2.8
LV VOLTAGE WHICH SIDE THE HIGH IMP REF WILL COME
atly GENERATED
ng and 3Winding transfomer only
bilizing resistor calculation under progress