SCHEDULE OF FIRE FIGHTING PUMPS & HEAD CALCULATIONS
Total
                                       Flow    Pumping                                      Remark/
S. No. Description of Pump                                  Qty.      Motor KW   Motor
                                       Rate     Head                                        Location
                                                                                  KW
 A.                    FIRE FIGHTING PUMPS LOCATED IN FIRE PUMP ROOM AT BASEMENT-2
        Electrical Driven Hydrant      2850                                                pump Room
 1.                                               110M      1 No.      106 KW    106 KW
        Pump                           LPM                                                (Basement-2)
        Electrical Driven Sprinkler    2850                                                pump Room
 2.                                               110 M     1 No.      106KW     106 KW
        Pump                           LPM                                                (Basement-2)
                                       2850                                                pump Room
 3.     Diesel Driven Fire Pump                   110 M     1 No.        -         -
                                       LPM                                                (Basement-2)
        Electrical Driven Jockey       180                                       24.00     pump Room
 4.                                               110 M     2 No.     12.00 Kw
        Pump                           LPM                                        Kw      (Basement-2)
        Electrical Driven Curtain      2280                                                pump Room
 5.                                               30 M      1 No.      40 Kw     40 Kw
        Nozzle Fire Pump               LPM                                                (Basement-2)
  DETAIL OF WATER CURTAIN NOZZLE PUMP
  [A]    Horizontal Mounted Downward Flow Open Nozzle:
        Total Length of Pipe Network for water curtain in one zone = 84 m
        Spacing between Open Nozzles                   = 2.5 m C/C [Nozzle
         Manufacturer recommends 2 m for better performance]
        Nos. of Open Nozzles                        =       84
                                                             2.5
                                                     =      34 Nos.
        The flow through each nozzle is calculated by formula.
         Q = K x P (As per IS: 9972/ NFPA 13)
         Where
         Q = Flow in lpm flowing through nozzle
             K = Nozzle Factor = 45 (As per manufacturer HD Fire)
             P = Total Pressure in Bar at flow Q = 1.6 bar
             Q = 45 x 1.6 = 56.92 lpm
            Total Flow rate required                    =34 Nos. Nozzle x 56.92 lpm Flow on each
                                                             nozzle.
                                                         =1935 LPM
                                                         = 116.11 m3/Hour
             Maximum water curtain Pump capacity required= 1935 LPM = 116.11 m3/hour
             Capacity of pump proposed                       = 2280 lpm =137 m3/hour
PUMP HEAD CALCULATIONS FOR WATER CURTAIN
Head requirement for Fire Pump has been decided as below
As Per water curtain requirement, there shall be minimum pressure of 1.6 kg/sq.cm at the last water
curtain
Note: Considering that basement shall be provided the water curtain system:
Total Vertical Length of Pipe from Plant Room to remotest water curtain          = 9M
Total Horizontal Length of Pipe from Plant Room to remotest water curtain= 50 M
Total Length of Pipe from Plant Room to remotest water curtain                  = 59 M
Equivalent Length of Pipe Due to Fittings @ 10 %                                =6M
Total Length of Pipe                                                     = 65 M
                                                                  Say    = 65 M
Design calculation for total pump head requirement as per using following pipe diameter.
    S. No.     Description                                                             Pipe Diameter 150 mm
     01.       Total length of pipe                                                     65 m
     02.       Required residual head                                                   16 m
     03.       Static Head                                                              9m
     04.       Head loss in Pipe                                                        2m
               (As per Hazen William’s Formula)
               Referring Annexure-II
     05.       Total (2) + (3) + (4)                                                   27 m
     06.       Head of Pump provided                                                   30 m
                                                                                                          2
Head Loss Calculations -Annexure -II
      Hazen William’s formula
H=    6.05 x 10^5 x Q^1.85 x L
      ----------------------
      C^1.85 x d^4.87
Where L = Length of pipe in meters = 65 m
      Q = Discharge in Lpm = 1280 Lpm
      C = 120
      D = Dia. of pipe in mm = 150 mm
      H = Head loss in bar.
Putting these values in the above formula:
H=    6.05 x 10^5 x 2280^1.85 x 65
       ----------------------
       120^1.85 x 150^4.87
      =     0.23 bar
  Say = 2
PUMP HEAD CALCULATIONS
Head requirement for Fire Pump has been decided as below
As Per NBC Rule, there shall be minimum pressure of 3.5kg/sq.cm at the highest Fire
Hydrant:
Note: Considering that Tower shall be provided the Fire fighting system:
Total Vertical Length of Pipe from Plant Room to remotest Fire Hydrant = 64 M
Total Horizontal Length of Pipe from Plant Room to remotest Fire Hydrant = 80 M
Total Length of Pipe from Plant Room to remotest Fire Hydrant           = 144 M
Equivalent Length of Pipe Due to Fittings @ 10 %                        =14.4 M
Total Length of Pipe                                                   = 158.4 M
                                                                                      3
                                                                Say    = 159 M
Design calculation for total pump head requirement as per using following pipe diameter.
 S. No.    Description                                                     Pipe Diameter 150 mm
  01.      Total length of pipe                                             159 m
  02.      Required residual head                                           35.0 m
  03.      Static Head                                                      64 m
  04.      Head loss in Pipe                                                9m
           (As per Hazen William’s Formula)
           Referring Annexure-II
  05.      Total (2) + (3) + (4)                                           108 m
  06.      Head of Pump provided                                           110 m
Head Loss Calculations -Annexure -II
        Hazen William’s formula
H=      6.05 x 10^5 x Q^1.85 x L
        ----------------------
        C^1.85 x d^4.87
Where L = Length of pipe in meters = 159 m
        Q = Discharge in Lpm = 2850 Lpm
        C = 120
        D = Dia. of pipe in mm = 150 mm
        H = Head loss in bar.
Putting these values in the above formula:
H=      6.05 x 10^5 x 2850^1.85 x 159
         ----------------------
         120^1.85 x 150^4.87
       = 0.85 bar
  Say = 9 M
 A) Suction Header size for Sprinkler , Hydrant ,Diesel & water curtain pump:
    Flow rate Q for Sprinkler & Hydrant pump =                  2850 LPM
                                                                                                  4
                                                  =             171 M3/Hr
     No. of Pumps                                 =                       2No.
     Flow rate Q for Water                        =                   2280 LPM
     Curtain pump                                 =                  136.8 M3/Hr
     No. of Pumps                                 =                       1No.
     Total Flow Rate                              =                  0.133M3/s
     Considered water velocity (v)                =                     1.5m/s
     Suction pipe                                 =                 2 Nos.
     Flow rate Q                                  = Area x velocity
                                                  = Axv
     D ( considering 2 nos. suction pipe)         = √4Q/π v
                                                  =                  0.250m
                                                  =                    250mm
*    Say                                          =                    250mm- 2 Nos
  B) Delivery Header size for Sprinkler, Hydrant , Diesel & Water curtain Pump:
     Flow rate Q for Sprinkler                  =                   2850LPM
     & Hydrant pump                             =                    171M3/Hr
     No. of Pumps                               =                      2No.
     Flow rate Q for Water                      =                    2280LPM
     Curtain pump                               =                   136.8M3/Hr
     No. of Pumps                               =                      1No.
     Total Flow Rate                            =                   0.133M3/s
     Considered water velocity (v)              =                       3m/s
     Flow rate Q                                = Area x velocity
                                                = Axv
     d                                          =
                                                =                   0.250m
                                                =                     250mm
     Say                                        =                     250mm
 C) Individual Suction Header size for Sprinkler , Hydrant ,Diesel pump:
    Flow rate Q                                   =                  2850LPM
                                                  =                   171M3/Hr
    Considered water velocity (v)                 =                    1.5m/s
    Flow rate Q                                   = Area x velocity
                                                                                      5
                                                = Axv
     d                                          = √4Q/π v
                                                =                   0.200m
                                                =                      200mm
   Say                                          =                      200mm
D) Individual Delivery Header size for Sprinkler , Hydrant ,Diesel pump:
   Flow rate Q                                  =                    2850LPM
                                                =                      171M3/Hr
   Considered water velocity (v)                =                         3m/sec
   Flow rate Q                                  = Area x velocity
                                                = Axv
   d                                            =
                                                =                   0.142m
                                                =                      142mm
   Say                                          =                      150mm
E) Suction size of jockey pumps :
   Flow rate Q                                  =                      180LPM
                                                =                     10.8M3/Hr
                                                =                   0.003M3/s
   Considered water velocity (v)                =                       1.5m/s
   Flow rate Q                                  = Area x velocity
                                                = Axv
   d                                            = √4Q/π v
                                                =                   0.080m
                                                =                   80.02mm
   Say                                          =                        80mm
F) Delivery size jockey pumps:
   Flow rate Q                                  =                      180LPM
                                                =                     10.8M3/Hr
                                                =                   0.003M3/s
   Considered water velocity (v)                =                         3m/s
   Flow rate Q                                  = Area x velocity
                                                = Axv
   d                                            = √4Q/π v
                                                =                   0.065m
                                                =                   65.01mm
   Say                                          =                        65mm
G)   Individual Suction Header size for Water curtain Pump:
     Flow rate Q                                                 =                 2280 LPM
                                                                 =                 136.8 M3/Hr
     Considered water velocity (v)                               =                  1.5 m/s
                                                                                                 6
     Flow rate Q                                               = Area x velocity
                                                               = Axv
     d                                                         = √4Q/π v
                                                               =                 0.200 m
                                                               =                   200 mm
     Say                                                       =                   200 mm
H)   Individual Delivery Header size for Water curtain pump:
     Flow rate Q                                               =                2280 LPM
                                                               =                136.8 M3/Hr
     Considered water velocity (v)                             =                     3   m/sec
     Flow rate Q                                               = Area x velocity
                                                               = Axv
     d                                                         =
                                                               =
                                                               =                 0.150   m
                                                               =                   150   mm
     Say                                                       =                   150   mm