0% found this document useful (0 votes)
160 views3 pages

IP-16-07-01 Motor Application

This document provides guidelines for motor application and selection. It discusses the applicable standards and practices for motor manufacture and testing. It also includes tables that list enclosure selection guidelines and definitions for acceptable and preferred practices. The document provides design considerations for motor ventilation, cooling, protection, and auxiliary power requirements.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
160 views3 pages

IP-16-07-01 Motor Application

This document provides guidelines for motor application and selection. It discusses the applicable standards and practices for motor manufacture and testing. It also includes tables that list enclosure selection guidelines and definitions for acceptable and preferred practices. The document provides design considerations for motor ventilation, cooling, protection, and auxiliary power requirements.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 3

Motor Application IP 16-7-1

INTERNATIONAL Page 1 of 3
PRACTICE
Rev. 0 June 1997

Changes shown by 

SCOPE
I  1.1 This practice covers application of motors.
I 1.2 An asterisk () indicates that additional information is required. If a job is contracted, this additional
information is furnished in the Job Specification.
I  1.3 The following references are synonymous: BP and IP.

SUMMARY OF ADDITIONAL CODES AND STANDARDS


I  
2.1 Applicable standards of manufacture and test for motors are given in the practices listed in Table 1. For
other conditions of purchase and use, motors shall conform to nationally recognized codes and standards
which are approved by the Owner's Engineer and which are acceptable within the country where the
motors will be used.

TABLE 1

PRACTICES

IP 16-9-1 Low Voltage A-C Motors Up to 200 HP (150 kW)


IP 16-9-2 A-C Motors: Medium Voltage and Low Voltage Over 200 HP (150 kW)
IP 16-14-1 Standard LV Variable Frequency Drives
IP 16-14-2 Additional Requirements for Variable Frequency Drives Driving a Special Purpose Machinery
Train

DEFINITIONS
I  3.1 Acceptable and Preferred Practices. Where this practice lists more than one type of equipment or
method as acceptable or preferred, the contractor shall make the selection based on optimum cost
benefits. Optimum cost benefits may be achieved by reducing maintenance and operating expense
through initial added investment. Economic basis for calculating optimum cost benefits will be specified in
the design documents.

SELECTION
S 4.1 Table 2 lists the Enclosure Selection Guidelines.
R ç 
4.2 Modifications to Table 2 shall be made, with the Owner's Engineer's approval, where special conditions
make this necessary. For example:
a. Filters may be required for drip-proof or weather-protected motors in locations that have large
quantities of air borne contaminants, dirt, sand, or other solid particles in the air.
b. Totally-enclosed fan-cooled or totally-enclosed water-air-cooled motors may be required:
1. When filters cannot provide effective separation because of small size and/or quantity of
solid particles in the air or
2. In locations having marine exposure to prevent contamination of windings due to high salt
content in the air.
S ç 
4.3 Transient rotor temperature shall be checked for non-explosion-proof motors driving fans and other high-
inertia loads in Division 2 locations. Calculated rotor temperature during a normal start from design
operating temperature must not exceed 80% of the autoignition temperature in C of the gas or vapor
involved. Owner’s Engineer shall be advised of any situation requiring modification to vendor’s standard
design.
C,R ç 
4.4 Transient rotor over-temperature during locked-rotor or repeated-start conditions is classed as an
abnormal occurrence. Special protection shall not be provided against this condition. Specifically,
specially designed motors such as "increased safety" types, and associated fast overcurrent relays, shall
not be used unless required by local standards.
R 4.5 3-phase motors shall be used in all critical services, such as process units or boiler plants, 1/2 hp (0.37
kW) and larger.

THIS INFORMATION FOR AUTHORIZED COMPANY USE ONLY


EXXON RESEARCH AND ENGINEERING COMPANY — FLORHAM PARK, N.J.
IP 16-7-1 Motor Application
Page 2 of 3 INTERNATIONAL
PRACTICE
Rev. 0 June 1997

DESIGN
R ç 5.1 When resistance temperature detectors are provided in the stator winding, a minimum of three of the
six or more detectors furnished shall be connected to an external monitoring system. This can be
accomplished via remote data logging or PLC. If the system is local to the motor location, detectors shall
be connected through a selector switch to a temperature indicator-controller with double-throw high alarm
contacts. The detectors connected to the switch shall be spaced uniformly around the circumference of
the stator. The system shall operate as follows:
a. The alarm contact shall have an adjustable set point.
b. Indicator shall be capable of reading at least 68F (20C) above controller set point.
c. Two resistors shall be provided, preferably mounted in the indicator, so as to test the alarm
operation and the calibration of the indicator.
d. The selector switch shall permit switching among detectors and have test and calibrate positions.
The contacts shall be arranged to prevent alarm actuation during switching.
S ç 5.2 Ventilating air for totally-enclosed pipe-ventilated and forced-ventilated motors shall be drawn from a
clean, non-hazardous air source. Air shall be filtered if necessary.
O,R ç 5.3 Auxiliary fan motors for totally-enclosed forced-ventilated motors shall be supplied via individual feeders,
connected to separate power sources if possible. Fan motor starters shall have time-delay undervoltage
release. Loss of auxiliary fan shall be alarmed.
R 5.4 Control of totally-enclosed forced-ventilated motors shall be arranged to prevent starting of main motor
unless one of the auxiliary fans is operating. Control stations for fan motors shall be located adjacent to
the control station for the main motor. Each fan control station shall have a pilot light which shall indicate
when the fan motor is energized.
R 5.5 Double tube coolers are required for totally-enclosed water-air-cooled motors having the coolers mounted
within the motor enclosure. Annular spaces between tube walls shall be drained to an inspection point
outside the motors.
An enclosed float switch and collecting pan shall be provided mounted externally on the motor housing to
sense water draining from the tube annulus and to operate a water leakage alarm.
C,R 
5.6 Single tube coolers may be used for totally-enclosed water-air-cooled motors if the coolers are mounted
below the motor in a design, approved by the Owner's Engineer, which provides the following:
a. Baffling against leaks impinging directly on windings.
b. Vertical sections in paths from cooler to fan inlets with design air velocity under 600 fpm (3 m/s).
c. Indication of water leaks.
d. Access to cooler for maintenance and its removal without moving the motor.
e. Running with once-through ventilation if the cooler is out of service (not applicable for pressurized
design).
R 5.7 High and low flow devices shall be provided in the cooling water circuit of totally-enclosed water-air-
cooled motors. The high flow device shall operate an alarm and the low flow device shall operate an alarm
immediately and then trip the motor after a time delay through a hand-reset lockout relay.
S 5.8 Power for excitation auxiliary circuits of synchronous motors shall be powered such that the auxiliary
circuits are safely deenergized when the motor controller is removed from service.

Revision Memo
9/68 Original Issue of Basic Practice
1/72 Revision 1
6/75 Revision 2
1/76 Revision 3
12/92 Revision 4
6/97 Revision 0 - Original Issue of International Practice.
Purpose Codes added throughout. The following paragraphs contained in BP 16-7-1 Rev. 4 have been deleted: 4.1,
4.2, 4.7, 4.9-13, 5.8. Par. 1.1 wording was revised. Par. 1.3 BP/IP reference was added. Par. 2.1 revised to be
consistent with motor and VFD practices and added Table 1 listing of applicable IPs. Par. 3.1 life cycle costs added.
Par. 4.2b combines Old Subpars. b & c and clarifies wording. Par. 4.3 added OE notification. Par. 4.4 added local
standards comment. Par. 5.1 remote temperature monitoring was added. Par. 5.2 deleted information covered in IP
16-9-2. Par. 5.3 added alarm. Table 2 zones and equivalent motor enclosures were added.

 Exxon Research and Engineering Company, 1992, 1997

THIS INFORMATION FOR AUTHORIZED COMPANY USE ONLY


EXXON RESEARCH AND ENGINEERING COMPANY — FLORHAM PARK, N.J.
Motor Application IP 16-7-1
INTERNATIONAL Page 3 of 3
PRACTICE
Rev. 0 June 1997

TABLE 2
ENCLOSURE SELECTION GUIDELINES

LOCATION ENCLOSURE

 Class I Division 1 locations, indoor or outdoor Preferred: Explosion-proof (See Note 4)


Acceptable where cooling water is available: Totally-enclosed
water-air-cooled pressurized (See Note 1)
Acceptable where cooling water is unavailable:
a. Totally-enclosed pipe-ventilated (See Note 1)
b. Totally-enclosed forced-ventilated (See Note 1)
(Zone 1) c. Ex”d” to EN 50 018 or IEC 79-1
 Class I Division 2 locations, outdoor SQUIRREL-CAGE INDUCTION AND BRUSHLESS
SYNCHRONOUS MOTORS (3-phase, and 1-phase induction
without starting winding cutout)
a. Totally-enclosed (non-ventilated or fan cooled)
b. Weather-protected (See Note 1)
(Zone 2) c. Ex”n” to IEC 79-15
d. Ex”e” (See Note 1)
Class I Division 2 locations, protected or indoor SQUIRREL-CAGE INDUCTION AND BRUSHLESS
(See Note 2) SYNCHRONOUS MOTORS (3-phase, and 1-phase induction
without starting winding cutout)
a. Drip-proof (See Note 1)
b. Totally-enclosed (non-ventilated or fan cooled)
Class I Division 2 locations, indoor, outdoor or 1-PHASE MOTORS WITH ARCING DEVICE
protected (See Note 2) Explosion-proof
3-PHASE OR D-C MOTORS WITH SLIP RINGS OR
COMMUTATOR
Non-arcing parts enclosed as specified for squirrel-cage
induction motors
Arcing parts enclosed as follows: (See Note 3)
a. Explosion-proof
b. Totally-enclosed forced-ventilated (See Note 1)
c. Totally-enclosed pressurized (See Note 1)
Alternatively: whole motor as specified for Class I Division 1
Non-hazardous locations; indoor, outdoor, or ALL MOTORS
protected (See Note 2) As specified for squirrel-cage induction motors

Notes:

(1) Use of such enclosures shall be approved by the Owner’s Engineer.
(2) A protected location is a location within an open-sided building where wind-driven rain cannot enter the motor
ventilation openings.
(3) Pressurized commutator or slip ring enclosures shall be pressurized with clean, dry, non-contaminated air
where available, or otherwise with an inert gas. Total leakage from the enclosure and shaft seals shall not
exceed 100 cu ft (2.8 cu m) per day, provided the internal pressure does not exceed 2 in. H2O (0.5 kPa).
Forced-ventilated commutator or slip-ring enclosures shall be ventilated with clean, dry, non-contaminated air.
(4) Explosion-proof motors not having a temperature limiting device inside their enclosure to limit surface
temperature to a value less than the ignition temperature of the vapors or gasses at the motor location are
preferred. Use of motors having temperature limiting devices within their enclosures shall be approved by the
Owner’s Engineer.

THIS INFORMATION FOR AUTHORIZED COMPANY USE ONLY


EXXON RESEARCH AND ENGINEERING COMPANY — FLORHAM PARK, N.J.

You might also like