Product Specifications PSS 2A-1Z9 E

I/A Series® Electronic Pressure Transmitters


Options and Accessories
IAP10, IAP20, IGP10, IGP20, IDP10, and IMV30 Series

A wide variety of features, options, accessories, and services enhance the performance and capabilities of the
versatile I/A Series Family of Digital, Analog, and Multivariable Pressure Transmitters.

FEATURES/ACCESSORIES/SERVICES
• Intelligent Transmitters with FoxCom, HART, or • External Zero Adjustment
FOUNDATION fieldbus Communication • Quality Assurance Certificates
Protocols • Integral Flow Orifices for Very Low Flow Rates
• Transmitters with Electronic 4 to 20 mA and • Static Pressure Rating to 4500 psi with IDP10
low power, low voltage 1 to 5 V dc Analog • Custody Transfer Cover Locks and Seals
Outputs • Primary Devices (Nozzles, Venturis, etc.)
• Hand-Held Terminals for FoxCom and HART • Differential Pressure Regulators
• PC-Based Configurator Software for FoxCom • Power Supplies
• Integral LCD Indicator with Pushbuttons • Rotameters for Control of Purge Rate
• Remote Mounted Indicators • Pressure Snubbers
• Electrical Conduit Adapters • Supplemental Customer Tag
• Two- and Three-Valve Bypass Manifolds • Accessories Conforming to European Union
• Process Venting and Bleeding Options Directives are marked with “CE” Logo
• Special Degreasing • Custom Options to User's Requirements
• Bracket Set for Pipe Mounting • Instruction Books
• Cleaning for Oxygen/Chlorine Service • Standard 2-Year Warranty; 5-Year Optional
• NACE MR 01-75 Compliance • See Inside Pages for more Accessories/Services
• Special Stainless Steel and NACE Bolting
• Standard and Custom Pressure Seals
• Custom Configuration

An Invensys company
PSS 2A-1Z9 E
Page 2

OPTIONAL FEATURES AND ACCESSORIES

I/A Series Pressure Transmitters


Using Suffix Dash (-) Code to Specify Options and
• Differential Pressure
Accessories
• Gauge Pressure
• Absolute Pressure Options with Model Code Suffix, such as LCD
• Flanged Liquid Level Indicator (-L1) or Stainless Steel Mounting Bracket
• Differential Pressure with Seals (-M2) are specified by adding the 2-character code to
• Multivariable Transmitter for Pressure, the end of the transmitter Model Number. For
Temperature, Density, and Mass Flow example, for basic transmitter IDP10-D20B2NF, add
Rate Measurements suffixes “-L1M2” (or “-M2L1”) to make a complete
• Transmitter for Sanitary Pressure or Model Number of IDP10-D20B2NF-L1M2 for a
Sanitary Open Tank Level Measurement transmitter with LCD Indicator and stainless steel
Mounting Bracket options.
Match the Transmitter to the Application For Other Options and Accessories, specify the basic
• Select only the Option Required Model Number and Optional Model Code Suffix as
• Meet the Application Needs indicated above. For optional selections not listed in
• Contact Foxboro if Custom Option is required the Model Code, separately specify the “AS”
Reference Code(s), Foxboro Part Number(s), and/or
Accessory Model Number(s), as applicable, and as
identified in this document.

NOTE
For option/accessory ordering information and the application of these options and accessories with
each transmitter model and type, refer to the Summary Selection Table at the end of this document.
TRANSMITTER SPECIFICATION SHEETS

I/A Series Intelligent Digital Output Transmitters and Configurators


Transmitter/Configurator Specification Sheet
Output Code Output Code Output Code
“-D” Transmitter “-T” Transmitter “-F” Transmitter
FoxCom HART FOUNDATION fieldbus
Communication Communication Communication
Transmitter and Configurator Type Protocol Protocol Protocol
IAP10/IAP20 Absolute Pressure Transmitters PSS 2A-1C13 A PSS 2A-1C13 B PSS 2A-1C13 E
IGP10/IGP20 Gauge Pressure Transmitters PSS 2A-1C13 A PSS 2A-1C13 B PSS 2A-1C13 E
IDP10 d/p Cell® Transmitter PSS 2A-1C14 A PSS 2A-1C14 B PSS 2A-1C13 E
IDP10 d/p Cell Transmitter with Pressure Seals PSS 2A-1C14 D PSS 2A-1C14 F PSS 2A-1C13 E
IDP10 d/p Cell Flanged Level Transmitter PSS 2A-1C14 E PSS 2A-1C14 G PSS 2A-1C13 E
IMV30 Multivariable Transmitter PSS 2A-1C15 A Not Applicable Not Applicable
Model HHT Hand-Held Terminal PSS 2A-1Z3 A Not Applicable Not Applicable
PC20 PC-Based Configurator PSS 2A-1Z3 E PSS 2A-1Z3 E Not Applicable
PC30 Multivariable Flow Configurator PSS 2A-1Z3 F Not Applicable Not Applicable

I/A Series Electronic Analog Output Transmitters


Transmitter Specification Sheet
Output Code Output Code Output Code
“-A” Transmitter “-I” Transmitter “-V” Transmitter
4 to 20 mA dc 4 to 20 mA dc 1 to 5 V dc
Analog Output Analog Output Analog Output
Transmitter Type (Note a) (Note b) (Note c)
IAP10/IAP20 Absolute Pressure Transmitters PSS 2A-1C13 C PSS 2A-1C13 C PSS 2A-1C13 D
IGP10/IGP20 Gauge Pressure Transmitters PSS 2A-1C13 C PSS 2A-1C13 C PSS 2A-1C13 D
IDP10 d/p Cell® Transmitter PSS 2A-1C14 C PSS 2A-1C14 C PSS 2A-1C13 D
IDP10 d/p Cell Transmitter w/Press. Seals PSS 2A-1C14 H PSS 2A-1C14 H PSS 2A-1C13 D
IDP10 d/p Cell Flanged Level Transmitter PSS 2A-1C14 J PSS 2A-1C14 J PSS 2A-1C13 D
(a) The “-A” Transmitter includes an explosionproof rating, but does not include an Intrinsically Safe rating (see Note b).
(b) The “-I” Transmitter includes both an explosionproof and an Intrinsically Safe rating.
(c) A low power, low voltage transmitter; 9 V dc minimum voltage, 3 mA maximum current.

INTELLIGENT TRANSMITTER CONFIGURATORS

Model HHT Hand-Held Terminal


This Foxboro battery-powered Hand-Held Terminal
permits remote testing, configuration, and diagnostic
testing of most Foxboro Intelligent Transmitters using
FoxCom protocol. Refer to PSS 2A-1Z3 A for
standard specifications and ordering instructions.
INTELLIGENT TRANSMITTER CONFIGURATORS (Cont.)

Model PC20 PC-Based Configurator


HART Model 275 Configurator
The Foxboro PC20 is a powerful Windows 95/NT-
This battery-powered configurator is the common
based software and hardware package with external
interface with all microprocessor-based devices using
modem(s) providing remote bidirectional
the HART protocol. It will communicate the common
communications with Foxboro, Foxboro-Eckardt-
commands to any HART device. Specific device
HART, and FoxCom protocol intelligent field devices.
descriptions (DDs) have been loaded by Foxboro to
The software also supports the Common Practice
ensure complete functionality with various brands of
and Universal HART commands for all non Foxboro
HART devices. See table and notes below.
HART devices. Shown below is a user-supplied PC
with different Intelligent Field Devices. Refer to
PSS 2A-1Z3 E for standard specifications and
ordering instructions.

Foxboro Part Approval or DDs Loaded into


Number Certification Configurator
D0165BF FM Foxboro (Note 1)
D0165BM FM Many (Note 2)
D0165BX FM All (Note 3)
D0165BN CSA Foxboro (Note 1)
Model PC30 FlowExpert Multivariable Flow D0165BP CSA Many (Note 2)
Configurator D0165BY CSA All (Note 3)
The Foxboro Model PC30 FlowExpert is a Windows- D0165BD CENELEC Foxboro (Note 1)
based software package for use with the IMV30 D0165BE CENELEC Many (Note 2)
Multivariable Transmitter and PC20 Configurator D0165BW CENELEC All (Note 3)
(Version 2 or higher). It contains primary device and
process data, and algorithms to allow for the NOTES
calculation of process density, and mass and volume 1. DDs for Foxboro and Foxboro-Eckardt HART
flow rate at standard and flowing conditions. See devices have been loaded into the configurator
PSS 2A-1Z3 F for further specification and ordering including Temperature (RTT20/TI20), Vortex
information. (83), Magnetic Flow (IMT25), Pressure
(DMU130, DMU140, and I/A Series), SRD991,
and TSV175.
2. DDs for all devices from all manufacturers
registered through the HART Foundation
have been loaded into the configurator: Bailey
F&P, Eckardt, Foxboro, Honeywell,
Micromotion, Robertshaw, Rosemount,
Rosemount Analytical, Westlock Controls,
and Yokogawa.
3. The DDs for all devices from all manufacturers
registered through the HART Foundation have
been loaded into the configurator, including all
Foxboro and Foxboro-Eckardt DDs (Note 1).
INDICATOR OPTIONS
A wide choice of indicating meters gives you an easily viewed “window” into the process. These indicators are
available integrally-mounted to the transmitter, or for remote mounting.

Integral LCD Indicator with Pushbuttons


(Standard with Output Codes “-A”, “-I”, and “-V”)
(Optional with Output Codes “-D”, “-F”, and “-T”)
Indicator is integrally mounted to electronics housing
(transmitter topworks). “CE” Logo marked on product
indicates conformance to applicable European Union
Directives.
Indicator Provides:
• Two Lines; Five numeric characters on top line
(four when a minus sign is needed) and seven
alphanumeric characters on bottom line.
• Measurement Readout; Value displayed on top
line and units label displayed on bottom line.
• Configuration and Calibration prompts.
Pushbuttons (two) typically provide the following
Configuration and Calibration Functions, depending TOPWORKS SHOWN WITH COVER REMOVED
on the electronics used:
• Linear and Square Root Output (as Applicable)
• Forward or Reverse Output 4 to 20 mA Output Indicator – Conduit Mounting
• Damping Adjustment
• Failsafe Action (High or Low) For 4 to 20 mA output signals only. This is a rugged,
• Units Label on Bottom Line of Display remotely-mounted (to conduit) indicator. It is
• Settable LRVs and URVs for Transmission weatherproof (per NEMA 4) and designed for use in
and Display (on Top Line) various hazardous area locations. See MI 020-438 for
• Zero and Span settings, non-interactive to details. Scales available are as follows:
automatically set output to either 4 mA or 20 mA "AS" Code Indicator Scale
using the “NEXT” and “ENTER” pushbuttons
(with 4 to 20 mA Output Transmitters only)
LMO-A 0 to 100 Percent Linear
• 4 and 20 mA Jog Settings, allowing the user to LMO-B 0 to 100 Percent Square Root
easily increment the mA output signal up or LMO-C Scale as Specified
down in fine steps to match a value shown on LMO-D 0 to 10 Percent Square Root
an external calibrator (with 4 to 20 mA Output
Transmitters only)
• Reranging to set new calibrated ranges without
applying pressure (not available with Output
Code “-I”)
• Temperature Sensor Failure Strategy
• Enable/Disable Optional External Zero
• Tag (with Digital Output Transmitters only)
Model Code
Suffix Description
-L1 LCD Indicator with Window
(“-D”, “-F”, and “-T” Versions Only)
-L2 Blind Solid Cover over Standard LCD
Indicator (“-A”, “-I”, and “-V” Versions
Only)
INDICATOR OPTIONS (Cont.)

4 to 20 mA Output Indicator –
Digital Indicator –
Surface or Conduit Mounting
Surface or Conduit Mounting
For 4 to 20 mA output signals only. This Model 65FS
For FoxCom digital output signal (“-D” Electronics
indicator may be mounted to a surface or conduit. It
Output Code) only. The Model RDM10 connects to
has a NEMA 4 rating, and classified for use in
I/A Series Intelligent Transmitter wiring to provide
hazardous areas by BASEEFA, CSA, FM, PTB, and
continuous remote monitoring of the digital
SAA. The “CE” Logo Marked on product indicates
measurement value. Indicator can only be used with
conformance to applicable European Union
output digitally configured to I/A Series System
Directives. This indicator is available with linear,
through FBM18 or FBM39. Mounts to a rigid conduit
square root, or custom scales. Order with a
or to a surface. Enclosure meets IEC IP65 and
transmitter by specifying “AS” Code “FMI” plus the
provides the environmental and corrosion resistant
mounting, electrical classification, and scale required.
protection of NEMA Type 4X. Refer to PSS 2A-1Z4 A
Or order separately by specifying the Model Number
to specify the precise indicator required.
shown in PSS 2A-3B1 C.
ELECTRICAL CONDUIT CONNECTORS
The transmitter housing includes two PG 13.5 or 1/2 NPT (as specified) threaded conduit entry ways for the field
wiring. The following connectors are for use with the conduit entry ways.

Hawke-Type 1/2 NPT Brass Cable Gland


M20 Stainless Steel Threaded Adapter
Used with a 1/2 NPT Conduit Connection. Hawke- This adapter is used with a 1/2 NPT Conduit
type cable gland with 1/2 NPT external thread. Connection, and has an M20 x 1.5-6H internal thread.
Available with Electrical Safety Codes “E”, “D”, Per KEMA No. Ex-98.E.3093 U. Used with Electrical
“N”, and “H”. See table below. Safety Codes “E”, “D”, “N”, and “H”. See table below.
Model Code Model Code
Suffix Description Suffix Description
-A1 Hawke-Type 1/2 NPT Cable Gland -A3 M20 Threaded Adapter, 303 ss

M20
CABLE GLAND (20 mm)
1/2 NPT

1/2 NPT

PG 13.5 Nickel-Plated Brass Cable Gland


PG 13.5 Plastic Cable Gland Use with a PG 13.5 Connection. This cable gland
A nylon cable gland for use with a PG 13.5 Conduit provides a smooth trumpet-shaped entrance and
Connection. For cable diameters between 9 and 14 strain-relieved support for open cable wiring. For
mm. Available with Electrical Safety Codes “E” and cable diameters between 9 and 14 mm. Used with
“H” only. See table below. Electrical Safety Codes “E” and “H”. See table below.
Model Code Model Code
Suffix Description Suffix Description
-A2 Plastic PG 13.5 Cable Gland -A4 Trumpet-Shaped PG 13.5 Cable Gland

CABLE GLAND
PG 13.5 CABLE GLAND
PG 13.5

Electrical Safety Codes and Description


E CENELEC Certified Intrinsically Safe, EEx, ia, IIC, Zone 0.
D CENELEC Certified Flameproof, EEx, d, IIC, Zone 1.
N European Certified Nonsparking, Ex, N, IIC, Zone 2.
H SAA Certified Intrinsically Safe, Ex, ia, IIC, Zone 0.
PROCESS RELATED OPTIONS

B7M Bolting
NACE MR 01-75 Service
For IDP10, IGP20, IAP20, and IMV30 Transmitters.
Used in sour gas service. All metallic, process wetted
Where the bolting is directly exposed to sour
parts comply with NACE Standard MR 01-75 for
environments, will be buried, insulated, or otherwise
resistance to sulfide stress cracking. For additional
denied atmospheric exposure, or if the bolting may be
information on material conformance to NACE, refer
exposed to sour environments through leakage,
to Foxboro Technical Instruction, TI 005-102.
bleeding of vent screws, etc., Foxboro offers NACE
Class II bolting. This bolting is in accordance with “AS”
ASTM A193 Gr. B7M and A194 Gr. 2HM (Nuts). This Reference
option provides the same maximum pressure rating Code Description
(25 MPa, 3625 psi) as the standard B7 steel bolting. MR-01 Compliance of Foxboro Instruments
The proof pressure rating with this option is 94.5 MPa with NACE Standard MR 01-75
(13 700 psi).
“AS”
Reference Special Degreasing
Code Description For IDP10 d/p Cell Transmitters, IGP20 Gauge
B7M B7M Bolting Pressure Transmitters, IAP20 Absolute Pressure
Transmitters, and IMV30 Multivariable Transmitters.
Nonprocess-Wetted Bolting Transmitter is cleaned, calibrated, labeled, and
For IDP10, IGP20, IAP20, and IMV30 Transmitters. packaged in a Clean Room. NOT FOR USE ON
Either 316 ss or 17-4 ss bolts and nuts are provided, OXYGEN, CHLORINE, OR OTHER FLUIDS THAT
as specified. See table below for Overrange and MAY REACT WITH SILICONE OIL.
Proof Pressure Ratings with these options: Model Code
Static Overrange Proof Pressure Suffix Description
Option Rating Rating -X1 Special Degreasing
-B1(a) 15 MPa (2175 psi) 60 MPa (8700 psi)
-B2(b) 25 MPa (3625 psi) 100 MPa (14 500 psi)
Oxygen or Chlorine Service Cleaning
(a) The “-B1” option is pressure derated to the values
listed. This option is not applicable to IDP10 For IDP10 d/p Cell Transmitters, IGP20 Gauge
Transmitters with remote pressure seals, or flanged Pressure Transmitters, IAP20 Absolute Pressure
level.
Transmitters, and IMV30 Multivariable Transmitters.
(b) There is no pressure derating with the “-B2” option.
The values listed are standard. Transmitter is cleaned, calibrated, labeled, and
. packaged in a Clean Room. Available with Fluorinert
Model Code fill fluid only. Oxygen or Chlorine Service not offered
Suffix Description when carbon steel process covers and silicone fill
-B1 316 ss Bolts and Nuts fluid are used.
-B2 17-4 ss Bolts and Nuts Model Code
Suffix Description
-X2 Oxygen Service Cleaning
-X3 Chlorine Service Cleaning
MOUNTING HARDWARE, MANIFOLD VALVES, AND PROCESS CONNECTIONS
The I/A Series Transmitters, because of their small size and lightweight design, are often self-supported by the
process piping, making the installation quicker, easier, and less expensive. But, Mounting Bracket Sets are
offered for installations that require pipe stand mounting. Bypass Manifolds and Valves are also offered to mount
transmitters and isolate them from the process.

Mounting Bracket Set


Used for all transmitters except flanged liquid level
transmitters. Used for attaching transmitter to a
mounting bracket, which attaches to user-supplied
horizontal or vertical DN50 or 2-in pipe.
Model Code
Suffix Description
-M1 Painted Steel Bracket and Plated Steel
Bolts
-M2 Stainless Steel Bracket and Stainless
Steel Bolts

MOUNTING BRACKET REQUIRED FOR DIRECT CONNECTED TRANSMITTER WHEN USING 1/4 NPT INTERNAL PROCESS CON

Leveling Pipe Saddle


PIPE SADDLE
For quick and easy attachment of a DN50 or 2-in
mounting pipe to another pipe. Saddle is cast iron
and includes U-bolts and nuts. For pipe sizes larger
than DN150 or 6 in, contact Foxboro.
Foxboro
Part No. Description
0032017 For DN50 or 2-in Pipe
0046935 For DN80 or 3-in Pipe
0016508 For DN100 or 4-in Pipe
0036694 For DN150 or 6-in Pipe

DN 50 OR
2 in PIPE

Block and Bleed Valve


Not offered if “-G” process connector option is used.
IAP10 OR IGP10
For quick and easy mounting, blocking, and venting of "-V1" VENT SCREW OPTION; 5/32 INCH SOCKET HEAD
a direct-connected absolute or gauge pressure
transmitter. Process connection is external 1/2 NPT.
Stem packing is universally corrosion resistant ptfe, 1/2 NPT TRANSMITTER CONNECTION
"-V2", "-V3" AND "-V4" BLOCK AND BLEED VALVE OPTION
suitable for 40 MPa (6000 psi) maximum at 38°C
(100°F), or 25 MPa (4000 psi) maximum at 250°C
(400°F). Transmitter can be easily field-calibrated by
using calibration screw F0101ES or B0142NA. See
calibration screw section that follows.
Model Code VENT SCREW
Suffix Description
1/2 NPT
-V1 Vent Screw in Process Connection PROCESS CONNECTION,
-V2 Block and Bleed Valve, Carbon Steel
-V3 Block and Bleed Valve, 316 ss
-V4 Block and Bleed Valve, 316 ss Body
with Monel Trim (NACE Approved)
MOUNTING HARDWARE, MANIFOLD VALVES, AND PROCESS CONNECTIONS (Cont.)

Calibration Screw
Manometer Process Connector
Allows the d/p Cell Transmitter, or Direct-Connected
Used with direct connected absolute or gauge
Pressure Transmitter (with optional block and bleed
pressure transmitters only. Provides a G 1/2 B
valve), to be easily field calibrated without having to
process connection (rather than standard 1/2 NPT)
remove it from the process.
for use with a manometer pressure seal connection.
Foxboro Not available with Block and Bleed Valve option.
Part No. Description
Model Code
F0101ES Calibration Screw; use with Poly-Flo Suffix Description
fitting (up to 0.7 MPa [100 psi]) -G G 1/2 B Manometer Process
B0142NA Calib. Screw; use with 1/4 in Connector
Swagelok fitting (up to 40 MPa
[6000 psi])

SHOWN WITH DIRECT CONNECTED

FIELD TERMINALS
TRANSMITTER

1/2 NPT TRANSMITTER CONNECTION SHOWN WITH BLOCK AND BLEED VALVE

1/2 NPT STANDARD G 1/2 B OPTION

Vent Screw
Optional vent screw(s) are provided to vent each
cavity as described below. The user may invert
CALIBRATION SCREW
PROCESS CONNECTION, 1/2 NPT IDP10 d/p Cell Transmitter, IGP20 Gauge Pressure
Transmitter, IAP20 Absolute Pressure Transmitter,
and IMV30 Multivariable Transmitter process cover(s)
and use the vent screw as a bottom drain.
Model Code
R 1/2 Process Connection Suffix Description
Converts the standard 1/2 NPT external thread of a -V Vent Screw in Side(s) of Process
direct connected absolute or gauge pressure Cover(s), as follows:
transmitter to a metric Rc 1/2 external thread. Not IDP10 – Both Hi and Lo Sides
available with Block and Bleed Valve option. IAP20 – Hi Side Only
Model Code IGP20 – Hi Side Only
Suffix Description IMV30 – Both Hi and Lo Sides
-R Rc 1/2 Process Connection
(1/2 NPT to Rc 1/2 Adapter)

DIRECT CONNECTED ABSOLUTE OR GUAGE PRESSURE TRANSMITTER

PROCESS COVER
PROCESS COVER
1/2 NPT TRANSMITTER CONNECTION
METRIC ADAPTER
Rc 1/2 PROCESS CONNECTION VENT SCREW
VENT SCREW
Two- and Three-Valve Bypass Manifolds
DIN 19213 Construction
A two-valve manifold is offered specifically for
Process Covers used with IDP10, IAP20, IGP20, and
transmitters having no process connector (Connector
IMV30 Transmitters only when Process Connector
Code “0”, cover tapped for 1/4 NPT). A block valve
Code “0” is selected. DIN Construction option results
isolates transmitter from process and is open during
in certain pressure deratings as listed below.
normal operation. When block valve is closed, the
bleed valve vents pressure from the transmitter. See Span and Range Limits
PSS 2B-1Z2 A to specify manifold materials, and DIN 19213 Option Derated to:
optional manifold mounting bracket, if required. “-D3” and “-D7” Not Derated; Std. Limits are:
25 MPa (3625 psi)
Three-valve manifolds offered in large selection of “-D1” 16 MPa (3620 psi)
configurations and materials. They provide a quick “-D5” 15 MPa (2175 psi)
means of installing the combination of one bypass
“-D2”, “-D4”, “-D6”, 10 MPa (1500 psi)
and two block valves as a single unit. The manifolds
and “-D8” (a)
are used to easily and economically adapt a d/p Cell
transmitter to flow or liquid level measurement (a) DIN Construction Options “D2”, “-D4”, “-D6” and “-D8” limited
to operating temperatures from 0 to 60°C (32 to 140°F).
devices. They are also available with brackets for
mounting manifold to a pipe. See PSS 2B-1Z2 A to
Model Code
specify precise model required.
Suffix Description
BLOCK VALVE -D1 Single Ended Process Cover,
M10, B7 Alloy Steel Bolting
BLEED VALVE -D2 Double Ended Process Cover,
PROCESS SIDE
INLET PORT (BLEED PORT ON SURFACE OPPOSITE TO BLEED VALVE) M10, B7 Alloy Steel Bolting
OPTIONAL MANIFOLD MOUNTING BRACKET (with Blind Flange)
-D3 Single Ended Process Cover,
7/16 in, B7 Alloy Steel Bolting
-D4 Double Ended Process Cover,
7/16 in, B7 Alloy Steel Bolting
TRANSMITTER SIDE
(with Blind Flange)
-D5 Single Ended Process Cover,
7/16 in, 316 ss Bolting
TWO VALVE BYPASS MANIFOLD BM-M4T SHOWN
-D6 Double Ended Process Cover,
7/16 in, 316 ss Bolting
(with Blind Flange)
-D7 Single Ended Process Cover,
7/16 in, 17-4 ss Bolting
-D8 Double Ended Process Cover,
BYPASS VALVE 7/16 in, 17-4 ss Bolting
(with Blind Flange)
BOLT-ON PROCESS CONNECTIONS MOUNT ON THIS SURFACE

PROCESS CONNE

BLOCK VALVE ON THIS END AND OTHER END

BLIND F
OPTIONAL MANIFOLD MOUNTING BRACKET
64
2.5
THREE VALVE BYPASS MANIFOLD BM-M4A SHOWN OPTIONAL DIN
CONSTRUCTION, SINGLECONSTRUCTION, DOUBLE ENDED PROCESS COVER ENDED PR
MOUNTING HARDWARE, MANIFOLD VALVES, AND PROCESS CONNECTIONS (Cont.)

Ermeto Connectors
For IAP20, IGP20, IDP10 (not with seals or flanged
level), and IMV30 Transmitters only. Carbon steel COMPRESSION NUT
(cs) or stainless steel (ss) compression fittings for
connecting 6 or 12 mm tubing to 1/4 or 1/2 NPT
process connections.
Model Code
Suffix Description
-E1 Connector, 6 mm, 1/4 NPT, cs
-E2 Connector, 12 mm, 1/2 NPT, cs
-E3 1/4 OR 1/2 NPT
Connector, 6 mm, 1/4 NPT, ss 6 OR 12 mm TUBING
-E4 Connector, 12 mm, 1/2 NPT, ss

MISCELLANEOUS PRODUCT ENHANCING OPTIONS

Electronics Housing Features

External Zero Adjustment


An external, moisture sealed pushbutton is provided
on the electronics housing. This zero adjust
pushbutton function is non-intrusive and magnetically
operated through the housing. This allows the user to
locally reset zero without removing the housing cover.
Not offered with IMV30 Transmitter.

Custody Transfer Lock and Seal EXTERNAL ZERO ADJUSTMENT

Offered for use in custody transfer applications. Two


set screws are used to position and lock the two
housing covers after they are fully engaged. Two
approved custody transfer seals are used to indicate
entry into the electronics housing.

External Zero Adjustment and Custody Transfer Lock


and Seal
This option provides both External Zero Adjustment
and Custody Transfer Lock and Seal. Not offered with
IMV30 Transmitter.
COVER
Model Code LOCK SCREW
Suffix Description
COVER CUSTODY TRANSFER SEALS
-Z1 External Zero Adjustment LOCK SCREW
-Z2 Custody Transfer Cover Locks
and Seals
-Z3 Both External Zero Adjustment and
Custody Transfer Cover Locks and
Seals
MISCELLANEOUS PRODUCT ENHANCING OPTIONS (Cont.)

Standard Data Plate


All Transmitters are supplied with a stainless steel
data plate using embossed characters. The data plate
encircles the neck of the electronics housing, and is
secured. If order is supplied with tag data, it is
automatically included on the data plate
(approximately thirty characters). For additional tag
DATA PLATE ENCIRCLES NECK
space, refer to “Supplemental Customer Tag”.

Supplemental Customer Tag SUPPLEMENTAL CUSTOMER TAG


The standard, permanently-attached, stainless steel
data plate provides one line of space, 76 mm (3 in)
STANDARD DATA PLATE
long for customer tagging information. This option
WARNING CAUTION
adds a 90 x 40 mm (3.5 x 1.5 in) stainless steel tag,
for additional customer data. The tag is fastened to
the transmitter with stainless steel wire. ELECTRICAL SAFETY DATA
CUSTOMER TAG DATA
Model Code
Suffix Description TRANSMITTER DATA
-T Supplemental Customer Tag

Quality Assurance Certificate


Foxboro offers certificates for parts and products to
satisfy the needs of many customers. Quality
assurance certificates offered are for compliance,
conformance, material and parts, calibration,
pressure test, cleaning, weight, SASO, electrical
safety classifications, and custom certificates not
listed above. Refer to TI 037-094 for a detailed
description of the certificates.
Order by
Specifying Description
CERT-A Certificate of Compliance
CERT-B Certificate of Conformance
CERT-C Material Certificate (Typical) Listing,
Description, and Conformance
statements.
CERT-D Material Certificate - Same as
CERT-C except that material
certificates are included in package.
CERT-E Calibration Certificate
CERT-F Pressure Test Certificate
CERT-G Certificate of Cleaning
CERT-H Weight Certificate
CERT-I SASO Certificate
CERT-J Testing Laboratory Certificate
Other Contact Foxboro
MISCELLANEOUS PRODUCT ENHANCING OPTIONS (Cont.)

Transmitter Instruction Documentation


Optional Custom Configurations
The standard transmitter (without the “-K1” or “-K4”
Transmitter databases can be changed via:
options) is shipped with a basic Paper Instruction
Manual, and a Full Documentation Set (MIs, PLs, • “-D” (FoxCom): HHT; PC-based Configurator;
DPs, etc.) on a compact disc (CD). I/A Series system; or Optional LCD Indicator
with On-board Pushbuttons
Optionally the user selects the “-K1” or “-K4” options,
as follows: • “-F” (FOUNDATION fieldbus): I/A Series
• “-K1”; with this option, only a brief “Getting System Host Workstation having a Fieldbus
Started” document is provided. Interface Electronics PWA; PC Host having a
Fieldbus Interface Electronics PWA; or
• “-K4”; with this option, only the traditional paper Optional LCD Indicator with On-board
Foxboro Instruction Book is provided. This Pushbuttons
Instruction Book includes all of the MIs, PLs,
• “-T” (HART): Model 275 HART Communicator;
DPs, etc. associated with the transmitter.
or Optional LCD Indicator with On-board
If the user does not require the standard transmitter Pushbuttons
documentation, or the “-K4” traditional transmitter
• “-A” (Analog Output): Standard LCD Indicator
Instruction Book with an order of many identical
transmitters, then the “-K1” option is generally with On-board Pushbuttons
specified for the additional transmitters. For example, • “-I” (Analog Output): Standard LCD Indicator
to order ten identical transmitters with only one with On-board Pushbuttons
standard documentation set:
• “-V” (Analog Output): Standard LCD Indicator
– For the 1st transmitter, neither “-K1” nor “-K4” with On-board Pushbuttons
is specified, and you then receive the
standard documentation with the 1st Foxboro modifies the default configuration per user's
transmitter; request when Optional Selection Code “-C1” or “-C2”
– And for the 2nd through 10th transmitters, is specified.
specify Option “-K1”, and you then receive a See tables in each transmitter PSS for the standard
“Getting Started” document with 2nd through configuration, and an example of optional custom
10th transmitters, but not the standard configuration “-C2”.
documentation set.
Model Code
And to order ten identical transmitters with only one Suffix Description
traditional documentation set, then: -C1 Digital Output Configuration (for
– For the 1st transmitter, specify Option “- Electronics Code “-D” only). There is a
K4”, and you receive the traditional Foxboro 4 to 20 mA Default if not Selected.
Instruction Book rather than the standard -C2 Custom Configuration. Factory
documentation set; Configuration per User's Requirement
– And for the 2nd through 10th transmitters, (User must fill out Data Form for
specify Option “-K1”, and you receive the factory to custom configure the
“Getting Started” document with the 2nd Transmitter)
through 10th transmitters, but not the
traditional Instruction Book or the standard
documentation set.
IDP10 Static Pressure Rating Increase
Five Year Warranty
This option applies to the IDP10 Transmitter only, but
The standard two-year warranty is increased to a five
not one having pressure seals or for flanged level. It
year warranty. In either case, the I/A Series Pressure
is available with transmitter Span Limit Codes B and
Transmitters provide outstanding quality, service, and
C, and with standard bolting or “-B2” optional bolting
reliability that users have come to expect from
only. This option increases the static pressure rating
Foxboro transmitters.
from 25 to 31 MPa (from 3625 to 4500 psi).
Model Code
Model Code
Suffix Description
Suffix Description
-W Five Year Warranty
-Y Static Pressure Rating to 31 MPa
(4500 psi)
WARRANTY
Foxboro warrants the original purchaser that Foxboro manu-
Shorting Plug
factured I/A Series Pressure Transmitters shall be free from
The nominal supply voltage limits for many of these defects in material and workmanship, and, if a transmitter fails
transmitters are 11.5 and 42 V dc. If required by the in normal operation (i.e., within specified installation and
operating conditions), agrees to either replace or repair, free of
user, the 11.5 V dc minimum voltage can be reduced charge, any such transmitter or part thereof which shall be
to 11 V dc by inserting a plug-in shorting bar across returned to the nearest authorized Foxboro repair facility within
the test receptacles in the field wiring compartment two years (or five years with Optional Feature -W) from date of
terminal block. Not applicable to transmitters with delivery, transportation charges prepaid by the purchaser.
Electronics Codes “-F” and “-V”, or with the IMV30 Purchaser retains responsibility for the application, sufficiency
of corrosion resistance, and functional adequacy of the
Transmitter. transmitter. For further details of this warranty, refer to Section
“AS” 11A of “General Conditions of Sale for Instruments and Parts”
available from Foxboro.
Reference
Code Description
SB-11 Plug-in Shorting Bar

BANANA PLUGS INSERTED INTO TEST RECEPTACLES OF TERMINAL BLOCK


ORIFICES AND PRESSURE SEALS

Integral Flow Orifice


Pressure Seals
A wide variety of integral flow orifices, for use with
Many styles available for use with pressure and d/p
d/p Cell transmitters, are offered for measurement of
Cell transmitters. Seals are used to isolate transmitter
extremely low flow rates. They are available as in-line
from corrosive or viscous process mediums, or
(IFO) or U-bend (IFOU) types that mount integral to
mediums that tend to solidify. They can be direct-
the process connectors, or offered as assemblies
connected or used with capillary tubing. The pressure
that mount directly to the process connector or
seal system is filled with a suitable fluid. Sanitary
manifold and that feature no flow through the
versions are also available.
transmitter body (IFOA). The orifice plates
themselves are easily replaceable. Refer to PSS 3-2C1 A to select and specify the
pressure seal required for your application.
Model Specify Model Number From
IFOA PSS 3-5A1 B
IFOU PSS 3-5A1 C
IFO PSS 3-5A1 D

IFOA
BYPASS MANIFOLD

Orifice Plates
For installation in pipeline. A wide selection of
materials and sizes are available; orifice plates, orifice
IFOU plate holding rings, universal orifice plates, orifice
plate spacers, orifice flange unions, and orifice meter
ORIFICE PLATE pipe assemblies. Contact Foxboro for details.

U-BEND

IFO
IN-LINE

CALIBRATION
All I/A Series Pressure Transmitters are factory calibrated to customer’s specified range. This calibrated range is
also stamped on the data plate. If a calibrated range is not specified, the transmitter will be calibrated at its
maximum span with the data plate left blank. Calibrations are done at ambient temperature and pressure.
The following is a 3-point check, sample calibration certificate which can be provided (note, computer-generated
calibration available from Foxboro, MA only).
ACCESSORIES
Foxboro stocks a wide variety of accessories to help tailor your installation. These accessories may be ordered
by using the Foxboro Part Numbers listed, or by contacting Foxboro directly for application and other
information.

Power Supply
Hand Valves
Acopian plug-in power supply capable of powering as
For installation at process piping. Steel construction
many as three transmitters with 4 to 20 mA dc output
with 1/2 NPT internal thread at both ends.
signal. Each power supply requires an octal socket.
Foxboro
Foxboro
Part No. Description
Part No. Description 0046091 Valve for 10.5 MPa (1500 psi) at 38°C
P0300BR Power Supply (100°F) maximum
B0113AA Octal Socket 0019883 Valve for 20 MPa (3000 psi) at 230°C
(450°F) maximum

Siphon Pigtail Differential Pressure Regulator


To rapidly reduce temperature at transmitter with a Maintains a constant pressure drop to control the
minimum of process piping. Steel construction with purge rate in purge or bubble tube systems. Refer to
1/4 NPT male threads at both ends. Approximately MI 11-170 and MI 020-328 for additional information.
115 mm (4.6 in) in length. Suitable to 14 MPa (2000
Foxboro
psi) at up to 340°C (650°F), or to 7 MPa (1000 psi) at
Part No. Description
up to 480°C (900°F).
B0107XY 10 kPa (1.5 psi) Differential (Air Only)
Foxboro B0107XX 20 kPa (3 psi) Differential (Liquid or
Part No. Description Gas)
0005838 Siphon Pigtail
ACCESSORIES (cont.)

Rotameter
Flexible Hose Connector
For control of purge rate and visual indication in a
Anchor coupling or Dayco braided hose with 1/4 NPT
purge or bubble tube system. For additional details
swivel connections for use as impulse piping between
refer to Instruction Manuals MI 005-529 and
process and transmitter. Suitable for up to 17.5 MPa
MI 020-328.
(2500 psi).
Suitable for gas or liquid purges up to 1.4 MPa
Foxboro
(200 psi) at 70°C (160°F). See descriptions below.
Part No. Description
Foxboro B0110EB 3 ft Hose
Part No. Description B0110EC 6 ft Hose
D0105NX 0.2 to 30 scfh (Gas), or
0.1 to 5 gph (Liquid)
D0105PF 5 to 60 scfh (Gas)
D0105PB 4 to 40 gph (Liquid)
M0153YM 5 to 200 mL/s (Gas),
or 0.1 to 5 mL/s (Liquid)
M0153YN 20 to 500 mL/s (Gas)
M0153YP 5 to 40 mL/s (Liquid)
Suitable for gas or liquid purges up to 1.4 MPa
(200 psi) at 90°C (200°F). See descriptions below.
Foxboro
Part No. Description
D0127MF 0.2 to 30 scfh (Gas), Pressure Snubbers
or 0.1 to 5 gph (Liquid) For installation in the process line to reduce or
D0127ML 5 to 60 scfh (Gas) eliminate any unwanted pressure pulsations, 1/4 NPT
D0127MK 4 to 40 gph (Liquid) at both ends.
Foxboro
Part No. Description
0045162 Brass, 1500 psi (100 Bar)
For air, water, or steam
0045163 303 ss, 5000 psi (340 Bar)
For thin liquids and gases
0044596 Brass, 1500 psi (100 Bar)
For oils and thick liquids
0044597 303 ss, 5000 psi (340 Bar)
For oils and thick liquids
ACCESSORIES (cont.)

Condensing Chamber
Other Primary Devices
Good for steam service up to 7 MPa (1000 psi)
Flow nozzles and venturi tubes are used as primary
absolute at 510°C (950°F) if condensing chamber
devices and are directly installed in the pipeline.
temperature does not exceed 340°C (650°F).
Contact Foxboro to specify your requirements.
Chamber has 1/2 NPT connections with top vent
screw assembly.
Foxboro
Part No. Description
0045776 Condensing Chamber

Vapor Trap
A vapor trap is for installation at the manifold when
the manifold is above the transmitter and transmitter
is above the process line. Available for applications
where the pressure does not exceed 140 bar
(2000 psi).
Foxboro
Part No. Description NOZZLE
0022817 Vapor Trap

Laboratory Flow Calibration


Precision flow calibration of primary device and d/p
Cell Transmitters are performed in the Foxboro Flow
Laboratory. Refer to Foxboro.

VENTURI TUBE
CUSTOM OPTIONS
Many times a particular instrument or option with simple or complex modifications will greatly enhance the
versatility of an I/A Series Pressure Transmitter. If you have the need for a custom option not listed in this
document, please contact Foxboro.

OPTIONS AND ACCESSORIES ORDERING INFORMATION


Refer to Table 1 for a summary of the options and accessories described in this document, and their availability
(and applicability) for the numerous offerings in the I/A Series Pressure Transmitters. Within the table, “YES”
means that the option or accessory is offered, “NO” means that the option or accessory is not offered or not
applicable to the particular transmitter listed. For further information regarding Table 1 and its contents, contact
Foxboro.
Table 1. Summary Selection Table - Options and Accessories (See Inside Pages for Details)
Model Code I/A Series Intelligent Pressure Transmitters
Optional Suffix
(-); AS Code, or IAP10 IAP20 IDP10 IDP10 IDP10 IMV30
Part No. (PN); and and w/Proc with with Multi
Option or Accessory, and Description or PSS No. IGP10 IGP20 Conn. Seals Flange Variable
Intelligent Transmitter Foxboro Model HHT PSS 2A-1Z3 A(a) YES YES YES YES YES NO
Configurators Foxboro Model PC20 PSS 2A-1Z3 E b) YES YES YES YES YES YES
Foxboro Model PC30 PSS 2A-1Z3 F(a) NO NO NO NO NO YES
HART Model 275 Inside Pages(c) YES YES YES YES YES NO
Foxboro Model HT991 Inside Pages(c) YES YES YES YES YES NO
LCD Indicator with on-board Pushbuttons, Integral -L1 Suffix(d) YES YES YES YES YES YES
Blind Cover replaces Glass Window Cover on LCD Indicator -L2 Suffix(e) YES YES YES YES YES NO
Indicator, Digital, Surface- or Conduit-Mounted Inside Pages(f) YES YES YES YES YES YES
Indicator, 4 to 20 mA Output 0 to 100% Uniform AS-LMO-A YES YES YES YES YES YES
Remote-Mounted to Conduit 0 to 100% Square Root AS-LMO-B NO NO YES YES NO YES
Scale as Specified AS-LMO-C YES YES YES YES YES YES
0 to 10% Square Root AS-LMO-D NO NO YES YES NO YES
Indicator, 4 to 20 mA Output AS-FMI YES YES YES YES YES YES
Remote-Mounted to Surface or Conduit PSS 2A-3B1 C
Mounting Bracket Set for DN50 Painted Steel -M1 Suffix YES YES YES YES NO YES
or 2-in Pipe (Bracket and Bolts) Stainless Steel -M2 Suffix YES YES YES YES NO YES
Levelling Pipe Saddle DN50 or 2 in Pipe PN 0032017 YES YES YES YES NO YES
Attaches DN50 or 2-in Pipe DN80 or 3 in Pipe PN 0046935 YES YES YES YES NO YES
to Another Pipe DN100 or 4 in Pipe PN 0016508 YES YES YES YES NO YES
DN150 or 6 in Pipe PN 0036694 YES YES YES YES NO YES
Manometer Process Connector, G 1/2 B Thread -G Suffix YES NO NO NO NO NO
Not available with V1, V2, V3, or V4 options.
Rc 1/2 Process Connection, Adapts 1/2 NPT to Rc 1/2 -R Suffix YES NO NO NO NO NO
Not available with V2, V3, or V4 options.
Vent Screw In Side of each Process Cover (g) -V Suffix NO YES YES NO NO YES
In Process Connection -V1 Suffix YES NO NO NO NO NO
Block and Bleed Valve Carbon Steel -V2 Suffix YES NO NO NO NO NO
Not available with “-G” option. 316 ss -V3 Suffix YES NO NO NO NO NO
NACE Approved -V4 Suffix YES NO NO NO NO NO
Ermeto Connectors for Connecting 6 mm, 1/4 NPT, cs -E1 Suffix NO YES YES NO NO YES
Tubing to Process Connectors 12 mm, 1/2 NPT, cs -E2 Suffix NO YES YES NO NO YES
6 mm, 1/4 NPT, ss -E3 Suffix NO YES YES NO NO YES
12 mm, 1/2 NPT, ss -E4 Suffix NO YES YES NO NO YES
Calibration Screw up to 0.7 MPa (100 psi) PN F0101ES YES YES YES NO NO YES
up to 40 MPa (6000 psi) PN B0142NA YES YES YES NO NO YES
DIN 19213 Single Ended Cover, M10, B7 Bolting -D1 Suffix NO YES YES NO NO YES
Construction Double Ended Cover, M10, B7 Bolting -D2 Suffix (h) NO YES YES NO NO YES
(Process Single Ended Cover, 7/16 in, B7 Bolting -D3 Suffix NO YES YES NO NO YES
Covers) Double Ended Cover, 7/16 in, B7 Bolting -D4 Suffix (h) NO YES YES NO NO YES
Single Ended Cover, 7/16 in, 316 ss Bolting -D5 Suffix (h) NO YES YES NO NO YES
Double Ended Cover, 7/16 in, 316 ss -D6 Suffix (h) NO YES YES NO NO YES
Bolting Single Ended Cover, 7/16 in, 17-4 -D7 Suffix NO YES YES NO NO YES
ss Bolting -D8 Suffix (h) NO YES YES NO NO YES
Double Ended Cover, 7/16 in, 17-4 ss Bolting
Electrical Hawke-Type 1/2 NPT Cable Gland -A1 Suffix YES YES YES YES YES YES
Conduit Plastic PG 13.5 Cable Gland -A2 Suffix YES YES YES YES YES YES
Connectors M20 Connector (1/2 NPT to M20) -A3 Suffix YES YES YES YES YES YES
Brass Trumpet-Shaped PG 13.5 Cable Gland -A4 Suffix YES YES YES YES YES YES
Process-Wetted Parts in Compliance with NACE MR 01-75 AS-MR-01 YES YES YES YES YES YES
Nonprocess-Wetted Bolting 316 ss Bolts and Nuts -B1 Suffix (h)(i) NO YES YES NO NO YES
17-4 ss Bolts and Nuts -B2 Suffix NO YES YES YES YES YES
(a) For use with Output Code “-D”, FoxCom Communications, only.
(b) For use with Output Codes “D” and “T” (FoxCom and HART).
(c) For use with Output Code “-T”, HART Communications, only.
(d) Standard construction with Output Codes “-A”, “-I”, and “-V”. Optional with Output Codes “-D”, “-F”, and “-T”.
(e) For use with Analog Output Transmitters, Output Codes “-A”, “-I”, and “-V” only.
(f) For use with digital output only; FoxCom, FOUNDATION fieldbus, and HART Digital Communication.
(g) In hi-side process cover only for IAP20 and IGP20.
(h) See inside pages for pressure derating with these options.
(i) Not available with IAP20/IGP20 using Custom Seals.
Table 2. Summary Selection Table - Options and Accessories (See Inside Pages for Details)(Cont.)
Model Code I/A Series Intelligent Pressure Transmitters
Optional Suffix
(-); AS Code, or IAP10 IAP20 IDP10 IDP10 IDP10 IMV30
Part No. (PN); and and w/Proc with with Multi
Option or Accessory, and Description or PSS No. IGP10 IGP20 Conn. Seals Flange Variable
B7M Bolting (NACE Class II) AS-B7M NO YES YES NO NO YES
Transmitter Special Degreasing -X1 Suffix NO YES YES NO NO YES
Cleaning Oxygen Service Cleaning -X2 Suffix NO YES YES NO NO YES
(Clean Room) Chlorine Service Cleaning -X3 Suffix NO YES YES NO NO YES
Bypass Manifolds, w/wo Mounting Bracket PSS 2B-1Z2 A NO YES YES NO NO YES
Orifice Plates Contact Foxboro NO NO YES NO NO YES
Integral Flow IFOA; no flow through bottomworks PSS 3-5A1 B NO NO YES NO NO YES
Orifice IFOU; U-bend, flow through bottomworks PSS 3-5A1 C NO NO YES NO NO YES
IFO; In-line, flow through bottomworks PSS 3-5A1 D NO NO YES NO NO YES
Pressure Seals, Direct or Capillary Connected PSS 3-2C1 A YES NO NO YES NO NO
Electronics External Zero Adjustment -Z1 Suffix YES YES YES YES YES YES
Housing Custody Transfer Lock and Seal -Z2 Suffix YES YES YES YES YES YES
Features Both Extended Zero and Custody Transfer -Z3 Suffix YES YES YES YES YES YES
Custom Digital Output Configuration -C1 Suffix(a) YES YES YES YES YES YES
Configuration Custom Configuration -C2 Suffix(b) YES YES YES YES YES YES
Accessories for Purging or Bubble Diff. Press Regulator Inside Pages NO NO YES NO NO NO
Type Installations Rotameters Inside Pages NO NO YES NO NO NO
Pressure Accessories and Hardware Inside Pages YES YES YES YES YES YES
Calibration to Customer's Specified Range Inside Pages YES YES YES YES YES YES
Transmitter Brief “Getting Started Document provided -K1 YES YES YES YES YES YES
Instruction(c) Traditional Paper Instruction Book provided -K4 YES YES YES YES YES YES
Supplemental Customer Tag (for surplus data) -T Suffix YES YES YES YES YES YES
Five Year Warranty -W Suffix YES YES YES YES YES YES
31 MPa (4500 psi, 310 bar or kg/cm2 Static Pressure Rating -Y Suffix(d) NO NO YES NO NO NO
Plug-in Shorting Bar - Reduces Voltage from 11.5 to 11 V dc AS-SB-11(e) YES YES YES YES YES NO
Quality Assurance Certificates Inside Pages YES YES YES YES YES YES
(a) Applies to Output Code “-D” only. There is a 4 to 20 mA default if “-C1” is not selected.
(b) User must fill out a data form for this selection.
(c) The standard transmitter (without “-K1” or “-K4” options) is shipped with a basic paper Instruction Manual and a full
documentation set on a CD.
(d) See inside pages for applicability of this option with the IDP10 Transmitter.
(e) Not for use with Electronics Versions “-V” or “-F”.
I/A Series INTELLIGENT TRANSMITTERS

PRODUCT SPECIFICATION SHEETS (PSSs) FOR INTELLIGENT TRANSMITTERS


Category Device Types Models PSS Numbers
Mass Flow Flowtubes CFS10; CFS20; CFS30 1-2B1 A; 1-2B4 A; 1-2B5 A
Transmitters CFT10; CFT15; CFT30 1-2B3 C; 1-2B3 D; 1-2B5 A
Magnetic Flow Flowtubes 2800 Series 1-6B5 A, 1-6B5 C, 1-6B5 E
Transmitters IMT25/IMTL25L 1-6F5 A/1-6F6 A
IMT96 (MagEXPERT) 1-6F8 A
Vortex Flow Flowmeters 83 Series 1-8A1 E (83F and 83W); 1-8A2 D (83S)
Pressure Transmitters I/A Series (-D) 2A-1C13 A; 2A-1C14 A; 2A-1C14 D; 2A-1C14 E; 2A-1Z9
I/A Series (-T) E
I/A Series (-F) 2A-1C13 B; 2A-1C14 B; 2A-1C14 F; 2A-1C14 G; 2A-1Z9
E
2A-1C13 E; 2A-1Z9 E
Multivariable (Press. and Temp.) Transmitter I/A Series (IMV30-D) 2A-1C15 A; 2A-1Z9 E
Electrochemical Transmitters 870IT Series 6-1B1 B; 6-3N2 A
Analyzers 875 Series 6-1A1 E; 6-3A1 B; 6-3N1 C; 6-9A1 B
Temperature Transmitters RTT20 2A-1F4 A; 2A-1Z9 F (Options)
Valves Positioner SRD991 EVE0105 A-(en)
Remote Configurators HHT (FoxCom Only) 2A-1Z3 A
Communication PC 20 (FoxCom & HART) 2A-1Z3 E
PC30 (FoxCom Only) 2A-1Z3 F
Model 275 (HART Only) Not Applicable
Model HT991 (HART Only) Not Applicable
I/A Series I’faces FBM18 & FBM39 21H-2D5 B4; 21H-2C4 B4
(FoxCom Only) FBM43 & FBM44 21H-2D8 B4; 21H-2D4 B4

The Foxboro Company


Foxboro, d/p Cell, Fox, and I/A Series are trademarks of The Foxboro Company.
33 Commercial Street
Ermeto is a trademark of Weatherhead Division of Dana Corporation.
Foxboro, MA 02035-2099
Fluorinert is a trademark of Minnesota Mining and Manufacturing Company.
United States of America
FOUNDATION is a trademark of The Fieldbus Foundation.
http://www.foxboro.com
HART is a trademark of The Hart Communications Foundation.
Monel is a trademark of Inco Alloys, International.
Inside U.S.: 1-888-FOXBORO
Swagelok is a trademark of Crawford Fitting Company.
(1-888-369-2676)
Windows 95 and Windows NT are trademarks of Microsoft Corporation.
Outside U.S.: Contact your
local Foxboro representative.
Copyright 1997-1999 by The Foxboro Company
Facsimile (508) 549-4492
All rights reserved
An Invensys company