PV Solar Project - 1100 kWp Block Size
Cable Calculation for Cable from Inverter to LT Breaker
            Inverter Details
          Output of Inverter                                 1100 Kw
          Voltage of Inverter                                 330 Volts
          Current                                       1924.5574 Amps
          Current at 0.95 PF                            2025.8498 Amps
          Derating of Current (With 0.8 factor)         2532.3123 Amps
            Cable Details
          Cable Used (LT XLPE (Cu))                     1 C X 400 SQmm
          Current Carrying Capacity of 1 Run of 1 C X
          400 Sqmm Cable (In Air)                             660 Amps
          No. of Runs Required                          3.8368368 Nos.
          No. of Runs Required                                  4 Nos.
BUS DUCT Calculation from LT Breaker to Transformer
                                Case - I
          Output of Inverter                                 1100 Kw
          Voltage of Inverter                                 330 Volts
          Current                                       1924.5574 Amps
          Current at 0.95 PF                            2025.8498 Amps
          Derating of Current (With 0.8 factor)         2532.3123 Amps
          Switchgear Available 2500 Amp or 3200 Amp
            BUS DUCT Details
                                                        3200 Amp ,TP-E (AL) Air
          Bus Duct Proposed                                   Insulated
          Current Carrying Capacity of Bus Duct              3200 Amps