Section 13
Cathodic Protection
13         Cathodic Protection
           Cathodic protection is a secondary line of defence against corrosion, the
           primary defence being the coating. When damage to the coating occurs eg
           through impact on the coating during back filling on a pipeline, sling damage
           during the lowering in operation, or flotsam impact on an offshore platform leg,
           the underlying steel can then be in contact with electrolyte and corrosion can
           occur. But if these areas can become cathodic ie receive current, corrosion can
           be avoided. In order for cathodic protection to be applied, an electrolyte must
           be present. For example the external surface of a tank cannot have cathodic
           protection, but internal surfaces can if the tank is holding an electrolytic
           medium, but only up to the level of medium, not above. Underground and
           subsea pipelines can be protected, but steelwork above ground in an AGI needs
           painting. Cathodic protection can be applied in one of two ways:
              Sacrificial anodes systems.
              Impressed current systems.
13.1       Sacrificial anode systems
           This system sometimes called, galvanic anode system, works on the principle of
           bimetallic corrosion, the natural potential between metals. Any metal which is
           more electronegative (less noble) or below steel on the galvanic list can be used
           as an anode. The choice of metal used would depend upon the potential
           required to protect the prescribed area. Sacrificial systems only protect small
           areas and the anodes need changing regularly as they corrode away.
               Approximately
               50m maximum                           Connecting wire of
                                                     copper. Minimum
                                                     resistance
                                              Aluminium zinc or
                                              magnesium or
                                      +       alloys of these
            Figure 13.1 Sacrificial system.
13.2       Impressed current system
           The impressed current system is used to protect long lengths of pipeline from
           one installation, a distance of approximately 10 miles. The current needed to
           run the system comes from the national grid and is connected through a
           transformer rectifier (TR). The national grid is very high voltage and very high
           amperage and also AC. Anti-corrosion currents need to be DC. The TR rectifies
           the current to DC and transforms it to low voltage and amperage. The positive
           side of the TR is connected to a ground bed (anode system) and the negative to
           the pipe, making the pipe the cathode.
           The current is released into the electrolyte at the ground bed, passes through
           the electrolyte and is received at areas of coating damage on the pipe.
ATC88-40915
Cathodic Protection                           13-1                               Copyright © TWI Ltd
           A typical ground bed will be approximately 50m in length, at the same depth as
           and running parallel to the pipe. The cables carrying the current are of a
           substantial diameter and pure copper to produce a circuit of little or no
           resistance at the anode. The resistance encountered comes in the soil/clay/rock
           bearing the electrolyte and this will govern the driving voltage required and the
           number of anodes required to maintain negative potential on the buried pipe.
           The voltage required varies but is usually within the range of 10-50v at an
           amperage of around 0.15 amps. A CP system does not eliminate corrosion, it
           controls where corrosion occurs.
                                                                        To national grid
                                                       TR.                  supply
                                                   Transformer
                                                     rectifier
           Current received
             at cathode.
              Protected.
                                         Ground bed
                                           releases
                                         current into
            Figure 13.2 Impressed current system.
13.3       Interference
           When a buried steel structure is near to, or in the case of another pipeline,
           passes over or below a pipeline which is cathodically protected, problems can
           occur. This is interference but the term can be misleading. The offending
           structure does not adversely affect the CP system, but instead is affected by it.
           The interference structure picks up current released from the anode bed and
           conducts the current through a circuit of minimal resistance and releases the
           current again into the electrolyte near to the protected line. The interference
           therefore becomes a secondary anode and can suffer severe corrosion.
           If there is a possibility of a structure becoming interference then precautions
           need to be taken to avoid this eventuality. With the permission of the owner of
           the offending structure, three main methods can be employed.
           1    Attach isolation joints one pipe length either side of the nearest point of the
                offending line to the protected line. Join the two pipe lengths to the
                protected line with insulated wire and doubler plates, thus making them the
                same potential.
           2    Attach isolation joints to both lines, one pipe length either side of the
                nearest point. Join the two isolated sections together and install a sacrificial
                anode to protect both sections.
           3    Double wrap and contra-wrap the protected line giving four tape
                thicknesses with Cold Applied Laminate Tape for one pipe length either side
                of the nearest point.
           The method chosen would be at the discretion of the engineer.
ATC88-40915
Cathodic Protection                            13-2                                 Copyright © TWI Ltd
13.4       Monitoring CP
           It is considered that -850mv will maintain a pipeline in a passive state but most
           CP engineers will require a more negative value, -1 to -2V being typical. To
           ensure that the required potential is being maintained, checks need to be
           carried out at regular intervals. One method of monitoring is known as half-cell
           reference electrode. The most commonly used half-cell electrode is the
           copper/copper sulphate half-cell electrode. It is used for measuring the pipe to
           earth potential, ie cathode to earth, the other half of the circuit being anode to
           earth.
           Periodically along the line, CP monitoring posts are installed, with a direct wire
           connection to the pipe, accessed from a stud on the CP post panel. A voltmeter
           is connected to the stud and to the copper/copper sulphate half-cell, which is
           then pushed into the earth directly above the pipe. This provides a circuit for
           electrons from the pipe, into the electrolyte, back to the anode bed.
                                                                                  Half cell
                                                                                  reference
                                                                                  electrode
                                                                                  filled with
                                                Voltmeter
                                                                                  copper
             CP post                                                              sulphate
                                                                                  solution
           Ground
           level
                                                                             Porous plug
                              Pipe
            Figure 13.3 Monitoring CP.
13.5       Cathodic disbondment
           Part of the electrical circuit of the corrosion reaction is the evolvement of
           hydrogen gas from the cathode. Hydrogen is a very powerful gas and can cause
           cracking in steel, (HICC). If hydrogen gas can penetrate underneath a coating it
           can easily disbond it. This is known as cathodic or hydrogen disbondment. Over
           protection of damaged areas on a pipe, results in over production of hydrogen
           and subsequent disbondment of more of the coating, resulting in a bigger area
           to protect, needing more current.
           All material used on a pipeline have to undergo tests to determine their
           resistance to cathodic disbondment. The test is done in the following manner.
           A 6mm diameter hole is drilled into a plate coated with the material to be
           tested, through the coating and into but not through the underlying steel. A
           short length, approximately 50mm of plastic tube approximately 50mm
           diameter is fixed in position, using typically araldite epoxy or elastomeric
           sealant with the drilled hole central to the tube. This is then part filled with 3%
           solution of common salt, sodium chloride and a lid fitted. The lid can be
           machined from a block of polyethylene with a suitable diameter hole drilled
           through. The plate is connected to the negative pole of a battery; an anode is
           connected to the positive pole and inserted through the hole in the lid into the
           salt solution.
ATC88-40915
Cathodic Protection                           13-3                                 Copyright © TWI Ltd
           When the circuit is switched on the plate is the cathode and hydrogen (and
           chlorine) will be evolved from the steel and also at the interface of
           steel/coating. This enables hydrogen to penetrate under the coating, simulating
           areas of coating damage.
           The circuit is stopped after 28 days stripped down, dried off and using a craft
           knife; two cuts are made at an inclusive angle of approximately 30° radiating
           from the centre of the hole, through the coating to the substrate. Where
           disbondment has occurred the coating will chip off as the cuts are being made.
           The distance from the edge of the hole to the extent of the disbondment is
           measured and should not exceed the stated requirements. For example, FBE
           maximum 5mm after 28 days.
            Figure 13.4 Cathodic disbondment.
ATC88-40915
Cathodic Protection                         13-4                               Copyright © TWI Ltd