ARV System

This document provides information on product lineups for modular VRF outdoor units, mini VRF outdoor units, and indoor units. It includes tables listing the capacities and appearances of different units. It also describes features of the indoor units related to comfort, health, fresh air intake, long-term filters, self-cleaning, anti-cold air, follow me temperature control, fast cooling/heating, auto swing, independent dehumidification, 3D air flow, dimmer, and silent mode. The document additionally mentions heat recovery ventilators and fresh air processors.

Uploaded by

محمد علي
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
253 views44 pages

ARV System

This document provides information on product lineups for modular VRF outdoor units, mini VRF outdoor units, and indoor units. It includes tables listing the capacities and appearances of different units. It also describes features of the indoor units related to comfort, health, fresh air intake, long-term filters, self-cleaning, anti-cold air, follow me temperature control, fast cooling/heating, auto swing, independent dehumidification, 3D air flow, dimmer, and silent mode. The document additionally mentions heat recovery ventilators and fresh air processors.

Uploaded by

محمد علي
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 44

1 2

Product Lineup
Modular VRF Outdoor Units
INDEX Capacity(kW) Appearance 25.2 28.0 33.5 40.0 45.0 50.4 56.0 Page

Outdoor Units
50Hz 9

ARV 5X

60Hz 9
ARV 5X 09
ARV 4 23 50Hz 23
ARV Mini 38 ARV 4

60Hz 23

Indoor Units
One-way Cassette 44 ARV 5X
Two-way Cassette 45 8/10/12HP 14/16HP 18/20/22/24/26/28/30/32HP 34/36/38/40/42/44/46/48HP
Compact&Four-way Cassette 46
Slim Duct 51
Mid ESP Duct 53
High ESP Duct 56
Fresh Air Processing Unit 58
Ceiling&Floor 60 50/52/54/56/60/62/64HP
Wall-mounted 64

Control System
Remote Controller 68
Wired Controller 69 ARV 4
Centralized Controller 70
8/10/12HP 14/16/18HP 20HP 22/24/26/28/30/32/34/36/38HP
Network Control Software 71
Accessories 78

HRV
Heat Recovery Ventilator 84
40/42/44/46/48/50/52/54/56/58HP 60/62/64/66/68/70/72/74/76/78/80HP

Branch Pipe
Branch Pipe 85

3 4
Product Lineup Health
Mini VRF Outdoor Units
Fresh Air Intake Long-term Filter Self-Cleaning
Capacity(kW) Appearance 8 10 12 14 16 22 28 Page
Air outside can be led into the room via a The latest long-term filter ensures better air Indoor unit will continue running with special
connection pipe, which keeps the indoor air quality. Meanwhile, the cleaning frequency combined mode to blow and dry indoor
50Hz 38 fresh and healthy. has been decreased, and maintenance is also evaporator after the unit switch off so as to
much easier. keep clean and healthy.
ARV Mini
60Hz 42

Indoor Units
Capacity(kW) Appearance 2.2 2.8 3.6 4.5 5.6 7.1 8.0 9.0 10.0 11.2 12.5 14.0 15.0 Page
Comfort
One-way Cassette 44

Two-way Cassette 45 Anti-Cold-Air Follow Me Fast Cooling/Heating Auto swing

Four-way Cassette 46 When starting the heating operation, the fan Temperature sensor built in the remote Startup at high frequency increases cooling/ Distributes cool/warm air to maximum
speed is regulated automatically from the control will sense its surrounding heating capacity and reduces time to reach area by moving horizontal and vertical flags
lowest speed to the preset level. This function temperature, so the unit can achieve accurate set temperature, thus you can enjoy cooling automatically.
Slim Duct 51 can prevent cold air from blowing out at the and comfortable temperature control just like and heating in seconds.
beginning of the operation, which avoids the the air conditioner is following you.
discomfort to the user.
Mid ESP Duct 53

High ESP Duct 56


Independent
Dehumidification 3D Air Flow Dimmer Silent
Ceiling&Floor 60
With the independent dehumidification Combine vertical and horizontal auto swing Press this button to shut off the display light Indoor fan will run at super breeze speed and
function, the unit can efficiently dehumidify to ensure an even distribution of air flow on the front panel. indoor noise level can be extremely low when
Wall-mounted 64 the room and give you more comfort. throughout the room. the unit enters silent mode operation.

Capacity(KW) Appearance 22.0 28.0 45.0 56.0 Page

High ESP Duct

Fresh Air Processor


56

58
Reliability
Heat Recovery Ventilator
Self-diagnosis Function Low Ambient Cooling Intelligent Defrosting Compressor Heating Belt

Once abnormal operation or parts failure With special designed PCB, outdoor fan speed Normal defrost function can only be operated Auxiliary heating belt can increase compressor oil
3
happen, the unit will monitor the failures, the can be changed automatically according to in certain time,but AUX commercial air temperature in winter and prevent defrosting
Volume(m /h) Appearance 200 300 400 500 600 800 1000 1500 2000 2500 3000 4000 5000 Page microcomputer of air conditioner will switch condensation temperature. The air conditioner conditioner’s intelligent defrost can start water accumulated, which improves heat
off and protect the system automatically can run cooling operation even when the outdoor automatically according to the surrounding transfer efficiency.
when it happens. Meanwhile, the error or ambient temperature down to-15。C. condition.
HRV 82 protection code will be displayed on the
indoor unit.

Golden

No Frosting Chassis Golden Fin Optional Electric Heater Fire-proof Electric Box

The unique pipeline design makes the Effectively prevent bacteria breeding Built-in auxiliary electric heater as option, the Electrical control box adopts new design,
temperature on chassis higher than normal and improve heat transfer efficiency. The heating performance will be more powerful. which can meet the higher fire safety
units, and it prevents defrosting water unique anti-corrosive golden coating on the requirement to prevent the internal fire due
accumulated, which improves heat transfer condenser can withstand the rain, salty air to the electric spark accident.
efficiency and solves the drainage problem. and other corrosive elements.

5 6
Energy Saving Nomenclature
Indoor Unit
0.5W
180° Sine Wave Control 0.5W Standby Sleep Mode Hydrophilic aluminum fin
ARV CA - H 028 / 4 R1 A

With considerable advantages, DC Inverter Intelligent technology enables AUX products The function enables the air conditioner to The louvered hydrophilic aluminum foil
180° sine wave driving technology has much to cut energy consumption from normal 5W automatically increase cooling or decrease has improved by more than 10%. There
wider range of frequency and voltage, higher to 0.5W per hourwhen standby, which counts heating 1。C per hour for the first 2 hours, then refrigerant inlet and outlet are separated, Design Series Code
energy efficiency, more smooth running and 90% of saving. holds steady for the next 5 hours, after that to ensure the sub-cooling and enhance the
lower noise. it will switch off. This function maintains both cooling capacity. Refrigerant Type:
energy saving and comfort in night. R1: R410a. R22 Omitted

Power Supply:
2: 208-230V~, 1Ph, 60Hz 4: 220-240V~, 1Ph, 50Hz
5: 380-415V~, 3Ph, 50Hz 6: 380-415V~, 3Ph, 60Hz
Full Process
By DC Drive Full Process By DC Driv 9: 208-230V~, 3Ph, 60Hz Full DC Inverter(Universal) Omitted

Cooling Capacity (×100W)


DC control,DC Compressor,DC indoor
motor,DC outdoor motor,and DC Electronic
H: Cooling & Heating C: Cooling Only
expansion valve make low noise and high
efficiency.
Indoor Unit Type:
C1: One-Way Cassette C2: Two-Way Cassette
CA: Four-Way Cassette CF: Ceiling&Floor
LD: Low ESP Duct MD: Mid ESP Duct
HD: High ESP Duct WM: Wall-Mounted

Convenience
FA: Fresh Air Processer

AUX Refrigerant Variable AC

24-hour Timer Built-in Drain Pump Dual side Drainage Digital Tube Display

Users can turn on or turn off the air


conditioner at any time in 24 hours with
The built-in pump can lift the condensing
water 1200 mm upmost from the drainage
Both left and right sides of the indoor unit are
possible for drainage hose connection, and
Easily for the running parameters checking
and more convenient for troubleshooting,
Outdoor Unit
remote controller or wireless controller. pan. it’s easy for installation with this function. digital tube displays work status such as
indoor temperature, setting temperature, the
mode of operation, etc.
ARV - H 280 / 4 R1 M A

Remote Control Wired Control Central Control WIFI Control

Help users to control the air conditioner Help users to control the air conditioner With the control function of weekly timer, With the WIFI control, you can easily turn off
easily, you can design your most comfortable easily, the wired controller can be fixed on zone (or group) setting etc., the centralized the air conditioner outside your house via
settings with this controller. the wall and avoid mislaying. It’s mainly controller can control 64 units with RS 485 smart device. Furthermore, you can turn it on Design Series Code
used for commercial zone and makes air wire connection and the central control before you come back.The indoor unit filter
conditioner control more convenient. adapter. can be taken off to wash easily and it keeps M: Modular Outdoor Unit Non- Modular One Omitted
cleaning air all the time.
Refrigerant Type:
R1: R410a . R22 Omitted

Power Supply:
Washable Filter Auto Restart Function 2: 208-230V~, 1Ph, 60Hz 4: 220-240V~, 1Ph, 50Hz
5: 380-415V~, 3Ph, 50Hz 6: 380-415V~, 3Ph, 60Hz
9: 208-230V~, 3Ph, 60Hz Full DC Inverter(Universal) Omitted
The indoor unit filter can be taken off to wash If the air conditioner breaks off unexpectedly
easily and it keeps cleaning air all the time. due to the power cut, it will restart with the
previous setting mode automatically when Cooling Capacity (×100W)
the power resume.
H: Cooling & Heating C: Cooling Only

AUX Refrigerant Variable AC

7 8
Modular VRF-
ARV 5X

High Efficient And Energy Saving


The Industry’s Leading
IPLV Value
9.15
8.90 8.70
ARV 5X achieves the industry’s top class energy efficiency 9.00
8.45 8.35
of cooling and heating by utilizing the advanced 180° sine 8.00
wave DC Inverter driving technology,patent energy-saving 7.00
operation technology and improved performance of heat 6.00
exchange. 5.00
3.60 3.60 3.55 3.55 3.55
4.00

Because the outdoor ambient temperature and indoor unit 3.00

Outdoor Units-ARV 5X
load keep changing with the tine of a day. Most of time, 2.00
1.00
the system works under part load. So it is better to assess
0.00
the energy saving performance with IPLV. IPLV(C)=0.5EER(1 8HP 10HP 12HP 14HP 16HP
00%)+0.3EER(75%)+0.4EER(50%)+0.25EER(25%)
AUX Standrad China National Standrad

Excellent In EER&COP
ARV 5X Series achieves the industry’s top class energy efficiency in cooling and heating by utilizing all DC inverter compressors, and high
efficiency heat exchanger.
The cooling EER is up to 4.67 and the heating COP is up to 4.79 in the 8HP category.

EER COP
4.67 4.79
5.00 5.00 4.38
4.00 3.99 3.81 4.21 4.13
4.50 3.63 4.50 4.03

4.00 4.00

3.50 3.50

3.00 3.00

2.50 2.50

2.00 2.00

1.50 1.50

1.00 1.00

0.50 0.50

0.00 0.00
8HP 10HP 12HP 14HP 16HP 8HP 10HP 12HP 14HP 16HP

9 10
High Efficiency DC Inverter Compressor 180° Sine Wave Control
DC inverter compressor uses 180° sine wave vector control
technique,make motor operate smoothly and increases
efficiency significantly compared with traditional sawtooth
wave. It also can lower the noise level.

1. Direct suction 4. Exclusive high-precision asymmetric Traditional Control 180° Sine Wave DC Control

Small suction overheating, high vortex disk


efficiency. Using asymmetric type vortex disk structure,
compared with the symmetric structure, can
DC Brushless Fan Motor
Load Rev Curve

reduce the compressor loss, improve the 1150 DC fan stepless adjustment

efficiency of suction.
AC fan 2-3 level adjustment
DC brushless motor adjusts the fan speed by the system
pressure,and running load to enhance the efficiency by 230

45%. The super aero fan provides a larger air volume and
0 20 40 60 80 100 Load%
higher static pressure.
Fixed scroll 90% energy saving in part load
Exhaust port
2. HP chamber structure Suction gas
The back wall shell and a large Suction port
number of air cushion volume,
reduce exhaust air flow noise.
Orbiting scroll
High-Efficient Inverter Control 80
New HP chamber DC Inverter Compressor

Technology

Compressor efficiency(%)
Common DC Inverter compressor

70
The unit have the higher capacity in partial load according
to controlling the operation number of the compressor and
5. Concentrated winding adjusting the EXV opening of the condenser side, making
the compressor always maintain the highest efficiency
Common AC Inverter compressor

60
Magnetic efficiency is 12% higher than running state. 50 100
distributed winding. Load rate(%)

3. With throwing oil tubing for


compressor

Outdoor Units-ARV 5X
Outdoor Units-ARV 5X

6. Magnetic resistance DC motor

Energy utilization ratio


When the compressor oil level higher than
the warning line, system through tubing Use powerful rubidium magnet, inhibit
eliminate redundant frozen oil, keep the rotary vibration, reduce the loss of magnetic
oil balance between compressor. field, and the efficiency increased by 25%.

10 50 100 140
Load

High-efficient permanent magnetic motors are installed,


giving better performance than traditional DC inverter
Optimized Fan Grille New Profile Fan Blade
compressors.
Optimized fan blade shape with new air outlet grille The new axial fan designed
improves air flow volume which greatly improves fan with aerodynamics principle,
performance and decreases noise. it can reduce air loss and
Compressor efficiency New DC motor-centralized winding noise level.
Common DC motor-distributing winding
Efficiency-Rotor Speed Curve

Centralizing winding

Rotor Speed(s-1)

20 40 60 80 100

Distnbutin winding Powerful magnets provide high torque and efficiency and achieve 70% reduction in volume.
Optimized fan Conventional fan

11 12
High Efficient Heat Exchanger Wide Application Range
Optimized 2 to 1 refrigerant circuit design increases the Optimized fin design, reduces the water resistance and
heat exchanging efficiency and enhances the ratio of liquid wind resistance.
which flow to the evaporator.
Wide Operation Range
Optimized fin Previous fin

Normal refrigerant circuit The unit could operate perfectly between 52 C in hot

summer and -20 C in cold winter making you feel like

52℃
Gas refrigerant Liquid refrigerant
spring all year around, advanced system design and strict
2 to 1refringerant circuit system matching and test. (cooling in -15℃ ) -20℃
Gas refrigerant Liquid refrigerant

Gas refrigerant Liquid refrigerant

Enhance liquid refrigerant ratio Inner grooved copper tube,strength


heat exchange efficiency
Wide Voltage Design Changeable ESP
In country with unstable voltage, ARV can also run stable. Optimized fan provide outdoor unit up to 82Pa static
pressure. Outdoor units can be installed in the service floor
or facility room.
Sub-Cooling Technology For 3 Level
453V
Optimize the design of the condenser 0 pa 20 pa 20-82 pa

11.2 C sub-cooling by optimized refrigerant circuit and "Inverse fin type" window fin design. 415V
380V GB ±10% ARV ±15%
342V
325V
37 C 。

43。C GB ±10% ARV ±15% 15m


75。C 75。C

Outdoor Units-ARV 5X
Outdoor Units-ARV 5X

37。C

43。C
Normal condenser e-pass condenser
"Inverse fin type" window fin design
Long Piping Length
ambient 35。C ambient 35。C
Because of using DC inverter control technology and sub-cooling circuit technology ,it is possible to design a system with
longer piping and elevation difference which make it easier to design and installation.

4.5 C sub-cooling by special plate heat exchanger further reduce the refrigerant temperature flowing into the indoor unit.

Scroll Compressor

logP 1 4
6 5 Pc 4 4' 23 Condenser

Evaporator
T4 T4 '
Pm 9 30m
8 9 3
2 90m
Pe Plate heat 5
7 0 1 exchanger
Maximum
7 6 8 5 meters drop
EXV 2 EXV 1

P-H Diagram Structure Diagram


90m

1.1 C sub-cooling by dual EXV with a special effectives plate heat exchanger.
Max. Total piping length — 1000m
Max. Actual piping length —200m
Max. Level difference between indoor units — 30m
Max. Level difference between ODU and IDU units —90m
Max. Level difference in the same system between ODU and ODU units —5m
Max. piping length from 1st indoor Branch to the farthest indoor unit —90m

Plate heat exchanger Dual EXV

13 14
Precise Temperature Control
Comfortable And Healthy Environment Double EXVs Control
Double EXVs in one system ,each EXV part achieves 480 Plus
rate to precisely adjust refrigerant flow.
Silence Operation Indoor Unit Quiet Mode
Innovative centrifugal fan for large diameter and a new
design of the spiral duct system equipped with high-quality
Outdoor Unit Quiet Mode motor at the same time, making the air supply more
By using optimized fan blades and the CFD(computational quietly and smoothly. The lowest noise is 20 db(A). AUX composite temperature control technology, through the The unit uses PI calculation principle to calculate the percentage
Fluid Dynamics) technology, the product is equipped with indoor/outdoor operation condition detection, adjust outdoor of indoor capacity demand according to indoor temperature
the night low-noise operation function. Provide more quiet power output, optimize the indoor air distribution, achieve the fluctuations, to perform real-time control to the compressor
operation during the night. Minimum operation noise only high precision adjustment of 0.5 ℃ . operating frequency and through the double EXV adjustment,
45dB(A) precision up to level 1000, accurately control the refrigerant
50dB(A) flow, assure indoor comfort.
Office

40dB(A)
Capacity %

Electronic expansion valve


AUX silent mode at night Quiet library Convertional throttling method
100
Temp(℃)
30dB(A) Cooling rapidly
Quiet bedroom
Load %

50

Setting humidity
±0.5℃
26dB(A) Ts Comfortable
temperature 26
Super mute unit bare machine running
58
Noise dB

Cooling slow

Human hearing range is 0-25 dB(A)


80 20dB(A) Cooling rapidly
Time
Leaves rustling sound eration
8:00 12:00 16:00 20:00 0:00 4:00 8:00 Cooling op

18dB(A)
Super mute unit silent running

0dB(A)

Outdoor Units-ARV 5X
Outdoor Units-ARV 5X

Humanization Design
Intelligent Defrosting VIP Function
Temp

24

Special VIP control function, the VIP room will decide


20 Comfortable
18

the whole system operation mode, prior to other mode


Normal defrosting Cold

AUX intelligent defrosting technique extends the heating 10

operation and decrease the frequency of defrosting. Result in Temp



Defrosting Heating Operation Defrosting Heating Operation Defrosting Heating Operation Time
or economic locking function, ensure the priority of the
stable room temperature, offer comfort life.
24

20 Comfortable
important room.
Base on the main unit and at the end of the EXV control the
18
Conventional
intelligent defrosting Cold

output, fast bolt in liquid refrigerant system, unit operation 10

Defrosting Heating Operation Defrosting Heating Operation Defrosting Heating Operation Time

is more stable; Through the dry run, defrosting exhaust


Temp

24

temperature higher, more complete, more conventional. The 20 Comfortable

Auto Restart Function Economic Locking Function


18

defrosting time less 3 min than others at least UX intelligent


defrosting Cold

The AC can automatically memorize the operation setting Special design economic locking function, through outdoor PCB
10

Defrosting Heating Operation Defrosting Heating Operation Defrosting Heating Operation Time

when power is cut off accidently. It can return to previous switch setting. If work in economic lock, AC lowest work cooling

setting when power resumes. temperature will keep in 26 C and highest heating temperature

Recover the former operation state when power is restored , keep 20 C.
no need restart the unit manually

Fast Warm Up And Cool Down Technology


50 power failure
45
40 power cut
35
The DC Inverter Compressor system reaches full load 30
Tc( ℃ )

25 operation state auto restart


rapidly providing less temperature fluctuation and an 20 to A state
improved living environment, bring great user experience. 15
10
5
0
5 10 15 20 25
26℃
Time (min) power recovered
Capacity reaches 100% in 120s Restart state when power recovered

15 16
Easy Installation &Maintenance Reliable &Stable

No Oil Balance Pipe Between Non-Polar Communication Module Alternate Operation


ODUS No polar in communication wire ,easy installation and In one combination system,any module could run as the
commissioning. master unit according to the running time.Balance the life
High efficient oil/gas separating tech,make the system oil of the outdoor units in one system. 1 2 3 2 1 3 2 3 1

1st time operation 2nd time operation 3rd time operation


balance between compressors without oil balance pipe.
Master Unit Slave Unit Slave Unit
Back-Up Operation Technology
Module Back-Up Technology Fan Motor Back-Up Technology
As one of module breaks down, the rest of modules in the As one of fan motor breaks down, the rest of fan in the
A, B A, B A, B A, B same refrigerant system start-up urgently. outdoor unit start-up, ensure the outdoor unit is normal
Oil Balance pipe operation.
Gas pipe

Liquid pipe

1 2 3
This module fails This module start-up

Auto Addressing Auto Refrigerant Charging All-Around Protection Refrigerant Cooling


The outdoor units distribute indoor system address All-around protection to ensure long-term life of the unit. Using cold media to filter plate heat

Outdoor Units-ARV 5X
Outdoor Units-ARV 5X

The system according to all kinds of sensor acquisition


automatically. No need manually setting. More convenient system parameters, automatically calculate the amount of exchanger, keep the machine filter
and saving the installation time. refrigerant, filling automatically. plate temperature at a relatively
Refrigerant lack protection
Discharge
temperature protection low temperature operation, unit
High/low pressure protection
Four-way valve protection operation more reliable.
Indoor unit quantity
Drive module protection decreasing alarm function
Compressor
Phase sequence protection over-current protection

Oil Return Control Technology


Dynamic Oil Return Control Technology
Monitor compressor running state and running time,
computing system reasonable oil return time.

6-Step Oil Separating Technology Compressor Throwing Oil Technology


Completely solve the problem of oil, the system more When the compressor oil level higher than the warning
Easy Maintainence stable and reliable line, system through tubing eliminate redundant frozen oil,
keep the oil balance between compressor.
The PCB could record 30 minutes running information before the error occur.Self-diagnosis function helps service engnieer locate faults 1. Compressor with oil mist separator
quickly and easily.It’s convenient for the trouble shooting. 2. Oil self balancing control design
3. High efficient oil separator
4. Capillary static oil return control
5. SV1 auxiliary oil return control
6. System with oil return design

17 18
ARV 5X Series 380~415V-50(60)Hz/220V-60Hz
HP 8 10 12 14 16

380~415V ARV-H250/R1MX ARV-H280/R1MX ARV-H330/R1MX ARV-H400/R1MX ARV-H450/R1MX


Model Outdoor

ARV 5X
220V ARV-H250/9R1MX ARV-H280/9R1MX ARV-H330/9R1MX ARV-H400/9R1MX ARV-H450/9R1MX
Combination HP 8 10 12 14 16
Cooling kW 25.2 28 33.5 40 45
Capacity
Heating kW 28.0 31.5 37.5 45 50
Power Supply V~,Hz,Ph 380~415,50(60),3&220,60,3 380~415,50(60),3&220,60,3 380~415,50(60),3&220,60,3 380~415,50(60),3&220,60,3 380~415,50(60),3&220,60,3
Cooling Power Input kW 5.40 7.00 8.40 10.50 12.40
Heating Power Input kW 5.85 7.20 8.90 10.90 12.40
Electric Data Cooling Current A 8.60 10.80 13.50 18.20 20.30
Heating Current A 8.75 10.95 13.80 16.50 19.00
EER 4.67 4.00 3.99 3.81 3.63
COP 4.79 4.38 4.21 4.13 4.03
Air Flow Volume m3/h 12000 12000 12000 7250×2 7500×2
Flexible Outdoor Unit Combination Performance
Noise Level dB(A) 45-58 45-58 45-58 47-61 47-61
Type DC Inverter DC Inverter DC Inverter DC Inverter DC Inverter
kW HP 8HP 10HP 12HP 14HP 16HP Compressor
Quantity 1 1 1 1 1
Type DC motor DC motor DC motor DC motor DC motor
25.2 8 ★ Fan Motor
Quantity 1 1 1 2 2
Max. No. of Indoor Units unit 13 16 19 23 26
28.0 10 ★ Connection Ratio % 50~130 50~130 50~130 50~130 50~130

33.5 12 ★ Dimension(WxDxH)
Net mm 935×765×1600 935×765×1600 935×765×1600 1340×765×1600 1340×765×1600
Packing mm 980×810×1850 980×810×1850 980×810×1850 1400×810×1850 1400×810×1850

40.0 14 ★ Weight
Net kg 223 223 248 298 298
Gross kg 243 243 268 320 320

45.0 16 ★ Refrigerant Type R410a R410a R410a R410a R410a


Liquid Side mm(inch) 12.7(1/2) 12.7(1/2) 12.7(1/2) 12.7(1/2) 12.7(1/2)
Pipe Diameter
53.2 18 ★ ★ Gas Side mm(inch) 22.2(7/8) 22.2(7/8) 22.2(7/8) 28.6(9/8) 28.6(9/8)
Cooling ℃ -15~52 -15~52 -15~52 -15~52 -15~52
Operation Range
56.0 20 ★★ Heating ℃ -20~29 -20~29 -20~29 -20~29 -20~29
Stuffing Quantity 20/40/40H unit 14/28/28 14/28/28 14/28/28 11/22/22 11/22/22
61.5 22 ★ ★
67.0 24 ★★
73.0 26 ★ ★
ARV 5X Series 380~415V-50(60)Hz/220V-60Hz
HP 18 20 22 24 26
78.5 28 ★ ★

Outdoor Units-ARV 5X
Outdoor Units-ARV 5X

380~415V ARV-H530/R1MX ARV-H560/R1MX ARV-H610/R1MX ARV-H670/R1MX ARV-H730/R1MX


Model Outdoor
85.0 30 ★ ★ 220V ARV-H530/9R1MX ARV-H560/9R1MX ARV-H610/9R1MX ARV-H670/9R1MX ARV-H730/9R1MX
Combination HP 8+10 10×2 10+12 12×2 10+16
90.0 32 ★★ Capacity
Cooling kW 53.2 56 61.5 67 73
Heating kW 59.5 63 69 75 81.5
95.0 34 ★ ★★ Power Supply V~,Hz,Ph 380~415,50(60),3&220,60,3 380~415,50(60),3&220,60,3 380~415,50(60),3&220,60,3 380~415,50(60),3&220,60,3 380~415,50(60),3&220,60,3

Cooling Power Input kW 12.4 14 15.4 16.8 19.4


100.5 36 ★★★ Heating Power Input kW 13.05 14.4 16.1 17.8 19.6
Electric Data Cooling Current A 19.4 21.6 24.3 24 31.1
106.5 38 ★ ★ ★ Heating Current A 19.7 21.9 24.75 27.6 29.95
EER 4.29 4.00 3.99 3.99 3.76
112.0 40 ★★ ★ COP 4.56 4.38 4.29 4.21 4.16
m3/h
118.5 42 ★ ★ ★ Performance
Air Flow Volume 12000×2 12000×2 12000×2 12000×2 12000+7500×2
Noise Level dB(A) 47~61 47~61 47~61 47~62 47~62

123.5 44 ★★ ★ Compressor
Type DC Inverter DC Inverter DC Inverter DC Inverter DC Inverter
Quantity 2 2 2 2 2

130.0 46 ★ ★★ Fan Motor


Type DC motor DC motor DC motor DC motor DC motor
Quantity 2 2 2 2 3
135.0 48 ★★★ Max. No. of Indoor Units unit 31 33 36 39 43
Connection Ratio % 50~130 50~130 50~130 50~130 50~130
140.0 50 ★ ★★ ★ Net mm (935×765×1600)×2 (935×765×1600)×2 (935×765×1600)×2 (935×765×1600)×2 935×765×1600+1340×765×1600
Dimension(WxDxH)
Packing mm (980×810×1850)×2 (980×810×1850)×2 (980×810×1850)×2 (980×810×1850)×2 980×810×1850+1400×810×1850
145.5 52 ★★★ ★ Net kg 223×2 223×2 223+248 248×2 223+298
Weight
Gross kg 243×2 243×2 243+268 268×2 243+320
151.5 54 ★ ★ ★★ Refrigerant Type R410a R410a R410a R410a R410a
Liquid Side mm(inch) 12.7(1/2) 15.88(5/8) 15.88(5/8) 15.88(5/8) 19.05(3/4)
157.0 56 ★★ ★★ Pipe Diameter
Gas Side mm(inch) 28.6(9/8) 28.6(9/8) 28.6(9/8) 28.6(9/8) 34.93(11/8)
Cooling ℃ -15~52 -15~52 -15~52 -15~52 -15~52
163.0 58 ★ ★★★ Operation Range
Heating ℃ -20~29 -20~29 -20~29 -20~29 -20~29

168.5 60 ★ ★★★
Notes:
175.0 62 ★ ★★★ 1.Cooling Capacity: Indoor temperature 27℃ DB/19℃ WB;Outdoor temperature:35℃ DB/24℃ WB.
2.Heating Capacity:Indoor temperature 20℃ DB;Outdoor temperature:7℃ DB/6℃ WB.

180.0 64 ★★★★ 3.Piping Length:Equivalent piping length:7.5m,level differernce:0m.


4.Anechoic chamber conversion value,measured in test room.During actual operation.These values are normally somewhat higher as a result of ambient conditons.
5.The above designs and specifications are subject to change without prior notice. Final specifications please refer to technical specification provided by sales representative.

19 20
ARV 5X Series 380~415V-50(60)Hz/220V-60Hz ARV 5X Series 380~415V-50(60)Hz/220V-60Hz
HP 28 30 32 34 36 HP 48 50 52 54 56

380~415V ARV-H780/R1MX ARV-H850/R1MX ARV-H900/R1MX ARV-H950/R1MX ARV-H1000/R1MX 380~415V ARV-H1350/R1MX ARV-H1400/R1MX ARV-H1450/R1MX ARV-H1510/R1MX ARV-H1570/R1MX
Model Outdoor Model Outdoor
220V ARV-H780/9R1MX ARV-H850/9R1MX ARV-H900/9R1MX ARV-H950/9R1MX ARV-H1000/9R1MX 220V ARV-H1350/9R1MX ARV-H1400/9R1MX ARV-H1450/9R1MX ARV-H1510/9R1MX ARV-H1570/9R1MX
Combination HP 12+16 14+16 16×2 10+12×2 12×3 Combination HP 16×3 10+12×2+16 12×3+16 10+12+16×2 12×2+16×2
Cooling kW 78.5 85 90 95 100.5 Cooling kW 135 140 145.5 151.5 157
Capacity Capacity
Heating kW 87.5 95 100 106.5 112.5 Heating kW 150 156.5 162.5 169 175
Power Supply V~,Hz,Ph 380~415,50(60),3&220,60,3 380~415,50(60),3&220,60,3 380~415,50(60),3&220,60,3 380~415,50(60),3&220,60,3 380~415,50(60),3&220,60,3 Power Supply V~,Hz,Ph 380~415,50(60),3&220,60,3 380~415,50(60),3&220,60,3 380~415,50(60),3&220,60,3 380~415,50(60),3&220,60,3 380~415,50(60),3&220,60,3
Cooling Power Input kW 20.8 22.9 24.8 23.8 25.2 Cooling Power Input kW 37.2 36.2 37.6 40.2 41.6
Heating Power Input kW 21.3 23.3 24.8 25 26.7 Heating Power Input kW 37.2 37.4 39.1 40.9 42.6
Electric Data Cooling Current A 33.8 38.5 40.6 37.8 40.5 Electric Data Cooling Current A 60.9 58.1 60.8 64.9 67.6
Heating Current A 32.8 35.5 38 38.55 41.4 Heating Current A 57 57.55 60.4 62.75 65.6
EER 3.77 3.71 3.63 3.99 3.99 EER 3.63 3.87 3.87 3.77 3.77
COP 4.11 4.08 4.03 4.26 4.21 COP 4.03 4.18 4.16 4.13 4.11
Air Flow Volume m3/h 12000+7500×2 7250×2+7500×2 7500×4 12000×3 12000×3 Air Flow Volume m3/h 7500×6 12000×3+7500×2 12000×3+7500×2 12000×2+7500×4 12000×2+7500×4
Performance Performance
Noise Level dB(A) 47~62 47~63 47~63 47~63 47~63 Noise Level dB(A) 47~64 47~64 47~64 47~64 47~65
Type DC Inverter DC Inverter DC Inverter DC Inverter DC Inverter Type DC Inverter DC Inverter DC Inverter DC Inverter DC Inverter
Compressor Compressor
Quantity 2 2 2 3 3 Quantity 3 4 4 4 4
Type DC motor DC motor DC motor DC motor DC motor Type DC motor DC motor DC motor DC motor DC motor
Fan Motor Fan Motor
Quantity 3 4 4 3 3 Quantity 6 5 5 6 6
Max. No. of Indoor Units unit 46 50 53 56 59 Max. No. of Indoor Units unit 64 64 64 64 64
Connection Ratio % 50~130 50~130 50~130 50~130 50~130 Connection Ratio % 50~130 50~130 50~130 50~130 50~130
Net mm 935×765×1600+1340×765×1600 (1340×765×1600)×2 (1340×765×1600)×2 (935×765×1600)×3 (935×765×1600)×3 Net mm (1340×765×1600)×3 (935×765×1600)×3+(1340×765×1600) (935×765×1600)×3+(1340×765×1600) (935×765×1600)×2+(1340×765×1600)×2 (935×765×1600)×2+(1340×765×1600)×2
Dimension(WxDxH) Dimension(WxDxH)
Packing mm 980×810×1850+1400×810×1850 (1400×810×1850)×2 (1400×810×1850)×2 (980×810×1850)×3 (980×810×1850)×3 Packing mm (1400×810×1850)×3 (980×810×1850)×3+(1400×810×1850) (980×810×1850)×3+(1400×810×1850) (980×810×1850)×2+(1400×810×1850)×2 (980×810×1850)×2+(1400×810×1850)×2

Net kg 248+298 298×2 298×2 223+248×2 248×3 Net kg 298×3 223+248×2+298 248×3+298 223+248+298×2 248×2+298×2
Weight Weight
Gross kg 268+320 320×2 320×2 243+268×2 268×3 Gross kg 320×3 243+268×2+320 268×3+320 243+268+320×2 268×2+320×2
Refrigerant Type R410a R410a R410a R410a R410a Refrigerant Type R410a R410a R410a R410a R410a
Liquid Side mm(inch) 19.05(3/4) 19.05(3/4) 19.05(3/4) 19.05(3/4) 19.05(3/4) Liquid Side mm(inch) 19.05(3/4) 19.05(3/4) 22.2(7/8) 22.2(7/8) 22.2(7/8)
Pipe Diameter Pipe Diameter
Gas Side mm(inch) 34.93(11/8) 34.93(11/8) 34.93(11/8) 34.93(11/8) 41.3(13/8) Gas Side mm(inch) 41.3(13/8) 41.3(13/8) 47.6(15/8) 47.6(15/8) 47.6(15/8)
Cooling ℃ -15~52 -15~52 -15~52 -15~52 -15~52 Cooling ℃ -15~52 -15~52 -15~52 -15~52 -15~52
Operation Range Operation Range
Heating ℃ -20~29 -20~29 -20~29 -20~29 -20~29 Heating ℃ -20~29 -20~29 -20~29 -20~29 -20~29

ARV 5X Series 380~415V-50(60)Hz/220V-60Hz ARV 5X Series 380~415V-50(60)Hz/220V-60Hz


HP 38 40 42 44 46 HP 58 60 62 64

Outdoor Units-ARV 5X
Outdoor Units-ARV 5X

380~415V ARV-H1060/R1MX ARV-H1120/R1MX ARV-H1180/R1MX ARV-H1230/R1MX ARV-H1300/R1MX 380~415V ARV-H1630/R1MX ARV-H1680/R1MX ARV-H1750/R1MX ARV-H1800/R1MX
Model Outdoor Model Outdoor
220V ARV-H1060/9R1MX ARV-H1120/9R1MX ARV-H1180/9R1MX ARV-H1230/9R1MX ARV-H1300/9R1MX 220V ARV-H1630/9R1MX ARV-H1680/9R1MX ARV-H1750/9R1MX ARV-H1800/9R1MX
Combination HP 10+12+16 12×2+16 12+14+16 12+16×2 14+16×2 Combination HP 10+16×3 12+16×3 14+16×3 16×4
Cooling kW 106.5 112 118.5 123.5 130 Cooling kW 163 168.5 175 180
Capacity Capacity
Heating kW 119 125 132.5 137.5 145 Heating kW 181.5 187.5 195 200
Power Supply V~,Hz,Ph 380~415,50(60),3&220,60,3 380~415,50(60),3&220,60,3 380~415,50(60),3&220,60,3 380~415,50(60),3&220,60,3 380~415,50(60),3&220,60,3 Power Supply V~,Hz,Ph 380~415,50(60),3&220,60,3 380~415,50(60),3&220,60,3 380~415,50(60),3&220,60,3 380~415,50(60),3&220,60,3
Cooling Power Input kW 27.8 29.2 31.3 33.2 35.3 Cooling Power Input kW 44.2 45.6 47.7 49.6
Heating Power Input kW 28.5 30.2 32.2 33.7 35.7 Heating Power Input kW 44.4 46.1 48.1 49.6
Electric Data Cooling Current A 44.6 47.3 52 54.1 58.8 Electric Data Cooling Current A 71.7 74.4 79.1 81.2
Heating Current A 43.75 46.6 49.3 51.8 54.5 Heating Current A 67.95 70.8 73.5 76
EER 3.83 3.84 3.79 3.72 3.68 EER 3.69 3.70 3.67 3.63
COP 4.18 4.14 4.11 4.08 4.06 COP 4.09 4.07 4.05 4.03
Air Flow Volume m3/h 12000×2+7500×2 12000×2+7500×2 12000+7250×2+7500×2 12000+7500×4 7250×2+7500×4 Air Flow Volume m3/h 12000+7500×6 12000+7500×6 7250×2+7500×6 7500×8
Performance Performance
Noise Level dB(A) 47~64 47~64 47~64 47~64 47~64 Noise Level dB(A) 47~65 47~65 47~65 47~65
Type DC Inverter DC Inverter DC Inverter DC Inverter DC Inverter Type DC Inverter DC Inverter DC Inverter DC Inverter
Compressor Compressor
Quantity 3 3 3 3 3 Quantity 4 4 4 4
Type DC motor DC motor DC motor DC motor DC motor Type DC motor DC motor DC motor DC motor
Fan Motor Fan Motor
Quantity 4 4 5 5 6 Quantity 7 7 8 8
Max. No. of Indoor Units unit 62 64 64 64 64 Max. No. of Indoor Units unit 64 64 64 64
Connection Ratio % 50~130 50~130 50~130 50~130 50~130 Connection Ratio % 50~130 50~130 50~130 50~130
Net mm (935×765×1600)×2+1340×765×1600 (935×765×1600)×2+1340×765×1600 (935×765×1600)+(1340×765×1600)×2 (935×765×1600)+(1340×765×1600)×2 (1340×765×1600)×3 Net mm 935×765×1600+(1340×765×1600)×3 935×765×1600+(1340×765×1600)×3 (1340×765×1600)×4 (1340×765×1600)×4
Dimension(WxDxH) Dimension(WxDxH)
Packing mm (980×810×1850)×2+1400×810×1850 (980×810×1850)×2+1400×810×1850 (980×810×1850)+(1400×810×1850)×2 (980×810×1850)+(1400×810×1850)×2 (1400×810×1850)×3 Packing mm 980×810×1850+(1400×810×1850)×3 980×810×1850+(1400×810×1850)×3 (1400×810×1850)×4 (1400×810×1850)×4
Net kg 223+248+298 248×2+298 248+298×2 248+298×2 298×3 Net kg 223+298×3 248+298×3 298×4 298×4
Weight Weight
Gross kg 243+268+320 268×2+320 268+320×2 268+320×2 320×3 Gross kg 243+320×3 268+320×3 320×4 320×4
Refrigerant Type R410a R410a R410a R410a R410a Refrigerant Type R410a R410a R410a R410a
Liquid Side mm(inch) 19.05(3/4) 19.05(3/4) 19.05(3/4) 19.05(3/4) 19.05(3/4) Liquid Side mm(inch) 22.2(7/8) 22.2(7/8) 22.2(7/8) 22.2(7/8)
Pipe Diameter Pipe Diameter
Gas Side mm(inch) 41.3(13/8) 41.3(13/8) 41.3(13/8) 41.3(13/8) 41.3(13/8) Gas Side mm(inch) 47.6(15/8) 47.6(15/8) 47.6(15/8) 47.6(15/8)
Cooling ℃ -15~52 -15~52 -15~52 -15~52 -15~52 Cooling ℃ -15~52 -15~52 -15~52 -15~52
Operation Range Operation Range
Heating ℃ -20~29 -20~29 -20~29 -20~29 -20~29 Heating ℃ -20~29 -20~29 -20~29 -20~29

Notes: Notes:
1.Cooling Capacity: Indoor temperature 27℃ DB/19℃ WB;Outdoor temperature:35℃ DB/24℃ WB. 1.Cooling Capacity: Indoor temperature 27℃ DB/19℃ WB;Outdoor temperature:35℃ DB/24℃ WB.
2.Heating Capacity:Indoor temperature 20℃ DB;Outdoor temperature:7℃ DB/6℃ WB. 2.Heating Capacity:Indoor temperature 20℃ DB;Outdoor temperature:7℃ DB/6℃ WB.
3.Piping Length:Equivalent piping length:7.5m,level differernce:0m. 3.Piping Length:Equivalent piping length:7.5m,level differernce:0m.
4.Anechoic chamber conversion value,measured in test room.During actual operation.These values are normally somewhat higher as a result of ambient conditons. 4.Anechoic chamber conversion value,measured in test room.During actual operation.These values are normally somewhat higher as a result of ambient conditons.
5.The above designs and specifications are subject to change without prior notice. Final specifications please refer to technical specification provided by sales representative. 5.The above designs and specifications are subject to change without prior notice. Final specifications please refer to technical specification provided by sales representative.

21 22
Modular VRF-
ARV 4

High Efficient And Energy Saving


The Industry’s Leading
IPLV Value
ARV 5X achieves the industry’s top class energy efficiency 7.00 6.17
of cooling and heating by utilizing the advanced 180°since 6.00
6.08 5.90 6.03 5.85 5.81
5.60
wave DC Inverter driving technology,patent energy-saving
5.00
operation technology and improved performance of heat
3.60 3.60
exchange. 4.00
3.55 3.55 3.55 3.55 3.55
3.00
Because the outdoor ambient temperature and indoor unit

Outdoor Units-ARV 4
2.00
load is different at different times of day, most of time, the
1.00
system works under part load. So it is better to assess the
0.00
energy saving performance using IPLV. IPLV(C)=0.5EER(100 8HP 10HP 12HP 14HP 16HP 18HP 20HP
%)+0.3EER(75%)+0.4EER(50%)+0.25EER(25%)
AUX Standrad China National Standrad

Excellent In EER&COP
ARV 5X Series achieves the industry’s top class energy efficiency in cooling and heating by utilizing all DC inverter compressors, and high
efficiency heat exchanger.
The cooling EER is up to 4.43 and the heating COP is up to 4.59in the 8HP category.

EER 4.59 COP


4.43
4.50 4.50 4.14
3.94 4.12 4.13
3.76 3.91 3.70 3.94
4.00 3.54 4.00
3.49 3.52
3.50 3.35 3.50

3.00 3.00

2.50 2.50

2.00 2.00

1.50 1.50

1.00 1.00

0.50 0.50

0.00 0.00
8HP 10HP 12HP 14HP 16HP 18HP 20HP 8HP 10HP 12HP 14HP 16HP 18HP 20HP

23 24
High Efficiency DC Inverter Compressor 180° Sine Wave Control
DC inverter compressor users 180° sine wave vector control
technique makes motor operate smooth and increases the
efficiency. significantly compared with traditional sawtooth
wave. It also can lower the noise level.

1. Direct suction 4. Exclusive high-precision asymmetric Traditional Control 180° Sine Wave DC Control

Small suction overheating, high vortex disk


efficiency. Using asymmetric type vortex disk structure,
compared with the symmetric structure, can
DC Brushless Fan Motor
Load Rev Curve

reduce the compressor loss, improve the 1150 DC fan stepless adjustment

efficiency of suction.
AC fan 2-3 level adjustment
DC brushless motor adjusts the fan speed according to the
system pressure,and running load to enhance the efficiency 230

by 45%. The super aero fan provides a larger air volume


0 20 40 60 80 100 Load%
and higher static pressure.
Fixed scroll 90% energy saving in part load
Exhaust port
2. HP chamber structure Suction gas
The back wall shell and a large Suction port
number of air cushion volume,
reduce exhaust air flow noise.
Orbiting scroll
High-Efficient Inverter Control 80
New HP chamber DC Inverter Compressor

Technology

Compressor efficiency(%)
Common DC Inverter compressor

70
The unit have the higher capacity in partial load according
to controlling the operation number of the compressor and
5. Concentrated winding adjusting the EXV opening of the condenser side, making
the compressor always maintain the highest efficiency
Common AC Inverter compressor

60
Magnetic efficiency is 12% higher than running state. 50 100
distributed winding. Load rate(%)

3. With throwing oil tubing for


compressor

Outdoor Units-ARV 4
Outdoor Units-ARV 4

6. Magnetic resistance DC motor

Energy utilization ratio


When the compressor oil level higher than
the warning line, system through tubing Use powerful rubidium magnet, inhibit
eliminate redundant frozen oil, keep the rotary vibration, reduce the loss of magnetic
oil balance between compressor. field, and the efficiency increased by 25%.

10 50 100 140
Load

High-efficient permanent magnetic motors are installed,


giving better performance than traditional DC inverter
Optimized Fan Grille New Profile Fan Blade
compressors.
Optimized fan blade shape with new air outlet grille The new axial fan designed
enhances air flow volume which greatly improves fan with aerodynamics principle,
performance and decreases noise. it can reduce air loss and
Compressor efficiency New DC motor-centralized winding noise level.
Common DC motor-distributing winding
Efficiency-Rotor Speed Curve

Centralizing winding

Rotor Speed(s-1)

20 40 60 80 100

Distnbutin winding Powerful magnets provide high torque and efficiency and achieve 70% reduction in volume.
Optimized fan Conventional fan

25 26
High Efficient Heat Exchanger Wide Application Range
Optimized 2 to 1 refrigerant circuit design,increase the Optimized fin design, reduces the water resistance and
heat exchanging efficiency and enhance the ratio of liquid wind resistance.
which flow to the evaporator.
Wide Operation Range
Optimized fin Previous fin

Normal refrigerant circuit The unit could operate perfectly between 52 C in hot

summer and -20 C in cold winter making you feel like

52℃
Gas refrigerant Liquid refrigerant
spring all year around, advanced system design and strict
2 to 1refringerant circuit system matching and test. (cooling in -15℃ ) -20℃
Gas refrigerant Liquid refrigerant

Gas refrigerant Liquid refrigerant

Enhance liquid refrigerant ratio Inner grooved copper tube,strength


heat exchange efficiency
Wide Voltage Design Changeable ESP
In country with unstable voltage, ARV can also run stably. Optimized fan provide outdoor unit up to 82Pa static
pressure. Outdoor units can be installed in the service floor
or facility room.
Sub-Cooling Technology For 3 Level
453V
Optimize the design of the condenser 0 pa 20 pa 20-82 pa

11.2 C sub-cooling by optimized refrigerant circuit and "Inverse fin type" window fin design. 415V
380V GB ±10% ARV ±15%
342V
325V
37 C 。

43。C GB ±10% ARV ±15% 15m


75。C 75。C

Outdoor Units-ARV 4
Outdoor Units-ARV 4

37。C

43。C
Normal condenser e-pass condenser
"Inverse fin type" window fin design
Long Piping Length
ambient 35。C ambient 35。C
Thanks to the DC inverter control technology and sub-cooling circuit technology ,it is possible to design a system with
longer piping and elevation difference which make it easier to design and installation.

4.5 C sub-cooling by special plate heat exchanger further reduce the refrigerant temperature flowing into the indoor unit.

Scroll Compressor

logP 1 4
6 5 Pc 4 4' 23 Condenser

Evaporator
T4 T4 '
Pm 9 30m
8 9 3 90m
2
Pe Plate heat 5
7 0 1 exchanger
Maximum
7 6 8 5 meters drop
EXV 2 EXV 1

P-H Diagram Structure Diagram 90m


1.1 C sub-cooling by dual EXV with a special and effective plate heat exchanger.
Max. Total piping length — 1000m
Max. Actual piping length —175m
Max. Level difference between indoor units — 30m
Max. Level difference between ODU and IDU units —90m
Max. Level difference in the same system between ODU and ODU units —5m
Max. piping length from 1st indoor Branch to the farthest indoor unit —90m

Plate heat exchanger Dual EXV

27 28
Precise Temperature Control
Comfortable And Healthy Environment Double EXVs Control
Double EXVs in one system ,each EXV part achieves 480 Plus
rate to precisely adjust refrigerant flow.
Silence Operation Indoor Unit Quiet Mode
Innovative centrifugal fan for large diameter and a new
design of the spiral duct system equipped with high-quality
Outdoor Unit Quiet Mode motor at the same time, making the air supply more
By using optimized fan blades and the CFD(computational quietly and smoothly. The lowest noise is 20 db(A). AUX composite temperature control technology, through the The unit uses PI calculation principle to calculate the percentage
Fluid Dynamics) technology, the product is equipped with indoor/outdoor operation condition detection, adjust outdoor of indoor capacity demand according to indoor temperature
the night low-noise operation function. Provide more quiet power output, optimize the indoor air distribution, achieve the fluctuations, to perform real-time control to the compressor
operation during the night. Minimum operation noise only high precision adjustment of 0.5 ℃ . operating frequency and through the double EXV adjustment,
45dB(A) precision up to level 1000, accurately control the refrigerant
50dB(A) flow, assure indoor comfort.
Office

40dB(A)
Capacity %

Electronic expansion valve


AUX silent mode at night Quiet library Convertional throttling method
100
Temp(℃)
30dB(A) Cooling rapidly
Quiet bedroom
Load %

50

Setting humidity
±0.5℃
26dB(A) Ts Comfortable
temperature 26
Super mute unit bare machine running
58
Noise dB

Cooling slow

Human hearing range is 0-25 dB(A)


80 20dB(A) Cooling rapidly
Time
Leaves rustling sound eration
8:00 12:00 16:00 20:00 0:00 4:00 8:00 Cooling op

18dB(A)
Super mute unit silent running

0dB(A)

Outdoor Units-ARV 4
Outdoor Units-ARV 4

Humanization Design
Intelligent Defrosting VIP Function
Temp

24

Special VIP control function, the VIP room will decide


20 Comfortable
18

the whole system operation mode, prior to other mode


Normal defrosting Cold

AUX intelligent defrosting technique extends the heating 10

operation and decrease the frequency of defrosting. Result in Temp



Defrosting Heating Operation Defrosting Heating Operation Defrosting Heating Operation Time
or economic locking function, ensure the priority of the
stable room temperature, offer comfort life.
24

20 Comfortable
important room.
Base on the main unit and at the end of the EXV control the
18
Conventional
intelligent defrosting Cold

output, fast bolt in liquid refrigerant system, unit operation 10

Defrosting Heating Operation Defrosting Heating Operation Defrosting Heating Operation Time

is more stable; Through the dry run, defrosting exhaust


Temp

24

temperature higher, more complete, more conventional. The 20 Comfortable

Auto Restart Function Economic Locking Function


18

defrosting time less 3 min than others at least UX intelligent


defrosting Cold

The AC can automatically memorize the operation setting Special design economic locking function, through outdoor PCB
10

Defrosting Heating Operation Defrosting Heating Operation Defrosting Heating Operation Time

when power is cut off accidently. It can return to previous switch setting. If work in economic lock, AC lowest work cooling

setting when power resumes. temperature will keep in 26 C and highest heating temperature

Recover the former operation state when power is restored , keep 20 C.
no need restart the unit manually

Fast Warm Up and Cool Down Technology


50 power failure
45
40 power cut
35
The DC Inverter Compressor system reaches full load 30
Tc( ℃ )

25 operation state auto restart


rapidly providing less temperature fluctuation and an 20 to A state
improved living environment, bring great user experience. 15
10
5
0
5 10 15 20 25
26℃
Time (min) power recovered
Capacity reaches 100% in 120s Restart state when power recovered

29 30
Easy Installation &Maintenance Reliable &Stable

No Oil Balance Pipe Between Non-Polar Communication Module Alternate Operation


ODUS No polar in communication wire ,easy installation and In one combination system,any module could run as the
commissioning. master unit according to the running time.Balance the life
High efficient oil/gas separating tech,make the system oil of the outdoor units in one system. 1 2 3 2 1 3 2 3 1

1st time operation 2nd time operation 3rd time operation


balance between compressors without oil balance pipe.
Master Unit Slave Unit Slave Unit
Back-Up Operation Technology
Module Back-Up Technology
As one module breaks down, the rest of modules in the
A, B A, B A, B A, B same refrigerant system start-up urgently.
Oil Balance pipe
1 2 3
Gas pipe This module fails This module start-up

Liquid pipe Compressor Back-Up Technology Fan Motor Back-Up Technology


As one fan motor breaks down, the rest of fan in the As one fan motor breaks down, the rest of fan in the outdoor unit
outdoor unit start-up, ensure the outdoor unit is normal start-up, ensure the outdoor unit is normal operation.
operation.

Auto Addressing Auto Refrigerant Charging


Running Failure or downtime Start-up
The outdoor units distribute indoor system address

Outdoor Units-ARV 4
Outdoor Units-ARV 4

The system according to all kinds of sensor acquisition


automatically. No need manually setting. More convenient system parameters, automatically calculate the amount of
and saving the installation time. refrigerant, filling automatically. Discharge Refrigerant lack protection

All-Around Protection temperature protection


High/low pressure protection
Four-way valve protection
Indoor unit quantity
Drive module protection decreasing alarm function
All-around protection to ensure long-term life of the unit. Compressor
Phase sequence protection over-current protection

Oil Return Control Technology


Dynamic Oil Return Control Technology
Monitor compressor running state and running time,
computing system reasonable oil return time.

6-Step Oil Separating Technology Compressor Throwing Oil Technology


Completely solve the problem of oil, the system more When the compressor oil level higher than the warning line, system
Easy Maintainence stable and reliable through tubing eliminate redundant frozen oil, keep the oil balance
between compressor.
The PCB could record 30 minutes running information before the error occur.Self-diagnosis function helps service engnieer locate faults 1. Compressor with oil mist separator
quickly and easily.It’s convenient for the trouble shooting. 2. Oil self balancing control design
3. High efficient oil separator
4. Capillary static oil return control
5. SV1 auxiliary oil return control
6. System with oil return design

31 32
ARV 4 Series 380~415V-50Hz/380~415V-60Hz
HP 8 10 12 14 16

50Hz ARV-H250/5R1MA-P ARV-H280/5R1MA-P ARV-H330/5R1MA-P ARV-H400/5R1MA-P ARV-H450/5R1MA-P

ARV 4
Model Outdoor
60Hz ARV-H250/6R1MA-P ARV-H280/6R1MA-P ARV-H330/6R1MA-P ARV-H400/6R1MA-P ARV-H450/6R1MA-P
Combination HP 8 10 12 14 16
Cooling kW 25.20 28.00 33.50 40.00 45.00
Capacity
Heating kW 28.00 31.50 37.50 45.00 50.00
Power Supply V~,Hz,Ph 380~415,50,3&380~415,60,3 380~415,50,3&380~415,60,3 380~415,50,3&380~415,60,3 380~415,50,3&380~415,60,3 380~415,50,3&380~415,60,3
Cooling Power Input kW 5.8 7.1 8.9 11.3 12.9
Heating Power Input kW 6.1 7.6 9.1 11.2 12.8
Electric Data Cooling Current A 8.8 10.8 13.5 18.7 21.1
Heating Current A 9.3 11.5 13.8 16.9 19.5
EER 4.34 3.94 3.76 3.54 3.49
COP 4.59 4.14 4.12 4.02 3.91
Air Flow Volume m3/h 12000 12000 12000 7250×2 7500×2
Performance
Flexible Outdoor Unit Combination Noise Level dB(A) 45-58 45-58 45-58 47-61 47-61
Type DC Inverter DC Inverter DC Inverter DC Inverter+Fixed DC Inverter+Fixed

kW HP 8HP 10HP 12HP 14HP 16HP 18HP 20HP


Compressor
Quantity 1 1 1 2 2
Type DC motor DC motor DC motor DC motor+AC motor DC motor+AC motor
25.2 8 ★ Fan Motor
Quantity 1 1 1 2 2

28.0 10 ★ Max. No. of Indoor Units unit 13 16 19 23 26


Connection Ratio % 50~130 50~130 50~130 50~130 50~130
33.5 12 ★ Net mm 930×765×1600 930×765×1600 930×765×1600 1340×765×1600 1340×765×1600
Dimension(WxDxH)
40.0 14 ★ Packing mm 980×810×1850 980×810×1850 980×810×1850 1400×810×1850 1400×810×1850
Net kg 223 223 248 303 303
45.0 16 ★ Weight
Gross kg 243 243 268 325 325

50.4 18 ★ Refrigerant Type R410a R410a R410a R410a R410a


Liquid Side mm(inch) 12.7(1/2) 12.7(1/2) 12.7(1/2) 12.7(1/2) 12.7(1/2)
56.0 20 ★ Pipe Diameter
Gas Side mm(inch) 22.2(7/8) 22.2(7/8) 22.2(7/8) 28.6(9/8) 28.6(9/8)

61.5 22 ★ ★ Operation Range


Cooling ℃ -15~52 -15~52 -15~52 -15~52 -15~52
Heating ℃ -20~29 -20~29 -20~29 -20~29 -20~29
67.0 24 ★★ Stuffing Quantity 20/40/40H unit 14/28/28 14/28/28 14/28/28 11/22/22 11/22/22

73.0 26 ★ ★
78.5 28 ★ ★
83.9 30 ★ ★ ARV 4 Series 380~415V-50Hz/380~415V-60Hz
90.0 32 ★★
HP 18 20 22 24 26
95.4 34 ★ ★

Outdoor Units-ARV 4
Outdoor Units-ARV 4

50Hz ARV-H500/5R1MA-P ARV-H560/5R1MA-P ARV-H610/5R1MA-P ARV-H670/5R1MA-P ARV-H730/5R1MA-P


Model Outdoor
100.8 36 ★★ 60Hz ARV-H500/6R1MA-P ARV-H560/6R1MA-P ARV-H610/9R1MA-P ARV-H670/9R1MA-P ARV-H730/9R1MA-P
Combination HP 18 20 10+12 12×2 10+16
106.4 38 ★ ★ Cooling kW 50.40 56.00 61.5 67 73
Capacity
112.0 40 ★★ ★ Heating kW 55.50 63.00 69 75 81.5
Power Supply V~,Hz,Ph 380~415,50,3&380~415,60,3 380~415,50,3 380~415,50,3&380~415,60,3 380~415,50,3&380~415,60,3 380~415,50,3&380~415,60,3
118.5 42 ★ ★ ★ Cooling Power Input kW 14.3 16.7 16 17.8 20

123.5 44 ★ ★★ Heating Power Input kW 15.0 16.0 16.7 18.2 20.4


Electric Data Cooling Current A 23.3 27.1 24.3 27 31.9
128.9 46 ★ ★ ★ Heating Current A 22.8 25.4 25.3 27.6 31

134.3 48 ★ ★★ EER 3.52 3.35 3.84 3.76 3.65


COP 3.70 3.94 4.13 4.12 4.00
140.8 50 ★ ★★ Air Flow Volume m3/h 7500×2 7500×2 12000×2 12000×2 12000+7500×2
Performance
145.8 52 ★ ★★ Noise Level dB(A) 47-61 45-65 47~61 47~62 47~62
Type DC Inverter+Fixed DC Inverter+Fixed DC Inverter DC Inverter DC Inverter+Fixed
151.2 54 ★★★ Compressor
Quantity 2 2 2 2 2+1

156.8 56 ★ ★★ Fan Motor


Type DC motor+AC motor DC motor+AC motor DC motor DC motor DC motor+AC motor
Quantity 2 2 2 2 3
162.4 58 ★ ★★ Max. No. of Indoor Units unit 30 33 36 39 43

167.8 60 ★★ ★★ Connection Ratio % 50~130 50~130 50~130 50~130 50~130


Net mm 1340×765×1600 1340×765×1600 (935×765×1600)×2 (935×765×1600)×2 935×765×1600+1340×765×1600
173.9 62 ★ ★★ ★ Dimension(WxDxH)
Packing mm 1400×810×1850 1400×810×1850 (980×810×1850)×2 (980×810×1850)×2 980×810×1850+1400×810×1850

179.3 64 ★ ★ ★★ Weight
Net kg 318 355 223+248 248×2 223+298
Gross kg 340 371 243+268 268×2 243+320
184.7 66 ★ ★★★ Refrigerant Type R410a R410a R410a R410a R410a

190.8 68 ★★ ★★ Pipe Diameter


Liquid Side mm(inch) 12.7(1/2) 12.7(1/2) 15.88(5/8) 15.88(5/8) 19.05(3/4)
Gas Side mm(inch) 28.6(9/8) 28.6(9/8) 28.6(9/8) 28.6(9/8) 34.93(11/8)
196.2 70 ★ ★★★ Cooling ℃ -15~52 -15~52 -15~52 -15~52 -15~52
Operation Range
201.6 72 ★★★★ Heating ℃ -20~29 -20~29 -20~29 -20~29 -20~29
Stuffing Quantity 20/40/40H unit 11/22/22 11/22/22 /  /   /
207.2 74 ★★★ ★
212.8 76 ★★ ★★ Notes:
1.Cooling Capacity: Indoor temperature 27℃ DB/19℃ WB;Outdoor temperature:35℃ DB/24℃ WB.
218.4 78 ★ ★★★ 2.Heating Capacity:Indoor temperature 20℃ DB;Outdoor temperature:7℃ DB/6℃ WB.
3.Piping Length:Equivalent piping length:7.5m,level differernce:0m.
224.0 80 ★★★★ 4.Anechoic chamber conversion value,measured in test room.During actual operation.These values are normally somewhat higher as a result of ambient conditons.
5.The above designs and specifications are subject to change without prior notice. Final specifications please refer to technical specification provided by sales representative.

33 34
ARV 4 Series 380~415V-50Hz/380~415V-60Hz ARV 4 Series 380~415V-50Hz/380~415V-60Hz
HP 28 30 32 34 36 HP 48 50 52 54 56

50Hz ARV-H780/5R1MA-P ARV-H840/5R1MA-P ARV-H900/5R1MA-P ARV-H950/5R1MA-P ARV-H1010/5R1MA-P 50Hz ARV-H1340/5R1MA-P ARV-H1410/5R1MA-P ARV-H1460/5R1MA-P ARV-H1510/5R1MA-P ARV-H1570/5R1MA-P
Model Outdoor Model Outdoor
60Hz ARV-H780/9R1MA-P ARV-H840/9R1MA-P ARV-H900/9R1MA-P ARV-H950/9R1MA-P ARV-H1010/9R1MA-P 60Hz ARV-H1340/9R1MA-P ARV-H1410/9R1MA-P ARV-H1460/9R1MA-P ARV-H1510/9R1MA-P ARV-H1570/9R1MA-P
Combination HP 12+16 12+18 16×2 16+18 18×2 Combination HP 12+18×2 14+18×2 16+18×2 18×3 18×2+20
Cooling kW 78.5 83.9 90 95.4 100.8 Cooling kW 134.3 140.8 145.8 151.2 156.8
Capacity Capacity
Heating kW 87.5 93 100 105.5 111 Heating kW 148.5 156 161 166.5 174
Power Supply V~,Hz,Ph 380~415,50,3&380~415,60,3 380~415,50,3&380~415,60,3 380~415,50,3&380~415,60,3 380~415,50,3&380~415,60,3 380~415,50,3&380~415,60,3 Power Supply V~,Hz,Ph 380~415,50,3&380~415,60,3 380~415,50,3&380~415,60,3 380~415,50,3&380~415,60,3 380~415,50,3&380~415,60,3 380~415,50,3&380~415,60,3
Cooling Power Input kW 21.8 23.2 25.8 27.2 28.6 Cooling Power Input kW 37.5 39.9 41.5 42.9 45.3
Heating Power Input kW 21.9 24.1 25.6 27.8 30 Heating Power Input kW 39.1 41.2 42.8 45 46
Electric Data Cooling Current A 34.6 36.8 42.2 44.4 46.6 Electric Data Cooling Current A 60.1 65.3 67.7 69.9 73.7
Heating Current A 33.3 36.6 39 42.3 45.6 Heating Current A 59.4 62.5 65.1 68.4 71
EER 3.60 3.62 3.49 3.51 3.52 EER 3.58 3.53 3.51 3.52 3.46
COP 4.00 3.86 3.91 3.79 3.70 COP 3.80 3.79 3.76 3.70 3.78
Air Flow Volume m3/h 12000+7500×2 12000+7500×2 7500×4 7500×4 7500×4 Air Flow Volume m3/h 12000+7250×4 7250×2+7500×4 7500×6 7500×6 7500×6
Performance Performance
Noise Level dB(A) 47~62 47~63 47~63 47~63 47~63 Noise Level dB(A) 47~64 47~64 47~64 47~64 47~65
Type DC Inverter+Fixed DC Inverter+Fixed DC Inverter+Fixed DC Inverter+Fixed DC Inverter+Fixed Type DC Inverter+Fixed DC Inverter+Fixed DC Inverter+Fixed DC Inverter+Fixed DC Inverter+Fixed
Compressor Compressor
Quantity 2+1 2+1 2+2 2+2 2+2 Quantity 3+2 3+3 3+3 3+3 3+3
Type DC motor+AC motor DC motor+AC motor DC motor+AC motor DC motor+AC motor DC motor+AC motor Type DC motor+AC motor DC motor+AC motor DC motor+AC motor DC motor+AC motor DC motor+AC motor
Fan Motor Fan Motor
Quantity 3 3 4 4 4 Quantity 5 6 6 6 6
Max. No. of Indoor Units unit 46 49 53 56 59 Max. No. of Indoor Units unit 64 64 64 64 64
Connection Ratio % 50~130 50~130 50~130 50~130 50~130 Connection Ratio % 50~130 50~130 50~130 50~130 50~130
Net mm 935×765×1600+1340×765×1600 935×765×1600+1340×765×1600 (1340×765×1600)×2 (1340×765×1600)×2 (1340×765×1600)×2 Net mm (935×765×1600)+(1340×765×1600)×2 (1340×765×1600)×3 (1340×765×1600)×3 (1340×765×1600)×3 (1340×765×1600)×3
Dimension(WxDxH) Dimension(WxDxH)
Packing mm 980×810×1850+1400×810×1850 980×810×1850+1400×810×1850 (1400×810×1850)×2 (1400×810×1850)×2 (1400×810×1850)×2 Packing mm (980×810×1850)+(1400×810×1850)×2 (1400×810×1850)×3 (1400×810×1850)×3 (1400×810×1850)×3 (1400×810×1850)×3
Net kg 248+298 248+318 303×2 303+318 318×2 Net kg 248+318×2 303+318×2 303+318×2 318×3 318×2+355
Weight Weight
Gross kg 268+320 268+340 325×2 325+340 340×2 Gross kg 268+340×2 325+340×2 325+340×2 340×3 340×2+371
Refrigerant Type R410a R410a R410a R410a R410a Refrigerant Type R410a R410a R410a R410a R410a
Liquid Side mm(inch) 19.05(3/4) 19.05(3/4) 19.05(3/4) 19.05(3/4) 19.05(3/4) Liquid Side mm(inch) 19.05(3/4) 19.05(3/4) 22.2(7/8) 22.2(7/8) 22.2(7/8)
Pipe Diameter Pipe Diameter
Gas Side mm(inch) 34.93(11/8) 34.93(11/8) 34.93(11/8) 34.93(11/8) 41.3(13/8) Gas Side mm(inch) 41.3(13/8) 41.3(13/8) 47.6(15/8) 47.6(15/8) 47.6(15/8)
Cooling ℃ -15~52 -15~52 -15~52 -15~52 -15~52 Cooling ℃ -15~52 -15~52 -15~52 -15~52 -15~52
Operation Range Operation Range
Heating ℃ -20~29 -20~29 -20~29 -20~29 -20~29 Heating ℃ -20~29 -20~29 -20~29 -20~29 -20~29

ARV 4 Series 380~415V-50Hz/380~415V-60Hz ARV 4 Series 380~415V-50Hz/380~415V-60Hz


HP 38 40 42 44 46 HP 58 60 62 64

Outdoor Units-ARV 4
Outdoor Units-ARV 4

50Hz ARV-H1060/5R1MA-P ARV-H1120/5R1MA-P ARV-H1180/5R1MA-P ARV-H1230/5R1MA-P ARV-H1290/5R1MA-P 50Hz ARV-H1620/5R1MA-P ARV-H1680/5R1MA-P ARV-H1740/5R1MA-P ARV-H1800/5R1MA-P
Model Outdoor Model Outdoor
60Hz ARV-H1060/9R1MA-P ARV-H1120/9R1MA-P ARV-H1180/9R1MA-P ARV-H1230/9R1MA-P ARV-H1290/9R1MA-P 60Hz ARV-H1620/9R1MA-P ARV-H1680/9R1MA-P ARV-H1740/9R1MA-P ARV-H1800/9R1MA-P
Combination HP 18+20 12×2+16 12+14+16 12+16×2 12+16+18 Combination HP 18+20×2 12×2+18×2 12+16×2+18 12+16+18×2
Cooling kW 106.4 112 118.5 123.5 128.9 Cooling kW 162.4 167.8 173.9 179.3
Capacity Capacity
Heating kW 118.5 125 132.5 137.5 143 Heating kW 181.5 186 193 198.5
Power Supply V~,Hz,Ph 380~415,50,3&380~415,60,3 380~415,50,3&380~415,60,3 380~415,50,3&380~415,60,3 380~415,50,3&380~415,60,3 380~415,50,3&380~415,60,3 Power Supply V~,Hz,Ph 380~415,50,3&380~415,60,3 380~415,50,3&380~415,60,3 380~415,50,3&380~415,60,3 380~415,50,3&380~415,60,3
Cooling Power Input kW 31 30.7 33.1 34.7 36.1 Cooling Power Input kW 47.7 46.4 49 50.4
Heating Power Input kW 31 31 33.1 34.7 36.9 Heating Power Input kW 47 48.2 49.7 51.9
Electric Data Cooling Current A 50.4 48.1 53.3 55.7 57.9 Electric Data Cooling Current A 77.5 73.6 79 81.2
Heating Current A 48.2 47.1 50.2 52.8 56.1 Heating Current A 73.6 73.2 75.6 78.9
EER 3.43 3.65 3.58 3.56 3.57 EER 3.40 3.62 3.55 3.56
COP 3.82 4.03 4.00 3.96 3.88 COP 3.86 3.86 3.88 3.82
Air Flow Volume m3/h 7500×4 12000×2+7500×2 12000+7250×2+7500×2 12000+7500×4 12000+7250×4 Air Flow Volume m3/h 7500×6 12000×2+7500×4 12000+7500×6 12000+7500×6
Performance Performance
Noise Level dB(A) 47~64 47~64 47~64 47~64 47~64 Noise Level dB(A) 47~65 47~65 47~65 47~65
Type DC Inverter+Fixed DC Inverter+Fixed DC Inverter+Fixed DC Inverter+Fixed DC Inverter+Fixed Type DC Inverter+Fixed DC Inverter+Fixed DC Inverter+Fixed DC Inverter+Fixed
Compressor Compressor
Quantity 2+2 3+1 3+2 3+2 3+2 Quantity 3+3 4+2 4+3 4+3
Type DC motor+AC motor DC motor+AC motor DC motor+AC motor DC motor+AC motor DC motor+AC motor Type DC motor+AC motor DC motor+AC motor DC motor+AC motor DC motor+AC motor
Fan Motor Fan Motor
Quantity 4 4 5 5 5 Quantity 6 6 7 7
Max. No. of Indoor Units unit 62 64 64 64 64 Max. No. of Indoor Units unit 64 64 64 64
Connection Ratio % 50~130 50~130 50~130 50~130 50~130 Connection Ratio % 50~130 50~130 50~130 50~130
Net mm (1340×765×1600)×2 (935×765×1600)×2+1340×765×1600 (935×765×1600)+(1340×765×1600)×2 (935×765×1600)+(1340×765×1600)×2 (935×765×1600)+(1340×765×1600)×2 Net mm (1340×765×1600)×3 (935×765×1600)×2+(1340×765×1600)×2 (935×765×1600)+(1340×765×1600)×3 (935×765×1600)+(1340×765×1600)×3
Dimension(WxDxH) Dimension(WxDxH)
Packing mm (1400×810×1850)×2 (980×810×1850)×2+1400×810×1850 (980×810×1850)+(1400×810×1850)×2 (980×810×1850)+(1400×810×1850)×2 (980×810×1850)+(1400×810×1850)×2 Packing mm (1400×810×1850)×3 (980×810×1850)×2+(1400×810×1850)×2 (980×810×1850)+(1400×810×1850)×3 (980×810×1850)+(1400×810×1850)×3

Net kg 318+355 248×2+303 248+303×2 248+303×2 248+303+318 Net kg 318+355×2 248×2+318×2 248+303×2+318 248+303+318×2
Weight Weight
Gross kg 340+371 268×2+325 268+325×2 268+325×2 268+325+340 Gross kg 340+371×2 268×2+340×2 268+225×2+340 268+225+340×2
Refrigerant Type R410a R410a R410a R410a R410a Refrigerant Type R410a R410a R410a R410a
Liquid Side mm(inch) 19.05(3/4) 19.05(3/4) 19.05(3/4) 19.05(3/4) 19.05(3/4) Liquid Side mm(inch) 22.2(7/8) 22.2(7/8) 22.2(7/8) 22.2(7/8)
Pipe Diameter Pipe Diameter
Gas Side mm(inch) 41.3(13/8) 41.3(13/8) 41.3(13/8) 41.3(13/8) 41.3(13/8) Gas Side mm(inch) 47.6(15/8) 47.6(15/8) 47.6(15/8) 47.6(15/8)
Cooling ℃ -15~52 -15~52 -15~52 -15~52 -15~52 Cooling ℃ -15~52 -15~52 -15~52 -15~52
Operation Range Operation Range
Heating ℃ -20~29 -20~29 -20~29 -20~29 -20~29 Heating ℃ -20~29 -20~29 -20~29 -20~29

Notes: Notes:
1.Cooling Capacity: Indoor temperature 27℃ DB/19℃ WB;Outdoor temperature:35℃ DB/24℃ WB. 1.Cooling Capacity: Indoor temperature 27℃ DB/19℃ WB;Outdoor temperature:35℃ DB/24℃ WB.
2.Heating Capacity:Indoor temperature 20℃ DB;Outdoor temperature:7℃ DB/6℃ WB. 2.Heating Capacity:Indoor temperature 20℃ DB;Outdoor temperature:7℃ DB/6℃ WB.
3.Piping Length:Equivalent piping length:7.5m,level differernce:0m. 3.Piping Length:Equivalent piping length:7.5m,level differernce:0m.
4.Anechoic chamber conversion value,measured in test room.During actual operation.These values are normally somewhat higher as a result of ambient conditons. 4.Anechoic chamber conversion value,measured in test room.During actual operation.These values are normally somewhat higher as a result of ambient conditons.
5.The above designs and specifications are subject to change without prior notice. Final specifications please refer to technical specification provided by sales representative. 5.The above designs and specifications are subject to change without prior notice. Final specifications please refer to technical specification provided by sales representative.

35 36
ARV 4 Series 380~415V-50Hz/380~415V-60Hz
HP 66 68 70 72

50Hz ARV-H1850/5R1MA-P ARV-H1910/5R1MA-P ARV-H1960/5R1MA-P ARV-H2010/5R1MA-P


Model Outdoor
60Hz ARV-H1850/9R1MA-P ARV-H1910/9R1MA-P ARV-H1960/9R1MA-P ARV-H2010/9R1MA-P
Combination HP 12+18×3 16×2+18×2 16+18×3 18×4
Cooling kW 184.7 190.8 196.2 201.6
Capacity
Heating kW 204 211 216.5 222
Power Supply V~,Hz,Ph 380~415,50,3&380~415,60,3 380~415,50,3&380~415,60,3 380~415,50,3&380~415,60,3 380~415,50,3&380~415,60,3
Cooling Power Input kW 51.8 54.4 55.8 57.2
Heating Power Input kW 54.1 55.6 57.8 60
Electric Data Cooling Current A 83.4 88.8 91 93.2
Heating Current A 82.2 84.6 87.9 91.2
EER 3.57 3.51 3.52 3.52
COP 3.77 3.79 3.75 3.70
Air Flow Volume m3/h 12000+7500×6 7500×8 7500×8 7500×8
Performance
Noise Level dB(A) 47~65 47~65 47~65 47~65
Type DC Inverter+Fixed DC Inverter+Fixed DC Inverter+Fixed DC Inverter+Fixed
Compressor
Quantity 4+3 4+4 4+4 4+4
Type DC motor+AC motor DC motor+AC motor DC motor+AC motor DC motor+AC motor
Fan Motor
Quantity 7 8 8 8
Max. No. of Indoor Units unit 64 64 64 64
Connection Ratio % 50~130 50~130 50~130 50~130
Net mm (935×765×1600)+(1340×765×1600)×3 (1340×765×1600)×4 (1340×765×1600)×4 (1340×765×1600)×4
Dimension(WxDxH)
Packing mm (980×810×1850)+(1400×810×1850)×3 (1400×810×1850)×4 (1400×810×1850)×4 (1400×810×1850)×4

Net kg 248+318×3 303×2+318×2 303+318×3 318×4


Weight
Gross kg 268+340×3 325×2+340×2 325+340×3 340×4
Refrigerant Type R410a R410a R410a R410a
Liquid Side mm(inch) 22.2(7/8) 22.2(7/8) 22.2(7/8) 22.2(7/8)
Pipe Diameter
Gas Side mm(inch) 47.6(15/8) 47.6(15/8) 47.6(15/8) 47.6(15/8)
Cooling ℃ -15~52 -15~52 -15~52 -15~52
Operation Range
Heating ℃ -20~29 -20~29 -20~29 -20~29

ARV 4 Series 380~415V-50Hz/380~415V-60Hz


HP 74 76 78 80
Outdoor Units-ARV 4

50Hz ARV-H2070/5R1MA-P ARV-H2130/5R1MA-P ARV-H2180/5R1MA-P ARV-H2240/5R1MA-P


Model Outdoor
60Hz ARV-H2070/9R1MA-P ARV-H2130/9R1MA-P ARV-H2180/9R1MA-P ARV-H2240/9R1MA-P
Combination HP 18×3+20 18×2+20×2 18+20×3 20×4
Cooling kW 207.2 212.8 218.4 224
Capacity
Heating kW 229.5 237 244.5 252
Power Supply V~,Hz,Ph 380~415,50,3&380~415,60,3 380~415,50,3&380~415,60,3 380~415,50,3&380~415,60,3 380~415,50,3&380~415,60,3
Cooling Power Input kW 59.6 62 64.4 66.8
Heating Power Input kW 61 62 63 64
Electric Data Cooling Current A 97 100.8 104.6 108.4
Heating Current A 93.8 96.4 99 101.6
EER 3.48 3.43 3.39 3.35
COP 3.76 3.82 3.88 3.94
Air Flow Volume m3/h 7500×8 7500×8 7500×8 7500×8
Performance
Noise Level dB(A) 47~65 47~65 47~65 47~65
Type DC Inverter+Fixed DC Inverter+Fixed DC Inverter+Fixed DC Inverter+Fixed
Compressor
Quantity 4+4 4+4 4+4 4+4
Type DC motor+AC motor DC motor+AC motor DC motor+AC motor DC motor+AC motor
Fan Motor
Quantity 8 8 8 8
Max. No. of Indoor Units unit 64 64 64 64
Connection Ratio % 50~130 50~130 50~130 50~130
Net mm (1340×765×1600)×4 (1340×765×1600)×4 (1340×765×1600)×4 (1340×765×1600)×4
Dimension(WxDxH)
Packing mm (1400×810×1850)×4 (1400×810×1850)×4 (1400×810×1850)×4 (1400×810×1850)×4
Net kg 318×3+355 318×2+355×2 318+355×3 355×4
Weight
Gross kg 340×3+371 340×2+371×2 340+371×3 371×4
Refrigerant Type R410a R410a R410a R410a
Liquid Side mm(inch) 22.2(7/8) 22.2(7/8) 22.2(7/8) 22.2(7/8)
Pipe Diameter
Gas Side mm(inch) 47.6(15/8) 47.6(15/8) 47.6(15/8) 47.6(15/8)
Cooling ℃ -15~52 -15~52 -15~52 -15~52
Operation Range
Heating ℃ -20~29 -20~29 -20~29 -20~29

Notes:
1.Cooling Capacity: Indoor temperature 27℃ DB/19℃ WB;Outdoor temperature:35℃ DB/24℃ WB.
2.Heating Capacity:Indoor temperature 20℃ DB;Outdoor temperature:7℃ DB/6℃ WB.
3.Piping Length:Equivalent piping length:7.5m,level differernce:0m.
4.Anechoic chamber conversion value,measured in test room.During actual operation.These values are normally somewhat higher as a result of ambient conditons.
5.The above designs and specifications are subject to change without prior notice. Final specifications please refer to technical specification provided by sales representative.

37 38
Auto Restart Function power failure

Mini VRF-
The AC can automatically memorize the operation setting power cut
when power is cut off accidently. It can return to previous
setting when power resumes. operation state auto restart
to A state

ARV Mini
Recover the former operation state when power is restored ,
no need restart the unit manually

power recovered
Restart state when power recovered

Fast Cooling/Heating Technology


The DC Inverter Compressor system reaches full load rapidly providing less temperature fluctuation and an improved living environment,
bring great user experience.

180° Sine Wave Control


180 degree sine wave DC inverter technology, DC inverter
output smooth sine wave, of compressor speed and system Electronic expansion valve
output capability of precise control, according to the actual Accurate Temperature Control Convertional throttling method

load linear output, improve the operation efficiency of the


motor. ensure the high efficiency under low load. According to change trend of indoor ambient temperature,

Setting humidity
the unit can use PI algorithm to calculate capacity demand
percentage of indoor unit, control operating frequency
of compressor in real time and realize accurate control of
room temperature.

Long Piping Technology Cooling op


eration
Time

Outdoor Units-ARV Mini


Outdoor Units-ARV Mini

The maximum single piping length of 3HP unit is up to 25m, and the height can reach 15 meters; the 5HP and 6HP units single piping
length can be 50 meters, and the height can be up to 30m.

Flexible And Diversified Matching of Indoor and


Outdoor Unit
AUX offers a variety indoor unit, more than 100 models of 7 types. Capacity ranges are from 2.2Kw to 14Kw. It is full compliance with
residential and light commercial place. Our systems can operate up to 130% of capacity which allows any system to be designed to the
Wide Operation Range customers and applications needs.


The unit could operate perfectly between 52 C in hot

summer and -20 C in cold winter making you feel like
spring all year around with advanced system design and

strict matching test(cooling in -10 C ). -15℃ 52℃
Wide Voltage Design
453V
In country with unstable voltage, ARV can also run 415V
stably.
380V GB ±10% ARV ±15%

DC Inverter Compressor 342V


325V

Made of rare earth permanent magnetic material, the rotor could change the motor’s round speed by changing the DC voltage motor, GB ±10% ARV ±15%
thus overcome the electromagnetic noise and rotor loss of AC inverter compressor, then achieves high efficiency as well as low noise.

39 40
ARV Mini Series 50Hz
Model Outdoor ARV-H080/4R1A ARV-H100/4R1A ARV-H120/4R1A ARV-H140/4R1A ARV-H160/4R1A ARV-H220/5R1A ARV-H280/5R1A
Cooling kW 8.00 10.00 12.00 14.00 16.00 22.40 26.00
Capacity
Heating kW 9.00 11.00 13.20 15.40 17.00 24.50 28.50
Power Supply V~,Hz,Ph 220~240,50,1 220~240,50,1 220~240,50,1 220~240,50,1 220~240,50,1 380~415,50,3 380~415,50,3
Cooling Power Input kW 2.50 3.20 3.75 4.38 4.95 7.20 8.40
Heating Power Input kW 2.63 3.20 3.80 4.53 5.00 6.70 7.90
Electric Data Cooling Current A 11.50 14.70 17.00 20.00 22.50 11.60 13.50
Heating Current A 12.00 14.60 17.50 20.60 22.80 11.00 13.00
EER 3.20 3.13 3.20 3.20 3.23 3.11 3.10
COP 3.42 3.44 3.47 3.40 3.40 3.66 3.61

Indoor Units
Air Flow Volume m3/h 4000 4000 5000 5000 6000 15300 15300
Performance
Noise Level dB(A) ≤ 60 ≤ 60 ≤ 60 ≤ 60 ≤ 63 60 60
Vertical Pipe Length m ≤ 15 ≤ 15 ≤ 30 ≤ 30 ≤ 30 ≤ 30 ≤ 30
Actual Pipe Length m 20 20 45 45 45 45 45
Piping Limite
Equivalent Pipe Length m 25 25 50 50 50 50 50
Total Pipe length m 50 50 100 100 100 100 100
Max. No. of Indoor Units unit 4 4 6 6 6 11 12
Connection Ratio % 50~130 50~130 50~130 50~130 50~130 50~130 50~130
Net mm 900×320×790 900×320×790 940×368×1366 940×368×1366 940×368×1366 1120×400×1510 1120×400×1510
Dimension(WxDxH)
Packing mm 1030×430×850 1030×430×850 1080×460×1500 1080×460×1500 1080×460×1500 1270×560×1710 1270×560×1710

Weight
Net kg 65 67 100 100 102 150 150 One-way Cassette
Gross kg 70 72 113 113 115 170 170
Refrigerant Type R410a R410a R410a R410a R410a R410a R410a

Pipe Diameter
Liquid Side
Gas Side
mm(inch)
mm(inch)
9.52(3/8)
15.88(5/8)
9.52(3/8)
15.88(5/8)
9.52(3/8)
19.05(3/4)
9.52(3/8)
19.05(3/4)
9.52(3/8)
19.05(3/4)
9.52(3/8)
22.22(7/8)
9.52(3/8)
22.22(7/8)
Two-way Cassette
Cooling ℃ -10~52 -10~52 -10~52 -10~52 -10~52 -10~52 -10~52
Operation Range
Heating ℃ -15~24 -15~24 -15~24 -15~24 -15~24 -15~24 -15~24
Stuffing Quantity 20/40/40H unit 60/122/183 60/122/183 27/54/54 27/54/54 27/54/54 17/37/37 17/37/37 Compact Four-way Cassette

Four-way Cassette

Slim Duct
ARV Mini Series 60Hz
Outdoor Units-ARV Mini

Model Outdoor ARV-H080/2R1A ARV-H100/2R1A ARV-H120/2R1A ARV-H140/2R1A ARV-H160/2R1A Mid ESP Duct
Cooling kW 8.00 10.00 12.00 14.00 16.00
Capacity
Heating kW 9.00 11.00 13.20 15.40 17.00
Power Supply
Cooling Power Input
V~,Hz,Ph
kW
208~230,60,1
2.50
208~230,60,1
3.20
208~230,60,1
3.75
208~230,60,1
4.38
208~230,60,1
4.95
High ESP Duct
Electric Data Heating Power Input kW 2.63 3.20 3.80 4.53 5.00
Cooling Current A 11.50 14.70 17.00 20.00 22.50
Heating Current A 12.00 14.60 17.50 20.60 22.80 Fresh Air Processing Unit
Air Flow Volume m3/h 4000 4000 5000 5000 6000
Performance
Noise Level dB(A) ≤ 60 ≤ 60 ≤ 60 ≤ 60 ≤ 63
Vertical Pipe Length
Actual Pipe Length
m
m
≤ 15
20
≤ 15
20
≤ 30
45
≤ 30
45
≤ 30
45
Ceiling&Floor
Piping Limite
Equivalent Pipe Length m 25 25 50 50 50
Total Pipe length m 50 50 100 100 100
Max. No. of Indoor Units
Connection Ratio
unit
%
4
50~130
4
50~130
6
50~130
6
50~130
6
50~130
Wall-mounted
Net mm 900×320×790 900×320×790 940×368×1366 940×368×1366 940×368×1366
Dimension(WxDxH)
Packing mm 1030×430×850 1030×430×850 1080×460×1500 1080×460×1500 1080×460×1500
Net kg 65 67 100 100 102
Weight
Gross kg 70 72 113 113 115
Refrigerant Type R410a R410a R410a R410a R410a
Liquid Side mm(inch) 9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8)
Pipe Diameter
Gas Side mm(inch) 15.88(5/8) 15.88(5/8) 19.05(3/4) 19.05(3/4) 19.05(3/4)
Cooling ℃ -10~52 -10~52 -10~52 -10~52 -10~52
Operation Range
Heating ℃ -15~24 -15~24 -15~24 -15~24 -15~24
Stuffing Quantity 20/40/40H unit 60/122/183 60/122/183 27/54/54 27/54/54 27/54/54

Notes:
1.Cooling Capacity: Indoor temperature 27℃ DB/19℃ WB;Outdoor temperature:35℃ DB/24℃ WB.
2.Heating Capacity:Indoor temperature 20℃ DB;Outdoor temperature:7℃ DB/6℃ WB.
3.Piping Length:Equivalent piping length:7.5m,level differernce:0m.
4.Anechoic chamber conversion value,measured in test room.During actual operation.These values are normally somewhat higher as a result of ambient conditons.
5.The above designs and specifications are subject to change without prior notice. Final specifications please refer to technical specification provided by sales representative.

41 42
Cassette Series One-Way Cassette

High-Lift Pump Fresh Air, Improved Air Quality


Standard built-in drain pump with 750mm pumphead. Fresh air makes indoor air healthy and comfortable.

One-way Cassette

750

Two-way Cassette

Specification-DC Inverter 50Hz&60Hz


Model Indoor ARVC1-H028/R1X ARVC1-H036/R1X ARVC1-H045/R1X ARVC1-H056/R1X ARVC1-H071/R1X

Cooling kW 2.8 3.6 4.5 5.6 7.1


Compact Four-way Capacity

Indoor Units-Cassette Semes


Heating kW 3.2 4 5 6.3 8
Indoor Units-Cassette Semes

Cassette Electric Data


Power Supply V~,Hz,Ph 220~240,50(60),1 220~240,50(60),1 220~240,50(60),1 220~240,50(60),1 220~240,50(60),1

Rated Power W 40 40 45 45 100

Air Flow Volume(Hi/Mid/Low) m3/h 530 600 720 910 1000


Performance
Noise Level(Hi/Mid/Low) dB(A) 36/34/32 38/36/34 41/38/35 43/40/37 44/41/38

Net(Body) mm 870×460×250 870×460×250 870×460×250 1180×495×290 1180×495×290

Packing(Body) mm 1130×570×355 1130×570×355 1130×570×355 1440×660×385 1440×660×385


Dimension(WxDxH)
Net(Panel) mm 1070×520×33 1070×520×33 1070×520×33 1380×550×33 1380×550×33

Packing(Panel) mm 1085×555×175 1085×555×175 1085×555×175 1400×585×175 1400×585×175

Four-way Cassette
Net/Gross(Body) kg 24/31 26/33 26/33 38/45 38/45
Weight
Net/Gross(Panel) kg 3/5 3/5 3/5 5/7 5/7

Refrigerant Type R410a R410a R410a R410a R410a

Liquid Side mm(inch) 6.35(1/4) 6.35(1/4) 6.35(1/4) 6.35(1/4) 9.52(3/8)

Pipe Diameter Gas Side mm(inch) 12.7(1/2) 12.7(1/2) 12.7(1/2) 12.7(1/2) 15.88(5/8)

Drainage mm(inch) R3/4in(DN20) R3/4in(DN20) R3/4in(DN20) R3/4in(DN20) R3/4in(DN20)

Stuffing Quantity 20/40/40H unit 88/186/210 88/186/210 88/186/210 60/120/123 60/120/123

Independent
Dehumidification Digital Tube Display Sleep Mode Built-in Drain Pump Fast Cooling/Heating

Notes:
1.Cooling Capacity: Indoor temperature 27℃ DB/19℃ WB;Outdoor temperature:35℃ DB/24℃ WB.
2.Heating Capacity:Indoor temperature 20℃ DB;Outdoor temperature:7℃ DB/6℃ WB.
3.Piping Length:Equivalent piping length:7.5m,level differernce:0m.
4.Sound level is measured at 1.4m below the unit.
3D Air Flow Fresh Air Intake Wired Control Central Control 5.5.The above designs and specifications are subject to change without prior notice. Final specifications please refer to technical specification provided by sales representative.

43 44
Two-Way Cassette Compact&Four-Way Cassette

5-Segment Heat Exchanger Built-in Water Drainage Pump


Ultra Slim Design
Innovative 3D spiral wind leaf increases air volume and Digital tube displays all contents: indoor temperature,
Only 315mm in height, save installation space. 315mm setting temperature, operation mode, etc.
makes the air supply more quietly and smoothly.
Clearly to check the running status, more convenient for
trouble shooting.

Quiet Operation High Airflow 1200mm

Innovative 3D spiral wind leaf increases air volume and High airflow for high ceiling application guarantees comfort
makes the air supply more quietly and smoothly. in large space .Guarantees even airflow and temperature
throughout the room .

Optimized Electric Box Ultra Slim Design


Better fire-proof and easy to maintenance.
Only 250mm in height, save installation space.
Specification-DC Inverter 50Hz&60Hz
Model Indoor ARVC2-H028/R1X ARVC2-H036/R1X ARVC2-H045/R1X ARVC2-H056/R1X ARVC2-H071/R1X

Cooling kW 2.8 3.6 4.5 5.6 7.1


Capacity 250m m
Heating kW 3.2 4 5 6.3 8

Power Supply V~,Hz,Ph 220~240,50(60),1 220~240,50(60),1 220~240,50(60),1 220~240,50(60),1 220~240,50(60),1


Electric Data
Rated Power W 60 62 68 85 94

Air Flow Volume(Hi/Mid/Low) m3/h 550 620 780 900 1165


Performance
Noise Level(Hi/Mid/Low) dB(A) 36/32/29 36/32/29 39/35/30 39/35/30 43/39/36

Indoor Units-Cassette Semes


Indoor Units-Cassette Semes

Net(Body) mm 840×520×315 840×520×315 960×520×315 960×520×315 1200×520×315

Packing(Body) mm 1145×685×395 1145×685×395 1265×685×395 1265×685×395 1505×685×395


Dimension(WxDxH)

Fresh Air Intake Quiet Operation


Net(Panel) mm 1083×630×33 1083×630×33 1203×630×33 1203×630×33 1443×630×33

Packing(Panel) mm 1100×665×175 1100×665×175 1220×665×175 1220×665×175 1460×665×175

Net/Gross(Body) kg 31/38 31/38 36/43 36/43 39/46


Weight
Net/Gross(Panel) kg 4.5/6.5 4.5/6.5 5/7 5/7 7.5/11.5 Fresh air makes indoor air healthy and comfortable. Innovative 3D spiral wind leaf increases air volume and
Refrigerant Type R410a R410a R410a R410a R410a makes the air supply more quietly and smoothly.
Liquid Side mm(inch) 6.35(1/4) 6.35(1/4) 6.35(1/4) 6.35(1/4) 9.52(3/8)

Pipe Diameter Gas Side mm(inch) 12.7(1/2) 12.7(1/2) 12.7(1/2) 12.7(1/2) 15.88(5/8)

Drainage mm(inch) R3/4in(DN20) R3/4in(DN20) R3/4in(DN20) R3/4in(DN20) R3/4in(DN20)

Stuffing Quantity 20/40/40H unit 88/186/210 88/186/210 88/186/210 60/120/123 60/120/123

Digital Tube Display


Notes:
1.Cooling Capacity: Indoor temperature 27℃ DB/19℃ WB;Outdoor temperature:35℃ DB/24℃ WB.
Digital tube displays all contents: indoor temperature,
2.Heating Capacity:Indoor temperature 20℃ DB;Outdoor temperature:7℃ DB/6℃ WB. setting temperature, operation mode, etc.
3.Piping Length:Equivalent piping length:7.5m,level differernce:0m. Clearly to check the running status, more convenient for
4.Sound level is measured at 1.4m below the unit.
5.The above designs and specifications are subject to change without prior notice. Final specifications please refer to technical specification provided by sales representative.
trouble shooting.

45 46
Compact&Four-Way Cassette Four-Way Cassette

Specification-DC Inverter 50Hz&60Hz Specification-50Hz


Model Indoor ARVCA-H028/R1X ARVCA-H036/R1X ARVCA-H045/R1X ARVCA-H056/R1X ARVCA-H071/R1X ARVCA-H080/R1X Model Indoor ARVCA-H028/4R1A ARVCA-H036/4R1A ARVCA-H045/4R1A ARVCA-H056/4R1A ARVCA-H071/4R1B ARVCA-H080/4R1B

Cooling kW 2.8 3.6 4.5 5.6 7.1 8.0 Cooling kW 2.8 3.6 4.5 5.6 7.1 8.0
Capacity Capacity
Heating kW 3.0 4.3 5.0 6.3 8.0 10.0 Heating kW 3.0 4.3 5.0 6.3 8.0 10.0

Power Supply V~,Hz,Ph 220~240,50(60),1 220~240,50(60),1 220~240,50(60),1 220~240,50(60),1 220~240,50(60),1 220~240,50(60),1 Power Supply V~,Hz,Ph 220~240,50,1 220~240,50,1 220~240,50,1 220~240,50,1 220~240,50,1 220~240,50,1
Electric Data Electric Data
Rated Power W 45 45 50 50 60 60 Rated Power W 70 70 80 80 100 100

Air Flow Volume(Hi/Mid/Low) m3/h 620/496/434 620/496/434 850/680/595 850/680/595 1250/1040/910 1250/1040/910 Air Flow Volume(Hi/Mid/Low) m3/h 620/496/434 620/496/434 850/680/595 850/680/595 1250/1040/910 1250/1040/910
Performance Performance
Noise Level(Hi/Mid/Low) dB(A) 38/35/32 38/35/32 39/36/33 39/36/33 38/34/30 38/34/30 Noise Level(Hi/Mid/Low) dB(A) 38/35/32 38/35/32 39/36/33 39/36/33 38/34/30 38/34/30

Net(Body) mm 570×570×260 570×570×260 570×570×260 570×570×260 835×835×250 835×835×250 Net(Body) mm 615×615×263 615×615×263 615×615×263 615×615×263 835×835×250 835×835×250

Dimension Packing(Body) mm 670×670×290 670×670×290 670×670×290 670×670×290 910×910×310 910×910×310 Dimension Packing(Body) mm 700×700×330 700×700×330 700×700×330 700×700×330 910×910×310 910×910×310
(WxDxH) Net(Panel) mm 650×650×55 650×650×55 650×650×55 650×650×55 950×950×55 950×950×55 (WxDxH) Net(Panel) mm 650×650×55 650×650×55 650×650×55 650×650×55 950×950×55 950×950×55

Packing(Panel) mm 710×710×80 710×710×80 710×710×80 710×710×80 1000×1000×100 1000×1000×100 Packing(Panel) mm 710×710×80 710×710×80 710×710×80 710×710×80 1000×1000×100 1000×1000×100

Net/Gross(Body) kg 20/25 20/25 20/25 20/25 27/34 27/34 Net/Gross(Body) kg 20/25 20/25 20/25 20/25 27/34 27/34
Weight Weight
Net/Gross(Panel) kg 3/5 3/5 3/5 3/5 5/7 5/7 Net/Gross(Panel) kg 3/5 3/5 3/5 3/5 5/7 5/7

Refrigerant Type R410a R410a R410a R410a R410a R410a Refrigerant Type R410a R410a R410a R410a R410a R410a

Liquid Side mm(inch) 6.35(1/4) 6.35(1/4) 6.35(1/4) 6.35(1/4) 9.52(3/8) 9.52(3/8) Liquid Side mm(inch) 6.35(1/4) 6.35(1/4) 6.35(1/4) 6.35(1/4) 9.52(3/8) 9.52(3/8)

Pipe Diameter Gas Side mm(inch) 12.7(1/2) 12.7(1/2) 12.7(1/2) 12.7(1/2) 15.88(5/8) 15.88(5/8) Pipe Diameter Gas Side mm(inch) 12.7(1/2) 12.7(1/2) 12.7(1/2) 12.7(1/2) 15.88(5/8) 15.88(5/8)

Drainage mm(inch) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4) Drainage mm(inch) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4)

Stuffing Quantity 20/40/40H unit 140/312/354 140/312/354 140/312/354 140/312/354 78/168/184 78/168/184 Stuffing Quantity 20/40/40H unit 140/312/354 140/312/354 140/312/354 140/312/354 78/168/184 78/168/184

Specification-DC Inverter 50Hz&60Hz Specification-50Hz

Indoor Units-Cassette Semes


Indoor Units-Cassette Semes

Packing(Body) Outdoor ARVCA-H090/4R1B ARVCA-H100/4R1B ARVCA-H112/4R1B ARVCA-H125/4R1B ARVCA-H140/4R1B


Packing(Body) Outdoor ARVCA-H090/R1X ARVCA-H100/R1X ARVCA-H112/R1X ARVCA-H125/R1X ARVCA-H140/R1X
Cooling kW 9.0 10.0 11.2 12.5 14.0
Cooling kW 9.0 10.0 11.2 12.5 14.0 Capacity
Capacity Heating kW 11.0 12.0 12.8 13.3 15.0
Heating kW 11.0 12.0 12.8 13.3 15.0
Power Supply V~,Hz,Ph 220~240,50,1 220~240,50,1 220~240,50,1 220~240,50,1 220~240,50,1
Power Supply V~,Hz,Ph 220~240,50(60),1 220~240,50(60),1 220~240,50(60),1 220~240,50(60),1 220~240,50(60),1 Electric Data
Electric Data Rated Power W 176 176 200 200 200
Rated Power W 90 90 150 150 150
Air Flow Volume(Hi/Mid/Low) m3/h 1500/1200/1050 1500/1200/1050 1800/1440/1260 1800/1440/1260 1800/1440/1260
Air Flow Volume(Hi/Mid/Low) m3/h 1500/1200/1050 1500/1200/1050 1800/1440/1260 1800/1440/1260 1800/1440/1260 Performance
Performance Noise Level(Hi/Mid/Low) dB(A) 41/37/34 41/37/34 41/38/35 41/38/35 41/38/35
Noise Level(Hi/Mid/Low) dB(A) 41/37/34 41/37/34 41/38/35 41/38/35 41/38/35
Net(Body) mm 835×835×250 835×835×250 835×835×290 835×835×290 835×835×290
Net(Body) mm 835×835×250 835×835×250 835×835×290 835×835×290 835×835×290
Dimension Packing(Body) mm 910×910×310 910×910×310 910×910×350 910×910×350 910×910×350
Dimension Packing(Body) mm 910×910×310 910×910×310 910×910×350 910×910×350 910×910×350
(WxDxH) Net(Panel) mm 950×950×55 950×950×55 950×950×55 950×950×55 950×950×55
(WxDxH) Net(Panel) mm 950×950×55 950×950×55 950×950×55 950×950×55 950×950×55
Packing(Panel) mm 1000×1000×100 1000×1000×100 1000×1000×100 1000×1000×100 1000×1000×100
Packing(Panel) mm 1000×1000×100 1000×1000×100 1000×1000×100 1000×1000×100 1000×1000×100
Net(Body) kg 28/35 28/35 30/37 30/37 30/37
Net(Body) kg 28/35 28/35 30/37 30/37 30/37 Weight
Weight Gross(Body) kg 5/7 5/7 5/7 5/7 5/7
Gross(Body) kg 5/7 5/7 5/7 5/7 5/7
Refrigerant Type R410a R410a R410a R410a R410a
Refrigerant Type R410a R410a R410a R410a R410a
Liquid Side mm(inch) 9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8)
Liquid Side mm(inch) 9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8)
Pipe Diameter Gas Side mm(inch) 15.88(5/8) 15.88(5/8) 15.88(5/8) 15.88(5/8) 15.88(5/8)
Pipe Diameter Gas Side mm(inch) 15.88(5/8) 15.88(5/8) 15.88(5/8) 15.88(5/8) 15.88(5/8)
Drainage mm DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4)
Drainage mm DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4)
Stuffing Quantity 20/40/40H unit 78/168/184 78/168/184 68/150/170 68/150/170 68/150/170
Stuffing Quantity 20/40/40H unit 78/168/184 78/168/184 68/150/170 68/150/170 68/150/170

Notes: Notes:
1.Cooling Capacity: Indoor temperature 27℃ DB/19℃ WB;Outdoor temperature:35℃ DB/24℃ WB. 1.Cooling Capacity: Indoor temperature 27℃ DB/19℃ WB;Outdoor temperature:35℃ DB/24℃ WB.
2.Heating Capacity:Indoor temperature 20℃ DB;Outdoor temperature:7℃ DB/6℃ WB. 2.Heating Capacity:Indoor temperature 20℃ DB;Outdoor temperature:7℃ DB/6℃ WB.
3.Piping Length:Equivalent piping length:7.5m,level differernce:0m. 3.Piping Length:Equivalent piping length:7.5m,level differernce:0m.
4.Sound level is measured at 1.4m below the unit. 4.Sound level is measured at 1.4m below the unit.
5.The above designs and specifications are subject to change without prior notice. Final specifications please refer to technical specification provided by sales representative. 5.The above designs and specifications are subject to change without prior notice. Final specifications please refer to technical specification provided by sales representative.

47 48
Duct Series
Four-Way Cassette

Specification-60Hz
Model Indoor ARVCA-H028/2R1 ARVCA-H036/2R1 ARVCA-H045/2R1 ARVCA-H056/2R1 ARVCA-H071/2R1A ARVCA-H080/2R1A
Slim Duct
Cooling kW 2.8 3.6 4.5 5.6 7.1 8.0
Capacity
Heating kW 3.0 4.3 5.0 6.3 8.0 10.0

Power Supply V~,Hz,Ph 220~240,60,1 220~240,60,1 220~240,60,1 220~240,60,1 220~240,60,1 220~240,60,1


Electric Data
Rated Power W 84 84 96 96 95 95

Air Flow Volume(Hi/Mid/Low) m3/h 620/496/434 620/496/434 850/680/595 850/680/595 1250/1040/910 1250/1040/910
Performance
Noise Level(Hi/Mid/Low) dB(A) 38/35/32 38/35/32 39/36/33 39/36/33 38/34/30 38/34/30

Net(Body) mm 615×615×263 615×615×263 615×615×263 615×615×263 835×835×250 835×835×250

Dimension Packing(Body) mm 700×700×330 700×700×330 700×700×330 700×700×330 910×910×310 910×910×310


(WxDxH) Net(Panel) mm 650×650×55 650×650×55 650×650×55 650×650×55 950×950×55 950×950×55

Packing(Panel) mm 710×710×80 710×710×80 710×710×80 710×710×80 1000×1000×100 1000×1000×100


Mid ESP Duct
Net/Gross(Body) kg 20/25 20/25 20/25 20/25 27/34 27/34
Weight
Net/Gross(Panel) kg 3/5 3/5 3/5 3/5 5/7 5/7

Refrigerant Type 6.35(1/4) 6.35(1/4) 6.35(1/4) 6.35(1/4) 9.52(3/8) 9.52(3/8)

Liquid Side mm(inch) 12.7(1/2) 12.7(1/2) 12.7(1/2) 12.7(1/2) 15.88(5/8) 15.88(5/8)

Pipe Diameter Gas Side mm(inch) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4)

Drainage mm(inch) 140/312/354 140/312/354 140/312/354 140/312/354 78/168/184 78/168/184

Stuffing Quantity 20/40/40H unit 140/312/354 140/312/354 140/312/354 140/312/354 78/168/184 78/168/184

High ESP Duct


Specification-60Hz

Indoor Units-Duct Semes


Indoor Units-Cassette Semes

Packing(Body) Outdoor ARVCA-H090/2R1A ARVCA-H100/2R1A ARVCA-H112/2R1A ARVCA-H125/2R1A ARVCA-H140/2R1A

Cooling kW 9.0 10.0 11.2 12.5 14.0


Capacity
Heating kW 11.0 12.0 12.8 13.3 15.0

Power Supply V~,Hz,Ph 220~240,60,1 220~240,60,1 220~240,60,1 220~240,60,1 220~240,60,1


Electric Data
Rated Power W 122 122 165 165 165

Air Flow Volume(Hi/Mid/Low) m3/h 1500/1200/1050 1500/1200/1050 1800/1440/1260 1800/1440/1260 1800/1440/1260


Performance
Noise Level(Hi/Mid/Low) dB(A) 41/37/34 41/37/34 41/38/35 41/38/35 41/38/35

Net(Body) mm 835×835×250 835×835×250 835×835×290 835×835×290 835×835×290 Fresh Air Processor


Dimension Packing(Body) mm 910×910×310 910×910×310 910×910×350 910×910×350 910×910×350
(WxDxH) Net(Panel) mm 950×950×55 950×950×55 950×950×55 950×950×55 950×950×55

Packing(Panel) mm 1000×1000×100 1000×1000×100 1000×1000×100 1000×1000×100 1000×1000×100

Net(Body) kg 28/35 28/35 30/37 30/37 30/37


Weight
Gross(Body) kg 5/7 5/7 5/7 5/7 5/7

Refrigerant Type 9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8)

Liquid Side mm(inch) 15.88(5/8) 15.88(5/8) 19.05(3/4) 19.05(3/4) 19.05(3/4)

Pipe Diameter Gas Side mm(inch) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4)

Drainage mm 78/168/184 78/168/184 68/150/170 68/150/170 68/150/170

Stuffing Quantity 20/40/40H unit 78/168/184 78/168/184 68/150/170 68/150/170 68/150/170 Wired Control Intelligent Defrosting Sleep Mode Fast Cooling/Heating 3D Air Flow

Notes:
1.Cooling Capacity: Indoor temperature 27℃ DB/19℃ WB;Outdoor temperature:35℃ DB/24℃ WB.
2.Heating Capacity:Indoor temperature 20℃ DB;Outdoor temperature:7℃ DB/6℃ WB.
3.Piping Length:Equivalent piping length:7.5m,level differernce:0m.
4.Sound level is measured at 1.4m below the unit.
5.The above designs and specifications are subject to change without prior notice. Final specifications please refer to technical specification provided by sales representative. Fresh Air Intake Remote Control Central Control

49 50
Slim Duct
Slim Duct
2 Ways Draining Connection Built-in Water Pump
There two outlet in left and right, both left and right side The built-in pump can lift condensing water up to 700mm
of unit are possible for drainage hose connection, easy for high from the drainage pan.
installation.

Specification-DC Inverter 50Hz&60Hz


derric k Model Indoor ARVSD-H022/R1X ARVSD-H028/R1X ARVSD-H036/R1X ARVSD-H045/R1X ARVSD-H056/R1X ARVSD-H071/R1X

Cooling kW 2.2 2.8 3.6 4.5 5.6 7.1


700mm Capacity
Heating kW 2.5 3.0 4.3 5.0 6.0 8.0
The righ t outle t
The left outle t
Power Supply V~,Hz,Ph 220~240,50(60),1 220~240,50(60),1 220~240,50(60),1 220~240,50(60),1 220~240,50(60),1 220~240,50(60),1
Electric Data
The ceilin g Rated Power W 55 55 60 91 91 110
Air Flow Volume(Hi/Mid/Low) m3/h 480/390/320 480/390/320 560/430/390 850/680/575 850/680/575 1000/810/685
Performance Noise Level(Hi/Mid/Low) dB(A) 30/26/23 30/26/23 32/28/25 38/35/32 38/35/32 39/36/32
External Static Pressure(ESP) Pa 10/30 10/30 10/30 10/30 10/30 10/30

Digital Tube Display (Optional)


Net mm 840×460×185 840×460×185 840×460×185 1160×460×185 1160×460×185 1160×460×185

Ultra Slim Design


Dimension
(WxDxH) Packing mm 1030×545×250 1030×545×250 1030×545×250 1350×545×250 1350×545×250 1350×545×250
Weight Net/Gross kg 15.5/19 15.5/19 16.5/20 20/24 20/24 22/26

The thickness is only 185mm, save installation space. Digital tube displays all contents: indoor temperature, Liquid Side mm(inch) 6.35(1/4) 6.35(1/4) 6.35(1/4) 6.35(1/4) 6.35(1/4) 9.52(3/8)
Pipe Diameter Gas Side mm(inch) 9.52(3/8) 9.52(3/8) 12.7(1/2) 12.7(1/2) 12.7(1/2) 15.88(5/8)
setting temperature, operation mode, etc.
Drainage mm(inch) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4)
Clearly to check the running status, more convenient for Stuffing Quantity 20/40/40H unit 198/414/460 198/414/460 198/414/460 153/306/340 153/306/340 153/306/340
trouble shooting.

18 5 m m
Specification-50Hz
Model Indoor ARVSD-H022/4R1A ARVSD-H028/4R1A ARVSD-H036/4R1A ARVSD-H045/4R1A ARVSD-H056/4R1A ARVSD-H071/4R1A

Cooling kW 2.2 2.8 3.6 4.5 5.6 7.1


Capacity
Heating kW 2.5 3.0 4.3 5.0 6.0 8.0
Power Supply V~,Hz,Ph 220~240,50,1 220~240,50,1 220~240,50,1 220~240,50,1 220~240,50,1 220~240,50,1
Electric Data
Rated Power W 59 59 65 91 91 113

Flexible Air Intake Options Performance


Air Flow Volume(Hi/Mid/Low)
Noise Level(Hi/Mid/Low)
m3/h
dB(A)
480/390/320
30/26/23
480/390/320
30/26/23
560/430/390
32/28/25
850/680/575
38/35/32
850/680/575
38/35/32
1000/810/685
39/36/32
External Static Pressure(ESP) Pa 10/30 10/30 10/30 10/30 10/30 10/30
Air intake from rear as standard, from bottom is optional. Dimension Net mm 840×460×185 840×460×185 840×460×185 1160×460×185 1160×460×185 1160×460×185
The size of the plate from bottom is the same as the flange from back, which makes it convenient to change installation style due to

Indoor Units-Duct Semes


Indoor Units-Duct Semes

(WxDxH) Packing mm 1030×545×250 1030×545×250 1030×545×250 1350×545×250 1350×545×250 1350×545×250


different decoration requirements. Weight Net/Gross kg 15.5/19 15.5/19 16.5/20 20/24 20/24 22/26
Liquid Side mm(inch) 6.35(1/4) 6.35(1/4) 6.35(1/4) 6.35(1/4) 6.35(1/4) 9.52(3/8)
Pipe Diameter Gas Side mm(inch) 9.52(3/8) 9.52(3/8) 12.7(1/2) 12.7(1/2) 12.7(1/2) 15.88(5/8)
Drainage mm(inch) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4)
Ai r intak e from below Ai r intak e from rea r Stuffing Quantity 20/40/40H unit 198/414/460 198/414/460 198/414/460 153/306/340 153/306/340 153/306/340

Specification-60Hz
Model Indoor ARVSD-H022/2R1 ARVSD-H028/2R1 ARVSD-H036/2R1 ARVSD-H045/2R1 ARVSD-H056/2R1 ARVSD-H071/2R1

Cooling kW 2.2 2.8 3.6 4.5 5.6 7.1


Capacity
Heating kW 2.5 3.0 4.3 5.0 6.0 8.0
Power Supply V~,Hz,Ph 220~240,60,1 220~240,60,1 220~240,60,1 220~240,60,1 220~240,60,1 220~240,60,1
Electric Data
Rated Power W 59 59 65 97 97 113

Silence Operation Performance


Air Flow Volume(Hi/Mid/Low)
Noise Level(Hi/Mid/Low)
m3/h
dB(A)
480/390/320
30/26/23
480/390/320
30/26/23
560/430/390
32/28/25
850/680/575
38/35/32
850/680/575
38/35/32
1000/810/685
39/36/32
External Static Pressure(ESP) Pa 10/30 10/30 10/30 10/30 10/30 10/30
Innovative centrifugal fan for large diameter and a new design of the spiral duct system equipped with high-quality motor at the same time,
Dimension Net mm 840×460×185 840×460×185 840×460×185 1160×460×185 1160×460×185 1160×460×185
making the air supply more quiet and smooth. The lowest noise is 18 db(A). (WxDxH) Packing mm 1030×545×250 1030×545×250 1030×545×250 1350×545×250 1350×545×250 1350×545×250
The lowest operation noise is 18 db(A),the industry’s most advanced mute value. Weight Net/Gross kg 15.5/19 15.5/19 16.5/20 20/24 20/24 22/26
Liquid Side mm(inch) 6.35(1/4) 6.35(1/4) 6.35(1/4) 6.35(1/4) 6.35(1/4) 9.52(3/8)
Pipe Diameter Gas Side mm(inch) 9.52(3/8) 9.52(3/8) 12.7(1/2) 12.7(1/2) 12.7(1/2) 15.88(5/8)
Drainage mm(inch) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4)

16db(A) 18 db(A) 30db(A) 40db(A) Stuffing Quantity 20/40/40H unit 198/414/460 198/414/460 198/414/460 153/306/340 153/306/340 153/306/340

Notes:
1.Cooling Capacity: Indoor temperature 27℃ DB/19℃ WB;Outdoor temperature:35℃ DB/24℃ WB.
2.Heating Capacity:Indoor temperature 20℃ DB;Outdoor temperature:7℃ DB/6℃ WB.
3.Piping Length:Equivalent piping length:7.5m,level differernce:0m.
Leaves rustling sound Quiet bedroom Quiet library 4.Sound level is measured at 1.4m below the unit.
5.The above designs and specifications are subject to change without prior notice. Final specifications please refer to technical specification provided by sales representative.

51 52
Mid ESP Duct
Mid ESP Duct
Flexible Air Intake Options
Air intake from rear as standard, from bottom is
optional.
The size of the plate from bottom is the same as the
flange from back, which makes it convenient to change
Specification-DC Inverter 50Hz&60Hz
installation style according to different decoration Model Indoor ARVMD-H045/R1X ARVMD-H056/R1X ARVMD-H071/R1X ARVMD-H080/R1X ARVMD-H090/R1X

requirements. Capacity
Cooling kW 4.5 5.6 7.1 8.0 9.0
Heating kW 5.0 6.0 8.0 10.0 11.0

Power Supply V~,Hz,Ph 220~240,50(60),1 220~240,50(60),1 220~240,50(60),1 220~240,50(60),1 220~240,50(60),1


Electric Data
Rated Power W 150 150 190 200 200

Air Flow Volume(Hi/Mid/Low) m3/h 950/760/665 950/760/665 1200/960/840 1500/1200/1050 1500/1200/1050


Performance Noise Level(Hi/Mid/Low) dB(A) 42/39/37 42/39/37 45/42/39 48/45/42 48/45/42
External Static Pressure(ESP) Pa 50/80 50/80 50/80 50/80 50/80

Dimension Net mm 890×785×290 890×785×290 890×785×290 890×785×290 890×785×290

Built In With Water Pump


(WxDxH) Packing mm 1100×880×360 1100×880×360 1100×880×360 1100×880×360 1100×880×360

1200mm Weight Net/Gross kg 35/41 35/41 37/43 37/43 37/43

(Optional)
Liquid Side mm(inch) 6.35(1/4) 6.35(1/4) 9.52(3/8) 9.52(3/8) 9.52(3/8)
Pipe Diameter Gas Side mm(inch) 12.7(1/2) 12.7(1/2) 15.88(5/8) 15.88(5/8) 15.88(5/8)
Drainage mm(inch) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4)

The built-in pump can lift condensing water up to Stuffing Quantity 20/40/40H unit 72/156/182 72/156/182 72/156/182 72/156/182 72/156/182

1200mm high from the drainage pan.


Specification-DC Inverter 50Hz&60Hz
Model Indoor ARVMD-H100/R1X ARVMD-H112/R1X ARVMD-H125/R1X ARVMD-H140/R1X ARVMD-H150/R1X

Cooling kW 10.0 11.2 12.5 14.0 15.0


Capacity
Heating kW 12.0 12.8 13.3 15.0 16.0

Power Supply V~,Hz,Ph 220~240,50(60),1 220~240,50(60),1 220~240,50(60),1 220~240,50(60),1 220~240,50(60),1

Optional ESP Ultra Slim Design Fresh Air Intake


Electric Data
Rated Power W 200 320 320 320 320

Air Flow Volume(Hi/Mid/Low) m3/h 1500/1200/1050 2000/1600/1400 2000/1600/1400 2000/1600/1400 2200/1760/1540


Performance Noise Level(Hi/Mid/Low) dB(A) 48/45/42 51/43/40 51/43/40 51/43/40 51/43/40

50Pa and 80Pa are both optional. Only 290mm in height, save Fresh air makes indoor air healthy External Static Pressure(ESP) Pa 50/80 50/80 50/80 50/80 50/80

installation space. and comfortable. Dimension Net mm 890×785×290 1250×785×290 1250×785×290 1250×785×290 1250×785×290
(WxDxH) Packing mm 1100×880×360 1460×880×360 1460×880×360 1460×880×360 1460×880×360

Indoor Units-Duct Semes


Indoor Units-Duct Semes

Weight Net/Gross kg 37/43 53/60 53/60 53/60 53/60

Liquid Side mm(inch) 9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8)

ceiling The Indoor Unit Pipe Diameter Gas Side mm(inch) 15.88(5/8) 15.88(5/8) 15.88(5/8) 15.88(5/8) 15.88(5/8)

50pa air outlet indoor unit Drainage mm(inch) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4)

suspended ceiling Stuffing Quantity 20/40/40H unit 72/156/182 60/126/147 60/126/147 60/126/147 60/126/147
return air inlet

80pa air outlet duct indoor unit


ceiling Intake Of
Fresh Air Specification-50Hz
Model Indoor ARVMD-H045/4R1A ARVMD-H056/4R1A ARVMD-H071/4R1A ARVMD-H080/4R1A ARVMD-H090/4R1A
suspended ceiling
return air inlet Outlet
Reversing I ntake Cooling kW 4.5 5.6 7.1 8.0 9.0
Capacity
Heating kW 5.0 6.0 8.0 10.0 11.0

Power Supply V~,Hz,Ph 220~240,50,1 220~240,50,1 220~240,50,1 220~240,50,1 220~240,50,1


Electric Data
Rated Power W 150 150 220 250 250

Air Flow Volume(Hi/Mid/Low) m3/h 950/760/665 950/760/665 1200/960/840 1500/1200/1050 1500/1200/1050


Performance Noise Level(Hi/Mid/Low) dB(A) 42/39/37 42/39/37 45/42/39 48/45/42 48/45/42
External Static Pressure(ESP) Pa 50/80 50/80 50/80 50/80 50/80

Applicable to A Variety Of Dimension


(WxDxH)
Net
Packing
mm
mm
890×785×290
1100×880×360
890×785×290
1100×880×360
890×785×290
1100×880×360
890×785×290
1100×880×360
890×785×290
1100×880×360

Room Types Weight Net/Gross

Liquid Side
kg

mm(inch)
35/41

6.35(1/4)
35/41

6.35(1/4)
37/43

9.52(3/8)
37/43

9.52(3/8)
37/43

9.52(3/8)

Specific ESP design can be applied to various room types Pipe Diameter Gas Side mm(inch) 12.7(1/2) 12.7(1/2) 15.88(5/8) 15.88(5/8) 15.88(5/8)
Drainage mm(inch) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4)
easily, like rooms of L type or U type; the air outlet can
Stuffing Quantity 20/40/40H unit 72/156/182 72/156/182 72/156/182 72/156/182 72/156/182
be set separately from the indoor unit, so the air flow
can be equally distributed even the room is in irregular Notes:
structure. Room1: L Type Room2: U Type Room3: Narrow Type 1.Cooling Capacity: Indoor temperature 27℃ DB/19℃ WB;Outdoor temperature:35℃ DB/24℃ WB.
2.Heating Capacity:Indoor temperature 20℃ DB;Outdoor temperature:7℃ DB/6℃ WB.
3.Piping Length:Equivalent piping length:7.5m,level differernce:0m.
4.Sound level is measured at 1.4m below the unit.
5.The above designs and specifications are subject to change without prior notice. Final specifications please refer to technical specification provided by sales representative.

53 54
High ESP Duct Type
Mid ESP Duct
Long Distance Air Supply Fresh Air Intake
High ESP makes the air supply distance up to 50m. Fresh air makes indoor air healthy and comfortable.

Specification-50Hz The Indoor Unit

Model Indoor ARVMD-H100/4R1A ARVMD-H112/4R1A ARVMD-H125/4R1A ARVMD-H140/4R1A ARVMD-H150/4R1A

Cooling kW 10.0 11.2 12.5 14.0 15.0


Capacity
Heating kW 12.0 12.8 13.3 15.0 16.0

Power Supply V~,Hz,Ph 220~240,50,1 220~240,50,1 220~240,50,1 220~240,50,1 220~240,50,1


Electric Data Intake Of
Rated Power W 250 320 320 320 320 Fresh Air
3
Air Flow Volume(Hi/Mid/Low) m /h 1500/1200/1050 2000/1600/1400 2000/1600/1400 2000/1600/1400 2200/1760/1540
Performance Noise Level(Hi/Mid/Low) dB(A) 48/45/42 51/43/40 51/43/40 51/43/40 51/43/40
External Static Pressure(ESP) Pa 50/80 50/80 50/80 50/80 50/80 Outlet
Reversing I ntake
Dimension Net mm 890×785×290 1250×785×290 1250×785×290 1250×785×290 1250×785×290
(WxDxH) Packing mm 1100×880×360 1460×880×360 1460×880×360 1460×880×360 1460×880×360

Weight Net/Gross kg 37/43 53/60 53/60 53/60 53/60

Liquid Side mm(inch) 9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8)


Pipe Diameter Gas Side
Drainage
mm(inch)
mm(inch)
15.88(5/8)
DN20(R3/4)
15.88(5/8)
DN20(R3/4)
15.88(5/8)
DN20(R3/4)
15.88(5/8)
DN20(R3/4)
15.88(5/8)
DN20(R3/4)
Applicable to A Variety Of
Stuffing Quantity 20/40/40H unit 72/156/182 60/126/147 60/126/147 60/126/147 60/126/147
Room Types
Specification-60Hz Specific ESP design can be applied to various room types
Model Indoor ARVMD-H045/2R1 ARVMD-H056/2R1 ARVMD-H071/2R1 ARVMD-H080/2R1 ARVMD-H090/2R1
easily, like rooms of L type or U type; the air outlet can be
Capacity
Cooling kW 4.5 5.6 7.1 8.0 9.0 set separately from the indoor unit, so the air flow can be
Heating kW 5.0 6.0 8.0 10.0 11.0 equally distributed even the room is in irregular structure.
Electric Data
Power Supply V~,Hz,Ph 220~240,60,1 220~240,60,1 220~240,60,1 220~240,60,1 220~240,60,1 Room1: L Type Room2: U Type Room3: Narrow Type
Rated Power W 180 180 264 300 300

Air Flow Volume(Hi/Mid/Low) m3/h 950/760/665 950/760/665 1200/960/840 1500/1200/1050 1500/1200/1050


Performance Noise Level(Hi/Mid/Low) dB(A) 42/39/37 42/39/37 45/42/39 48/45/42 48/45/42
External Static Pressure(ESP) Pa 50/80 50/80 50/80 50/80 50/80

Dimension Net mm 890×785×290 890×785×290 890×785×290 890×785×290 890×785×290


(WxDxH) Packing mm 1100×880×360 1100×880×360 1100×880×360 1100×880×360 1100×880×360

Indoor Units-Duct Semes


Indoor Units-Duct Semes

Weight Net/Gross

Liquid Side
kg

mm(inch)
35/41

6.35(1/4)
35/41

6.35(1/4)
37/43

9.52(3/8)
37/43

9.52(3/8)
37/43

9.52(3/8) Specification-DC Inverter 50Hz&60Hz


Pipe Diameter Gas Side mm(inch) 12.7(1/2) 12.7(1/2) 15.88(5/8) 15.88(5/8) 15.88(5/8)
Drainage mm(inch) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4) Model Indoor ARVHD-H112/R1X ARVHD-H125/R1X ARVHD-H140/R1X ARVHD-H150/R1X ARVHD-H220/R1X ARVHD-H280/R1X
Stuffing Quantity 20/40/40H unit 72/156/182 72/156/182 72/156/182 72/156/182 72/156/182
Cooling kW 11.2 12.5 14.0 15.0 22.4 28.0
Capacity

Specification-60Hz
Heating kW 12.8 13.3 15.0 16.0 25.0 31.5

Power Supply V~,Hz,Ph 220~240,50(60),1 220~240,50(60),1 220~240,50(60),1 220~240,50(60),1 220~240,50,1 220~240,50,1


Electric Data
Model Indoor ARVMD-H100/2R1 ARVMD-H112/2R1 ARVMD-H125/2R1 ARVMD-H140/2R1 ARVMD-H150/2R1 Rated Power W 600 600 600 600 1250 1250

Cooling kW 10.0 11.2 12.5 14.0 15.0 Air Flow Volume(Hi/Mid/Low) m3/h 2000/1600/1400 2000/1600/1400 2000/1600/1400 2000/1600/1400 4000/3200/2600 4000/3200/2600
Capacity
Heating kW 12.0 12.8 13.3 15.0 16.0 Performance Noise Level(Hi/Mid/Low) dB(A) 60/57/51 60/57/51 60/57/51 60/57/51 55 55
Power Supply V~,Hz,Ph 220~240,60,1 220~240,60,1 220~240,60,1 220~240,60,1 220~240,60,1
Electric Data External Static Pressure(ESP) Pa 196 196 196 196 220 220
Rated Power W 300 384 384 384 384
Dimension Net mm 1200×719×380 1200×719×380 1200×719×380 1200×719×380 1350×700×460 1350×700×460
Air Flow Volume(Hi/Mid/Low) m3/h 1500/1200/1050 2000/1600/1400 2000/1600/1400 2000/1600/1400 2200/1760/1540
(WxDxH) Packing mm 1235×760×415 1235×760×415 1235×760×415 1235×760×415 1540×810×610 1540×810×610
Performance Noise Level(Hi/Mid/Low) dB(A) 48/45/42 51/43/40 51/43/40 51/43/40 51/43/40
External Static Pressure(ESP) Pa 50/80 50/80 50/80 50/80 50/80 Weight Net/Gross kg 56/59 56/59 56/59 56/59 91/110 91/110

Net mm 890×785×290 1250×785×290 1250×785×290 1250×785×290 1250×785×290 Liquid Side mm(inch) 9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8) 12.7(1/2) 12.7(1/2)
Dimension
(WxDxH) Packing mm 1100×880×360 1460×880×360 1460×880×360 1460×880×360 1460×880×360 Pipe Diameter Gas Side mm(inch) 19.05(3/4) 19.05(3/4) 19.05(3/4) 19.05(3/4) 22.2(7/8) 22.2(7/8)
Weight Net/Gross kg 37/43 53/60 53/60 53/60 53/60 Drainage mm DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN25 DN25
Liquid Side mm(inch) 9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8)
Stuffing Quantity 20/40/40H unit 65/140/168 65/140/168 65/140/168 65/140/168 / /
Pipe Diameter Gas Side mm(inch) 15.88(5/8) 15.88(5/8) 15.88(5/8) 15.88(5/8) 15.88(5/8)
Drainage mm(inch) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4)

Stuffing Quantity 20/40/40H unit 72/156/182 60/126/147 60/126/147 60/126/147 60/126/147

Notes:
Notes:
1.Cooling Capacity: Indoor temperature 27℃ DB/19℃ WB;Outdoor temperature:35℃ DB/24℃ WB.
1.Cooling Capacity: Indoor temperature 27℃ DB/19℃ WB;Outdoor temperature:35℃ DB/24℃ WB.
2.Heating Capacity:Indoor temperature 20℃ DB;Outdoor temperature:7℃ DB/6℃ WB.
2.Heating Capacity:Indoor temperature 20℃ DB;Outdoor temperature:7℃ DB/6℃ WB.
3.Piping Length:Equivalent piping length:7.5m,level differernce:0m.
3.Piping Length:Equivalent piping length:7.5m,level differernce:0m.
4.Sound level is measured at 1.4m below the unit.
4.Sound level is measured at 1.4m below the unit.
5.The above designs and specifications are subject to change without prior notice. Final specifications please refer to technical specification provided by sales representative.
5.The above designs and specifications are subject to change without prior notice. Final specifications please refer to technical specification provided by sales representative.

55 56
Fresh Air Processor
High ESP Duct Innovative Air Supply
Technology For Excellent
Room Temperature Control
Specification-50Hz Fall all models, return air bellow and air filter are standard
configuration.
Model Indoor ARVHD-H112/4R1A ARVHD-H125/4R1A ARVHD-H140/4R1A ARVHD-H150/4R1A

Cooling kW 11.2 12.5 14.0 15.0


Capacity
Heating kW 12.8 13.3 15.0 16.0
Power Supply V~,Hz,Ph 220~240,50,1 220~240,50,1 220~240,50,1 220~240,50,1

Long Distance Air Supply Fresh Air Intake


Electric Data
Rated Power W 600 600 600 600
Air Flow Volume(Hi/Mid/Low) m3/h 2000/1600/1400 2000/1600/1400 2000/1600/1400 2000/1600/1400
Performance Noise Level(Hi/Mid/Low) dB(A) 60/57/51 60/57/51 60/57/51 60/57/51
External Static Pressure(ESP) Pa 196 196 196 196 High ESP makes the air supply distance up to 50m. Fresh air makes indoor air healthy and comfortable.
Dimension Net mm 1200×719×380 1200×719×380 1200×719×380 1200×719×380
(WxDxH) Packing mm 1235×760×415 1235×760×415 1235×760×415 1235×760×415
Weight Net/Gross kg 56/59 56/59 56/59 56/59
The Indoor Unit
Liquid Side mm(inch) 9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8)
Pipe Diameter Gas Side mm(inch) 19.05(3/4) 19.05(3/4) 19.05(3/4) 19.05(3/4)
Drainage mm DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4)
Stuffing Quantity 20/40/40H unit 65/140/168 65/140/168 65/140/168 65/140/168

Intake Of
Specification-50Hz Fresh Air

Model Indoor ARVHD-H220/4R1B ARVHD-H280/4R1B ARVHD-H450/5R1A ARVHD-H560/5R1A

Cooling kW 22.4 28.0 45.0 56.0 Outlet


Capacity Reversing I ntake
Heating kW 25.0 31.5 49.5 61.5
Power Supply V~,Hz,Ph 220~240,50,1 220~240,50,1 380~415,50,3 380~415,50,3
Electric Data
Rated Power W 1250 1250 2220 2220
Air Flow Volume(Hi/Mid/Low) m3/h 4000/3200/2600 4000/3200/2600 8000 8000
Performance Noise Level(Hi/Mid/Low) dB(A) 55 55 63 63

Applicable To A Variety Of
External Static Pressure(ESP) Pa 220 220 200 200

Dimension Net mm 1350×700×460 1350×700×460 2115×990×855 2115×990×855

Indoor Units-Duct Semes


Indoor Units-Duct Semes

Room Types
(WxDxH) Packing mm 1540×810×610 1540×810×610 2225×1025×1015 2225×1025×1015
Weight Net/Gross kg 91/110 91/110 225/260 225/260
Liquid Side mm(inch) 12.7(1/2) 12.7(1/2) 12.7(1/2)x2 12.7(1/2)x2
Pipe Diameter Gas Side mm(inch) 22.2(7/8) 22.2(7/8) 22.2(7/8)x2 22.2(7/8)x2
Specific ESP design can be applied to various room types easily, like rooms of L type or U type; the air outlet can be set separately from the
Drainage mm DN25 DN25 DN25 DN25
indoor unit, so the air flow can be equally distributed even the room is in irregular structure.
Stuffing Quantity 20/40/40H unit 30/63/84 30/63/84 10/22/22 10/22/22

Specification-60Hz
Model Indoor ARVHD-H112/2R1 ARVHD-H125/2R1 ARVHD-H140/2R1 ARVHD-H150/2R1

Cooling kW 11.2 12.5 14.0 15.0


Capacity
Heating kW 12.8 13.3 15.0 16.0
Power Supply V~,Hz,Ph 220~240,60,1 220~240,60,1 220~240,60,1 220~240,60,1
Electric Data
Rated Power W 720 720 720 720
Air Flow Volume(Hi/Mid/Low) m3/h 2000/1600/1400 2000/1600/1400 2000/1600/1400 2000/1600/1400
Performance Noise Level(Hi/Mid/Low) dB(A) 60/57/51 60/57/51 60/57/51 60/57/51
External Static Pressure(ESP) Pa 196 196 196 196
Dimension Net mm 1200×719×380 1200×719×380 1200×719×380 1200×719×380
(WxDxH) Packing mm 1235×760×415 1235×760×415 1235×760×415 1235×760×415
Weight Net/Gross kg 56/59 56/59 56/59 56/59
Liquid Side mm(inch) 9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8)
Pipe Diameter Gas Side mm(inch) 19.05(3/4) 19.05(3/4) 19.05(3/4) 19.05(3/4)
Drainage mm(inch) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4) Room1: L Type Room2: U Type Room3: Narrow Type
Stuffing Quantity 20/40/40H unit 65/140/168 65/140/168 65/140/168 65/140/168

Notes:
1.Cooling Capacity: Indoor temperature 27℃ DB/19℃ WB;Outdoor temperature:35℃ DB/24℃ WB.
2.Heating Capacity:Indoor temperature 20℃ DB;Outdoor temperature:7℃ DB/6℃ WB.
3.Piping Length:Equivalent piping length:7.5m,level differernce:0m.
4.Sound level is measured at 1.4m below the unit.
5.The above designs and specifications are subject to change without prior notice. Final specifications please refer to technical specification provided by sales representative.

57 58
Fresh Air Processor

Specification-DC Inverter 50Hz&60Hz


Model Indoor ARVFA-H220/R1X ARVFA-H280/R1X

Cooling kW 22.4 28.0


Capacity
Heating kW 18.0 22.0

Power Supply V~,Hz,Ph 220~240,50(60),1 220~240,50(60),1


Electric Data
Rated Power W 800 800

Air Flow Volume(Hi/Mid/Low) m3/h 3200 3200

Performance Noise Level(Hi/Mid/Low) dB(A) 55 55

External Static Pressure(ESP) Pa 220 220

Dimension Net mm 1350×700×460 1350×700×460


(WxDxH) Packing mm 1540×810×610 1540×810×610

Weight Net/Gross kg 91/110 91/110

Liquid Side mm(inch) 12.7(1/2) 12.7(1/2)

Pipe Diameter Gas Side mm(inch) 22.2(7/8) 22.2(7/8)

Drainage mm DN25 DN25

Stuffing Quantity 20/40/40H unit 30/63/84 30/63/84

Specification-50Hz
Model Indoor ARVFA-H220/4R1B ARVFA-H280/4R1B ARVFA-H450/5R1A ARVFA-H560/5R1A
Indoor Units-Duct Semes

Cooling kW 22.4 28.0 45.0 56.0


Capacity
Heating kW 18.0 22.0 49.5 61.5

Power Supply V~,Hz,Ph 220~240,50,1 220~240,50,1 380~415,50,3 380~415,50,3


Electric Data
Rated Power W 1000 1000 1520 1520

Air Flow Volume(Hi/Mid/Low) m3/h 3200 3200 4000 5000

Performance Noise Level(Hi/Mid/Low) dB(A) 55 55 57 59

External Static Pressure(ESP) Pa 220 220 220 220

Dimension Net mm 1350×700×460 1350×700×460 1820×990×855 2115×990×855


(WxDxH) Packing mm 1540×810×610 1540×810×610 1935×1025×1015 2225×1025×1015

Weight Net/Gross kg 91/110 91/110 150/170 225/255

Liquid Side mm(inch) 12.7(1/2) 12.7(1/2) 12.7(1/2)x2 12.7(1/2)x2

Pipe Diameter Gas Side mm(inch) 22.2(7/8) 22.2(7/8) 22.2(7/8)x2 22.2(7/8)x2

Drainage mm DN25 DN25 DN25 DN25

Stuffing Quantity 20/40/40H unit 30/63/84 30/63/84 10/22/22 10/22/22

Notes:
1.Cooling Capacity: Indoor temperature 27℃ DB/19℃ WB;Outdoor temperature:35℃ DB/24℃ WB.
2.Heating Capacity:Indoor temperature 20℃ DB;Outdoor temperature:7℃ DB/6℃ WB.
3.Piping Length:Equivalent piping length:7.5m,level differernce:0m.
4.Sound level is measured at 1.4m from the air outlet
5.The above designs and specifications are subject to change without prior notice. Final specifications please refer to technical specification provided by sales representative.
Auto Restart Function Sleep Mode Fast Cooling/Heating Long-term Filter Intelligent Defrosting 3D Air Flow Anti-Cold-Air

Connection Conditions:
The following restrictions must be observed in order to maintain the indoor units connected to the same system.
When outdoor-air processing units are connected,the total connection capacity must be within 50% to 100% of that of the outdoor units.
When outdoor-air processing units are standard indoor unigs are connected,the total connection capacity of the outdoor-processing units must not exceed 30% of that of the outdoor units. Remote Contorl Low Ambient Cooling Silent Wired Control Central Control Golden Fin WIFI Control
Outdoor-air processing units can be used without indoor units.

59 60
Ceiling & Floor
Ceiling & Floor

Specification-DC Inverter 50Hz&60Hz


Model Indoor ARVCF-H028/R1X ARVCF-H036/R1X ARVCF-H045/R1X ARVCF-H056/R1X ARVCF-H071/R1X ARVCF-H080/R1X

Cooling kW 2.8 3.6 4.5 5.6 7.1 8.0


Capacity
Heating kW 3.0 4.3 5.0 6.0 8.0 10.0

Power Supply V~,Hz,Ph 220~240,50(60),1 220~240,50(60),1 220~240,50(60),1 220~240,50(60),1 220~240,50(60),1 220~240,50(60),1


Electric Data
Rated Power W 60 60 60 60 125 125

Ultra Slim Design 4D Air Swing Performance


Air Flow Volume(Hi/Mid/Low)
Noise Level(Hi/Mid/Low)
m3/h
dB(A)
450/360/315
37/34/31
630/504/441
39/36/33
950/760/665
42/39/36
950/760/665
42/39/36
1300/1040/910
45/42/39
1500/1200/1050
47/44/41

Dimension Net mm 929×660×205 929×660×205 929×660×205 929×660×205 1280×660×205 1280×660×205


(WxDxH) Packing mm 1010×720×290 1010×720×290 1010×720×290 1010×720×290 1360×720×290 1360×720×290

Weight Net/Gross kg 26/29 26/29 26/29 26/29 35/39 35/39


The thickness is only 205mm, save installation space. Vertical and horizontal swing makes air below to every Liquid Side mm(inch) 6.35(1/4) 6.35(1/4) 6.35(1/4) 6.35(1/4) 9.52(3/8) 9.52(3/8)
corner of the room. Pipe Diameter Gas Side mm(inch) 12.7(1/2) 12.7(1/2) 12.7(1/2) 12.7(1/2) 15.88(5/8) 15.88(5/8)
Drainage mm(inch) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4)

Stuffing Quantity 20/40/40H unit 136/280/315 136/280/315 136/280/315 136/280/315 96/200/225 96/200/225

Specification-DC Inverter 50Hz&60Hz


205mm

Model Indoor ARVCF-H090/R1X ARVCF-H100/R1X ARVCF-H112/R1X ARVCF-H125/R1X ARVCF-H140/R1X

Cooling kW 9.0 10.0 11.2 12.5 14.0


Capacity
Heating kW 11.0 12.0 12.8 13.3 15.0

Power Supply V~,Hz,Ph 220~240,50(60),1 220~240,50(60),1 220~240,50(60),1 220~240,50(60),1 220~240,50(60),1


Electric Data
Rated Power W 125 160 160 160 160

Air Flow Volume(Hi/Mid/Low) m3/h 1500/1200/1050 1500/1200/1050 1800/1440/1260 1800/1440/1260 1800/1440/1260


Performance
Noise Level(Hi/Mid/Low) dB(A) 47/44/41 47/44/41 48/45/42 48/45/42 48/45/42

Dimension Net mm 1280×660×205 1280×660×205 1631×660×205 1631×660×205 1631×660×205

Indoor Units-Ceiling&Floor
Indoor Units-Ceiling&Floor

(WxDxH) Packing mm 1360×720×290 1360×720×290 1710×720×290 1710×720×290 1710×720×290

Weight Net/Gross kg 35/39 35/39 45/51 45/51 45/51

Liquid Side mm(inch) 9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8)

Flexible Installation Innovative Centrifugal Fan Pipe Diameter Gas Side


Drainage
mm(inch)
mm(inch)
15.88(5/8)
DN20(R3/4)
15.88(5/8)
DN20(R3/4)
15.88(5/8)
DN20(R3/4)
15.88(5/8)
DN20(R3/4)
15.88(5/8)
DN20(R3/4)

Stuffing Quantity 20/40/40H unit 96/200/225 96/200/225 80/168/189 80/168/189 80/168/189

Can be vertically installed against the wall or horizontally


installed under the ceiling.
All units are equipped with 3-speed fan mode, adjusting
the air flow rate in accordance with the ceiling height.
Specification-50Hz
Innovative centrifugal fan provides larger air volume Model Indoor ARVCF-H028/4R1A ARVCF-H036/4R1A ARVCF-H045/4R1A ARVCF-H056/4R1A ARVCF-H071/4R1A ARVCF-H080/4R1A

but lower noise, making the air supply more quiet and Cooling kW 2.8 3.6 4.5 5.6 7.1 8.0
Capacity
smooth. Heating kW 3.0 4.3 5.0 6.0 8.0 10.0

Power Supply V~,Hz,Ph 220~240,50,1 220~240,50,1 220~240,50,1 220~240,50,1 220~240,50,1 220~240,50,1


Electric Data
Rated Power W 80 80 80 80 140 140

Air Flow Volume(Hi/Mid/Low) m3/h 450/360/315 630/504/441 950/760/665 950/760/665 1300/1040/910 1500/1200/1050
Performance
Noise Level(Hi/Mid/Low) dB(A) 37/34/31 39/36/33 42/39/36 42/39/36 45/42/39 47/44/41

Dimension Net mm 929×660×205 929×660×205 929×660×205 929×660×205 1280×660×205 1280×660×205


(WxDxH) Packing mm 1010×720×290 1010×720×290 1010×720×290 1010×720×290 1360×720×290 1360×720×290

Weight Net/Gross kg 26/29 26/29 26/29 26/29 35/39 35/39

Liquid Side mm(inch) 6.35(1/4) 6.35(1/4) 6.35(1/4) 6.35(1/4) 9.52(3/8) 9.52(3/8)


Pipe Diameter Gas Side mm(inch) 12.7(1/2) 12.7(1/2) 12.7(1/2) 12.7(1/2) 15.88(5/8) 15.88(5/8)
Drainage mm(inch) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4)

Stuffing Quantity 20/40/40H unit 136/280/315 136/280/315 136/280/315 136/280/315 96/200/225 96/200/225

Notes:
1.Cooling Capacity: Indoor temperature 27℃ DB/19℃ WB;Outdoor temperature:35℃ DB/24℃ WB.
2.Heating Capacity:Indoor temperature 20℃ DB;Outdoor temperature:7℃ DB/6℃ WB.
3.Piping Length:Equivalent piping length:7.5m,level differernce:0m.
4.Sound level is measured at 1.4m below the unit.
5.The above designs and specifications are subject to change without prior notice. Final specifications please refer to technical specification provided by sales representative.

61 62
Ceiling & Floor

Specification-50Hz
Model Indoor ARVCF-H090/4R1A ARVCF-H100/4R1A ARVCF-H112/4R1A ARVCF-H125/4R1A ARVCF-H140/4R1A

Cooling kW 9.0 10.0 11.2 12.5 14.0


Capacity
Heating kW 11.0 12.0 12.8 13.3 15.0

Power Supply V~,Hz,Ph 220~240,50,1 220~240,50,1 220~240,50,1 220~240,50,1 220~240,50,1


Electric Data
Rated Power W 140 140 210 210 210

Air Flow Volume(Hi/Mid/Low) m3/h 1500/1200/1050 1500/1200/1050 1800/1440/1260 1800/1440/1260 1800/1440/1260


Performance
Noise Level(Hi/Mid/Low) dB(A) 47/44/41 47/44/41 48/45/42 48/45/42 48/45/42

Dimension Net mm 1280×660×205 1280×660×205 1631×660×205 1631×660×205 1631×660×205


(WxDxH) Packing mm 1360×720×290 1360×720×290 1710×720×290 1710×720×290 1710×720×290

Weight Net/Gross kg 35/39 35/39 45/51 45/51 45/51

Liquid Side mm(inch) 9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8)


Pipe Diameter Gas Side mm(inch) 15.88(5/8) 15.88(5/8) 15.88(5/8) 15.88(5/8) 15.88(5/8)
Drainage mm(inch) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4)

Stuffing Quantity 20/40/40H unit 96/200/225 96/200/225 80/168/189 80/168/189 80/168/189

Specification-60Hz
Model Indoor ARVCF-H028/2R1 ARVCF-H036/2R1 ARVCF-H045/2R1 ARVCF-H056/2R1 ARVCF-H071/2R1 ARVCF-H080/2R1

Cooling kW 2.8 3.6 4.5 5.6 7.1 8.0


Capacity
Heating kW 3.0 4.3 5.0 6.0 8.0 10.0

Power Supply V~,Hz,Ph 220~240,60,1 220~240,60,1 220~240,60,1 220~240,60,1 220~240,60,1 220~240,60,1


Electric Data
Rated Power W 96 96 96 96 168 168

Air Flow Volume(Hi/Mid/Low) m3/h 450/360/315 630/504/441 950/760/665 950/760/665 1300/1040/910 1500/1200/1050
Performance
Noise Level(Hi/Mid/Low) dB(A) 37/34/31 39/36/33 42/39/36 42/39/36 45/42/39 47/44/41

Dimension Net mm 929×660×205 929×660×205 929×660×205 929×660×205 1280×660×205 1280×660×205


Indoor Units-Ceiling&Floor

(WxDxH) Packing mm 1010×720×290 1010×720×290 1010×720×290 1010×720×290 1360×720×290 1360×720×290

Weight Net/Gross kg 26/29 26/29 26/29 26/29 35/39 35/39

Liquid Side mm(inch) 6.35(1/4) 6.35(1/4) 6.35(1/4) 6.35(1/4) 9.52(3/8) 9.52(3/8)


Pipe Diameter Gas Side mm(inch) 12.7(1/2) 12.7(1/2) 12.7(1/2) 12.7(1/2) 15.88(5/8) 15.88(5/8)
Drainage mm(inch) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4)

Stuffing Quantity 20/40/40H unit 136/280/315 136/280/315 136/280/315 136/280/315 96/200/225 96/200/225

Specification-60Hz
Model Indoor ARVCF-H090/2R1 ARVCF-H100/2R1 ARVCF-H112/2R1 ARVCF-H125/2R1 ARVCF-H140/2R1

Cooling kW 9.0 10.0 11.2 12.5 14.0


Capacity
Heating kW 11.0 12.0 12.8 13.3 15.0

Power Supply V~,Hz,Ph 220~240,60,1 220~240,60,1 220~240,60,1 220~240,60,1 220~240,60,1


Electric Data
Rated Power W 168 168 252 252 252

Air Flow Volume(Hi/Mid/Low) m3/h 1500/1200/1050 1500/1200/1050 1800/1440/1260 1800/1440/1260 1800/1440/1260


Performance
Noise Level(Hi/Mid/Low) dB(A) 47/44/41 47/44/41 48/45/42 48/45/42 48/45/42

Dimension Net mm 1280×660×205 1280×660×205 1631×660×205 1631×660×205 1631×660×205


(WxDxH) Packing mm 1360×720×290 1360×720×290 1710×720×290 1710×720×290 1710×720×290

Weight Net/Gross kg 35/39 35/39 45/51 45/51 45/51

Liquid Side mm(inch) 9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8)


Pipe Diameter Gas Side mm(inch) 15.88(5/8) 15.88(5/8) 15.88(5/8) 15.88(5/8) 15.88(5/8)
Drainage mm(inch) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4)
Remote Control Intelligent Defrosting Sleep Mode Fast Cooling/Heating Anti-Cold-Air
Stuffing Quantity 20/40/40H unit 96/200/225 96/200/225 80/168/189 80/168/189 80/168/189

Notes:
1.Cooling Capacity: Indoor temperature 27℃ DB/19℃ WB;Outdoor temperature:35℃ DB/24℃ WB.
2.Heating Capacity:Indoor temperature 20℃ DB;Outdoor temperature:7℃ DB/6℃ WB.
3.Piping Length:Equivalent piping length:7.5m,level differernce:0m.
4.Sound level is measured at 1.4m below the unit. Digital Tube Display Wired Control Central Control
5.The above designs and specifications are subject to change without prior notice. Final specifications please refer to technical specification provided by sales representative.

63 64
Wall-Mounted
Wall-Mounted
A Variety of Panels
A variety of panel can be chosen: LH, LI, LR,LK and so on.

Specification-DC Inverter 50Hz&60Hz


Model Indoor ARVWM-H022/R1X(L) ARVWM-H028/R1X(L) ARVWM-H036/R1X(L) ARVWM-H045/R1X(L) ARVWM-H056/R1X(L) ARVWM-H071/R1X(L)

Capacity Cooling kW 2.2 2.8 3.6 4.5 5.6 7.1


LH LI Heating kW 2.5 3.0 4.3 5.0 6.0 8.0
Power Supply V~,Hz,Ph 220~240,50(60),1 220~240,50(60),1 220~240,50(60),1 220~240,50(60),1 220~240,50(60),1 220~240,50(60),1
Electric Data
Rated Power W 20 20 20 45 45 60
Air Flow Volume(Hi/Mid/Low) m3/h 650/600/580 650/600/580 650/600/580 850/750/650 850/750/650 1200/950/800
Performance
Noise Level(Hi/Mid/Low) dB(A) 38/33/27 38/33/27 38/33/27 45/41/35 45/41/35 48/45/39
Dimension Net mm 850×300×198 850×300×198 850×300×198 970×315×235 970×315×235 1100×330×235
(WxDxH) Packing mm 885×360×270 885×360×270 885×360×270 1010×370×300 1010×370×300 1140×385×300

LR LK Weight Net/Gross kg 10/13 10/13 10/13 14/18 14/18 16/20


Liquid Side mm(inch) 6.35(1/4) 6.35(1/4) 6.35(1/4) 6.35(1/4) 6.35(1/4) 9.52(3/8)
Pipe Diameter Gas Side mm(inch) 9.52(3/8) 9.52(3/8) 9.52(3/8) 12.7(1/2) 12.7(1/2) 15.88(5/8)
Drainage mm(inch) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4)
Stuffing Quantity 20/40/40H unit 328/680/850 328/680/850 328/680/850 238/490/560 238/490/560 210/434/496

Wired Control 2 Ways Draining Connection Specification-50Hz


Model Indoor ARVWM-H022/4R1A(L) ARVWM-H028/4R1A(L) ARVWM-H036/4R1A(L) ARVWM-H045/4R1A(L) ARVWM-H056/4R1A(L) ARVWM-H071/4R1A(L)

Capacity Cooling kW 2.2 2.8 3.6 4.5 5.6 7.1

remote controller is standard, and wired controller is Both left and right sides of unit are possible for drainage
Heating kW 2.5 3.0 4.3 5.0 6.0 8.0
Power Supply V~,Hz,Ph 220~240,50,1 220~240,50,1 220~240,50,1 220~240,50,1 220~240,50,1 220~240,50,1
optional. Wired controller can be fixed on the wall and pipe connection, easy for installation. Electric Data
Rated Power W 38 38 38 68 68 82
avoid mislaying. It’s mainly used for commercial zone Air Flow Volume(Hi/Mid/Low) m3/h 650/600/580 650/600/580 650/600/580 850/750/650 850/750/650 1200/950/800
and makes air conditioner control more convenient. Performance
Noise Level(Hi/Mid/Low) dB(A) 38/33/27 38/33/27 38/33/27 45/41/35 45/41/35 48/45/39
Dimension Net mm 850×300×198 850×300×198 850×300×198 970×315×235 970×315×235 1100×330×235
(WxDxH) Packing mm 885×360×270 885×360×270 885×360×270 1010×370×300 1010×370×300 1140×385×300
Weight Net/Gross kg 10/13 10/13 10/13 14/18 14/18 16/20

Indoor Units-Wall-mounted
Indoor Units-Wall-mounted

Liquid Side mm(inch) 6.35(1/4) 6.35(1/4) 6.35(1/4) 6.35(1/4) 6.35(1/4) 9.52(3/8)


Pipe Diameter Gas Side mm(inch) 9.52(3/8) 9.52(3/8) 9.52(3/8) 12.7(1/2) 12.7(1/2) 15.88(5/8)
Drainage mm(inch) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4)
Stuffing Quantity 20/40/40H unit 328/680/850 328/680/850 328/680/850 238/490/560 238/490/560 210/434/496

Specification-60Hz
Model Indoor ARVWM-H022/2R1(L) ARVWM-H028/2R1(L) ARVWM-H036/2R1(L) ARVWM-H045/2R1(L) ARVWM-H056/2R1(L) ARVWM-H071/2R1(L)

Capacity Cooling kW 2.2 2.8 3.6 4.5 5.6 7.1


Heating kW 2.5 3.0 4.3 5.0 6.0 8.0
Power Supply V~,Hz,Ph 220~240,60,1 220~240,60,1 220~240,60,1 220~240,60,1 220~240,60,1 220~240,60,1
Electric Data
Rated Power W 39 39 39 88 88 88
3
Air Flow Volume(Hi/Mid/Low) m /h 650/600/580 650/600/580 650/600/580 850/750/650 850/750/650 1200/950/800
Performance
Noise Level(Hi/Mid/Low) dB(A) 38/33/27 38/33/27 38/33/27 45/41/35 45/41/35 48/45/39
Dimension Net mm 850×300×198 850×300×198 850×300×198 970×315×235 970×315×235 1100×330×235
(WxDxH) Packing mm 885×360×270 885×360×270 885×360×270 1010×370×300 1010×370×300 1140×385×300
Weight Net/Gross kg 10/13 10/13 10/13 14/18 14/18 16/20

Convenient Installation
Liquid Side mm(inch) 6.35(1/4) 6.35(1/4) 6.35(1/4) 6.35(1/4) 6.35(1/4) 9.52(3/8)
Pipe Diameter Gas Side mm(inch) 9.52(3/8) 9.52(3/8) 9.52(3/8) 12.7(1/2) 12.7(1/2) 15.88(5/8)
Drainage mm(inch) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4) DN20(R3/4)
Stuffing Quantity 20/40/40H unit 328/680/850 328/680/850 328/680/850 238/490/560 238/490/560 210/434/496

EXV is built-in the indoor unit,compact size.Adopts new type fixing plate,stable and easy to install.

Notes:
1.Cooling Capacity: Indoor temperature 27℃ DB/19℃ WB;Outdoor temperature:35℃ DB/24℃ WB.
2.Heating Capacity:Indoor temperature 20℃ DB;Outdoor temperature:7℃ DB/6℃ WB.
3.Piping Length:Equivalent piping length:7.5m,level differernce:0m.
4.Sound level is measured at 1.4m from the air outlet
5.The above designs and specifications are subject to change without prior notice. Final specifications please refer to technical specification provided by sales representative.

65 66
Remote Controller
YK-K

Control System
Remote Controller 68

Wired Controller 69 ON/OFF Sleep Function


Fan Speed Setting Mode Setting Temperature-Setting
HIGH/MED/LOW/AUTO Timer On/Off AUTO/COOL/DRY/HEAT/FAN /Timer Range Setting

Centralized Controller 70 Temperature-Setting


/Timer Range Setting I Feel Function Fan Speed Setting
ON/OFF
HIGH/MED/LOW/AUTO
Cooling Mode LED Display On/Off
Vertical Swing Timer On/Off

Network Control Software Heating Mode

Vertical Swing/Horizontal Swing


Anti-fungus Function

Clean Function
Feeling Function Horizontal Swing

Centralized Controller Software 73


Mode Setting
AUTO/COOL/DRY/HEAT/FAN Auxiliary Electric Heating Strong Wind Clean Function

Turbo Wind Spot Swing Sleep Function Health Function

Billing System 75 Health Function Economic Function


LED Display On/Off Fungusproof Function
Silence Function
BMS System 76

Wireless Network Control 77 Function

Control System
1. Background light
The background light allows users to operate the controller in a dark room. The device lights up when a button is pressed, and turns
Accessories off when a given operation is completed.

AHU Kit 78 2. Setting addresses


Besides the machine’s auto addressing function, users can set the indoor unit’s address on the remote controller YK-L.

Selection Software 80
Specifications
Monitoring Software 81
YK-L YK-K

Model

Dimesion (WxHxD) (mm) 52x160x25(max) 50x140x28.5(max)

Power(V) 3V(1.5V×2) 3V(1.5V×2)

67 68
Wired Controller Centralized Controller
Accessory: Centralized Controller Adaptor
Quick on/off
Set /change time
XK-02A XK-05A
Timer Mode: a. Current/Daily Timing; b. Weekly Timer
Zone/Unit Set; Zoned Control
Centralized Control and Lock Functions
Failure Inquiry Function

Function: Centralized controller adaptor is


used with centralized controller together.

Function
1. Remote signal receiving function
Wired controller provide a signal receiver for remote controller. Signal from remote controller can be received by wired controller, then sent
to the indoor unit and it's convenient to control.

2. Setting addresses
The address setting function is coupled with easy installation and simple future maintenance. Service personnel can set the address for the
indoor unit using XK-02A and XK-05A.

3. Keyboard locking Function

Control System
Control System

The locking function can be used to prevent other people from using the controller.
1. Operation status of as many as 512 indoor units can be monitored , including wind speed, set temperature, etc.
4. Easy connection 2. Mode, air speed and temperature setting are possible for individual/zoned/all indoor units.
The wired controller conveniently connects to the indoor unit’s display panel via connecting wire. 3. 3 operation modes are available: Last-in Preferred, Centralized Control and Lock;
4. The malfunctions of the indoor units can be monitored and saved for inquiry;
5. Timed on/off is possible by specifying the exact time or by weekly schedule.
6. Any number of centralized units can be zoned with as many as 63 indoor units (central controller) & 511 indoor units (touch screen
Specifications central controller) set as one zone, so that units in the same operation. (As the factory default, a centralized group is considered as a zone)

XK-02A XK-05A
Specifications
Model CC-01 CC-02

Model

Dimesion (WxHxD) (mm) 120x120x18(max) 86x86x18(47)

Power(V) 12V 12V Dimesion (WxHxD) (mm) 120x120x18.5(max) Coming Soon

69 70
Network Control Software

Control System
Control System

71 72
Network Control Software-Centralized Controller Software Network Control Software-Centralized Controller Software
System Overview Main Components Of Centralized Controller System

No Main Components Required


Operation system:
1 Host Computer
Windows XP SP2 and above, Windows 7

Communications adapter plate


Computer and communication protocol and unit end communication protocol
2 are incompatible with each other, must add communication adapter plate to make
both communicate.
RS-232 to RS-485/422 converter
The centralized control system RS485 network signal conversion for RS232 serial
signal to achieve the interconnection of computers with centralized control system.
3 USB to RS-485/422 converter
The centralized control system RS485 network signal conversion for USB
to achieve the interconnection of laptops with centralized control system.

RS-485/422 Repeater Extend the communication distance and increase the number of RS-485 bus network.
4 The repeater is not required, only when there is more than 64 communications
equipment or communication distance is more than 800 meters.

Software Introduction Main Interface

Control System
Control System

Features
Users do not need to go to the harsh environment of the site, they can monitor the function of units just through computer. This Area 1 -- Serial setting area, choose the serial and press “Start Working button, system will in operation, press “Stop Working” button,
greatly improves convenience of daily management and the efficiency of central air conditioners; system will stop working;
Area 2 -- The inquire area for air conditioner unit, it can be divided into the system inquire and user-defined group inquire, the inquired unit
Timely find the fault and save the maintenance cost of air conditioner units, minimize losses ;
will be displayed in area 4.
Timer function with multi-period week, fully automated schedule planning of unit; Area 3 -- Display area of single air conditioner indoor unit, select one of indoor units in area 4, then the area will display the name, ID
Each ARV unit can access at most 63 indoor sets; (address of indoor unit) , system belonged ,group belonged, current condition, the room temperature of indoor unit , failure etc.
Area 4 -- Display area of air conditioner group, as shown in above picture, it displayed all the indoor units in the group System01.
This system can access at most 64 ARV outdoor systems, it need to access repeater to increase RS485 network equipment if the outdoor Area 5 -- Control area of air conditioner, it can control one single air conditioner and some air conditioner group, this will be described in
systems are more than 64. detail later.

73 74
Network Control Software-Billing System Network Control Software-BMS System

Overall structure

Modbus

1. At most 99 outdoor systems and 1024 indoor units.


2. Real-time monitor for indoor units(ON/OFF, Error);
3. Variable Control Type(Individual Control/ Air-System Control/ Group Control & Schedule);
4. The Operation History(Error, Turn on/off-time);
5. Lock the indoor units when arrear occurs;
6. The PPD(Power Proportional Distribution) outputs bill by day with PDF-format report;

Software Interface

Control System
Control System

Lonworks

Configuration

Modbus style Baudrate Data-Bit Stop-Bit Check Slave-ID range Modbus code Support broadcast

MODBUS-RTU 9600 8 1 even 1~64 01,02,03,04,05,06 NO

75 76
Network Control Software-Wireless Network Control Accessories-AHU Kit
Mixed connected with other indoor units ARVK-01 ARVK-02

Wiring Example
AUX
Partial fresh air system
A-link

All fresh air syste

Control System
Control System

Features
1. AUX air conditioner can connect to intelligent terminal through WIFI or GPRS network,customers can enjoy fun and convenience of remote
control the AC via iphone, ipad and other mobile terminals(Android and IOS) at anytime and anywhere.
2. The function of software on Mobile terminal includes mode control,temperature control, swing control, timing control.
3. Customers can set schedule to plan their day, also the scene mode can be set conveniently.

77 78
Accessories-AHU Kit Accessories-Selection Software
To meet the customers' requirements, AUX has developed the advanced selection software. The software provides quick and convenient
Structure Diagram selectable options for users, supports multiple languages, greatly improves the selection and installation process.

Mixed connected with other indoor units


6 Parts Of The ARV Selection

No Steps Instruction

1 Selecting indoor units Selecting indoor unit for project according the capacity, air flow volume and room information.

Automatic selection suitable outdoor unit for project according to the capacity of indoor units,
2 Selecting outdoor units
the capacity ratio between indoor and outdoor unit, and the temperature of indoor and outdoor unit.

Every outdoor system can draw corresponding piping diagram. The system will auto select branch pipe,
3 Drawing piping diagram gas pipe and liquid pipe according to selected indoor and outdoor unit. The pipe length can be input
according to the project diagram if the project need. Ability compensation also can be displayed for the software.

Every outdoor system can draw wiring diagram. The wiring length can be input according to the project diagram
Individually connected with ODU 4 Drawing wiring diagram if the project need. Wring includes: power cable, signal cable and so on. Remote controller and wired controller
can be chosen according to the customer's demands.

Selecting BMS or
5 Centralized Controller
The software can be used to select either BMS or centralized controller and draw connecting wiring diagram.

6 Output the report The report can be output in 3 kinds of forms, PDF, word and CAD.

The Result As Below

AU X Projec t Expres s 
V1 . 0. 4

Control System
Control System

Specifications

Allowed heat Air Flow Volume (m3/h) Weight(kg) Dimension(W×D×H)(mm)


AHU Kit Mode Power(V~,Hz,Ph)
exchanger capacity Min Max Net Gross Packing

ARVK-01 ≤10HP 220~240,50,1 2500 5000 5.7 7.2 450×430×160

ARVK-02 ≤20HP 220~240,50,1 5000 9000 6 7.5 450×430×160

79 80
Accessories-Monitoring Software
HRV-Heat Recovery Ventilator
Self-diagnosis software can be used as remote controller, it is recommended for commissioning. It can monitor the running state of the
outdoor and indoor units real time. And display the malfunctions, be convenient to do the commissioning and trouble-shooting work.

Nomenclature
A HRV - 00 / 4

Power Supply:
4:220-240V~ , 1Ph, 50Hz
5:380-415V~ , 3Ph, 50Hz

Air Flow Volum( m3/h)

Heat Recovery Ventilator

AUX
Control System

HRV
Remote Control Intelligent Defrosting Sleep Mode Fast Cooling/Heating Anti-Cold-Air

Digital Tube Display Wired Control Central Control

81 82
HRV-Heat Recovery Ventilator
Adopt Centrifugal Fan With HRV
Lower Power Consumption And
Longer Air Supply Distance; Easy
Control, Friendly Operation. Specification-HRV
All units are equipped with 3-speed fan mode, adjusting
the air flow rate in accordance with the ceiling height. Model AHRV-200/4 AHRV-300/4 AHRV-400/4 AHRV-500/4 AHRV-600/4 AHRV-800/4 AHRV-1000/4

Innovative centrifugal fan provides larger air volume Volume


m3/h 200 300 400 500 600 800 1000

but lower noise, making the air supply more quietly and CFM 118 176 235 294 353 471 588

smoothly. External static pressure Pa 75 75 100 110 110 120 120

Power Supply V~,Hz,Ph 220~240,50,1 220~240,50,1 220~240,50,1 220~240,50,1 220~240,50,1 220~240,50,1 220~240,50,1
Electric Data
Power Input W 65 130 200 220 220 410 510

Temp. Efficiency % 62 63 61 60 63 63 62
Cooling

High Efficiency Low Noise


Enthalpy Efficiency % 56 56 56 54 55 54 52

Temp. Efficiency % 72 71.5 71 70 72 71 71


Heating
Enthalpy Efficiency % 58 56 56 56 62 62 62
Adopt high quality paper-core heat exchanger, less air Adopt sound absorption material, quiet operation.
resistance. Noise Level dB(A) 34 34.8 36 36 37.5 38.5 41.5

Fresh-air can get a great deal of energy from exhaust air. Net Dimension(WxDxH) mm 660x580x264 744x599x270 744x804x270 828x904x264 824x904x270 1116x884x388 1116x1134x388

Flange mm ¢ 144 ¢ 144 ¢ 144 ¢ 194 ¢ 194 ¢ 243 ¢ 243

Net Weight kg 23 27 33 46 48 63 79

Stuffing Quantity 20/40/40H unit 280/568/710 216/456/513 168/344/387 112/244/280 112/224/252 72/156/156 60/120/120

HRV (Heat Recorvery Energy Saving


Ventilator) Adopt High Fresh air and exhaust air are crossed through the heat
exchanger.
Efficiency Heat Exchanged Core. Temperature and humidity exchange happened in the heat
The heat exchanged core forming by special paper that be
processed with chemical treatment, which could create
recovery ventilator.
Fresh-air can get a great deal of energy from exhaust air.
Specification-HRV
the optimum result in temperature, humidity and cooling
recovery. Model AHRV-1500/5 AHRV-2000/5 AHRV-2500/5 AHRV-3000/5 AHRV-4000/5 AHRV-5000/5

m3/h 1500 2000 2500 3000 4000 5000


Volume
CFM 882 1176 1471 1765 2353 2941

External static pressure Pa 160 170 180 200 220 240

Power Supply V~,Hz,Ph 380~415,50,3 380~415,50,3 380~415,50,3 380~415,50,3 380~415,50,3 380~415,50,3


Electric Data

Different Modes For Your Choice


Power Input W 1000 1200 2000 2100 2400 3000
HRV

HRV
Temp. Efficiency % 62 60 62 64 64 64
Cooling
Enthalpy Efficiency % 51 52 50 55 51 55

Exhausting mode (Hi/Mid/Low fan speed can be chosen) Temp. Efficiency % 70.5 70 70 72 71 72
Heating
Air supply mode (Hi/Mid/Low fan speed can be chosen) Enthalpy Efficiency % 62 63 63 64 64 65

By pass mode (Hi/Mid/Low fan speed can be chosen) Noise Level dB(A) 51 53 55 57 64 64

In this mode, there is no heat exchanging happened, which is more energy saving. Net Dimension(WxDxH) mm 1500×1200×540 1500×1200×540 1500×1200×540 1500×1200×540 1620×1330×990 1620×1330×990
For example: Flange mm 320x300 320x300 320x300 320x300 323x253 500x690
If outdoor temperature is lower than indoor, we don't need heat exchanging, but we need fresh air. We can choose by pass mode. Net Weight kg 173 186 200 270 300 320
Remark: this mode is only available for HRV-200~1000. Stuffing Quantity 20/40/40H unit 20/40/40 20/40/40 20/40/40 20/40/40 8/18/18 8/18/18
Heat exchanging mode (Hi/Mid/Low fan speed can be chosen)
In this mode, supply air flow=exhaust air flow.
Auto mode
In this mode, the unit will run at heat exchange mode or by pass mode judged by outdoor temperature and indoor temperature with low
speed air flow.

Compact Design, Easily Installation & Maintenance.

83 84
Branch Pipe
Dimension
Model Appearance
Gas side joints Liquid side joints

AFG-00B

AFG-12B

AFG-24B

AFG-34B

AFG-50B

AFG-64B
Branch Pipe

Model Packing Dimension(mm) Gross Weight(kg) Description

AFG-00B 300x95x40 0.31/0.35 A* < 8HP


AFG-12B 330x100x40 0.44/0.49 8HP ≤ A* ≤ 12HP
AFG-24B 370x115x45 0.71/0.77 12HP < A* ≤ 24HP
AFG-34B 440x140x50 1.11/1.20 24HP < A* ≤ 34HP
AFG-50B 480x160x65 1.65/1.76 34HP < A* ≤ 50HP
AFG-64B 480x160x65 1.88/1.98 50HP < A* ≤ 80HP

A*:The total capacity of indoor units which is connected to this branch joint